60040188.pdf

PDF 280 KB Posted

Attached to
BEQ Repair AS4212
Solicitation number
N4008525R2620
Issued by

About this file

This architectural detail sheet (A-502) is part of a Navy BEQ (Bachelor Enlisted Quarters) repair project at Marine Corps Base Camp Lejeune, North Carolina. The document contains multiple technical construction details for roofing, wall flashing, downspouts, vents, and other architectural elements, specifically focusing on repair and retrofit techniques for an existing building.

Key technical details include specifications for standing seam metal roofing, roof expansion joints, vent stack penetrations, downspout attachments, stair retread installation, and wall flashing configurations. The drawings provide precise installation instructions for components such as continuous metal drip edges, air and moisture barriers, insulation types (R-10 spray foam, R-38 blown-in), and specific attachment methods using galvanized steel straps, expansion anchors, and sealants. The document is part of solicitation N4008525R2620 for repair work on Building AS4212, with technical specifications designed to ensure precise, durable renovation of the existing military infrastructure.

View the file

Other files

File Type Posted
Amend 0021.pdf PDF
Amend 0020.pdf PDF
Amend 0019.pdf PDF
Amend 0018.pdf PDF
Amend 0017.pdf PDF
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0013.pdf PDF
Amend 0014.pdf PDF
60040177.pdf PDF
60040178.pdf PDF
60040167.pdf PDF
Updated SUBMITTAL REGISTER.pdf PDF
60040172.pdf PDF
60040137.pdf PDF
Updated List of Drawings.pdf PDF
60040262.pdf PDF
60040179.pdf PDF
60040268.pdf PDF
Updated PROJECT TABLE OF CONTENTS.pdf PDF
60040164.pdf PDF
11 81 00.pdf PDF
60040186.pdf PDF
60040187.pdf PDF
60040189.pdf PDF
60040299.pdf PDF
07 60 00.pdf PDF
07 61 15.00 20.pdf PDF
60040174A.pdf PDF
60040250.pdf PDF
05 51 33.pdf PDF
Amend 12 and spec combined.pdf PDF
Amend 0012.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
60040202_PPI.pdf PDF
60040196_PPI.pdf PDF
60040201_PPI.pdf PDF
PROJECT.pdf PDF
60040198_PPI.pdf PDF
60040197_PPI.pdf PDF
SECTION 33 61 14.pdf PDF
60040199_PPI.pdf PDF
60040210_PPI.pdf PDF
Amend and cont sheet combined.pdf PDF
60040195_PPI.pdf PDF
60040290_PPI.pdf PDF
REGISTER.pdf PDF
60040194_PPI.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RIGID INSULATION

AIR AND MOISTURE

BARRIER

CONTINUOUS STAINLESS

STEEL DRIP EDGE

FINISH GRADE

GROUT CAVITY SOLID

WHERE BELOW GRADE

SELF ADHERING WALL

FLASHING AND

TERMINATION BAR. SEAL

TO AIR AND MOISTURE

BARRIER

NOTES:

1. DRIP EDGE SPLICES MUST BE 3" MIN

2. PEEL & STICK WALL FLASHING CONFIGURATION MAY VARY SLIGHTLY AS

ILLUSTRATED IN WALL SECTIONS AND DETAILS

3. VENEER WALL TIES AND JOINT REINFORCEMENT OMITTED FOR CLARITY

8" M

IN

WEEPS AT 2'-0" ON CENTER

ONE COURSE MIN .

ONE COURSE MIN

EXPANSION JOINT FILLER

SLAB

REINFORCEMENT

CAPILLARY STONE

COMPACTED FILL

EXISTING POURED IN PLACE REINFORCED

CONCRETE STAIR

PROVIDE RETROFIT STAIR TREAD/NOSING

MEMBER AT EACH EXISTING TREAD, INCLUDING

LANDINGS: PRE-DRILL ATTACHMENT HOLES AND

SCREW TREADS INTO EXISTING CONCRETE

EXISTING STEEL NOSING

TO REMAIN

3/

8"

9"

NO SEALANT

BETWEEN GUTTER

AND COVER TRIM

NO PENETRATIONS

BELOW NAILING

LINE

SILICONE SEALANT

1" MINIMUM OR IN

ACCORDANCE WITH

SMACNA RECOMMENDED

ASSEMBLY DETAILS

NOTES:

1. PROVIDE EXPANSION JOINTS AT 35'-0" INTERVALS, MAX.

2. TYPICAL GUTTER DIMENSIONS TO BE 6" x 6"

ROOF TRUSSES

ROOF ASSEMBLY,

SEE B2/A-501

SHEET METAL GUTTER

SHEET METAL FASCIA

CONTINUOUS 2x WOOD

BLOCKING

CONT. BENT PLATE - SEE

STRUCTURAL

VENTED ALUMINUM SOFFIT

INTAKE WEEPS @ 2'-0" ON CENTER (MAX.)

METAL DRIP EDGE

2-1/2" METAL STUD

INSULATION

SUPPORTS @ 24" ON

CENTEREXTERIOR WALL - SEE B/A-501

H E

E L

H T.

1' -3

CONTINUOUS ALUMINUM J-TRIM

R-10 SPRAY-FOAM INSULATION

BETWEEN ROOF DECK AND TOP

OF CMU WALL

6" WIDE x 6" DEEP GUTTER WITH 4"

DOWNSPOUT LEADER

6"

CONTINUOUS PREFINISHED METAL

DRIP EDGE TRIM

SHEET METAL FASCIA

SHEET METAL DOWNSPOUT

TERMINATE DOWNSPOUT 6" INSIDE

STEEL DOWNSPOUT

SECURE STEEL DOWNSPOUT TO

EXISTING MASONRY COLUMN AT

7'-0" ON CENTER WITH 12-GAUGE

x 2" WIDE GALVANIZED STEEL

STRAP WITH SLOTTED HOLES

AND (2) 1/2" DIAMETER x 2-1/2"

BOTS SET IN EPOXY

1' -6

EXISTING WOOD TRUSS FRAMED ROOF

OVER EXISTING PRECAST CONCRETE

CEILING

LINE OF COLUMN BEYOND

STANDING SEAM METAL ROOF

EXISTING ROOF SHEATHING TO REMAIN.

REMOVE DAMAGED SHEATHING AND

REPLACE WITH 3/4" PLYWOOD TO MATCH

EXISTING

ICE AND WATER SHIELD

1ST FLOOR

0"

1ST FLOOR

0' - 0"

1' -6

8"

4" W x 12" H CLEANOUT ACCESS HOLE WITH 1/8"

GALVANIZED COVER PLATE

PROVIDE HOLE AT PIPE OUTLET LOCATION

4" GALVANIZED STEEL PIPE OUTLET

DRAIN PIPE - SEE CIVIL PLANS FOR

ADDITIONAL INFORMATION

CONCRETE FOOTING, EXISTING

GROUT BELOW OUTLET

NEW CONCRETE SIDEWALK

GALVANIZED STEEL BASEPLATE

WITH LEVELING NUTS 3/4" DIAMETER

ANCHOR BOLTS AND NON-SHRINK

GROUT

SECURE STEEL DOWNSPOUT TO EXISTING MASONRY

COLUMN AT 7'-0" ON CENTER WITH 12-GAUGE x 2" WIDE

GALVANIZED STEEL STRAP WITH SLOTTED HOLES AND

(2) 1/2" DIAMETER x 2-1/2" BOTS SET IN EPOXY

LINE OF COLUMN BEYOND

VENT STACK TO CONTINUE THROUGH ROOF

FIRE RATED SEALANT PER REQUIRED RATING -

SEE LIFE SAFETY PLANS

R-38 BLOWN-IN

INSULATION

FLUID APPLIED AIR AND

MOISTURE BARRIER

EXISTING PRECAST

FLOOR/CEILING ASSEMBLY

FLASHING SEATED IN A BEAD OF

SEALANT AT FLANGE PERIMETER

AND SECURELY FASTEN

EXTEND FLASHING 8" MINIMUM OVER

ROOF PANEL PAN, SECURE WITH A

STAINLESS STEEL HOSE CLAMP AND

SEAL EXPOSED EDGE WITH SILICONE

EQ EQ

±4

TOP OF VENT STACK SHALL

EXTEND A MINIMUM OF 8" ABOVE

THE ADJACENT ROOF SURFACE.

PAINT EXPOSED VENT PIPING TO

MATCH METAL ROOF COLOR

VENT STACK FLASHING

CONCENTRIC

INTAKE/EXHAUST STACK

METAL CAP FLASHING. SECURE

TO STACK WITH A HEAVY DUTY

STAINLESS STEEL BAND CLAMP

SET HOT STACK COLLAR

FLASHING IN A FULL BED OF

SEALANT PRIOR TO FASTENING

WITH NO. 10 SELF DRILLING CAP

WASHER SCREWS. SEAL

EXPOSED EDGES WITH A CLEAN

BEAD OF SILICONE SEALANT

STANDING SEAM METAL ROOFING

MINERAL WOOL INSULATION

WALL BASE AS SCHEDULED

8" CMU

3/4" PLYWOOD - FASTEN TO CMU

PRESSURE TREATED NAILERS

SOLID SURFACE APRON

3/4" SOLID SURFACE COUNTERTOP

WITH EASED EDGES. SECURE TO 3/4"

PLYWOOD (UNLESS NOTED

OTHERWISE) PER MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

4"

1/ 2"

4' -3

3/4" 3/4"

2x8 PRESSURE TREATED NAILER -

FASTEN TO CMU WITH #12

EXPANSION ANCHORS AT 24" ON

CENTER

8" BOND BEAM - SOLID GROUTED

WITH (1) CONTINUOUS #4 REBAR

2x4 PRESSURE TREATED NAILER -

FASTEN TO CMU WALL WITH #12

EXPANSION ANCHORS AT 24" ON

CENTER

EXISTING CMU WALL

SLIP CLIP

ISOMETRIC BSECTION A

STANDING SEAM

ROOFING

VALLEY FLASHING

16 GAUGE

VALLEY PAN

BUTYL TAPE

1"

8" MIN

RIDGE CAP

16 GAUGE RIDGE PAN

STANDING SEAM ROOFING

BUTYL TAPE

AT THREE

SIDES

CONTINUOUS "Z"

CLOSURE BETWEEN

SEAMS

CONCEAL PANEL FASTENERS

UNDER RIDGE CAP

CLOSURE SCREWS

ROOF CRICKET BEYOND

30" x 54" ROOF ACCESS

HATCH

CLEAR OPENING

2'-6" MIN.

ROOF ACCESS LADDER. ATTACH AT

CATWALK FLOOR AND ROOF

STRUCTURE PER MANUFACTURERS

RECOMMENDATIONS

PROVIDE BLOCKING

FOR FLASHING

ATTACHMENT

EXISTING ROOF ASSEMBLY.

SEE STRUCTURAL FOR

OPENING FRAMING

REQUIREMENTS

2X BLOCKING

1"

EXPANSION DIMENSION

EXPANSION DIMENSION +1/2"

EXPANSION DIMENSION

EXISTING ROOF SHEATHING

GABLE CLIP SCREWS PER

MANUFACTURER

ELASTORMERIC MEMBRANE

ROOF FRAMING

EXPANSION JOINT FRAME.

FASTEN TO GABLE CLIP

WITH NEOPRENE WASHER

OR STAINLESS STEEL

RIVET AT EACH GABLE CLIP

CLOSURE

CONTINUOUS EXPANSION

JOINT COVER

GABLE CLIPS PER

MANUFACTURER

STANDING SEAM

METAL ROOF PANEL

F ile

P ri n t

SYM. DESCRIPTION DATE APP.

REVISIONS

T

T C

E

TI

HCRAD

R E

G I S

ERE

A N

I

L

ORA

N O

R

T H

C

N

D A

R

N

DE

.J UE

ER

III

C

N

NRB E

E W

M

A

P.

STCETIHCRA

FB

BERN N.C

.NEW

CERT. NO.

UTCETIHCRA

DERET

SI

G E R

N

OI

TA

RO

PR

OC

LAR

CAROLINANORTH

50679

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

S p ro je c ts

\2

\2

C

L R e p a ir B

E Q

A S

\2

D e s ig n \2

D w g s \2

A

R C

H

.r v t

/2

/2

:2

:3

A

M

A-502

JAS

DJE,III

JENNI REED

JAS

REPAIR BEQ AS4212

DETAILS

60040188 N40085-23-B-0035

11 JUNE 2024

SCALE: 1 1/2" = 1'-0"

A1

THROUGH WALL FLASHING DETAIL

GRAPHIC SCALE: 3/4"=1'-0"

1' 0 1' 2' 3'

GRAPHIC SCALE: 1 1/2"=1'-0"

1' 6" 3" 0 1'

SCALE: 1 1/2" = 1'-0"

E6

STAIR RETREAD DETAIL

SCALE: 1 1/2" = 1'-0"

D6

GUTTER EXPANSION JOINT DETAIL

SCALE: 1 1/2" = 1'-0"

B1

EAVE DETAIL - MECH BLDG

SCALE: 1" = 1'-0"

D1

DOWNSPOUT DETAIL AT GUTTER

SCALE: 1" = 1'-0"

E3

DOWNSPOUT DETAIL AT FOOTING

SCALE: 3" = 1'-0"

C5

VENT THROUGH EXISTING CEILING/ATTIC

SCALE: 1 1/2" = 1'-0"

B5

VENT THROUGH STANDING SEAM ROOF

SCALE: 1 1/2" = 1'-0"

C6

TYPICAL VENT THROUGH ROOF

SCALE: 1 1/2" = 1'-0"

B6

ROOF PENETRATION DETAIL

SCALE: 1 1/2" = 1'-0"

D5

LAUNDRY - PARTIAL HEIGHT WALL

SCALE: NOT TO SCALE

D3

STANDING SEAM SLIP CLIP

SCALE: 3" = 1'-0"

A3

VALLEY DETAIL

GRAPHIC SCALE: 3"=1'-0"

0 3" 6" 1'

SCALE: 3" = 1'-0"

B3

RIDGE DETAIL

SCALE: 3/4" = 1'-0"

A5

ROOF ACCESS HATCH DETAIL

GRAPHIC SCALE: 1"=1'-0"

1' 0 1' 2'

SCALE: 3" = 1'-0"

C3

ROOF EXPANSION DETAIL

4 ROOFING AMENDMENT 07/25/2025

File details come from the government source that posted it. Updated .