60040250.pdf

PDF 548 KB Posted

Attached to
BEQ Repair AS4212
Solicitation number
N4008525R2620
Issued by

About this file

This document is a mechanical HVAC plan drawing for a Barracks Equipment Quarters (BEQ) repair project at Marine Corps Base Camp Lejeune, North Carolina. The drawing (Sheet M-102) details the third floor and attic floor mechanical systems, specifically showing HVAC ductwork, ventilation mains, exhaust and supply systems, and equipment placement for rooms 301-343. Key technical specifications include:

The plan requires installation of Packaged Terminal Heat Pump (PTHP) units with ligature-proof protective covers, corrosion-resistant chassis, and condensate drains. Ductwork routing includes provisions for exhaust and supply ventilation mains, inline exhaust fans in the attic, and louvers in gable walls. The drawings specify structural modifications to wooden roof trusses will be necessary to accommodate ductwork routing and louver installations. The project is part of contract N40085-23-B-0035, with Morgan Hunter as the design firm, and is specifically identified as the Repair BEQ AS4212 project for the Department of the Navy Naval Facilities Engineering Systems Command.

View the file

Other files

File Type Posted
Amend 0021.pdf PDF
Amend 0020.pdf PDF
Amend 0019.pdf PDF
Amend 0018.pdf PDF
Amend 0017.pdf PDF
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0013.pdf PDF
Amend 0014.pdf PDF
60040177.pdf PDF
60040178.pdf PDF
60040167.pdf PDF
Updated SUBMITTAL REGISTER.pdf PDF
60040172.pdf PDF
60040137.pdf PDF
Updated List of Drawings.pdf PDF
60040262.pdf PDF
60040179.pdf PDF
60040268.pdf PDF
Updated PROJECT TABLE OF CONTENTS.pdf PDF
60040164.pdf PDF
11 81 00.pdf PDF
60040186.pdf PDF
60040187.pdf PDF
60040189.pdf PDF
60040299.pdf PDF
07 60 00.pdf PDF
07 61 15.00 20.pdf PDF
60040174A.pdf PDF
60040188.pdf PDF
05 51 33.pdf PDF
Amend 12 and spec combined.pdf PDF
Amend 0012.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
60040202_PPI.pdf PDF
60040196_PPI.pdf PDF
60040201_PPI.pdf PDF
PROJECT.pdf PDF
60040198_PPI.pdf PDF
60040197_PPI.pdf PDF
SECTION 33 61 14.pdf PDF
60040199_PPI.pdf PDF
60040210_PPI.pdf PDF
Amend and cont sheet combined.pdf PDF
60040195_PPI.pdf PDF
60040290_PPI.pdf PDF
REGISTER.pdf PDF
60040194_PPI.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

14"x10"10"x10"6"x10" 10"x10"6"x6" 14"x10" 10"x10" 6"x10"10"x10" 6"x8" 14"x10"10"x10"6"x10" 10"x10"6"x6" 14"x10" 10"x10" 10"x10" 6"x10" 6"x6"

10"x8"6"x8" 10"x8"6"x8"

10"x8"6"x8" 10"x8"6"x8"

6"x8"

10"x8" 6"x8"10"x8"

10"x8" 6"x8"10"x8" 6"x8"

10"x8"6"x8" 10"x8"6"x8"

10"x8"6"x8" 10"x8"6"x8"

10"x8" 6"x8"10"x8" 6"x8"

10"x8" 6"x8"10"x8" 6"x8"

M-110 A2

M-111 A2

M-110 A4

8"x8" EA

EF-5 M

L-7

L-5b L-6b

L-8

26"x26" EA

32"x22" EA

"x

E A

8"x8" EA

3(TYP)

MD-5

"x

O A

"x

O A

"x

O A

CATWALKCATWALK

38"x22"

"x

38"x22" L-6a

L-5a

"x

L-8b

26"x26"

22"x22"

"x

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-102

MAS

JDL

MORGAN HUNTER

LWM

REPAIR BEQ AS4212

OVERALL THIRD AND ATTIC FLOOR PLANS - HVAC

60040250 N40085-23-B-0035

# PLAN NOTES

1 PROVIDE EXHAUST AND SUPPLY (VENTILATION) MAINS AS

SHOWN. SEE ENLARGED PLANS FOR BRANCH DUCTS TO

DIFFUSERS/GRILLES. (TYPICAL ALL EXHAUST AND SUPPLY

MAINS)

2 PROVIDE PTHP UNIT WITH LIGATURE PROOF PROTECTIVE

COVER, CORROSION RESISTANT CHASSIS, AND 3/4"

CONDENSATE DRAIN WITH EXTERIOR CLEANOUT. (TYP)

3 LOUVER TO BE INSTALLED IN GABLE. (TYP)

4 PROVIDE 1'-0" DEEP SEMICIRCULAR INSULATED PLENUM SIZED

TO MATCH DIMENSIONS OF THE LOUVER AND CONNECT TO

EXHAUST LOUVER. PROVIDE MANUAL DAMPER IN EACH DUCT

PRIOR TO PLENUM CONNECTION. SEE ARCHITECTURAL

DRAWINGS FOR LOUVER LOCATION AND SPECIFICATION.

STRUCTURAL MODIFICATION TO WOODEN ROOF TRUSSES,

SUPPORTS AND BRACING WILL BE REQUIRED TO ROUTE DUCT

TO LOUVERS AND TO INSTALL LOUVERS IN GABLE/DORMER

WALL.

5 PROVIDE 1'-0" DEEP SEMICIRCULAR INSULATED PLENUM SIZED

TO MATCH DIMENSIONS OF THE LOUVER AND CONNECT TO

INTAKE LOUVER. PROVIDE MANUAL DAMPER IN EACH DUCT

PRIOR TO PLENUM CONNECTION. SEE ARCHITECTURAL

DRAWINGS FOR LOUVER LOCATION AND SPECIFICATION.

STRUCTURAL MODIFICATION TO WOODEN ROOF TRUSSES,

SUPPORTS AND BRACING WILL BE REQUIRED TO ROUTE DUCT

TO LOUVERS AND TO INSTALL LOUVERS IN GABLE/DORMER

WALL.

6 EXHAUST AND SUPPLY (VENTILATION) MAIN DUCT RISER UP

FROM LEVELS BELOW. ROUTE TO EXTERIOR LOUVERS AS

SHOWN. PROVIDE TRANSITION AND OFFSET IN OUTSIDE AIR

DUCTWORK TO ALLOW FOR ROUTING OF DUCTWORK UNDER

CATWALK.

7 ROUTE EXHAUST DUCT RISER TO INLINE EXHAUST FAN ON

PLATFORM IN ATTIC. ROUTE EXHAUST FROM FAN TO LOUVER

AS SHOWN.

8 PROVIDE INLINE EXHAUST FAN ON PLATFORM IN ATTIC.

9 ROUTE DUCTWORK AS REQUIRED IN ATTIC TO PROVIDE

CLEARANCE ZONE FOR CATWALK AS SHOWN. COORDINATE

EXACT ROUTING WITH STRUCTURAL BEAMS IN ATTIC SPACE.

GENERAL NOTES:

1. SEE SHEET M-001 FOR GENERAL NOTES, LEGEND &

ABBREVIATIONS

2. PLAN DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT

ILLUSTRATE ALL SPECIFIC DUCT TAKE-OFF CONFIGURATIONS,

TAPS, ETC. PROVIDE FLEXIBLE DUCTWORK RUNOUTS TO ALL

SUPPLY AND RETURN GRILLES WITH A MAXIMUM LENGTH OF 5

FEET AND SINGLE BENDS NO GREATER THAN 45 DEGREES.

REFER TO PROJECT SPECIFICATIONS AND DUCTWORK

DETAILS FOR SPECIFIC REQUIREMENTS.

3. PIPING IS TO BE INSTALLED SO THAT ALL VALVES, STRAINERS,

UNIONS, TRAPS AND FLANGES REQUIRING ACCESS ARE

EASILY ACCESSIBLE. ALL VALVES MUST BE INSTALLED SO

THAT THE SYSTEM REMAINS IN SERVICE WHEN EQUIPMENT

OR PIPING (ON EQUIPMENT SIDE OF VALVE) IS REMOVED. ALL

BALANCING VALVES AND BUTTERFLY VALVES MUST BE

PROVIDED WITH POSITION INDICATORS AND MAXIMUM

ADJUSTABLE STOPS. ALL VALVES (EXCEPT CONTROL VALVES)

AND STRAINERS MUST BE FULL SIZE OF PIPE BEFORE

REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT OR

CONTROLS.

GRAPHIC SCALE: 3/32"=1'-0"

8' 0 8' 16' 24'

3/32" = 1'-0" B1

THIRD FLOOR PLAN - MECHANICAL NEW WORK

N

N

3/32" = 1'-0"

ATTIC FLOOR PLAN - MECHANICAL NEW WORK

4 ROOFING AMENDMENT 07.25.25

File details come from the government source that posted it. Updated .