This federal solicitation is for design-build construction services for Dry Dock #1 at Portsmouth Naval Shipyard in Kittery, Maine. The project includes building two new dry dock sections labeled DD1N and DD1W to support maintenance and overhaul of Virginia Class submarines. Construction will comprise concrete floors, walls and a center wall separating the new sections, new pump well systems, a pump station building, crane rails, mooring hardware, mechanical and electrical utilities, tunnels and all necessary appurtenances. Modifications will also be made to the existing basin closure wall and Berths 1 and 11. The existing DD1 pump well will be connected to the new system and interior modified. The Navy Facilities Engineering Command is the contracting agency. The response due date and award date are not specified.
View the file
Other files
Show 40 more
Latest 50 of 123 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EQUIP. PLATFORM
EL 24.67
GROUND LEVEL
EL 12.00
PS-101.1
PS-101.2
EL 44' - 0"
9 10
T.O. PARAPET WALL
EQUIP. PLATFORM
EL 24.67
GROUND LEVEL
EL 12.00
PS-101.3
PS-101.4
6 6
EL 44' - 0"
T Y
P
T Y
P
T.O. PARAPET WALL
EQUIP. PLATFORM
EL 24.67
GROUND LEVEL
EL 12.00
EL 44' - 0"
JK
3 9
35' - 8"
T.O. PARAPET WALL
9' - 9"
20' - 0"
EQUIP. PLATFORM
EL 24.67
GROUND LEVEL
EL 12.00
EL 44' - 0"
J K
PS-ST2.2
33 4 1
/2
8 5
T.O. PARAPET WALL
/2
/2
23' - 4 5/8" 4' - 2"
4' - 4"
2' - 2"
/2
13' - 6 3/8"
REMOVABLE SELF SUPPORTING WEATHER TIGHT
TRANSLUCENT SKYLIGHT
12" LOAD BEARING CONCRETE INSULATED PANELS, TYP.
LOUVER WITH BIRD/INSECT SCREEN. REFER DETAIL
A4/PA601 AND MECHANICAL DRAWINGS.
INSULATED FRP DOOR AND FRAME; REFER TO DOOR
SCHEDULE
BIRD DETERRENT SYSTEM POST AND WIRE; REMOVABLE.
INSULATED STAINLESS STEEL OVERHEAD COILING DOOR;
REFER TO DOOR SCHEDULE
EXTERIOR LIGHT, SEAL PENETRATIONS WEATHER TIGHT; TYP.8
9 PARAPET MOUNTED BIRD SPIKES
4 LIGHTING ROD; REFER TO ELECTRICAL DRAWINGS.
10 2" WIDE x 1/4" DEEP REVEALS, TYPICAL
11 PARAPET COPING.
12 LOUVER WITH BIRD/INSECT SCREEN FOR PIPE
PENETRATION; REFER TO PLUMBING. SEAL WEATHER TIGHT
SIMILAR TO DETAIL A4/PA601.
13 PIPE PENETRATIONS, TYPICAL. REFER TO MECHANICAL AND
PLUMBING DRAWINGS.
K
IT
T E
R Y
M
A
IN
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
CHECK GRAPHIC SCALE BEFORE USING
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SHEET
NAVFAC DRAWING NO.
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
GRAPHIC SCALE
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
C A
P
IT
A L I
M P
R O
V E
M E
N T
C O
R E
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
V
IR
G
IN
IA
P -3
M U
L T
I- M
IS
S
IO
N
D R
Y D
O C
K
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C L A S S
IF
IE
D
UNCLASSIFIED
EJA
DSN
NBJ
LBT/LBL
1604959
DES DRW CHK
CONSTR. CONTR. NO.
SCALE: AS SHOWN
C
U se rs
P u b lic
D o c u m e n ts
L o c a l_ R e v it F i le s\ D
R Y
D S
W
TR
-1
-A
C h a rl e s.
r a u .r v t
/6
/2
:3
:4
A
M
P U
M P
S T
A T
IO
N
B
U
IL
D
IN
G E
L E
V A
T
IO
N S
PA201
RJK CVR THC
12823432
469 1056SCALE: 1/8" = 1'-0" PA101 A2
EAST ELEVATION
SCALE: 1/8" = 1'-0" PA101 A4
WEST ELEVATION
SCALE: 1/8" = 1'-0" PA101 B2
NORTH ELEVATION
SCALE: 1/8" = 1'-0" PA101 C2
SOUTH ELEVATION
KEYNOTES
4' 0' 4' 8' 12' 16'
1/8" = 1'-0"
A m e n d m e n t
-0
-2
V
M G
SEALSEAL
KI
TT
ER
Y, M
AI
N E
PO
R
TS
M
O U
TH
N
AV
AL
S H
IP
YA
R D
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
SHEET
NAVFAC DRAWING NO.
OF
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
CA
PI
TA
L I
MP
RO
VE
ME
NT
C
OR
E
NA
VA
L S
TA
TI
ON
N
OR
FO
LK
, V
IR
GI
NI
A
P-
M
U
LT
I-M
IS
SI
O
N D
R Y
D O
C K
#1
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C
LA
SS
IF
IE
D
UNCLASSIFIED
LBT/LBL
NBJ
EJA
DSN
SCALE: AS SHOWN
CHKDRWDES
CONSTR. CONTR. NO.
EPROJECT NO.: 1604959
C
U s er s\ Pu b l ic
\D oc u m en ts \L oc a l_ Re v i t_
Fi le s\ D
RY
D
S W
T R -1
5 9 -M
_k m c k eo n.
rv t 1/
7/ 2 0
1:
0 7
:3
A M
PU
M
P
ST
AT
IO
N
SC
H
ED
U
LE
S
- S H
EE
T
O
F
PM601
TJE DFA VAK
12823457 494 1029
PS-UH-2 LOWER LEVEL HORIZONTAL 130 1750 1/4 1,550 50 118 125 130 115 1 T-STAT 310
PS-UH-1 MAIN LEVEL HORIZONTAL 130 1750 1/4 1,550 50 118 125 130 115 1 T-STAT 310
TAG ROOM SERVED SPEED
(RPM) HP AIRFLOW
(CFM)
EDB
(F)
LDB
(F)
INLET
PRESSURE
(PSIG)
COND
CAPACITY
(LBS/HR)
VOLTS PHASE
UNIT IDENTIFICATION
TYPE CAPACITY
(MBH)
FAN AIR STEAM ELECTRICAL
CONTROL
TYPE
OPERATING WEIGHT
(LBS.) NOTES
UNIT HEATER SCHEDULE
NOTES:
1. PROVIDE WITH SOLE PLATE.
2. BASIS OF DESIGN IS MANUFACTURER: FLYGT, MODEL: NP 3301 HT. REFER TO SPEC SECTION 23 64 30.
3. PROVIDE WITH COMBINATION AIR RELEASE VALVE.
4. BID OPTION 4 BASIS OF DESIGN MANUFACTURER: KSB, MODEL: KRT K 100-401/954UNC2-S. REFER TO SPEC SECTION 23 64 30.
PS-ASWP-4 DD1W DUTY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4 PS-ASWP-3 DD1N DUTY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4 PS-ASWP-2 DD1E STANDBY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4 PS-ASWP-1 DD1E DUTY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4
TAG SYSTEM
SERVED REDUNDANCY FLUID TYPE
MAX FLUID
TEMP
(F)
FLOW
(GPM)
PUMP
HEAD
(FT)
EFFICIENCY
(%) BHP HP SPEED
(RPM) VOLTS PHASE
UNIT IDENTIFICATION
PUMP TYPE COUPLING
TYPE CONTROL
PERFORMANCE
PUMP MIN
FLOW
(GPM)
PUMP MOTOR ELECTRICAL
OPERATING
WEIGHT
(LBS.)
NOTES
ASW PUMP SCHEDULE
NOTES:
1. BASIS OF DESIGN: MANUFACTURER: RUSKIN, MODEL NUMBER ELF6350DMP.
2. PROVIDE LOUVER WITH INSECT SCREEN.
3. LOUVER MUST BE RATED FOR SEA COAST SERVICE.
PS-L-6 PIT VENT DRAINABLE STATIONARY 3 18 x 18 ALUMINUM 1,2,3 PS-L-5 PS-DHU-1 HOT EXHAUST DRAINABLE STATIONARY 1 12 x 12 ALUMINUM 1,2,3 PS-L-4 TUNNEL VENTILATION AIR INTAKE DRAINABLE STATIONARY 1 30 x 24 ALUMINUM 1,2,3 PS-L-3 PS-AHU-2 AIR INTAKE DRAINABLE STATIONARY 1 12 x 18 ALUMINUM 1,2,3 PS-L-2 PS-AHU-1 RELIEF AIR LOUVER DRAINABLE STATIONARY 1 36 x 42 ALUMINUM 1,2,3 PS-L-1 PS-AHU-1 AIR INTAKE LOUVER DRAINABLE STATIONARY 1 48 x 36 ALUMINUM 1,2,3
TAG UNIT/AREA SERVED
UNIT IDENTIFICATION
TYPE QUANTITY SIZE
H (IN) x W (IN) MATERIAL NOTES
LOUVER SCHEDULE
NOTES:
1. PROVIDE WITH REMOTE MOUNTED SUMP PUMP CONTROL PANEL.
2. BASIS OF DESIGN IS MANUFACTURER LIBERTY, MODEL NUMBER 1100 SERIES.
PS-SP-1 PUMP STATION
LOWER LEVEL SANITARY SUBMERSIBLE 2 80 40 1 1800 POLYETHYLENE 36 38
POWDER
COATED STEEL,
SEALED AND
VENTED
208 3 1,2
TAG LOCATION SYSTEM
SERVED TYPE QUANTITY FLOW
(GPM)
HEAD
(FT)
HP
(EA)
SPEED
(RPM) CONSTRUCTION DIAMETER
(IN)
DEPTH
(IN) BASIN COVER VOLTS PHASE
UNIT IDENTIFICATION PUMP BASIN ELECTRICAL
NOTES
SUMP PUMP SCHEDULE
NOTES:
1. BASIS OF DESIGN IS MANUFACTURER ZURN, MODEL NUMBER Z163.
2. BASIS OF DESIGN IS MANUFACTURER ZURN, MODEL NUMBER Z520.
3. BASIS OF DESIGN IS MANUFACTURER AERO, MODEL NUMBER 2F1-3036,
PS-SK-1 UTILITY SINK 1/2 1/2 2" 2" 2" 3
FLOOR MOUNTED 30" x 36" 14 GAUGE 304 STAINLESS STEEL UTILITY SINK.
PROVIDE WITH WALL MOUNTED FAUCET WITH 8" CENTERS, 6" SPOUT, 4"
WRIST BLADE HANDLES, AND 2.2 GPM AERATOR.
PS-RD-1 COMBINATION ROOF DRAIN AND
OVERFLOW ROOF DRAIN - - - SEE
PLANS - 2 15" DIAMETER COMBINATION MAIN ROOF AND OVERFLOW ROOF DRAIN
SET. PROVIDE WITH CAST IRON DOMES AND VANDAL PROOF SECURED...
PS-FD-1 FLOOR DRAIN - - SEE
PLANS
SEE
PLANS
SEE
PLANS 1
HEAVY DUTY ADJUSTABLE TOP CAST IRON FLOOR DRAIN WITH HEAVY
DUTY CAST IRON SLOTTED GRATE. PROVIDE WITH SEDIMENT BUCKET AND
ASSE 1072 APPROVED TRAP SEAL.
TAG FIXTURE COLD WATER
SUPPLY (IN)
HOT WATER
SUPPLY (IN)
TRAP SIZE
(IN)
DRAIN
SIZE (IN)
VENT SIZE
(IN) NOTES DESCRIPTION AND ACCESSORIES
PLUMBING FIXTURES SCHEDULE
NOTES:
1. BASIS OF DESIGN IS MANUFACTURER EEMAX, MODEL NUMBER ED024480T2T.
PS-WH-1 UTILITY SINK 18.19 x 3.74 12.14 24 480 29/PHASE 3 POINT OF USE ELECTRIC WATER HEATER 1
TAG FIXTURE SERVED L x W OR
DIA. (IN)
HEIGHT
(IN)
INPUT
(kW) VOLTS AMPS PHASE
UNIT IDENTIFICATION SIZE ELECTRICAL
DESCRIPTION/ACCESSORIES NOTES
INSTANTANEOUS DOMESTIC WATER HEATER SCHEDULE
NOTES:
1. BASIS OF DESIGN IS MANUFACTURER MUNTERS, MODEL NUMBER HC-300.
PS-DHU-1 PUMP STATION LOWER LEVEL 5.0 300 0.5 85.0 44.0 113 18.0 6,000 W 59 0.50 100.00 120.20 120 252 115 24 24 30 480 3 9.7 1
TAG ROOM SERVED
MOISTURE
REMOVAL
(LBS/HR)
AIRFLOW
(CFM)
ESP
(IN-WG)
EAT
(F)
EAT
(GR/LB)
LAT
(F)
LAT
(GR/LB)
REACT
HEATER
AIRFLOW
(CFM)
ESP
(IN-WG)
EAT
(F)
EAT
(GR/LB)
LAT
(F)
LAT
(GR/LB)
OPERATING
WEIGHT
(LBS)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN) VOLTS PHASE AMPS
UNIT IDENTIFICATION PROCESS REGENERATION PHYSICAL CHARACTERISTICS ELECTRICAL
NOTES
DESICCANT DEHUMIDIFICATION UNIT SCHEDULE
NOTES:
PS-CRAC-1 IT ROOM 1.5 750 0.3 0.2 1 18.1 16.3 75.0 61.0 SCROLL 1 VARIABLE SPEED R-407C HOT GAS 16.1 DISPOSABLE 8 SELF-CONTAINED 20 27 56 300 208 1 16.9 25 LIEBERT MMD18A-PR074 1
TAG ROOM SERVED AIRFLOW
(CFM)
ESP
(IN-WG) HP NO OF
FANS
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EDB
(F)
EWB
(F) TYPE CIRCUITS STAGES REFRIG TYPE
TOTAL
CAPACITY
(MBH)
TYPE EFFICIENCY
(MERV)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
OPERATING
WEIGHT
(LBS.)
VOLTS PHASE MCA MOP
UNIT IDENTIFICATION
NOMINAL
CAPACITY
(TONS)
FAN DX COOLING COIL COMPRESSOR REHEAT SECTION FILTER
CONFIG
PHYSICAL CHARACTERISTICS ELECTRICAL
MANUFACTURER MODEL NUMBER NOTES
COMPUTER ROOM AIR CONDITIONING UNIT
NOTES:
1. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE TTA24044D.
2. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE TTA07244D.
3. PROVIDE WITH CURB SUPPORT, 18" MIN HEIGHT. COORDINATE ROOF CURB WITH ROOF SLOPING TO MOUNT EQUIPMENT LEVEL.
4. CONDENSER COILS TO BE COATED FOR SEAWATER APPLICATION.
PS-ACCU-2 PS-AHU-02 6 12.9 DUAL 2 R-410A 1 0.5 40 36 41 279.0 480 3 14.0 20 2, 3, 4 PS-ACCU-1 PS-AHU-01 25 11.6 SCROLL 1 R-410A 2 1 45 46 94 856.8 480 3 49.0 60 1, 3, 4
TAG UNIT SERVED TYPE NO OF
CIRCUITS
REFRIG
TYPE
NO OF
FANS
HP
(EACH)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
OPERATING
WEIGHT
(LBS)
VOLTS PHASE MCA MOP
UNIT IDENTIFICATION
CAPACITY
(TONS) EER
COMPRESSORS CONDENSER FANS PHYSICAL CHARACTERISTICS ELECTRICAL
NOTES
AIR COOLED CONDENSING UNIT SCHEDULE
NOTES:
1. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE CSAA014
2. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE CSAA004
3. COILS TO BE COATED FOR SEAWATER APPLICATION.
PS-AHU-2 CEILING-HUNG LOWER
LEVEL LOWER LEVEL 1,600 1,600 200 1.00 3.03 1 1.25 1.5 2,631 N/A N/A N/A N/A N/A 1,119 32.5 44.0 116.9 PLEATED MEDIA 8 0.533 64.1 57.4 78.80 60.90 46.00 45.78 0.688 R-410A TBD 480 3 23.95 25.00 2, 3
PS-AHU-1 FLOOR GROUND
LEVEL
GROUND LEVEL &
MEZZANINE 7,000 6,000 230 0.50 2.95 2 5.11 3.00 2,306 0.50 2.108 3.922 5 1514 3,008 86.5 72.0 106.3 PLEATED MEDIA 8 0.606 339.71 219.90 85.00 70.80 56.41 56.01 1.224 R-410A TBD 480 3 20.93 30.00 1, 3
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
TAG
MOUNTING
SUPPORT
STYLE
LOCATION AREA SERVED
MAX
SUPPLY
AIR
(CFM)
MIN
SUPPLY
AIR
(CFM)
MIN
OUTSIDE
AIR
(CFM)
ESP
(IN-WG)
TSP
(IN-WG) QTY. BHP HP SPEED
(RPM)
ESP
(IN-WG)
TSP
(IN-WG) BHP HP SPEED
(RPM)
OPERATING
WEIGHT
(LBS)
MAXIMUM UNIT DIMENSIONS
FILTER TYPE MERV
RATING
MAX APD
(IN-WG)
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EDB
(F)
EWB
(F)
LDB
(F)
LWB
(F)
MAX APD
(IN-WG)
REFRIG
TYPE
REFRIG
CHARGE VOLTS PHASE MCA MOP
UNIT IDENTIFICATION AIRFLOW SUPPLY FAN EXHAUST FAN PHYSICAL CHARACTERISTICS FILTER DX COOLING COIL ELECTRICAL
NOTES
AIR HANDLING UNIT SCHEDULE
NOTES:
1. REFER TO STRUCTURAL DRAWINGS FOR FLOOR GRILLE INFORMATION.
2. BASIS OF DESIGN MANUFACTURER: TITUS, MODEL 272FL.
3. BASIS OF DESIGN MANUFACTURER: TITUS MODEL US-DL.
4. BASIS OF DESIGN MANUFACTURER: TITUS MODEL TMR-AA
5. BASIS OF DESIGN MANUFACTURER: TITUS, MODEL 3FS.
6. PROVIDE ALL FRAMES AND ACCESSORIES AS REQUIRED FOR PROPER INSTALLATION.
7. PROVIDE UNIT WITH OPPOSED BLADED DAMPER.
8. COLOR TO BE SELECTED BY ARCHITECT FROM STANDARD COLORS.
PS-RG-2 SEE DRAWINGS 22 x 18 DUCT ALUMINUM 5, 6, 8
PS-RG-1 SEE DRAWINGS 28 X 24 DUCT ALUMINUM 5, 6, 8
PS-SD-4 SEE DRAWINGS 8 DUCT ALUMINUM 4, 6, 8
PS-SD-3 SEE DRAWINGS 18 x 6 DUCT ALUMINUM 3, 6, 7, 8 PS-SD-2 SEE DRAWINGS 12 x 12 DUCT ALUMINUM 2, 6, 8 PS-SD-1 SEE DRAWINGS 30 x 20 FLOOR STEEL 1
TAG FLOW RANGE
(CFM)
DUCT CONNECTION
SIZE (IN)
MOUNTING
TYPE MATERIAL NOTES
DIFFUSER AND GRILLE SCHEDULE
AM
E N D
M
EN
T
/0 8/
VM
G
M
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
F I L E
N
M
E
U
S F
S h a r e d P r o j e c t s s h a r e d c a d d i n s t r u m e n t a t i o n P
I d w g
Y O
U T
M
E
U
T I L I T
Y
E
N C
L O
S U
R
I O
C A
T I O
N
P
L
P
O
T T
E D
W e d n e s d a y
J a n u a r y p m
S E
R p r e l f
D E
P A
R T
M E
F
T
H
V
Y
EPROJECT NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
C
O M
M A
N D
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
SEAL
OF
N A
V A
L
F
A C
I L
I T
I E
S
E
N G
I N
E E
R I N
G
C
O M
M A
D
D
A
T L
A N
T I C
DRAWFORM REVISION: 07 AUG 2018
CHECK GRAPHIC SCALE BEFORE USING
P
U L
T I M
I S
S I O
N
D
Y
C
K
LBT / LBL
EJA
KEY PLAN
GRAPHIC SCALE
NBJ
DSN
1604959
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
PM / DM
BRANCH MANAGER
CHIEF ENG / ARCH
FIRE PROTECTION
DRWDES CHK
CONSTR. CONTR. NO.
SCALE:
A / E INFO
C A
P I T
A L
I M
P R
O V
E M
E N
T
C
O R
E N
A V
A L
S
T A
T I O
N
N
O R
F O
L K
V
I R
G I N
I A
P O
R T
S M
O U
V
I P
Y A
R D
K I T
T E
R Y
M
A I N
E
AS SHOWN
PI101
12823525
U T
I L
I T
Y
E
N C
L O
S U
C
A T
I O
N
P
L A
N
1/2" = 1'-0"
4' 3' 2' 1' 0 4'
PR PR RR
RIO-P1
PLAN
NORTH
UTILITY ENCLOSURE -
SECOND FLOOR PLAN
SCALE: 1/2" = 1'-0"
IT
ROOM
A M
E N
D M
E N
T
V
M G
AutoCAD SHX Text
UNCLASSIFIED
AutoCAD SHX Text
UNCLASSIFIED
AutoCAD SHX Text
UNCLASSIFIED
AutoCAD SHX Text
FE
PI102
12823526
P U
M P
I N
G
S
T A
T I O
N
I N
S T
R U
M E
N T
A T
I O
N
S
I T
E
P
L A
N
1/4" = 1'-0"
4' 0 4' 8'
PLAN
NORTH
PUMPING STATION GROUND
LEVEL INSTRUMENTATION PLAN
SCALE: 1/4" = 1'-0"
PLAN
NORTH
PUMPING STATION VALVE VAULTS
INSTRUMENTATION PLAN
SCALE: 1/4" = 1'-0"
DEWATERING WET WELL
BUBBLER LEVEL PANEL AND
PIPEWORK LOCATION
PI501
A4
PI503
A1
PI503
A4
PR PR RR
DRAINAGE WET WELL
BUBBLER LEVEL PANEL AND
PIPEWORK LOCATION
DP-LCP1 DP-LCP2 DP-LCP3
SCADA
WORKSTATION
CHART
RECORDER
DEWATERING PUMPING
STATION CONTROL
PANEL (DCP)
MDP-LCP1
MDP1 LOCAL
INDICATOR
PANEL
PI501
A1
PI503
A1
PI503
A4
INSTRUMENT AIR
SYSTEM
LEVEL FLOATS FOR WEST
VALVE VAULT SUMP
PI501
A4LEVEL FLOATS FOR EAST
VALVE VAULT SUMP
MDP-LCP2MDP-LCP3
MDP2 LOCAL
INDICATOR
PANEL
PI501
A1
MDP3 LOCAL
INDICATOR
PANEL
PI501
A1
A
B
C
D
2 3 4 5
1 2 3 4 5
A
B
C
D
F I
M
E
U
S F
S h a r e d P r o j e c t s s h a r e d c a d d i n s t r u m e n t a t i o n P
I d w g
Y O
M
E
P
U M
P I N
G
S
T A
T I O
N
I N
S T
R U
M E
N T
A T
I O
N
S
I T
E
P
L
P
O
T T
E D
W e d n e s d a y
J a n u a r y p m
E
R p r e l f
D E
P A
R T
M E
F
T
V
Y
EPROJECT NO.
SHEET
NAVFAC DRAWING NO.
N A
V A
L
F
A C
I L
I T
I E
S
E
N G
I N
E E
R I N
G
C
O M
M A
N D
S Y
M D
E S
C R
I P
T I O
N D
A T
E A
P P
R
SEAL
OF
N A
V A
L
F
A C
I L I T
I E
S
E
N G
I N
E E
R I N
G
C
O M
M A
D
A
T L A
N T
I C
DRAWFORM REVISION: 07 AUG 2018
CHECK GRAPHIC SCALE BEFORE USING
P
U L
T I M
I S
S I O
N
D
Y
C
K
LBT / LBL
EJA
KEY PLAN
GRAPHIC SCALE
NBJ
DSN
1604959
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
PM / DM
BRANCH MANAGER
CHIEF ENG / ARCH
FIRE PROTECTION
DRWDES CHK
CONSTR. CONTR. NO.
SCALE:
A / E INFO
C A
P I T
P R
O V
E M
E N
T
C
O R
E N
A V
A
T I O
N
N
O R
F O
L K
V
I R
G I N
I A
P O
R T
S M
O U
V
A L
S
H I P
Y A
R D
K I T
T E
R Y
M
A I N
E
AS SHOWN
A M
E N
D M
E N
T
V
M G
AutoCAD SHX Text
UNCLASSIFIED
AutoCAD SHX Text
UNCLASSIFIED
AutoCAD SHX Text
UNCLASSIFIED
AutoCAD SHX Text
AutoCAD SHX Text
A3
UM301
UE-PWT-2UE-PWT-1
PW
FILTER
CYLINDER
PW
FILTER
CYLINDER
CARBON
FILTER
(VENDOR
SKID)
SAND
FILTERS
D
D.4 E F
3.3
5.3
ION
EXCHANGE
CONDUCTIVITY
METER
A3
UM302
4 4
A2
UM303
1/2" NI
MATERIAL LIFT
UE-ML1
STAIR
UE-ST1
COOLING TOWER
SUPPORT
EQUIPMENT
UE-301
STAIR
UE-ST2
1/2" NI
1/2" NI
C
UE-DHW-HX-1
UE-V-25
NO
UE-V-24
NC
UE-ST-4
UE-ST-3UE-ST-1
UE-ST-2
UE-V-6
NC
UE-V-9
NO
UE-V-12
NC
UE-V-26
NC
UE-V-3
NO
UE-V-16
NO
UE-V-15
NO
UE-V-23
NO
C4
UM303
A4
UM303
UE-CT-1A-VFD
UE-CT-1B-VFD
UE-CT-2-VFD UE-CT-3A-VFD
UE-CT-3B-VFD
UE-CT-4-VFD
UE-SF-2
UE-P-2 UE-P-4
UE-SF-4
UE-P-3
UE-P-1
UE-SF-1
UE-SF-3
A2
UM506
2 1/2" LPS
3/4" LPC
BOP: 1' - 0"
8" ASWS
8" ASWS
8" ASWR
1 1/2" ASWR
A S
W S
8" ASWS
1 1/2" NaOCL
2" VENT
2" VENT
2" VENT
1 1/2" ASWR
8" ASWS
8" ASWS
8" ASWS
1 1/2" ASWR
8" ASWS
8" ASWS
10 12
4 4
UE-DD1N-OV-8
UE-DD1N-OV-6
UE-DD1N-OV-06
UE-DD1N-OV-08
UE-DD1N-OV-09
UE-DD1N-OV-10
UE-DD1W-OV-09
UE-DD1W-OV-10
1" DR
1" DR
1" DR
2" SUCTION
1 1/2" ASWR
2" SUCTION
2" SUCTION
1/2" REF(L)
1" REF(V)
1" REF(V)
1/2" REF(L)
BOP: 7' - 10"
BOP: 9' - 2"
BOP: 9' - 0"
1 1/2" NaOCL
8" ASWS
8" ASWS
1 1/2" NaOCL
UE-FT-01N
UE-FT-01W
GENERAL NOTES
1. BOD AND BOP ELEVATIONS ARE
RELATIVE TO THE ASSOCIATED
FLOOR ELEVATION.
2. REFER TO UM207 FOR PURE
WATER PIPING.
KEY PLAN
K
IT
T E
R Y
M
A
IN
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
CHECK GRAPHIC SCALE BEFORE USING
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SHEET
NAVFAC DRAWING NO.
OF
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
GRAPHIC SCALE
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
C A
P
IT
A L
IM
P
R O
V E
M E
N T
C O
R E
N A
V A
L S
T A
T
IO
N N
O R
F O
LK
, V
IR
G
IN
IA
P -3
M
U L T
I- M
IS
S
IO
N
D R
Y D
O C
K
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C L A S S
IF
IE
D
UNCLASSIFIED
LBT/LBL
NBJ
EJA
DSN
SCALE: AS SHOWN
CHKDRWDES
CONSTR. CONTR. NO.
EPROJECT NO.: 1604959
C
U se rs
P u b lic
D o c u m e n ts
L o c a l_ R e v it
F ile s\ D
R Y
D S
W
TR
-1
-M te n v id
.r v t
/6
:5
:3
A
M
U T
IL
IT
Y E
N C
L O
S U
R E
T
H
IR
D F
L O
O R
P
IP
IN
G
P L A
N
UM204
TJE DFA VAK
12823615
652 1029
PLAN NORTH
SCALE: 1/4" = 1'-0"
UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN
KEYNOTES
1" DRAIN FROM SIDE STREAM FILTRATION SKID TO FLOOR
DRAIN.
8" ASWS DISTRIBUTION DOWN TO SECOND FLOOR. REFER
TO DRAWING UP103 FOR CONTINUATION.
8" ASWR UP FROM SECOND FLOOR. PIPE RISER CONTINUES
UP TO MEZZANINE LEVEL PLATFORM. REFER TO DRAWING
UM203 FOR CONTINUATION OF PIPE TO FLOOR BELOW.
PROVIDE 8" ASWS PIPING FROM 3,000 GALLON BUFFER
TANK TO SUCTION SIDE OF CIRCULATION PUMP. ROUTE
BOTTOM OF ASWS PIPE ELEVATION APPROXIMATELY 2'-0"
ABOVE FINISHED FLOOR FROM TANK OUTLET TO PUMP
SUCTION.
PROVIDE 1/2" NI PIPING AND ISOLATION VALVE. NI PIPING
DOWNSTREAM OF ISOLATION VALVE TO BE PROVIDED AS A
BID OPTION. REFER TO BID OPTION 003. REFER TO UM712
FOR NITROGEN BLANKET FIT UP.
ROUTE 3/4" CA LINE FROM FLOOR BELOW. PROVIDE 3/4" CA
SERVICE CONNECTION WITH VALVE AND CAP 3'-0" ABOVE
FINISHED FLOOR FOR GENERAL USE.
PROVIDE 2-1/2" LPS TO HEAT EXCHANGER, UE-DHW-HX-1.
3/4" LPC DOWN TO SECOND FLOOR FROM HEAT
EXCHANGER, UE-DHW-HX-1.
4" VENT UP TO ROOF FROM CONDENSATE PUMP SKID,
UE-CRU-1, LOCATED ON UTILITY ENCLOSURE TUNNEL.
4" OVERFLOW DRAIN DOWN FROM CONNECTION TO SUMP
TANK.
REFER TO UM203 FOR CONTINUATION OF PIPE.
REFER TO UM205 FOR CONTINUATION OF PIPE.
SIDE STREAM FILTRATION SKID - REFER TO CENTRIFUGAL
SIDE STREAM FILTER SCHEDULE ON DRAWING UM601 FOR
DETAILS.
REFRIGERANT PIPING FROM UE-AHU-1 UP TO UE-ACCU-1 ON
ROOF.
REFRIGERANT PIPING FROM UE-AHU-2 UP TO UE-ACCU-2 ON
ROOF.
REFRIGERANT PIPING FROM UE-CRAC-1 UP TO UE-ACCU-3
ON ROOF.
1/2" NI UP FROM SECOND FLOOR.
2" VENT UP FROM CHEMICAL FEED STATION TO THIRD
FLOOR.
SODIUM HYPOCHLORITE (NaOCL) CHEMICAL FEED STATION.
REFER TO MS704.
CHEMICAL INJECTION INTO ASW SYSTEM. REFER TO DETAIL
B2 ON UM505 AND MS704.
CONTROL PANEL FOR CHEMICAL FEED STATION.
4' 0' 4' 8'
1/4" = 1'-0"
A
M E
N D
M E
N T
/0 /2
V
M
K
IT
T E
R Y
M
A
IN
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SHEET
NAVFAC DRAWING NO.
OF
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
C A
P
IT
A L
I M
P R
O V
E M
E N
T C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
V
IR
G
IN
IA
P -3
M
U L T
I- M
IS
S
IO
N
D R
Y D
O C
K
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C L A S S
IF
IE
D
UNCLASSIFIED
LBT/LBL
NBJ
EJA
DSN
SCALE: AS SHOWN
CHKDRWDES
CONSTR. CONTR. NO.
EPROJECT NO.: 1604959
C
U se rs
P u b lic
D o c u m e n ts
L o c a l_ R e v it
F ile s\ D
R Y
D S
W
TR
-1
-M te n v id
.r v t
/6
:1
:4
A
M
U T
IL
IT
Y E
N C
L O
S U
R E
S
C H
E D
U L E
S
S H
E E
T
O F
UM601
TJE DFA VAK
12823629
666 1029
NOTES:
1. PROVIDE BUFFER TANK WITH INTEGRAL SWEEPER SYSTEM. 2. PROVIDE WITH (1) 5 FT. LADDER SECTION AND SAFETY CAGE
3. BASIS OF DESIGN IS MANUFACTURER DELTA COOLING TOWERS.
UE-ST--4 CT-4 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3
UE-ST--3 CT-3 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3
UE-ST--2 CT-2 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3
UE-ST--1 CT-1 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3
TAG
SYSTEM
SERVED
UNIT IDENTIFICATION
VOLUME
(GAL)
ASME
CONST
DIAMETER
(IN)
HEIGHT
(IN)
ARRANGEMENT SYSTEM FLUID
SYSTEM
TEMP
(F)
WEIGHT
(LBS)
NOTES
SUMP TANK SCHEDULE
NOTES:
1. PROVIDE WITH INERTIA BASE.
2. BASIS OF DESIGN IS MANUFACTURER BELL AND GOSSETT, MODEL NUMBER VSX-VSCS 4X6X17.5A.
3. PROVIDE PUMPS WITH FACTORY APPLIED EPOXY COATING TO THE PUMP INTERNAL CASING.
UE-P-4 DD1W STANDBY DOUBLE SUCTION SPLIT CASE FLEXIBLE
REDUCED VOLTAGE
SOFT START
FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3
UE-P-3 DD1W DUTY DOUBLE SUCTION SPLIT CASE FLEXIBLE
REDUCED VOLTAGE
SOFT START
FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3
UE-P-2 DD1N STANDBY DOUBLE SUCTION SPLIT CASE FLEXIBLE
REDUCED VOLTAGE
SOFT START
FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3
UE-P-1 DD1N DUTY DOUBLE SUCTION SPLIT CASE FLEXIBLE
REDUCED VOLTAGE
SOFT START
FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3
TAG
SYSTEM
SERVED
REDUNDANCY FLUID TYPE
FLUID
TEMP
(F)
FLOW
(GPM)
PUMP
HEAD
(FT)
OVERLOAD
FLOW
(GPM)
MIN
EFFICIENCY
BHP HP
SPEED
(RPM)
VOLTS PHASE
UNIT IDENTIFICATION
PUMP TYPE
COUPLING
TYPE
CONTROL
PERFORMANCE
PUMP MIN
FLOW
(GPM)
PUMP MOTOR ELECTRICAL
OPERATING
WEIGHT
(LBS.)
NOTES
CIRCULATION PUMP SCHEDULE
NOTES:
1. BASIS OF DESIGN IS MANUFACTURER PUROFLUX, MODEL NUMBER PF-64-015. ISOLATION VALVES PROVIDED WITH UNIT.
2. PROVIDE UNIT WITH NEMA 4X CONTROL PANEL WITH DISCONNECT, MOTOR OVERLOAD PROTECTION, ADJUSTABLE PURGE TIMER, AND HOA SWITCHES
UE-SF-4 CT-4 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2
UE-SF-3 CT-3 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2
UE-SF-2 CT-2 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2
UE-SF-1 CT-1 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2
TAG
SYSTEM
SERVED
INLET SIZE
(IN)
OUTLET
SIZE
(IN)
WIDTH
(IN)
LENGTH
(IN)
OPERATING
WEIGHT
(LBS)
MAX HEAD
(FT)
SPEED
(RPM)
HP VOLTS PHASE
FLA
(AMPS)
MCA
(AMPS)
UNIT IDENTIFICATION
FLOW
(GPM)
CENTRIFUGAL SEPARATOR PUMP DATA
NOTES
CENTRIFUGAL SIDE STREAM FILTER SCHEDULE
NOTES:
1. REMOTE SUMP. REFER TO SUMP TANK SCHEDULE.
2. BASIS OF DESIGN IS MANUFACTURER DELTA COOLING TOWERS, INC., MODEL NUMBER TM-210412.
3. BASIS OF DESIGN MANUFACTURER IS DELTA COOLING TOWERS, INC., MODEL NUMBER DT-70I.
4. BID OPTION 6 INCLUDES A CHEMICAL FREE TREATMENT SYSTEM FOR DD1N AND DD1W (QTY 2). REFER TO SPEC SECTION 23 25 00 TREATMENT OF WATER FOR MECHANICAL SYSTEMS.
5. VFD PROVIDED BY COOLING TOWER VENDOR.
UE-CT-4 DD1W INDUCED DRAFT COUNTERFLOW HDPE 1,050 118 85 81 158,000 4 10 460 3 24,600 190 204 198 1,2,4,5
UE-CT-3B DD1W INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5
UE-CT-3A DD1W INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5
UE-CT-2 DD1N INDUCED DRAFT COUNTERFLOW HDPE 1,050 118 85 81 158,000 4 10 460 3 24,600 190 204 198 1,2,4,5 UE-CT-1B DD1N INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5
UE-CT-1A DD1N INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5
TAG SYSTEM SERVED
FLOW
(GPM)
EWT
(F)
LWT
(F)
AMBIENT
AIR WB
(F)
AIRFLOW
(CFM)
NO OF
FANS
HP
(EACH)
VOLTS PHASE
OPERATING
WEIGHT
(LBS)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
UNIT IDENTIFICATION
TYPE TOWER MATERIAL
PERFORMANCE FANS DIMENSIONS
NOTES
COOLING TOWER SCHEDULE
WH WHEELER UTILITY ENCLOSURE 55 55 VACUUM VACUUM GALVANIZED STEEL / GROOVED FIELD UP TO 4" SCH. 40 NO - - PIPE STAND OR CLEVIS HANGER GALVANIZED
ST STORM UTILITY ENCLOSURE - - GRAVITY GRAVITY CAST IRON / HUB AND SPIGOT FIELD 3" TO 6" - NO - - CLEVIS HANGER OR U-BOLT GALVANIZED
SS SANITARY / SEWER UTILITY ENCLOSURE - - GRAVITY GRAVITY COPPER / SOLDER JOINTS FIELD UP TO 2-1/2" DWV NO - - CLEVIS HANGER OR U-BOLT COPPER
SS SANITARY / SEWER UTILITY ENCLOSURE - - GRAVITY GRAVITY CAST IRON / HUB AND SPIGOT FIELD 3" TO 6" - NO - - CLEVIS HANGER OR U-BOLT GALVANIZED
CW COLD WATER UTILITY ENCLOSURE 45-65 55 70 150 COPPER / SOLDER JOINTS FIELD UP TO 2-1/2" TYPE L OR K YES CELLULAR GLASS PVC CLEVIS HANGER OR U-BOLT COPPER
FW FRESH WATER UTILITY ENCLOSURE 45-65 55 70 150 DUCTILE IRON / FLANGED FIELD 3" TO 8" CLASS 52 OR 53 YES CELLULAR GLASS ALUMINUM CLEVIS HANGER OR U-BOLT GALVANIZED
ASW AUXILIARY SEA / TOWER WATER UTILITY ENCLOSURE 65-140 140 90 150 PP-R (BLUE PIPE), SDR 11, MF FIELD UP TO 10" SDR 11 NO - - PIPE STAND OR CLEVIS ROLLER STAINLESS STEEL
NI NITROGEN UTILITY ENCLOSURE 65 65 200 250 STAINLESS STEEL TUBE, TYPE 316 FIELD UP TO 3/4" 3000 PSI NO - - CLEVIS ROLLER OR CLAMP STAINLESS STEEL
CA COMPRESSED AIR UTILITY ENCLOSURE 65 100 125 150 BLACK STEEL, PE/PVC COATED FIELD UP TO 2" SCH. 40 NO - - ROLLER HANGER OR U-BOLT GALVANIZED CR CONDENSATE RETURN UTILITY ENCLOSURE 200 250 - 125 BLACK STEEL FIELD UP TO 2" SCH. 80 YES CELLULAR GLASS ALUMINUM ROLLER HANGER GALVANIZED
HPS HIGH PRESSURE STEAM UTILITY ENCLOSURE 410 450 125 150 BLACK STEEL FIELD UP TO 8" SCH. 80 YES CELLULAR GLASS ALUMINUM ROLLER HANGER GALVANIZED
LPS LOW PRESSURE STEAM (15 psig) UTILITY ENCLOSURE 250 300 15 125 BLACK STEEL FIELD UP TO 3" SCH. 40 YES CELLULAR GLASS ALUMINUM ROLLER HANGER GALVANIZED
PW PURE WATER UTILITY ENCLOSURE 55 55 100 150 STAINLESS STEEL TYPE 316 FIELD UP TO 2" SCH. 40S NO - - PIPE CLAMP OR PIPE STRAP STAINLESS STEEL
HPA HIGH PRESSURE AIR UTILITY ENCLOSURE 70 100 4500 6000 COPPER-NICKEL 70-30 FIELD UP TO 1" CLASS 6000 NO - - PIPE CLAMP STAINLESS STEEL
TAG NAME LOCATION OPERATING DESIGN OPERATING DESIGN
SYSTEM TEMPERATURE (DEG) PRESSURE (PSI)
CARRIER PIPE MATERIAL PIPE SYSTEM
DIAMETER
RANGE
SCHEDULE OR CLASS YES / NO MATERIAL JACKET TYPE MATERIAL
SYSTEM DESIGN CONDITIONS PIPING INSULATION TYPICAL SUPPORTS
MECHANICAL PIPING SCHEDULE
NOTES:
1. BASIS OF DESIGN IS MANUFACTURER AMERICAN COMPRESSOR COMPANY, MODEL NUMBER 55H75.
2. REFER TO BID OPTION 003.
UE-HPAC-2 UTILITY ENCLOSURE STAND-ALONE 85 REDUCED VOLTAGE SOFT START 114 82 59 7,000 75 460 3 89 1,2
UE-HPAC-1 UTILITY ENCLOSURE STAND-ALONE 85 REDUCED VOLTAGE SOFT START 114 82 59 7,000 75 460 3 89 1,2
TAG LOCATION TYPE
SCFM @
5,000 PSIG
STARTER
LENGTH
(IN)
WIDTH
(IN)
HEIGHT
(IN)
WEIGHT
(LBS)
HP VOLTS PHASE FLA
UNIT IDENTIFICATION CHARACTERISTICS ELECTRICAL
NOTES
HIGH PRESSURE AIR COMPRESSOR SCHEDULE
NOTES:
1. BASIS OF DESIGN IS MANUFACTURER CPI INDUSTRIES.
2. REFER TO BID OPTION 003.
UE-TK-4 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2
UE-TK-3 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2
UE-TK-2 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2
UE-TK-1 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2
TAG
SYSTEM
SERVED
UNIT IDENTIFICATION
VOLUME
(GAL)
ASME
CONSTRUCTION
DIAMETER
(IN OD)
HEIGHT
(IN)
ARRANGEMENT
SYSTEM
FLUID
DESIGN
PRESS
(PSIG)
TEST
PRESS
(PSIG)
WEIGHT
(LBS)
NOTES
FLASK TANK SCHEDULE
A
M E
N D
M E
N T
/1 /2
V
M G
A
M E
N D
M E
N T
/0 /2
V
M G
D.4 E F
3.3
5.3
4" ST
4"Ø ST OVERFLOW DN
FROM ROOF DRAIN
4"Ø ST PRIMARY DN
FROM ROOF DRAIN
6" ST
6" ST
4"Ø ST OVERFLOW DN
FROM ROOF DRAIN
4"Ø ST PRIMARY DN
FROM ROOF DRAIN 4" ST
6"Ø ST OVERFLOW
DN TO THIRD FLOOR
6"Ø ST PRIMARY DN
TO THIRD FLOOR
C
A2
UM506
UE-RD-1
UE-RD-1
UE-RD-1
4"Ø FW FROM
LEVEL BELOW
3" FW
3" FW
3" FW
3" FW
3" FW
3" FW
3"Ø ST OVERFLOW
DN TO THIRD FLOOR
3"Ø ST PRIMARY
DN TO THIRD
FLOOR
3"Ø ST PRIMARY DN
FROM ROOF DRAIN
3"Ø ST OVERFLOW DN
FROM ROOF DRAIN
4" DR
4" DR 4" DR
4" DR
3" ST
3" ST
3"Ø ST CLEANOUT
3"Ø ST
CLEANOUT
4" ST
BOP: 20' - 4"
BOP: 19' - 9"
BOP: 20' - 2"
BOP: 19' - 7"
BOP: 16' - 6"
BOP: 20' - 6"
BOP: 20' - 6"
BOP: 20' - 0"
BOP: 20' - 0"BOP: 20' - 0"
BOP: 16' - 7" BOP: 16' - 6"
BOP: 16' - 5"
BOP: 23' - 2"
BOP: 23' - 7"
BOP: 23' - 4"
BOP: 22' - 11"
BOP: 22' - 10"
BOP: 22' - 10"
UE-FT-02N
UE-FT-02W
GENERAL NOTES
1. BOD AND BOP ELEVATIONS ARE
RELATIVE TO THE ASSOCIATED
FLOOR ELEVATION.
KEY PLAN
K
IT
T E
R Y
M
A
IN
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
CHECK GRAPHIC SCALE BEFORE USING
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SHEET
NAVFAC DRAWING NO.
OF
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
GRAPHIC SCALE
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
C A
P
IT
A L
I M
P R
O V
E M
E N
T C
O R
E N
A V
A L
S T
A T
IO
N
N O
R F
O L
K
V
IR
G
IN
IA
P -3
M
U L T
I- M
IS
S
IO
N
D R
Y D
O C
K
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C L A S S
IF
IE
D
UNCLASSIFIED
LBT/LBL
NBJ
EJA
DSN
SCALE: AS SHOWN
CHKDRWDES
CONSTR. CONTR. NO.
EPROJECT NO.: 1604959
C
U se rs
P u b lic
D o c u m e n ts
L o c a l_ R e v it
F ile s\ D
R Y
D S
W
TR
-1
-M te n v id
.r v t
/6
:5
:5
A
M
U T
IL
IT
Y E
N C
L O
S U
R E
M
E Z
Z A
N
IN
E A
N D
L O
W E
R R
O O
F P
L U
M B
IN
G
P L A
N
UP105
TJE DFA VAK
12823659
696 1029
PLAN NORTH
SCALE: 1/4" = 1'-0"
UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN
KEYNOTES
6"Ø SS VENT THRU ROOF.
3"Ø SS FROM LEVEL BELOW, TRANSITION TO 4"Ø SS 2'-0"
BELOW ROOF PENETRATION, 4"Ø SS VENT THRU ROOF.
4' 0' 4' 8'
1/4" = 1'-0"
A
M E
N D
M E
N T
/0 /2
V
M
1 1
MM
M
MM
S
S
M
M
S S
M M
M
M
FT
AI
FT
ZC
DO
TCV
ZI
AI
OV
ZC
DO
ZI
DI
OV
ZC
DO
ZI
DI
IS
MN
DI
MC
OC
DO
SI
AI
GA
DI
SC
AO
IS
OC
DD
MC
MN
DI
IS
OC
DD
MC
MN
DI
ZC
DO
OV
ZI
DI
LSL
DI
LSL
OV
FL
OV
FL
ZC
DO
OV
ZI
DI
ZC
DO
ZI
DI
ZC
DO
OV
MM
ZI
DI
ZC
DO
OV
LSH
DI
LSH
LSHH
DI
LSHH
LSH
DI
LSH
LSHH
DI
LSHH
TT
AI
TT
TT
AI
TT
OC
DO
UC
GA
DI
OC
DO
UC
GA
DI
TT
AI
TT
FT
AI
FT
TT
AI
TT
PCV
ZI
AI
ZC
AO
PT
AI
PT
PT
AI
PT
TT
AI
TT
TT
AI
TT
M
M
LSL
DI
LSL
LSLL
DI
LSLL
LSLL
DI
LSLL
ZC
DO
OV
OV
OV
OV
M
M
OV
ZC
DO
ZI
DI
OV
ZC
DO
ZI
DI
IS
MN
DI
OC
DO
SI
AI
GA
DI
SC
AO
TT
AI
TT
MC
OV
OV
S
S
PI
IS
MN
DI
MC
OC
DO
SI
AI
GA
DI
SC
AO
PT
AI
PT
PT
AI
PT
T
T
D E
S
IG
N F
L O
W G
P M
M A
X F
L O
W
,0
G
P M
T
8" ASWR
8" ASWS
3" FW
UE-P-1 PUMP (STANDBY)
DESIGN NOTES
118 °F
UE-P-2 PUMP (DUTY)
NONO
140 °F
UE-V-1
118 °F
85° F
DRY DOCK 1N
DESIGN FLOW:
600 GPM
EWT: 85 F
LWT: 140 F
2" BD
UE-CT-2
COOLING TOWER
(DUTY) (4) 10 HP FANS
BLOW DOWN
TO SANITARY
4" OVERFLOW
TO DRAIN
UE-SF-1
SIDE STREAM
FILTRATION SKID
2"
1-1/2"
1"
PURGE
TO SANITARY
2" BD
BLOW DOWN
TO SANITARY
4"
OVERFLOW
TO DRAIN
UE-SF-2
SIDE STREAM
FILTRATION SKID
2"
8" ASWS
1-1/2"
1"
PURGE
TO SANITARY
3" FW
F W
A S
W R
A S
W R
O U
T D
O O
R S
IN
D
O O
R S
N C
FLOW
METER
FLOW
METER
AMBIENT CONDITIONS
81°F WET BULB
COOLING TOWERS (TYPICAL FOR EACH TOWER)
EWT: 118°F
LWT: 85°F
APPROACH: 4°F
HEAT LOAD (FROM PNSY): 14,400,000 BTU/Hr
EVAPORATION RATE: 35 GPM
BLOW DOWN RATE: 12 GPM
MAKE UP RATE: 46 GPM
EACH DRY DOCK HAS IT'S OWN COMPLETE SYSTEM
WITH ASW PUMPS, COOLING TOWERS, SUMP TANKS,
FILTRATION SYSTEM, ETC.
A CROSS CONNECTION LINE IS PROVIDED BETWEEN
THE TWO INDEPENDENT SYSTEMS.
RIVER WATER CONSUMPTION
0 MGD
MS701
SCHEMATIC DD1E
DD1N ASW SUPPLY (BACKUP)NC
NC
NO
8" ASWS
I
I
TOWER
BYPASS
VALVE
M S
S
C H
E M
A T
IC
D
D
W T
O W
E R
C R
O S
S C
O N
N E
C T
IO
N
M S
S
C H
E M
A T
IC
D
D
W
T O
W E
R C
R O
S S
C O
N N
E C
T
IO
N
M S
S
C H
E M
A T
IC
D
D
N A
S W
P U
M P
C R
O S
S C
O N
N E
C T
IO
N
M S
S
C H
E M
A T
IC
D
D
N A
S W
P U
M P
C R
O S
S C
O N
N E
C T
IO
N
CROSS CONNECTION
FOR N+2 REDUNDANCY
AT DD1N AND DD1W
CROSS CONNECTION
FOR N+2 REDUNDANCY
AT DD1N AND DD1W
CROSS CONNECTION
FOR N+2 REDUNDANCY
AT DD1N AND DD1W
MS701
SCHEMATIC DD1E
DD1N ASW RETURN (BACKUP)
8" ASW BACKUP
PUMP CONNECTIONS
T
90 PSIP P
MS703
SCHEMATIC DD1N
FW MAKEUP FOR COOLING TOWERS
140 °F
85 °F
8" ASWR
NO
UE-ST-1 UE-ST-2
M S
S
C H
E M
A T
IC
D
D
W
T O
W E
R C
R O
S S
C O
N N
E C
T
IO
N
2" TO SUMP
TANK
V E
N T
3" FW3" FW
ASWS (COOLING TOWER WATER)
ASWR (COOLING TOWER WATER)
ASWS (SEA WATER)
ASWR (SEA WATER)
V E
N T
VFD
AUTOMATIC
FLOW
CONTROL
1000 GPM
N C
SUMP TANK SUMP TANK
I
2"2"
6" ASWS
6" ASWR
6"X8"
6"X8"8
B Y
P A
B Y
P A
8" ASWS
8" ASWS
8"
ASWS
8"
ASWS
MS704
SCHEMATIC WTP CHEMICAL FEED
SODIUM HYPOCHLORITE FEED
1/2" NaOCI
OUTDOORS
INDOORS
NO
UE-V-2
NO
UE-V-3
NO
U E
-V -4
N C
U E
-V -5
N C
U E
-V -6
A S
W R
A S
W R
4" ASWS
UE-CT-1A
COOLING TOWER
O U
T D
O O
R S
IN
D
O O
R S
II
T
VFD I
2" TO SUMP
TANK
2"
4" ASWS
UE-CT-1B
COOLING
TOWER
VFD I
8" ASWS 8" ASWS
GPM
GPM
PP
(10%
LOAD)
(10%
LOAD)
2"
NC
UE-V-13
NC
UE-V-14
UE-V-15 UE-V-16
UE-V-17
UE-V-18
UE-V-19
UE-V-20
U E
-V -3
PULSE POWERED
WATER TREATMENT
BID OPTION 006
SEE SPEC SECTION
23 25 00 2.6
GENERAL NOTES
1. REFER TO M-001 FOR SYMBOLS AND ABBREVIATIONS.
2. NOT ALL COMPONENTS ARE SHOWN. REFER TO DETAILS
AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.
K
IT
T E
R Y
M
A
IN
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SHEET
NAVFAC DRAWING NO.
OF
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
C A
P
IT
A L
IM
P
R O
V E
M E
N T
C O
R E
N A
V A
L S
T A
T
IO
N N
O R
F O
LK
, V
IR
G
IN
IA
P -3
M
U L T
I- M
IS
S
IO
N
D R
Y D
O C
K
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C L A S S
IF
IE
D
UNCLASSIFIED
LBT/LBL
NBJ
EJA
DSN
SCALE: AS SHOWN
CHKDRWDES
CONSTR. CONTR. NO.
EPROJECT NO.: 1604959
C
U se rs
P u b lic
D o c u m e n ts
L o c a l_ R e v it
F ile s\ D
R Y
D S
W
TR
-1
-M te n v id
.r v t
/6
:5
:4
A
M
A S
W S
C H
E M
A T
IC
D D
N
MS702
TJE DFA VAK
12823796
833 1029 N.T.S.
A3
ASW - SCHEMATIC DD1N
A
M E
N D
M E
N T
/0 /2
V
PI
M
MM
M
MM
S
S
M
M
M
M
M M
M
M
FT
AI
FT
ZC
AO
TCV
ZI
AI
OV
ZC
DO
ZI
DI
OV
ZC
DO
ZI
DI
OV
ZC
DO
ZI
DI
OV
ZC
DO
ZI
DI
IS
MN
DI
MC
OC
DO
SI
AI
GA
DI
SC
AO
IS
OC
DO
MC
MN
DI
IS
OC
DD
MC
MN
DI
ZC
DO
OV
ZI
DI
LSL
DI
LSL
OV
FL
OV
FL
ZC
DO
OV
ZI
DI
ZC
DO
OV
ZI
DI
ZC
DO
OV
MM
ZI
DI
ZC
DO
OV
LSH
DI
LSH
LSHH
DI
LSHH
LSH
DI
LSH
LSHH
DI
LSHH
TT
AI
TT
TT
AI
TT
OC
DO
UC
GA
DI
OC
DO
UC
GA
DI
TT
AI
TT
FT
AI
FT
IS
MN
DI
OC
DO
SI
AI
GA
DI
SC
AO
TT
AI
TT
TT
AI
TT
PCV
ZI
AI
ZC
AO
PT
AI
PT
PT
AI
PT
TT
AI
TT
TT
AI
TT
M
MC
M
LSL
DI
LSL
LSLL
DI
LSLL
LSLL
DI
LSLL
ZC
DO
OV
OV
OV
OV
OV
S
S S
S
PI
IS
MN
DI
MC
OC
DO
SI
AI
GA
DI
SC
AO
PT
AI
PT
PT
AI
PT
DRY DOCK 1W
DESIGN FLOW: 600
GPM
EWT: 85F
LWT: 140F
4" FW
UM710
UE FRESH WATER SCHEMATIC
FROM UTILITY ENCLOSURE
T
T
M
IN
F L O
W
G
P M
M A
X F
L O
W
,0
G
P M
A S
W R
A S
W R
4" ASWS
VFD
T
8" ASWR
8" ASWS
3" FW
UE-P-3 PUMP (STANDBY)
DESIGN NOTES
118 °F
UE-P-4 PUMP (DUTY)
NO
NO
140 °F118 °F
85° F
2" BD
UE-CT-3A
COOLING TOWER
UE-CT-4
COOLING TOWER
(100% LOAD)
BLOW
DOWN TO
SANITARY
4" OVERFLOW
TO DRAIN
UE-SF-3
SIDE STREAM
FILTRATION SKID
2"
1-1/2"
1"
PURGE
TO
SANITARY
2" BD
BLOW
DOWN TO
SANITARY
4"
OVERFLOW
TO DRAIN
UE-SF-4
SIDE STREAM
FILTRATION SKID
2"
8" ASWS
1-1/2"
1"
PURGE
TO
SANITARY
3" FW
F W
A S
W R
A S
W R
O U
T D
O O
R S
IN
D
O O
R S
O U
T D
O O
R S
IN
D
O O
R S
FLOW
METER
FLOW METER
AMBIENT CONDITIONS
81°F WET BULB
COOLING TOWERS (TYPICAL FOR EACH TOWER)
EWT: 118°F
LWT: 85°F
APPROACH: 4°F
HEAT LOAD (FROM PNSY): 14,400,000 BTU/Hr
EVAPORATION RATE: 35 GPM
BLOW DOWN RATE: 12 GPM
MAKE UP RATE: 46 GPM
EACH DRY DOCK HAS IT'S OWN COMPLETE SYSTEM
WITH ASW PUMPS, COOLING TOWERS, SUMP TANKS,
FILTRATION SYSTEM, ETC.
A CROSS CONNECTION LINE IS PROVIDED BETWEEN
THE TWO INDEPENDENT SYSTEMS.
RIVER WATER CONSUMPTION
0 MGD
MS701
SCHEMATIC DD1E
DD1W ASW SUPPLY (BACKUP)NC
NC
NO
8" ASWS
II II
I
TOWER
BYPASS
VALVE
M S
S
C H
E M
A T
IC
D
D
N T
O W
E R
C R
O S
S C
O N
N E
C T
IO
N
M S
S
C H
E M
A T
IC
D
D
N
T O
W E
R C
R O
S S
C O
N N
E C
T
IO
N
NC
NC
M S
S
C H
E M
A T
IC
D
D
N A
S W
P U
M P
C R
O S
S C
O N
N E
C T
IO
N
M S
S
C H
E M
A T
IC
D
D
N A
S W
P U
M P
C R
O S
S C
O N
N E
C T
IO
N
CROSS CONNECTION
FOR N+2 REDUNDANCY
AT DD1N AND DD1W
CROSS CONNECTION
FOR N+2 REDUNDANCY
AT DD1N AND DD1W
CROSS CONNECTION
FOR N+2 REDUNDANCY
AT DD1N AND DD1W
MS701
SCHEMATIC DD1E
DD1W ASW RETURN (BACKUP)
8" ASW BACKUP
PUMP CONNECTIONS
T T
90 PSIP
140 °F
8" ASWR
NO
UE-ST-3 UE-ST-4
VFD I
M S
S
C H
E M
A T
IC
D
D
N
T O
W E
R C
R O
S S
C O
N N
E C
T
IO
N
V E
N T
V E
N T
NO
3" FW3" FW
ASWS (COOLING TOWER WATER)
ASWR (COOLING TOWER WATER)
ASWS (SEA WATER)
ASWR (SEA WATER)
P
N C
SUMP TANK SUMP TANK
2"
8" ASWS
6" ASWS
6" ASWR 6"X8"
6"X8"
B Y
P A
B Y
P A
8"
ASWS
8"
ASWS
MS702
SCHEMATIC DD1N
FW MAKEUP FOR COOING TOWERS
3" FW
4"X3"
3"X4"
MS704
SCHEMATIC WTP CHEMICAL FEED
SODIUM HYPOCHLORITE FEED
1/2" NaOCl
2" TO SUMP
TANK
2" TO SUMP
TANK
OUTDOORS
INDOORS
UE-V-7
N C
NO
UE-V-8
UE-V-9
NO
U E
-V -1
N C
U E
-V -1
N C
U E
-V -1
4" ASWS
UE-CT-3B
COOLING
TOWER
VFD I
8" ASWS 8" ASWS
AUTOMATIC
FLOW
CONTROL
1000 GPM
GPM
GPM
PP
(10%
LOAD)
(10%
LOAD)
2"
UE-V-21
NC
UE-V-22
NC
UE-V-23
UE-V-24
UE-V-25
UE-V-26
UE-V-27
UE-V-28
UE-V-29
UE-V-30
U E
-V -3
PULSE POWERED
WATER TREATMENT
BID OPTION 006
SEE SPEC SECTION
23 25 00 2.6
GENERAL NOTES
1. REFER TO M-001 FOR SYMBOLS AND ABBREVIATIONS.
2. NOT ALL COMPONENTS ARE SHOWN. REFER TO DETAILS
AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.
K
IT
T E
R Y
M
A
IN
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SHEET
NAVFAC DRAWING NO.
OF
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
C A
P
IT
A L
IM
P
R O
V E
M E
N T
C O
R E
N A
V A
L S
T A
T
IO
N N
O R
F O
LK
, V
IR
G
IN
IA
P -3
M
U L T
I- M
IS
S
IO
N
D R
Y D
O C
K
DRAWFORM REVISION: 07 AUG 2018
UNCLASSIFIED
U N C L A S S
IF
IE
D
UNCLASSIFIED
LBT/LBL
NBJ
EJA
DSN
SCALE: AS SHOWN
CHKDRWDES
CONSTR. CONTR. NO.
EPROJECT NO.: 1604959
C
U se rs
P u b lic
D o c u m e n ts
L o c a l_ R e v it
F ile s\ D
R Y
D S
W
TR
-1
-M te n v id
.r v t
/6
:5
:5
A
M
A S
W S
C H
E M
A T
IC
D D
W
MS703
TJE DFA VAK
12823797
834 1029 N.T.S.
A3
ASW - SCHEMATIC DD1W
A
M E
N D
M E
N T
/0 /2
V
| MS702 - ASW SCHEMATIC - DD1N |
| Sheets |
| MS702 - ASW SCHEMATIC - DD1N |
| MS703 - ASW SCHEMATIC - DD1W |
| UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN |
| UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN |
| MS703 - ASW SCHEMATIC - DD1W |
| Sheets |
| MS702 - ASW SCHEMATIC - DD1N |
| MS703 - ASW SCHEMATIC - DD1W |
| UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN |
| UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN |
| PM601 - PUMP STATION - SCHEDULES - SHEET 1 OF 2 |
| Sheets |
| PM601 - PUMP STATION - SCHEDULES - SHEET 1 OF 2 |
| UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN |
| Sheets |
| MS702 - ASW SCHEMATIC - DD1N |
| MS703 - ASW SCHEMATIC - DD1W |
| UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN |
| UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN |
| UM601 - UTILITY ENCLOSURE - SCHEDULES - SHEET 1 OF 5 |
| Sheets |
| UM601 - UTILITY ENCLOSURE - SCHEDULES - SHEET 1 OF 5 |
| UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN |
| Sheets |
| MS702 - ASW SCHEMATIC - DD1N |
| MS703 - ASW SCHEMATIC - DD1W |
| UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN |
| UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN |
| 2021-01-14T16:41:40-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:42:15-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:42:15-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:42:16-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:42:16-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:43:46-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:43:47-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:43:47-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:43:47-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:43:59-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:44:54-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:45:59-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:46:59-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:46:59-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:46:59-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:47:00-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:47:00-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-14T16:47:01-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
File details come from the government source that posted it. Updated .