Amendment 12 - Pump Station and Utility Enclosure.pdf

PDF 2 MB Posted

Attached to
P-381 MULTI-MISSION DRY DOCK #1, PORTSMOUTH NAVAL SHIPYARD (PNSY), KITTERY MAINE
Solicitation number
N4008520R0021
Issued by

About this file

This federal solicitation is for design-build construction services for Dry Dock #1 at Portsmouth Naval Shipyard in Kittery, Maine. The project includes building two new dry dock sections labeled DD1N and DD1W to support maintenance and overhaul of Virginia Class submarines. Construction will comprise concrete floors, walls and a center wall separating the new sections, new pump well systems, a pump station building, crane rails, mooring hardware, mechanical and electrical utilities, tunnels and all necessary appurtenances. Modifications will also be made to the existing basin closure wall and Berths 1 and 11. The existing DD1 pump well will be connected to the new system and interior modified. The Navy Facilities Engineering Command is the contracting agency. The response due date and award date are not specified.

View the file

Other files

File Type Posted
AMENDMENT 0015.pdf PDF
Amendment 14 - 25 00 00.00 22.pdf PDF
Amendment 14 - Electrical dwgs.pdf PDF
AMENDMENT 0014.pdf PDF
Amendment 14 - Mechanical Dwgs.pdf PDF
Amendment 14 - Electrical One Line.pdf PDF
Amendment 14 - Fire Protection One Line.pdf PDF
Amendment 14 - Henderson Point Dwgs.pdf PDF
Amendment 14 - Nitrogren Overall Plan.pdf PDF
Amendment 14 - Panelboards.pdf PDF
Amendment 14 - 32 31 13.53.pdf PDF
Amendment 14 - Raychem RHW 2-hour fire-rated power cable.pdf PDF
Amendment 14 - Civil Site Dwgs.pdf PDF
Amendment 14 - 25 00 00.00 22_ASW_Control.pdf PDF
Amendment 14 - General Dwgs.pdf PDF
Amendment 13 - Hendersen Pt Site Dwgs.pdf PDF
Amendment 13 - General Dwgs.pdf PDF
Amendment 13 - Electrical Dwgs.pdf PDF
Amendment 13 - Mechanical Dwgs.pdf PDF
Amendment 13 - Structural Dwgs.pdf PDF
Amendment 13 - Geotech dwgs.pdf PDF
AMENDMENT 0013.pdf PDF
Amendment 0013 - Price Proposal Form (rev).pdf PDF
Amendment 13 - Civil Dwgs.pdf PDF
Amendment 13 - 40 95 00 App B - IO List.pdf PDF
Amendment 13 - Process dwgs.pdf PDF
AMENDMENT 0012.pdf PDF
Amendment 12 - Structural Drawings.pdf PDF
Amendment 12 - General Drawings.pdf PDF
Amendment 12 - 40 95 00 App B - IO List.pdf PDF
Amendment 12 - LightFixt_BOD_1_5_2021.pdf PDF
Amendment 12 - Electrical drawings.pdf PDF
Amendment 0011.pdf PDF
Amendment 10 - General dwgs.pdf PDF
Amendment 10 - Drydock 1 existing pumpwell valve arrangements drawings.pdf PDF
Amendment 10 - Geotech- Structural dwgs.pdf PDF
Amendment 10 - Architectural dwgs.pdf PDF
Amendment 10 - Electrical dwgs.pdf PDF
Amendment 10 - Mechanical.dwgs.pdf PDF
AMENDMENT 0010.pdf PDF
Amendment 10 - Civil dwgs.pdf PDF
Amendment 0009.pdf PDF
Amendment 8 - Structural.pdf PDF
Amendment 8 -mechanical.pdf PDF
01 50 00.00 22.pdf PDF
Amendment 8 - Geotech.pdf PDF
23 81 23.00 20.pdf PDF
Amendment 8 -Civil.pdf PDF
Amendment 8 -Structural Bld.pdf PDF
21 13 13.00 20.pdf PDF
Show 40 more

Latest 50 of 123 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EQUIP. PLATFORM

EL 24.67

GROUND LEVEL

EL 12.00

PS-101.1

PS-101.2

EL 44' - 0"

9 10

T.O. PARAPET WALL

EQUIP. PLATFORM

EL 24.67

GROUND LEVEL

EL 12.00

PS-101.3

PS-101.4

6 6

EL 44' - 0"

T Y

P

T Y

P

T.O. PARAPET WALL

EQUIP. PLATFORM

EL 24.67

GROUND LEVEL

EL 12.00

EL 44' - 0"

JK

3 9

35' - 8"

T.O. PARAPET WALL

9' - 9"

20' - 0"

EQUIP. PLATFORM

EL 24.67

GROUND LEVEL

EL 12.00

EL 44' - 0"

J K

PS-ST2.2

33 4 1

/2

8 5

T.O. PARAPET WALL

/2

/2

23' - 4 5/8" 4' - 2"

4' - 4"

2' - 2"

/2

13' - 6 3/8"

REMOVABLE SELF SUPPORTING WEATHER TIGHT

TRANSLUCENT SKYLIGHT

12" LOAD BEARING CONCRETE INSULATED PANELS, TYP.

LOUVER WITH BIRD/INSECT SCREEN. REFER DETAIL

A4/PA601 AND MECHANICAL DRAWINGS.

INSULATED FRP DOOR AND FRAME; REFER TO DOOR

SCHEDULE

BIRD DETERRENT SYSTEM POST AND WIRE; REMOVABLE.

INSULATED STAINLESS STEEL OVERHEAD COILING DOOR;

REFER TO DOOR SCHEDULE

EXTERIOR LIGHT, SEAL PENETRATIONS WEATHER TIGHT; TYP.8

9 PARAPET MOUNTED BIRD SPIKES

4 LIGHTING ROD; REFER TO ELECTRICAL DRAWINGS.

10 2" WIDE x 1/4" DEEP REVEALS, TYPICAL

11 PARAPET COPING.

12 LOUVER WITH BIRD/INSECT SCREEN FOR PIPE

PENETRATION; REFER TO PLUMBING. SEAL WEATHER TIGHT

SIMILAR TO DETAIL A4/PA601.

13 PIPE PENETRATIONS, TYPICAL. REFER TO MECHANICAL AND

PLUMBING DRAWINGS.

K

IT

T E

R Y

M

A

IN

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SHEET

NAVFAC DRAWING NO.

OF

EPROJECT NO.:

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

C A

P

IT

A L I

M P

R O

V E

M E

N T

C O

R E

N A

V A

L S

T A

T

IO

N N

O R

F O

L K

V

IR

G

IN

IA

P -3

M U

L T

I- M

IS

S

IO

N

D R

Y D

O C

K

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C L A S S

IF

IE

D

UNCLASSIFIED

EJA

DSN

NBJ

LBT/LBL

1604959

DES DRW CHK

CONSTR. CONTR. NO.

SCALE: AS SHOWN

C

U se rs

P u b lic

D o c u m e n ts

L o c a l_ R e v it F i le s\ D

R Y

D S

W

TR

-1

-A

C h a rl e s.

r a u .r v t

/6

/2

:3

:4

A

M

P U

M P

S T

A T

IO

N

B

U

IL

D

IN

G E

L E

V A

T

IO

N S

PA201

RJK CVR THC

12823432

469 1056SCALE: 1/8" = 1'-0" PA101 A2

EAST ELEVATION

SCALE: 1/8" = 1'-0" PA101 A4

WEST ELEVATION

SCALE: 1/8" = 1'-0" PA101 B2

NORTH ELEVATION

SCALE: 1/8" = 1'-0" PA101 C2

SOUTH ELEVATION

KEYNOTES

4' 0' 4' 8' 12' 16'

1/8" = 1'-0"

A m e n d m e n t

-0

-2

V

M G

SEALSEAL

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

MP

RO

VE

ME

NT

C

OR

E

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

SCALE: AS SHOWN

CHKDRWDES

CONSTR. CONTR. NO.

EPROJECT NO.: 1604959

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -M

_k m c k eo n.

rv t 1/

7/ 2 0

1:

0 7

:3

A M

PU

M

P

ST

AT

IO

N

SC

H

ED

U

LE

S

- S H

EE

T

O

F

PM601

TJE DFA VAK

12823457 494 1029

PS-UH-2 LOWER LEVEL HORIZONTAL 130 1750 1/4 1,550 50 118 125 130 115 1 T-STAT 310

PS-UH-1 MAIN LEVEL HORIZONTAL 130 1750 1/4 1,550 50 118 125 130 115 1 T-STAT 310

TAG ROOM SERVED SPEED

(RPM) HP AIRFLOW

(CFM)

EDB

(F)

LDB

(F)

INLET

PRESSURE

(PSIG)

COND

CAPACITY

(LBS/HR)

VOLTS PHASE

UNIT IDENTIFICATION

TYPE CAPACITY

(MBH)

FAN AIR STEAM ELECTRICAL

CONTROL

TYPE

OPERATING WEIGHT

(LBS.) NOTES

UNIT HEATER SCHEDULE

NOTES:

1. PROVIDE WITH SOLE PLATE.

2. BASIS OF DESIGN IS MANUFACTURER: FLYGT, MODEL: NP 3301 HT. REFER TO SPEC SECTION 23 64 30.

3. PROVIDE WITH COMBINATION AIR RELEASE VALVE.

4. BID OPTION 4 BASIS OF DESIGN MANUFACTURER: KSB, MODEL: KRT K 100-401/954UNC2-S. REFER TO SPEC SECTION 23 64 30.

PS-ASWP-4 DD1W DUTY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4 PS-ASWP-3 DD1N DUTY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4 PS-ASWP-2 DD1E STANDBY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4 PS-ASWP-1 DD1E DUTY SUBMERSIBLE FLANGED STARTER SEA WATER 85 1,000 224 74.4 234 96.1 105 1,780 480 3 2,080 1,2,3,4

TAG SYSTEM

SERVED REDUNDANCY FLUID TYPE

MAX FLUID

TEMP

(F)

FLOW

(GPM)

PUMP

HEAD

(FT)

EFFICIENCY

(%) BHP HP SPEED

(RPM) VOLTS PHASE

UNIT IDENTIFICATION

PUMP TYPE COUPLING

TYPE CONTROL

PERFORMANCE

PUMP MIN

FLOW

(GPM)

PUMP MOTOR ELECTRICAL

OPERATING

WEIGHT

(LBS.)

NOTES

ASW PUMP SCHEDULE

NOTES:

1. BASIS OF DESIGN: MANUFACTURER: RUSKIN, MODEL NUMBER ELF6350DMP.

2. PROVIDE LOUVER WITH INSECT SCREEN.

3. LOUVER MUST BE RATED FOR SEA COAST SERVICE.

PS-L-6 PIT VENT DRAINABLE STATIONARY 3 18 x 18 ALUMINUM 1,2,3 PS-L-5 PS-DHU-1 HOT EXHAUST DRAINABLE STATIONARY 1 12 x 12 ALUMINUM 1,2,3 PS-L-4 TUNNEL VENTILATION AIR INTAKE DRAINABLE STATIONARY 1 30 x 24 ALUMINUM 1,2,3 PS-L-3 PS-AHU-2 AIR INTAKE DRAINABLE STATIONARY 1 12 x 18 ALUMINUM 1,2,3 PS-L-2 PS-AHU-1 RELIEF AIR LOUVER DRAINABLE STATIONARY 1 36 x 42 ALUMINUM 1,2,3 PS-L-1 PS-AHU-1 AIR INTAKE LOUVER DRAINABLE STATIONARY 1 48 x 36 ALUMINUM 1,2,3

TAG UNIT/AREA SERVED

UNIT IDENTIFICATION

TYPE QUANTITY SIZE

H (IN) x W (IN) MATERIAL NOTES

LOUVER SCHEDULE

NOTES:

1. PROVIDE WITH REMOTE MOUNTED SUMP PUMP CONTROL PANEL.

2. BASIS OF DESIGN IS MANUFACTURER LIBERTY, MODEL NUMBER 1100 SERIES.

PS-SP-1 PUMP STATION

LOWER LEVEL SANITARY SUBMERSIBLE 2 80 40 1 1800 POLYETHYLENE 36 38

POWDER

COATED STEEL,

SEALED AND

VENTED

208 3 1,2

TAG LOCATION SYSTEM

SERVED TYPE QUANTITY FLOW

(GPM)

HEAD

(FT)

HP

(EA)

SPEED

(RPM) CONSTRUCTION DIAMETER

(IN)

DEPTH

(IN) BASIN COVER VOLTS PHASE

UNIT IDENTIFICATION PUMP BASIN ELECTRICAL

NOTES

SUMP PUMP SCHEDULE

NOTES:

1. BASIS OF DESIGN IS MANUFACTURER ZURN, MODEL NUMBER Z163.

2. BASIS OF DESIGN IS MANUFACTURER ZURN, MODEL NUMBER Z520.

3. BASIS OF DESIGN IS MANUFACTURER AERO, MODEL NUMBER 2F1-3036,

PS-SK-1 UTILITY SINK 1/2 1/2 2" 2" 2" 3

FLOOR MOUNTED 30" x 36" 14 GAUGE 304 STAINLESS STEEL UTILITY SINK.

PROVIDE WITH WALL MOUNTED FAUCET WITH 8" CENTERS, 6" SPOUT, 4"

WRIST BLADE HANDLES, AND 2.2 GPM AERATOR.

PS-RD-1 COMBINATION ROOF DRAIN AND

OVERFLOW ROOF DRAIN - - - SEE

PLANS - 2 15" DIAMETER COMBINATION MAIN ROOF AND OVERFLOW ROOF DRAIN

SET. PROVIDE WITH CAST IRON DOMES AND VANDAL PROOF SECURED...

PS-FD-1 FLOOR DRAIN - - SEE

PLANS

SEE

PLANS

SEE

PLANS 1

HEAVY DUTY ADJUSTABLE TOP CAST IRON FLOOR DRAIN WITH HEAVY

DUTY CAST IRON SLOTTED GRATE. PROVIDE WITH SEDIMENT BUCKET AND

ASSE 1072 APPROVED TRAP SEAL.

TAG FIXTURE COLD WATER

SUPPLY (IN)

HOT WATER

SUPPLY (IN)

TRAP SIZE

(IN)

DRAIN

SIZE (IN)

VENT SIZE

(IN) NOTES DESCRIPTION AND ACCESSORIES

PLUMBING FIXTURES SCHEDULE

NOTES:

1. BASIS OF DESIGN IS MANUFACTURER EEMAX, MODEL NUMBER ED024480T2T.

PS-WH-1 UTILITY SINK 18.19 x 3.74 12.14 24 480 29/PHASE 3 POINT OF USE ELECTRIC WATER HEATER 1

TAG FIXTURE SERVED L x W OR

DIA. (IN)

HEIGHT

(IN)

INPUT

(kW) VOLTS AMPS PHASE

UNIT IDENTIFICATION SIZE ELECTRICAL

DESCRIPTION/ACCESSORIES NOTES

INSTANTANEOUS DOMESTIC WATER HEATER SCHEDULE

NOTES:

1. BASIS OF DESIGN IS MANUFACTURER MUNTERS, MODEL NUMBER HC-300.

PS-DHU-1 PUMP STATION LOWER LEVEL 5.0 300 0.5 85.0 44.0 113 18.0 6,000 W 59 0.50 100.00 120.20 120 252 115 24 24 30 480 3 9.7 1

TAG ROOM SERVED

MOISTURE

REMOVAL

(LBS/HR)

AIRFLOW

(CFM)

ESP

(IN-WG)

EAT

(F)

EAT

(GR/LB)

LAT

(F)

LAT

(GR/LB)

REACT

HEATER

AIRFLOW

(CFM)

ESP

(IN-WG)

EAT

(F)

EAT

(GR/LB)

LAT

(F)

LAT

(GR/LB)

OPERATING

WEIGHT

(LBS)

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN) VOLTS PHASE AMPS

UNIT IDENTIFICATION PROCESS REGENERATION PHYSICAL CHARACTERISTICS ELECTRICAL

NOTES

DESICCANT DEHUMIDIFICATION UNIT SCHEDULE

NOTES:

PS-CRAC-1 IT ROOM 1.5 750 0.3 0.2 1 18.1 16.3 75.0 61.0 SCROLL 1 VARIABLE SPEED R-407C HOT GAS 16.1 DISPOSABLE 8 SELF-CONTAINED 20 27 56 300 208 1 16.9 25 LIEBERT MMD18A-PR074 1

TAG ROOM SERVED AIRFLOW

(CFM)

ESP

(IN-WG) HP NO OF

FANS

TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH)

EDB

(F)

EWB

(F) TYPE CIRCUITS STAGES REFRIG TYPE

TOTAL

CAPACITY

(MBH)

TYPE EFFICIENCY

(MERV)

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

OPERATING

WEIGHT

(LBS.)

VOLTS PHASE MCA MOP

UNIT IDENTIFICATION

NOMINAL

CAPACITY

(TONS)

FAN DX COOLING COIL COMPRESSOR REHEAT SECTION FILTER

CONFIG

PHYSICAL CHARACTERISTICS ELECTRICAL

MANUFACTURER MODEL NUMBER NOTES

COMPUTER ROOM AIR CONDITIONING UNIT

NOTES:

1. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE TTA24044D.

2. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE TTA07244D.

3. PROVIDE WITH CURB SUPPORT, 18" MIN HEIGHT. COORDINATE ROOF CURB WITH ROOF SLOPING TO MOUNT EQUIPMENT LEVEL.

4. CONDENSER COILS TO BE COATED FOR SEAWATER APPLICATION.

PS-ACCU-2 PS-AHU-02 6 12.9 DUAL 2 R-410A 1 0.5 40 36 41 279.0 480 3 14.0 20 2, 3, 4 PS-ACCU-1 PS-AHU-01 25 11.6 SCROLL 1 R-410A 2 1 45 46 94 856.8 480 3 49.0 60 1, 3, 4

TAG UNIT SERVED TYPE NO OF

CIRCUITS

REFRIG

TYPE

NO OF

FANS

HP

(EACH)

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

OPERATING

WEIGHT

(LBS)

VOLTS PHASE MCA MOP

UNIT IDENTIFICATION

CAPACITY

(TONS) EER

COMPRESSORS CONDENSER FANS PHYSICAL CHARACTERISTICS ELECTRICAL

NOTES

AIR COOLED CONDENSING UNIT SCHEDULE

NOTES:

1. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE CSAA014

2. BASIS OF DESIGN MANUFACTURER AND MODEL: TRANE CSAA004

3. COILS TO BE COATED FOR SEAWATER APPLICATION.

PS-AHU-2 CEILING-HUNG LOWER

LEVEL LOWER LEVEL 1,600 1,600 200 1.00 3.03 1 1.25 1.5 2,631 N/A N/A N/A N/A N/A 1,119 32.5 44.0 116.9 PLEATED MEDIA 8 0.533 64.1 57.4 78.80 60.90 46.00 45.78 0.688 R-410A TBD 480 3 23.95 25.00 2, 3

PS-AHU-1 FLOOR GROUND

LEVEL

GROUND LEVEL &

MEZZANINE 7,000 6,000 230 0.50 2.95 2 5.11 3.00 2,306 0.50 2.108 3.922 5 1514 3,008 86.5 72.0 106.3 PLEATED MEDIA 8 0.606 339.71 219.90 85.00 70.80 56.41 56.01 1.224 R-410A TBD 480 3 20.93 30.00 1, 3

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

TAG

MOUNTING

SUPPORT

STYLE

LOCATION AREA SERVED

MAX

SUPPLY

AIR

(CFM)

MIN

SUPPLY

AIR

(CFM)

MIN

OUTSIDE

AIR

(CFM)

ESP

(IN-WG)

TSP

(IN-WG) QTY. BHP HP SPEED

(RPM)

ESP

(IN-WG)

TSP

(IN-WG) BHP HP SPEED

(RPM)

OPERATING

WEIGHT

(LBS)

MAXIMUM UNIT DIMENSIONS

FILTER TYPE MERV

RATING

MAX APD

(IN-WG)

TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH)

EDB

(F)

EWB

(F)

LDB

(F)

LWB

(F)

MAX APD

(IN-WG)

REFRIG

TYPE

REFRIG

CHARGE VOLTS PHASE MCA MOP

UNIT IDENTIFICATION AIRFLOW SUPPLY FAN EXHAUST FAN PHYSICAL CHARACTERISTICS FILTER DX COOLING COIL ELECTRICAL

NOTES

AIR HANDLING UNIT SCHEDULE

NOTES:

1. REFER TO STRUCTURAL DRAWINGS FOR FLOOR GRILLE INFORMATION.

2. BASIS OF DESIGN MANUFACTURER: TITUS, MODEL 272FL.

3. BASIS OF DESIGN MANUFACTURER: TITUS MODEL US-DL.

4. BASIS OF DESIGN MANUFACTURER: TITUS MODEL TMR-AA

5. BASIS OF DESIGN MANUFACTURER: TITUS, MODEL 3FS.

6. PROVIDE ALL FRAMES AND ACCESSORIES AS REQUIRED FOR PROPER INSTALLATION.

7. PROVIDE UNIT WITH OPPOSED BLADED DAMPER.

8. COLOR TO BE SELECTED BY ARCHITECT FROM STANDARD COLORS.

PS-RG-2 SEE DRAWINGS 22 x 18 DUCT ALUMINUM 5, 6, 8

PS-RG-1 SEE DRAWINGS 28 X 24 DUCT ALUMINUM 5, 6, 8

PS-SD-4 SEE DRAWINGS 8 DUCT ALUMINUM 4, 6, 8

PS-SD-3 SEE DRAWINGS 18 x 6 DUCT ALUMINUM 3, 6, 7, 8 PS-SD-2 SEE DRAWINGS 12 x 12 DUCT ALUMINUM 2, 6, 8 PS-SD-1 SEE DRAWINGS 30 x 20 FLOOR STEEL 1

TAG FLOW RANGE

(CFM)

DUCT CONNECTION

SIZE (IN)

MOUNTING

TYPE MATERIAL NOTES

DIFFUSER AND GRILLE SCHEDULE

AM

E N D

M

EN

T

/0 8/

VM

G

M

A

B

C

D

2 3 4 5

1 2 3 4 5

A

B

C

D

F I L E

N

M

E

U

S F

S h a r e d P r o j e c t s s h a r e d c a d d i n s t r u m e n t a t i o n P

I d w g

Y O

U T

M

E

U

T I L I T

Y

E

N C

L O

S U

R

I O

C A

T I O

N

P

L

P

O

T T

E D

W e d n e s d a y

J a n u a r y p m

S E

R p r e l f

D E

P A

R T

M E

F

T

H

V

Y

EPROJECT NO.

SHEET

NAVFAC DRAWING NO.

N A

V A

L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

C

O M

M A

N D

S Y

M D

E S

C R

I P

T I O

N D

A T

E A

P P

R

SEAL

OF

N A

V A

L

F

A C

I L

I T

I E

S

E

N G

I N

E E

R I N

G

C

O M

M A

D

D

A

T L

A N

T I C

DRAWFORM REVISION: 07 AUG 2018

CHECK GRAPHIC SCALE BEFORE USING

P

U L

T I M

I S

S I O

N

D

Y

C

K

LBT / LBL

EJA

KEY PLAN

GRAPHIC SCALE

NBJ

DSN

1604959

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM / DM

BRANCH MANAGER

CHIEF ENG / ARCH

FIRE PROTECTION

DRWDES CHK

CONSTR. CONTR. NO.

SCALE:

A / E INFO

C A

P I T

A L

I M

P R

O V

E M

E N

T

C

O R

E N

A V

A L

S

T A

T I O

N

N

O R

F O

L K

V

I R

G I N

I A

P O

R T

S M

O U

V

I P

Y A

R D

K I T

T E

R Y

M

A I N

E

AS SHOWN

PI101

12823525

U T

I L

I T

Y

E

N C

L O

S U

C

A T

I O

N

P

L A

N

1/2" = 1'-0"

4' 3' 2' 1' 0 4'

PR PR RR

RIO-P1

PLAN

NORTH

UTILITY ENCLOSURE -

SECOND FLOOR PLAN

SCALE: 1/2" = 1'-0"

IT

ROOM

A M

E N

D M

E N

T

V

M G

AutoCAD SHX Text

UNCLASSIFIED

AutoCAD SHX Text

UNCLASSIFIED

AutoCAD SHX Text

UNCLASSIFIED

AutoCAD SHX Text

FE

PI102

12823526

P U

M P

I N

G

S

T A

T I O

N

I N

S T

R U

M E

N T

A T

I O

N

S

I T

E

P

L A

N

1/4" = 1'-0"

4' 0 4' 8'

PLAN

NORTH

PUMPING STATION GROUND

LEVEL INSTRUMENTATION PLAN

SCALE: 1/4" = 1'-0"

PLAN

NORTH

PUMPING STATION VALVE VAULTS

INSTRUMENTATION PLAN

SCALE: 1/4" = 1'-0"

DEWATERING WET WELL

BUBBLER LEVEL PANEL AND

PIPEWORK LOCATION

PI501

A4

PI503

A1

PI503

A4

PR PR RR

DRAINAGE WET WELL

BUBBLER LEVEL PANEL AND

PIPEWORK LOCATION

DP-LCP1 DP-LCP2 DP-LCP3

SCADA

WORKSTATION

CHART

RECORDER

DEWATERING PUMPING

STATION CONTROL

PANEL (DCP)

MDP-LCP1

MDP1 LOCAL

INDICATOR

PANEL

PI501

A1

PI503

A1

PI503

A4

INSTRUMENT AIR

SYSTEM

LEVEL FLOATS FOR WEST

VALVE VAULT SUMP

PI501

A4LEVEL FLOATS FOR EAST

VALVE VAULT SUMP

MDP-LCP2MDP-LCP3

MDP2 LOCAL

INDICATOR

PANEL

PI501

A1

MDP3 LOCAL

INDICATOR

PANEL

PI501

A1

A

B

C

D

2 3 4 5

1 2 3 4 5

A

B

C

D

F I

M

E

U

S F

S h a r e d P r o j e c t s s h a r e d c a d d i n s t r u m e n t a t i o n P

I d w g

Y O

M

E

P

U M

P I N

G

S

T A

T I O

N

I N

S T

R U

M E

N T

A T

I O

N

S

I T

E

P

L

P

O

T T

E D

W e d n e s d a y

J a n u a r y p m

E

R p r e l f

D E

P A

R T

M E

F

T

V

Y

EPROJECT NO.

SHEET

NAVFAC DRAWING NO.

N A

V A

L

F

A C

I L

I T

I E

S

E

N G

I N

E E

R I N

G

C

O M

M A

N D

S Y

M D

E S

C R

I P

T I O

N D

A T

E A

P P

R

SEAL

OF

N A

V A

L

F

A C

I L I T

I E

S

E

N G

I N

E E

R I N

G

C

O M

M A

D

A

T L A

N T

I C

DRAWFORM REVISION: 07 AUG 2018

CHECK GRAPHIC SCALE BEFORE USING

P

U L

T I M

I S

S I O

N

D

Y

C

K

LBT / LBL

EJA

KEY PLAN

GRAPHIC SCALE

NBJ

DSN

1604959

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

PM / DM

BRANCH MANAGER

CHIEF ENG / ARCH

FIRE PROTECTION

DRWDES CHK

CONSTR. CONTR. NO.

SCALE:

A / E INFO

C A

P I T

P R

O V

E M

E N

T

C

O R

E N

A V

A

T I O

N

N

O R

F O

L K

V

I R

G I N

I A

P O

R T

S M

O U

V

A L

S

H I P

Y A

R D

K I T

T E

R Y

M

A I N

E

AS SHOWN

A M

E N

D M

E N

T

V

M G

AutoCAD SHX Text

UNCLASSIFIED

AutoCAD SHX Text

UNCLASSIFIED

AutoCAD SHX Text

UNCLASSIFIED

AutoCAD SHX Text

AutoCAD SHX Text

A3

UM301

UE-PWT-2UE-PWT-1

PW

FILTER

CYLINDER

PW

FILTER

CYLINDER

CARBON

FILTER

(VENDOR

SKID)

SAND

FILTERS

D

D.4 E F

3.3

5.3

ION

EXCHANGE

CONDUCTIVITY

METER

A3

UM302

4 4

A2

UM303

1/2" NI

MATERIAL LIFT

UE-ML1

STAIR

UE-ST1

COOLING TOWER

SUPPORT

EQUIPMENT

UE-301

STAIR

UE-ST2

1/2" NI

1/2" NI

C

UE-DHW-HX-1

UE-V-25

NO

UE-V-24

NC

UE-ST-4

UE-ST-3UE-ST-1

UE-ST-2

UE-V-6

NC

UE-V-9

NO

UE-V-12

NC

UE-V-26

NC

UE-V-3

NO

UE-V-16

NO

UE-V-15

NO

UE-V-23

NO

C4

UM303

A4

UM303

UE-CT-1A-VFD

UE-CT-1B-VFD

UE-CT-2-VFD UE-CT-3A-VFD

UE-CT-3B-VFD

UE-CT-4-VFD

UE-SF-2

UE-P-2 UE-P-4

UE-SF-4

UE-P-3

UE-P-1

UE-SF-1

UE-SF-3

A2

UM506

2 1/2" LPS

3/4" LPC

BOP: 1' - 0"

8" ASWS

8" ASWS

8" ASWR

1 1/2" ASWR

A S

W S

8" ASWS

1 1/2" NaOCL

2" VENT

2" VENT

2" VENT

1 1/2" ASWR

8" ASWS

8" ASWS

8" ASWS

1 1/2" ASWR

8" ASWS

8" ASWS

10 12

4 4

UE-DD1N-OV-8

UE-DD1N-OV-6

UE-DD1N-OV-06

UE-DD1N-OV-08

UE-DD1N-OV-09

UE-DD1N-OV-10

UE-DD1W-OV-09

UE-DD1W-OV-10

1" DR

1" DR

1" DR

2" SUCTION

1 1/2" ASWR

2" SUCTION

2" SUCTION

1/2" REF(L)

1" REF(V)

1" REF(V)

1/2" REF(L)

BOP: 7' - 10"

BOP: 9' - 2"

BOP: 9' - 0"

1 1/2" NaOCL

8" ASWS

8" ASWS

1 1/2" NaOCL

UE-FT-01N

UE-FT-01W

GENERAL NOTES

1. BOD AND BOP ELEVATIONS ARE

RELATIVE TO THE ASSOCIATED

FLOOR ELEVATION.

2. REFER TO UM207 FOR PURE

WATER PIPING.

KEY PLAN

K

IT

T E

R Y

M

A

IN

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

C A

P

IT

A L

IM

P

R O

V E

M E

N T

C O

R E

N A

V A

L S

T A

T

IO

N N

O R

F O

LK

, V

IR

G

IN

IA

P -3

M

U L T

I- M

IS

S

IO

N

D R

Y D

O C

K

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C L A S S

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

SCALE: AS SHOWN

CHKDRWDES

CONSTR. CONTR. NO.

EPROJECT NO.: 1604959

C

U se rs

P u b lic

D o c u m e n ts

L o c a l_ R e v it

F ile s\ D

R Y

D S

W

TR

-1

-M te n v id

.r v t

/6

:5

:3

A

M

U T

IL

IT

Y E

N C

L O

S U

R E

T

H

IR

D F

L O

O R

P

IP

IN

G

P L A

N

UM204

TJE DFA VAK

12823615

652 1029

PLAN NORTH

SCALE: 1/4" = 1'-0"

UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN

KEYNOTES

1" DRAIN FROM SIDE STREAM FILTRATION SKID TO FLOOR

DRAIN.

8" ASWS DISTRIBUTION DOWN TO SECOND FLOOR. REFER

TO DRAWING UP103 FOR CONTINUATION.

8" ASWR UP FROM SECOND FLOOR. PIPE RISER CONTINUES

UP TO MEZZANINE LEVEL PLATFORM. REFER TO DRAWING

UM203 FOR CONTINUATION OF PIPE TO FLOOR BELOW.

PROVIDE 8" ASWS PIPING FROM 3,000 GALLON BUFFER

TANK TO SUCTION SIDE OF CIRCULATION PUMP. ROUTE

BOTTOM OF ASWS PIPE ELEVATION APPROXIMATELY 2'-0"

ABOVE FINISHED FLOOR FROM TANK OUTLET TO PUMP

SUCTION.

PROVIDE 1/2" NI PIPING AND ISOLATION VALVE. NI PIPING

DOWNSTREAM OF ISOLATION VALVE TO BE PROVIDED AS A

BID OPTION. REFER TO BID OPTION 003. REFER TO UM712

FOR NITROGEN BLANKET FIT UP.

ROUTE 3/4" CA LINE FROM FLOOR BELOW. PROVIDE 3/4" CA

SERVICE CONNECTION WITH VALVE AND CAP 3'-0" ABOVE

FINISHED FLOOR FOR GENERAL USE.

PROVIDE 2-1/2" LPS TO HEAT EXCHANGER, UE-DHW-HX-1.

3/4" LPC DOWN TO SECOND FLOOR FROM HEAT

EXCHANGER, UE-DHW-HX-1.

4" VENT UP TO ROOF FROM CONDENSATE PUMP SKID,

UE-CRU-1, LOCATED ON UTILITY ENCLOSURE TUNNEL.

4" OVERFLOW DRAIN DOWN FROM CONNECTION TO SUMP

TANK.

REFER TO UM203 FOR CONTINUATION OF PIPE.

REFER TO UM205 FOR CONTINUATION OF PIPE.

SIDE STREAM FILTRATION SKID - REFER TO CENTRIFUGAL

SIDE STREAM FILTER SCHEDULE ON DRAWING UM601 FOR

DETAILS.

REFRIGERANT PIPING FROM UE-AHU-1 UP TO UE-ACCU-1 ON

ROOF.

REFRIGERANT PIPING FROM UE-AHU-2 UP TO UE-ACCU-2 ON

ROOF.

REFRIGERANT PIPING FROM UE-CRAC-1 UP TO UE-ACCU-3

ON ROOF.

1/2" NI UP FROM SECOND FLOOR.

2" VENT UP FROM CHEMICAL FEED STATION TO THIRD

FLOOR.

SODIUM HYPOCHLORITE (NaOCL) CHEMICAL FEED STATION.

REFER TO MS704.

CHEMICAL INJECTION INTO ASW SYSTEM. REFER TO DETAIL

B2 ON UM505 AND MS704.

CONTROL PANEL FOR CHEMICAL FEED STATION.

4' 0' 4' 8'

1/4" = 1'-0"

A

M E

N D

M E

N T

/0 /2

V

M

K

IT

T E

R Y

M

A

IN

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

C A

P

IT

A L

I M

P R

O V

E M

E N

T C

O R

E N

A V

A L

S T

A T

IO

N

N O

R F

O L

K

V

IR

G

IN

IA

P -3

M

U L T

I- M

IS

S

IO

N

D R

Y D

O C

K

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C L A S S

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

SCALE: AS SHOWN

CHKDRWDES

CONSTR. CONTR. NO.

EPROJECT NO.: 1604959

C

U se rs

P u b lic

D o c u m e n ts

L o c a l_ R e v it

F ile s\ D

R Y

D S

W

TR

-1

-M te n v id

.r v t

/6

:1

:4

A

M

U T

IL

IT

Y E

N C

L O

S U

R E

S

C H

E D

U L E

S

S H

E E

T

O F

UM601

TJE DFA VAK

12823629

666 1029

NOTES:

1. PROVIDE BUFFER TANK WITH INTEGRAL SWEEPER SYSTEM. 2. PROVIDE WITH (1) 5 FT. LADDER SECTION AND SAFETY CAGE

3. BASIS OF DESIGN IS MANUFACTURER DELTA COOLING TOWERS.

UE-ST--4 CT-4 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3

UE-ST--3 CT-3 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3

UE-ST--2 CT-2 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3

UE-ST--1 CT-1 3,000 YES 102 97 CLOSED-TOP FRESH WATER 85.0 25,036 1, 2, 3

TAG

SYSTEM

SERVED

UNIT IDENTIFICATION

VOLUME

(GAL)

ASME

CONST

DIAMETER

(IN)

HEIGHT

(IN)

ARRANGEMENT SYSTEM FLUID

SYSTEM

TEMP

(F)

WEIGHT

(LBS)

NOTES

SUMP TANK SCHEDULE

NOTES:

1. PROVIDE WITH INERTIA BASE.

2. BASIS OF DESIGN IS MANUFACTURER BELL AND GOSSETT, MODEL NUMBER VSX-VSCS 4X6X17.5A.

3. PROVIDE PUMPS WITH FACTORY APPLIED EPOXY COATING TO THE PUMP INTERNAL CASING.

UE-P-4 DD1W STANDBY DOUBLE SUCTION SPLIT CASE FLEXIBLE

REDUCED VOLTAGE

SOFT START

FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3

UE-P-3 DD1W DUTY DOUBLE SUCTION SPLIT CASE FLEXIBLE

REDUCED VOLTAGE

SOFT START

FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3

UE-P-2 DD1N STANDBY DOUBLE SUCTION SPLIT CASE FLEXIBLE

REDUCED VOLTAGE

SOFT START

FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3

UE-P-1 DD1N DUTY DOUBLE SUCTION SPLIT CASE FLEXIBLE

REDUCED VOLTAGE

SOFT START

FRESH WATER 85 1,000.0 175 1500 74 300 76.7 100 1,800 480 3 1207 1,2,3

TAG

SYSTEM

SERVED

REDUNDANCY FLUID TYPE

FLUID

TEMP

(F)

FLOW

(GPM)

PUMP

HEAD

(FT)

OVERLOAD

FLOW

(GPM)

MIN

EFFICIENCY

BHP HP

SPEED

(RPM)

VOLTS PHASE

UNIT IDENTIFICATION

PUMP TYPE

COUPLING

TYPE

CONTROL

PERFORMANCE

PUMP MIN

FLOW

(GPM)

PUMP MOTOR ELECTRICAL

OPERATING

WEIGHT

(LBS.)

NOTES

CIRCULATION PUMP SCHEDULE

NOTES:

1. BASIS OF DESIGN IS MANUFACTURER PUROFLUX, MODEL NUMBER PF-64-015. ISOLATION VALVES PROVIDED WITH UNIT.

2. PROVIDE UNIT WITH NEMA 4X CONTROL PANEL WITH DISCONNECT, MOTOR OVERLOAD PROTECTION, ADJUSTABLE PURGE TIMER, AND HOA SWITCHES

UE-SF-4 CT-4 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2

UE-SF-3 CT-3 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2

UE-SF-2 CT-2 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2

UE-SF-1 CT-1 80.0 2" 1-1/2" 28" 30" 332 60 3,600 3 460 3 3.8 4.7 1,2

TAG

SYSTEM

SERVED

INLET SIZE

(IN)

OUTLET

SIZE

(IN)

WIDTH

(IN)

LENGTH

(IN)

OPERATING

WEIGHT

(LBS)

MAX HEAD

(FT)

SPEED

(RPM)

HP VOLTS PHASE

FLA

(AMPS)

MCA

(AMPS)

UNIT IDENTIFICATION

FLOW

(GPM)

CENTRIFUGAL SEPARATOR PUMP DATA

NOTES

CENTRIFUGAL SIDE STREAM FILTER SCHEDULE

NOTES:

1. REMOTE SUMP. REFER TO SUMP TANK SCHEDULE.

2. BASIS OF DESIGN IS MANUFACTURER DELTA COOLING TOWERS, INC., MODEL NUMBER TM-210412.

3. BASIS OF DESIGN MANUFACTURER IS DELTA COOLING TOWERS, INC., MODEL NUMBER DT-70I.

4. BID OPTION 6 INCLUDES A CHEMICAL FREE TREATMENT SYSTEM FOR DD1N AND DD1W (QTY 2). REFER TO SPEC SECTION 23 25 00 TREATMENT OF WATER FOR MECHANICAL SYSTEMS.

5. VFD PROVIDED BY COOLING TOWER VENDOR.

UE-CT-4 DD1W INDUCED DRAFT COUNTERFLOW HDPE 1,050 118 85 81 158,000 4 10 460 3 24,600 190 204 198 1,2,4,5

UE-CT-3B DD1W INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5

UE-CT-3A DD1W INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5

UE-CT-2 DD1N INDUCED DRAFT COUNTERFLOW HDPE 1,050 118 85 81 158,000 4 10 460 3 24,600 190 204 198 1,2,4,5 UE-CT-1B DD1N INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5

UE-CT-1A DD1N INDUCED DRAFT COUNTERFLOW HDPE 75 125 85 81 13,100 1 3 460 3 4,050 146 84 84 1,3,4,5

TAG SYSTEM SERVED

FLOW

(GPM)

EWT

(F)

LWT

(F)

AMBIENT

AIR WB

(F)

AIRFLOW

(CFM)

NO OF

FANS

HP

(EACH)

VOLTS PHASE

OPERATING

WEIGHT

(LBS)

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

UNIT IDENTIFICATION

TYPE TOWER MATERIAL

PERFORMANCE FANS DIMENSIONS

NOTES

COOLING TOWER SCHEDULE

WH WHEELER UTILITY ENCLOSURE 55 55 VACUUM VACUUM GALVANIZED STEEL / GROOVED FIELD UP TO 4" SCH. 40 NO - - PIPE STAND OR CLEVIS HANGER GALVANIZED

ST STORM UTILITY ENCLOSURE - - GRAVITY GRAVITY CAST IRON / HUB AND SPIGOT FIELD 3" TO 6" - NO - - CLEVIS HANGER OR U-BOLT GALVANIZED

SS SANITARY / SEWER UTILITY ENCLOSURE - - GRAVITY GRAVITY COPPER / SOLDER JOINTS FIELD UP TO 2-1/2" DWV NO - - CLEVIS HANGER OR U-BOLT COPPER

SS SANITARY / SEWER UTILITY ENCLOSURE - - GRAVITY GRAVITY CAST IRON / HUB AND SPIGOT FIELD 3" TO 6" - NO - - CLEVIS HANGER OR U-BOLT GALVANIZED

CW COLD WATER UTILITY ENCLOSURE 45-65 55 70 150 COPPER / SOLDER JOINTS FIELD UP TO 2-1/2" TYPE L OR K YES CELLULAR GLASS PVC CLEVIS HANGER OR U-BOLT COPPER

FW FRESH WATER UTILITY ENCLOSURE 45-65 55 70 150 DUCTILE IRON / FLANGED FIELD 3" TO 8" CLASS 52 OR 53 YES CELLULAR GLASS ALUMINUM CLEVIS HANGER OR U-BOLT GALVANIZED

ASW AUXILIARY SEA / TOWER WATER UTILITY ENCLOSURE 65-140 140 90 150 PP-R (BLUE PIPE), SDR 11, MF FIELD UP TO 10" SDR 11 NO - - PIPE STAND OR CLEVIS ROLLER STAINLESS STEEL

NI NITROGEN UTILITY ENCLOSURE 65 65 200 250 STAINLESS STEEL TUBE, TYPE 316 FIELD UP TO 3/4" 3000 PSI NO - - CLEVIS ROLLER OR CLAMP STAINLESS STEEL

CA COMPRESSED AIR UTILITY ENCLOSURE 65 100 125 150 BLACK STEEL, PE/PVC COATED FIELD UP TO 2" SCH. 40 NO - - ROLLER HANGER OR U-BOLT GALVANIZED CR CONDENSATE RETURN UTILITY ENCLOSURE 200 250 - 125 BLACK STEEL FIELD UP TO 2" SCH. 80 YES CELLULAR GLASS ALUMINUM ROLLER HANGER GALVANIZED

HPS HIGH PRESSURE STEAM UTILITY ENCLOSURE 410 450 125 150 BLACK STEEL FIELD UP TO 8" SCH. 80 YES CELLULAR GLASS ALUMINUM ROLLER HANGER GALVANIZED

LPS LOW PRESSURE STEAM (15 psig) UTILITY ENCLOSURE 250 300 15 125 BLACK STEEL FIELD UP TO 3" SCH. 40 YES CELLULAR GLASS ALUMINUM ROLLER HANGER GALVANIZED

PW PURE WATER UTILITY ENCLOSURE 55 55 100 150 STAINLESS STEEL TYPE 316 FIELD UP TO 2" SCH. 40S NO - - PIPE CLAMP OR PIPE STRAP STAINLESS STEEL

HPA HIGH PRESSURE AIR UTILITY ENCLOSURE 70 100 4500 6000 COPPER-NICKEL 70-30 FIELD UP TO 1" CLASS 6000 NO - - PIPE CLAMP STAINLESS STEEL

TAG NAME LOCATION OPERATING DESIGN OPERATING DESIGN

SYSTEM TEMPERATURE (DEG) PRESSURE (PSI)

CARRIER PIPE MATERIAL PIPE SYSTEM

DIAMETER

RANGE

SCHEDULE OR CLASS YES / NO MATERIAL JACKET TYPE MATERIAL

SYSTEM DESIGN CONDITIONS PIPING INSULATION TYPICAL SUPPORTS

MECHANICAL PIPING SCHEDULE

NOTES:

1. BASIS OF DESIGN IS MANUFACTURER AMERICAN COMPRESSOR COMPANY, MODEL NUMBER 55H75.

2. REFER TO BID OPTION 003.

UE-HPAC-2 UTILITY ENCLOSURE STAND-ALONE 85 REDUCED VOLTAGE SOFT START 114 82 59 7,000 75 460 3 89 1,2

UE-HPAC-1 UTILITY ENCLOSURE STAND-ALONE 85 REDUCED VOLTAGE SOFT START 114 82 59 7,000 75 460 3 89 1,2

TAG LOCATION TYPE

SCFM @

5,000 PSIG

STARTER

LENGTH

(IN)

WIDTH

(IN)

HEIGHT

(IN)

WEIGHT

(LBS)

HP VOLTS PHASE FLA

UNIT IDENTIFICATION CHARACTERISTICS ELECTRICAL

NOTES

HIGH PRESSURE AIR COMPRESSOR SCHEDULE

NOTES:

1. BASIS OF DESIGN IS MANUFACTURER CPI INDUSTRIES.

2. REFER TO BID OPTION 003.

UE-TK-4 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2

UE-TK-3 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2

UE-TK-2 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2

UE-TK-1 UE-HPAC-1,2 80 YES 20 96 VERTICAL HPA 5,000 7,500 4,530 1,2

TAG

SYSTEM

SERVED

UNIT IDENTIFICATION

VOLUME

(GAL)

ASME

CONSTRUCTION

DIAMETER

(IN OD)

HEIGHT

(IN)

ARRANGEMENT

SYSTEM

FLUID

DESIGN

PRESS

(PSIG)

TEST

PRESS

(PSIG)

WEIGHT

(LBS)

NOTES

FLASK TANK SCHEDULE

A

M E

N D

M E

N T

/1 /2

V

M G

A

M E

N D

M E

N T

/0 /2

V

M G

D.4 E F

3.3

5.3

4" ST

4"Ø ST OVERFLOW DN

FROM ROOF DRAIN

4"Ø ST PRIMARY DN

FROM ROOF DRAIN

6" ST

6" ST

4"Ø ST OVERFLOW DN

FROM ROOF DRAIN

4"Ø ST PRIMARY DN

FROM ROOF DRAIN 4" ST

6"Ø ST OVERFLOW

DN TO THIRD FLOOR

6"Ø ST PRIMARY DN

TO THIRD FLOOR

C

A2

UM506

UE-RD-1

UE-RD-1

UE-RD-1

4"Ø FW FROM

LEVEL BELOW

3" FW

3" FW

3" FW

3" FW

3" FW

3" FW

3"Ø ST OVERFLOW

DN TO THIRD FLOOR

3"Ø ST PRIMARY

DN TO THIRD

FLOOR

3"Ø ST PRIMARY DN

FROM ROOF DRAIN

3"Ø ST OVERFLOW DN

FROM ROOF DRAIN

4" DR

4" DR 4" DR

4" DR

3" ST

3" ST

3"Ø ST CLEANOUT

3"Ø ST

CLEANOUT

4" ST

BOP: 20' - 4"

BOP: 19' - 9"

BOP: 20' - 2"

BOP: 19' - 7"

BOP: 16' - 6"

BOP: 20' - 6"

BOP: 20' - 6"

BOP: 20' - 0"

BOP: 20' - 0"BOP: 20' - 0"

BOP: 16' - 7" BOP: 16' - 6"

BOP: 16' - 5"

BOP: 23' - 2"

BOP: 23' - 7"

BOP: 23' - 4"

BOP: 22' - 11"

BOP: 22' - 10"

BOP: 22' - 10"

UE-FT-02N

UE-FT-02W

GENERAL NOTES

1. BOD AND BOP ELEVATIONS ARE

RELATIVE TO THE ASSOCIATED

FLOOR ELEVATION.

KEY PLAN

K

IT

T E

R Y

M

A

IN

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

C A

P

IT

A L

I M

P R

O V

E M

E N

T C

O R

E N

A V

A L

S T

A T

IO

N

N O

R F

O L

K

V

IR

G

IN

IA

P -3

M

U L T

I- M

IS

S

IO

N

D R

Y D

O C

K

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C L A S S

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

SCALE: AS SHOWN

CHKDRWDES

CONSTR. CONTR. NO.

EPROJECT NO.: 1604959

C

U se rs

P u b lic

D o c u m e n ts

L o c a l_ R e v it

F ile s\ D

R Y

D S

W

TR

-1

-M te n v id

.r v t

/6

:5

:5

A

M

U T

IL

IT

Y E

N C

L O

S U

R E

M

E Z

Z A

N

IN

E A

N D

L O

W E

R R

O O

F P

L U

M B

IN

G

P L A

N

UP105

TJE DFA VAK

12823659

696 1029

PLAN NORTH

SCALE: 1/4" = 1'-0"

UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN

KEYNOTES

6"Ø SS VENT THRU ROOF.

3"Ø SS FROM LEVEL BELOW, TRANSITION TO 4"Ø SS 2'-0"

BELOW ROOF PENETRATION, 4"Ø SS VENT THRU ROOF.

4' 0' 4' 8'

1/4" = 1'-0"

A

M E

N D

M E

N T

/0 /2

V

M

1 1

MM

M

MM

S

S

M

M

S S

M M

M

M

FT

AI

FT

ZC

DO

TCV

ZI

AI

OV

ZC

DO

ZI

DI

OV

ZC

DO

ZI

DI

IS

MN

DI

MC

OC

DO

SI

AI

GA

DI

SC

AO

IS

OC

DD

MC

MN

DI

IS

OC

DD

MC

MN

DI

ZC

DO

OV

ZI

DI

LSL

DI

LSL

OV

FL

OV

FL

ZC

DO

OV

ZI

DI

ZC

DO

ZI

DI

ZC

DO

OV

MM

ZI

DI

ZC

DO

OV

LSH

DI

LSH

LSHH

DI

LSHH

LSH

DI

LSH

LSHH

DI

LSHH

TT

AI

TT

TT

AI

TT

OC

DO

UC

GA

DI

OC

DO

UC

GA

DI

TT

AI

TT

FT

AI

FT

TT

AI

TT

PCV

ZI

AI

ZC

AO

PT

AI

PT

PT

AI

PT

TT

AI

TT

TT

AI

TT

M

M

LSL

DI

LSL

LSLL

DI

LSLL

LSLL

DI

LSLL

ZC

DO

OV

OV

OV

OV

M

M

OV

ZC

DO

ZI

DI

OV

ZC

DO

ZI

DI

IS

MN

DI

OC

DO

SI

AI

GA

DI

SC

AO

TT

AI

TT

MC

OV

OV

S

S

PI

IS

MN

DI

MC

OC

DO

SI

AI

GA

DI

SC

AO

PT

AI

PT

PT

AI

PT

T

T

D E

S

IG

N F

L O

W G

P M

M A

X F

L O

W

,0

G

P M

T

8" ASWR

8" ASWS

3" FW

UE-P-1 PUMP (STANDBY)

DESIGN NOTES

118 °F

UE-P-2 PUMP (DUTY)

NONO

140 °F

UE-V-1

118 °F

85° F

DRY DOCK 1N

DESIGN FLOW:

600 GPM

EWT: 85 F

LWT: 140 F

2" BD

UE-CT-2

COOLING TOWER

(DUTY) (4) 10 HP FANS

BLOW DOWN

TO SANITARY

4" OVERFLOW

TO DRAIN

UE-SF-1

SIDE STREAM

FILTRATION SKID

2"

1-1/2"

1"

PURGE

TO SANITARY

2" BD

BLOW DOWN

TO SANITARY

4"

OVERFLOW

TO DRAIN

UE-SF-2

SIDE STREAM

FILTRATION SKID

2"

8" ASWS

1-1/2"

1"

PURGE

TO SANITARY

3" FW

F W

A S

W R

A S

W R

O U

T D

O O

R S

IN

D

O O

R S

N C

FLOW

METER

FLOW

METER

AMBIENT CONDITIONS

81°F WET BULB

COOLING TOWERS (TYPICAL FOR EACH TOWER)

EWT: 118°F

LWT: 85°F

APPROACH: 4°F

HEAT LOAD (FROM PNSY): 14,400,000 BTU/Hr

EVAPORATION RATE: 35 GPM

BLOW DOWN RATE: 12 GPM

MAKE UP RATE: 46 GPM

EACH DRY DOCK HAS IT'S OWN COMPLETE SYSTEM

WITH ASW PUMPS, COOLING TOWERS, SUMP TANKS,

FILTRATION SYSTEM, ETC.

A CROSS CONNECTION LINE IS PROVIDED BETWEEN

THE TWO INDEPENDENT SYSTEMS.

RIVER WATER CONSUMPTION

0 MGD

MS701

SCHEMATIC DD1E

DD1N ASW SUPPLY (BACKUP)NC

NC

NO

8" ASWS

I

I

TOWER

BYPASS

VALVE

M S

S

C H

E M

A T

IC

D

D

W T

O W

E R

C R

O S

S C

O N

N E

C T

IO

N

M S

S

C H

E M

A T

IC

D

D

W

T O

W E

R C

R O

S S

C O

N N

E C

T

IO

N

M S

S

C H

E M

A T

IC

D

D

N A

S W

P U

M P

C R

O S

S C

O N

N E

C T

IO

N

M S

S

C H

E M

A T

IC

D

D

N A

S W

P U

M P

C R

O S

S C

O N

N E

C T

IO

N

CROSS CONNECTION

FOR N+2 REDUNDANCY

AT DD1N AND DD1W

CROSS CONNECTION

FOR N+2 REDUNDANCY

AT DD1N AND DD1W

CROSS CONNECTION

FOR N+2 REDUNDANCY

AT DD1N AND DD1W

MS701

SCHEMATIC DD1E

DD1N ASW RETURN (BACKUP)

8" ASW BACKUP

PUMP CONNECTIONS

T

90 PSIP P

MS703

SCHEMATIC DD1N

FW MAKEUP FOR COOLING TOWERS

140 °F

85 °F

8" ASWR

NO

UE-ST-1 UE-ST-2

M S

S

C H

E M

A T

IC

D

D

W

T O

W E

R C

R O

S S

C O

N N

E C

T

IO

N

2" TO SUMP

TANK

V E

N T

3" FW3" FW

ASWS (COOLING TOWER WATER)

ASWR (COOLING TOWER WATER)

ASWS (SEA WATER)

ASWR (SEA WATER)

V E

N T

VFD

AUTOMATIC

FLOW

CONTROL

1000 GPM

N C

SUMP TANK SUMP TANK

I

2"2"

6" ASWS

6" ASWR

6"X8"

6"X8"8

B Y

P A

B Y

P A

8" ASWS

8" ASWS

8"

ASWS

8"

ASWS

MS704

SCHEMATIC WTP CHEMICAL FEED

SODIUM HYPOCHLORITE FEED

1/2" NaOCI

OUTDOORS

INDOORS

NO

UE-V-2

NO

UE-V-3

NO

U E

-V -4

N C

U E

-V -5

N C

U E

-V -6

A S

W R

A S

W R

4" ASWS

UE-CT-1A

COOLING TOWER

O U

T D

O O

R S

IN

D

O O

R S

II

T

VFD I

2" TO SUMP

TANK

2"

4" ASWS

UE-CT-1B

COOLING

TOWER

VFD I

8" ASWS 8" ASWS

GPM

GPM

PP

(10%

LOAD)

(10%

LOAD)

2"

NC

UE-V-13

NC

UE-V-14

UE-V-15 UE-V-16

UE-V-17

UE-V-18

UE-V-19

UE-V-20

U E

-V -3

PULSE POWERED

WATER TREATMENT

BID OPTION 006

SEE SPEC SECTION

23 25 00 2.6

GENERAL NOTES

1. REFER TO M-001 FOR SYMBOLS AND ABBREVIATIONS.

2. NOT ALL COMPONENTS ARE SHOWN. REFER TO DETAILS

AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.

K

IT

T E

R Y

M

A

IN

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

C A

P

IT

A L

IM

P

R O

V E

M E

N T

C O

R E

N A

V A

L S

T A

T

IO

N N

O R

F O

LK

, V

IR

G

IN

IA

P -3

M

U L T

I- M

IS

S

IO

N

D R

Y D

O C

K

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C L A S S

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

SCALE: AS SHOWN

CHKDRWDES

CONSTR. CONTR. NO.

EPROJECT NO.: 1604959

C

U se rs

P u b lic

D o c u m e n ts

L o c a l_ R e v it

F ile s\ D

R Y

D S

W

TR

-1

-M te n v id

.r v t

/6

:5

:4

A

M

A S

W S

C H

E M

A T

IC

D D

N

MS702

TJE DFA VAK

12823796

833 1029 N.T.S.

A3

ASW - SCHEMATIC DD1N

A

M E

N D

M E

N T

/0 /2

V

PI

M

MM

M

MM

S

S

M

M

M

M

M M

M

M

FT

AI

FT

ZC

AO

TCV

ZI

AI

OV

ZC

DO

ZI

DI

OV

ZC

DO

ZI

DI

OV

ZC

DO

ZI

DI

OV

ZC

DO

ZI

DI

IS

MN

DI

MC

OC

DO

SI

AI

GA

DI

SC

AO

IS

OC

DO

MC

MN

DI

IS

OC

DD

MC

MN

DI

ZC

DO

OV

ZI

DI

LSL

DI

LSL

OV

FL

OV

FL

ZC

DO

OV

ZI

DI

ZC

DO

OV

ZI

DI

ZC

DO

OV

MM

ZI

DI

ZC

DO

OV

LSH

DI

LSH

LSHH

DI

LSHH

LSH

DI

LSH

LSHH

DI

LSHH

TT

AI

TT

TT

AI

TT

OC

DO

UC

GA

DI

OC

DO

UC

GA

DI

TT

AI

TT

FT

AI

FT

IS

MN

DI

OC

DO

SI

AI

GA

DI

SC

AO

TT

AI

TT

TT

AI

TT

PCV

ZI

AI

ZC

AO

PT

AI

PT

PT

AI

PT

TT

AI

TT

TT

AI

TT

M

MC

M

LSL

DI

LSL

LSLL

DI

LSLL

LSLL

DI

LSLL

ZC

DO

OV

OV

OV

OV

OV

S

S S

S

PI

IS

MN

DI

MC

OC

DO

SI

AI

GA

DI

SC

AO

PT

AI

PT

PT

AI

PT

DRY DOCK 1W

DESIGN FLOW: 600

GPM

EWT: 85F

LWT: 140F

4" FW

UM710

UE FRESH WATER SCHEMATIC

FROM UTILITY ENCLOSURE

T

T

M

IN

F L O

W

G

P M

M A

X F

L O

W

,0

G

P M

A S

W R

A S

W R

4" ASWS

VFD

T

8" ASWR

8" ASWS

3" FW

UE-P-3 PUMP (STANDBY)

DESIGN NOTES

118 °F

UE-P-4 PUMP (DUTY)

NO

NO

140 °F118 °F

85° F

2" BD

UE-CT-3A

COOLING TOWER

UE-CT-4

COOLING TOWER

(100% LOAD)

BLOW

DOWN TO

SANITARY

4" OVERFLOW

TO DRAIN

UE-SF-3

SIDE STREAM

FILTRATION SKID

2"

1-1/2"

1"

PURGE

TO

SANITARY

2" BD

BLOW

DOWN TO

SANITARY

4"

OVERFLOW

TO DRAIN

UE-SF-4

SIDE STREAM

FILTRATION SKID

2"

8" ASWS

1-1/2"

1"

PURGE

TO

SANITARY

3" FW

F W

A S

W R

A S

W R

O U

T D

O O

R S

IN

D

O O

R S

O U

T D

O O

R S

IN

D

O O

R S

FLOW

METER

FLOW METER

AMBIENT CONDITIONS

81°F WET BULB

COOLING TOWERS (TYPICAL FOR EACH TOWER)

EWT: 118°F

LWT: 85°F

APPROACH: 4°F

HEAT LOAD (FROM PNSY): 14,400,000 BTU/Hr

EVAPORATION RATE: 35 GPM

BLOW DOWN RATE: 12 GPM

MAKE UP RATE: 46 GPM

EACH DRY DOCK HAS IT'S OWN COMPLETE SYSTEM

WITH ASW PUMPS, COOLING TOWERS, SUMP TANKS,

FILTRATION SYSTEM, ETC.

A CROSS CONNECTION LINE IS PROVIDED BETWEEN

THE TWO INDEPENDENT SYSTEMS.

RIVER WATER CONSUMPTION

0 MGD

MS701

SCHEMATIC DD1E

DD1W ASW SUPPLY (BACKUP)NC

NC

NO

8" ASWS

II II

I

TOWER

BYPASS

VALVE

M S

S

C H

E M

A T

IC

D

D

N T

O W

E R

C R

O S

S C

O N

N E

C T

IO

N

M S

S

C H

E M

A T

IC

D

D

N

T O

W E

R C

R O

S S

C O

N N

E C

T

IO

N

NC

NC

M S

S

C H

E M

A T

IC

D

D

N A

S W

P U

M P

C R

O S

S C

O N

N E

C T

IO

N

M S

S

C H

E M

A T

IC

D

D

N A

S W

P U

M P

C R

O S

S C

O N

N E

C T

IO

N

CROSS CONNECTION

FOR N+2 REDUNDANCY

AT DD1N AND DD1W

CROSS CONNECTION

FOR N+2 REDUNDANCY

AT DD1N AND DD1W

CROSS CONNECTION

FOR N+2 REDUNDANCY

AT DD1N AND DD1W

MS701

SCHEMATIC DD1E

DD1W ASW RETURN (BACKUP)

8" ASW BACKUP

PUMP CONNECTIONS

T T

90 PSIP

140 °F

8" ASWR

NO

UE-ST-3 UE-ST-4

VFD I

M S

S

C H

E M

A T

IC

D

D

N

T O

W E

R C

R O

S S

C O

N N

E C

T

IO

N

V E

N T

V E

N T

NO

3" FW3" FW

ASWS (COOLING TOWER WATER)

ASWR (COOLING TOWER WATER)

ASWS (SEA WATER)

ASWR (SEA WATER)

P

N C

SUMP TANK SUMP TANK

2"

8" ASWS

6" ASWS

6" ASWR 6"X8"

6"X8"

B Y

P A

B Y

P A

8"

ASWS

8"

ASWS

MS702

SCHEMATIC DD1N

FW MAKEUP FOR COOING TOWERS

3" FW

4"X3"

3"X4"

MS704

SCHEMATIC WTP CHEMICAL FEED

SODIUM HYPOCHLORITE FEED

1/2" NaOCl

2" TO SUMP

TANK

2" TO SUMP

TANK

OUTDOORS

INDOORS

UE-V-7

N C

NO

UE-V-8

UE-V-9

NO

U E

-V -1

N C

U E

-V -1

N C

U E

-V -1

4" ASWS

UE-CT-3B

COOLING

TOWER

VFD I

8" ASWS 8" ASWS

AUTOMATIC

FLOW

CONTROL

1000 GPM

GPM

GPM

PP

(10%

LOAD)

(10%

LOAD)

2"

UE-V-21

NC

UE-V-22

NC

UE-V-23

UE-V-24

UE-V-25

UE-V-26

UE-V-27

UE-V-28

UE-V-29

UE-V-30

U E

-V -3

PULSE POWERED

WATER TREATMENT

BID OPTION 006

SEE SPEC SECTION

23 25 00 2.6

GENERAL NOTES

1. REFER TO M-001 FOR SYMBOLS AND ABBREVIATIONS.

2. NOT ALL COMPONENTS ARE SHOWN. REFER TO DETAILS

AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.

K

IT

T E

R Y

M

A

IN

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

M

ID

-A

T L A

N T

IC

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

C A

P

IT

A L

IM

P

R O

V E

M E

N T

C O

R E

N A

V A

L S

T A

T

IO

N N

O R

F O

LK

, V

IR

G

IN

IA

P -3

M

U L T

I- M

IS

S

IO

N

D R

Y D

O C

K

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C L A S S

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

SCALE: AS SHOWN

CHKDRWDES

CONSTR. CONTR. NO.

EPROJECT NO.: 1604959

C

U se rs

P u b lic

D o c u m e n ts

L o c a l_ R e v it

F ile s\ D

R Y

D S

W

TR

-1

-M te n v id

.r v t

/6

:5

:5

A

M

A S

W S

C H

E M

A T

IC

D D

W

MS703

TJE DFA VAK

12823797

834 1029 N.T.S.

A3

ASW - SCHEMATIC DD1W

A

M E

N D

M E

N T

/0 /2

V

MS702 - ASW SCHEMATIC - DD1N
Sheets
MS702 - ASW SCHEMATIC - DD1N
MS703 - ASW SCHEMATIC - DD1W
UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN
UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN
MS703 - ASW SCHEMATIC - DD1W
Sheets
MS702 - ASW SCHEMATIC - DD1N
MS703 - ASW SCHEMATIC - DD1W
UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN
UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN
PM601 - PUMP STATION - SCHEDULES - SHEET 1 OF 2
Sheets
PM601 - PUMP STATION - SCHEDULES - SHEET 1 OF 2
UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN
Sheets
MS702 - ASW SCHEMATIC - DD1N
MS703 - ASW SCHEMATIC - DD1W
UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN
UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN
UM601 - UTILITY ENCLOSURE - SCHEDULES - SHEET 1 OF 5
Sheets
UM601 - UTILITY ENCLOSURE - SCHEDULES - SHEET 1 OF 5
UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN
Sheets
MS702 - ASW SCHEMATIC - DD1N
MS703 - ASW SCHEMATIC - DD1W
UM204 - UTILITY ENCLOSURE - THIRD FLOOR PIPING PLAN
UP105 - UTILITY ENCLOSURE - MEZZANINE AND LOWER ROOF PLUMBING PLAN
2021-01-14T16:41:40-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:42:15-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:42:15-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:42:16-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:42:16-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:43:46-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:43:47-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:43:47-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:43:47-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:43:59-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:44:54-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:45:59-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:46:59-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:46:59-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:46:59-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:47:00-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:47:00-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-14T16:47:01-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.

File details come from the government source that posted it. Updated .