Amendment 10 - Electrical dwgs.pdf

PDF 6 MB Posted

Attached to
P-381 MULTI-MISSION DRY DOCK #1, PORTSMOUTH NAVAL SHIPYARD (PNSY), KITTERY MAINE
Solicitation number
N4008520R0021
Issued by

About this file

This solicitation is for a design-bid-build construction project to expand Dry Dock #1 located at Portsmouth Naval Shipyard in Kittery, Maine. The project will construct two new dry dock bays, labeled Dry Dock #1 North and Dry Dock #1 West, within the existing superflood basin area. The existing Dry Dock #1 will be renamed Dry Dock #1 East. The new construction will include concrete floors, walls and a center wall separating the new bays, new pumpwell systems, a new pump station building, portal crane rails, mooring hardware, mechanical and electrical utilities, utility tunnels, and all necessary appurtenances to ensure operational dry docks. Modifications will also be made to the existing basin closure wall and Berths 1 and 11 to support fully dewatered conditions and prevent undermining. The existing Dry Dock #1 pumpwell will be connected to the new pumpwell system and interior modified. The Navy Facilities Engineering Command is the issuing agency.

View the file

Other files

File Type Posted
AMENDMENT 0015.pdf PDF
Amendment 14 - 25 00 00.00 22.pdf PDF
Amendment 14 - Electrical dwgs.pdf PDF
AMENDMENT 0014.pdf PDF
Amendment 14 - Mechanical Dwgs.pdf PDF
Amendment 14 - Electrical One Line.pdf PDF
Amendment 14 - Fire Protection One Line.pdf PDF
Amendment 14 - Henderson Point Dwgs.pdf PDF
Amendment 14 - Nitrogren Overall Plan.pdf PDF
Amendment 14 - Panelboards.pdf PDF
Amendment 14 - 32 31 13.53.pdf PDF
Amendment 14 - Raychem RHW 2-hour fire-rated power cable.pdf PDF
Amendment 14 - Civil Site Dwgs.pdf PDF
Amendment 14 - 25 00 00.00 22_ASW_Control.pdf PDF
Amendment 14 - General Dwgs.pdf PDF
Amendment 13 - Hendersen Pt Site Dwgs.pdf PDF
Amendment 13 - General Dwgs.pdf PDF
Amendment 13 - Electrical Dwgs.pdf PDF
Amendment 13 - Mechanical Dwgs.pdf PDF
Amendment 13 - Structural Dwgs.pdf PDF
Amendment 13 - Geotech dwgs.pdf PDF
AMENDMENT 0013.pdf PDF
Amendment 0013 - Price Proposal Form (rev).pdf PDF
Amendment 13 - Civil Dwgs.pdf PDF
Amendment 13 - 40 95 00 App B - IO List.pdf PDF
Amendment 13 - Process dwgs.pdf PDF
AMENDMENT 0012.pdf PDF
Amendment 12 - Structural Drawings.pdf PDF
Amendment 12 - General Drawings.pdf PDF
Amendment 12 - 40 95 00 App B - IO List.pdf PDF
Amendment 12 - LightFixt_BOD_1_5_2021.pdf PDF
Amendment 12 - Pump Station and Utility Enclosure.pdf PDF
Amendment 12 - Electrical drawings.pdf PDF
Amendment 0011.pdf PDF
Amendment 10 - General dwgs.pdf PDF
Amendment 10 - Drydock 1 existing pumpwell valve arrangements drawings.pdf PDF
Amendment 10 - Geotech- Structural dwgs.pdf PDF
Amendment 10 - Architectural dwgs.pdf PDF
Amendment 10 - Mechanical.dwgs.pdf PDF
AMENDMENT 0010.pdf PDF
Amendment 10 - Civil dwgs.pdf PDF
Amendment 0009.pdf PDF
Amendment 8 - Structural.pdf PDF
Amendment 8 -mechanical.pdf PDF
01 50 00.00 22.pdf PDF
Amendment 8 - Geotech.pdf PDF
23 81 23.00 20.pdf PDF
Amendment 8 -Civil.pdf PDF
Amendment 8 -Structural Bld.pdf PDF
21 13 13.00 20.pdf PDF
Show 40 more

Latest 50 of 123 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SE

E

DW

G

. E D1 x x x x

U V

U

ED402

x x

ED402

ED401

3-5B

3-2B x x

U V

P1

C7C1

3-6A

BB

x

SUBSTATION

3 VAULT

P3P2 x x x x xx

P6

C26 C37C5

P13

P8 P11

P7 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x xx x x x x

U V

P6 P13 P19 P22 P27 V xC8 C10 C36

P14 P15

C22 C23 C35 C40 C43C12

... C38

P8 P23P12 x

C9 C35 ...

TYP

JB-B

x x x x x x x

EXISTING UTILITY TUNNEL BELOW DECK

CAPSTAN

CAPSTAN

CONTROL

CABINET

x x x

O

P

P9 P10

7 7

KEY PLAN KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 2:

P

M

D

EM

O

LI

TI

O

N P

LA

N

D

D 1N

A N

D C

EN

TE

R W

AL

L

- E

AS

T

ED102

12823887

PLAN NORTH

SCALE: 1" = 20'-0"

DEMOLITION PLAN - DD1N - EAST

KEYNOTES

DISCONNECT AND REMOVE 350 KW GENERATOR, TRANSFER

SWITCH AND ASSOCIATED EQUIPMENT. SEE ED402 FOR REMOVAL

OF GENERATOR FEEDERS.

SEE DETAILS ON ED401 AND ED402 FOR INTERIOR PUMP STATION

DEMOLITION.

INDICATES THE REMOVAL OF CIRCUITS BETWEEN AND INCLUDING

THE FEEDER TAGS INDICATED.

DISCONNECT AND REMOVE 30' HIGH-MAST LIGHT POLE AT

EXTERIOR OF TUNNEL ENTRANCE.

EXISTING UTILITY TUNNEL TO BE REMOVED. SEE DWG. ED403 FOR

DEMOLITION OF ELECTRICAL ITEMS WITHIN TUNNEL.

REMOVE EMPTY 1" AND 1-1/2" CONDUITS ON BACK OF UTILITY

TUNNEL CURB.

PROVIDE SELECTIVE DEMOLITION OF MANHOLE SO THAT SOUTH

PORTION CONTAINING CONDUITS TO GALLERY 2 IS SALVAGED FOR

RE-USE.

GRADE AT THIS MANHOLE WILL BE RAISED DURING

CONSTRUCTION. REMOVE EXISTING GRADE RINGS AND ENTRANCE

CASTING. PROVIDE REPLACEMENT GRADE RINGS AND CASTING TO

BRING MANHOLE ENTRANCE UP TO FINAL GRADE. COORDINATE

WITH CIVIL GRADE DRAWINGS.

20' 0 20' 40' 1" = 20'

GENERAL NOTES

EL. 9.70 + 12.0

1.

2.

3.

4.

5.

6.

7.

SEE DRAWING ED601 AND ED602 FOR DEMOLITION SINGLE LINE

DIAGRAM.

SEE DRAWINGS ED603, ED604 AND ED605 FOR DEMOLITION CONDUIT

AND WIRE SCHEDULES.

EXCEPT AS NOTED FOR SALVAGEABLE ITEMS, LEGALLY DISPOSE OF

ALL DEMOLISHED ITEMS.

SALVAGEABLE ITEMS MUST BE TURNED OVER TO THE GOVERNMENT.

CARE MUST BE TAKEN TO PREVENT DAMAGE TO THE ITEM.

EXISTING DD1 PUMPWELL MUST REMAIN OPERATIONAL UNTIL NEW

PUMP STATION IS OPERATIONAL. WORK MUST BE SEQUENCED

ACCORDINGLY.

EXISTING DD1 CAISSON, CAPSTAN, AND GALLERY 2 AND 4

ELECTRICAL SERVICES MUST REMAIN OPERATIONAL DURING

CONSTRUCTION EXCEPT FOR REQUIRED SHUTDOWNS TO CUTOVER

TEMPORARY OR PERMANENT SERVICES. SHUTDOWNS MUST BE

LIMITED TO 8 HOURS OR A LESSER TIME PERIOD. SEE GENERAL

CONDITIONS AND PROJECT SCHEDULE FOR FURTHER

CLARIFICATION.

SEE CIVIL DEMOLITION DRAWINGS FOR EXTENT OF EXISTING DUCT

BANKS AND MANHOLE REMOVALS.

SE

E

ED

FO

R

CO

NT

IN

UA

TI

O N

Am en dm en t 1

-2 0 -20

CS

ASALVAGEABLE ITEMS

350 KW GENERATOR

GENERATOR TRANSFER SWITCH (ASCO 7000)

GENERATOR CONNECTION BOX

GENERATOR LOAD BANK

30' HIGH MAST LIGHT POLE

E

ES

FO

R C

O N

TI

N

U

AT

IO

N

2UGEUGE AC-512

AC-528

T,FT,FT,FT,F

T,F

T,F

T,F

T,F

T,F

T,FT,FT,F T,F

T,FT,FT,F T,FT,FT,F T,F

T, F

T, F

EXISTING

IP OUTLET

AC-2952

602601

6026011

DP1

60187

73110111112113

114115116117292

LP1-WCW

END POINT OF

EXISTING DUCT

BANK

UG

E

85602601

878685

878685

878685

T,F

SE

E

ES

FO

R C

O N

TI

N

U

AT

IO

N

LC17-EAST

SP

UG

E

UG

E

UGE

UG

E

EXISTING UTILITY TUNNEL

HB16

TC1W-S3

FC-8

LC17-WEST

VAULT

UGEUGEUGE

UG

E

UG

E

KEY PLAN KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 2:

P

M

D D

1W P

O W

ER

A

N D

T

EL

C O

M P

LA

N

EA

ST

ES105

12823912

PLAN NORTH

SCALE: 1" = 20'-0"

PLAN-DD1W - EAST

KEYNOTES

ROUTE COMMUNICATIONS CABLE IN UTILITY TUNNEL ON

CABLE RACKS. SPACE RACKS 3'-0" APART AND COORDINATE

WITH EXISTING MECHANICAL PIPING.

PROVIDE MANHOLE, SEE DETAIL B4/ES516 AND MANHOLE

SCHEDULE ON ES605 FOR SIZE.

EXISTING 2 - OUTLET INDUSTRIAL POWER STATION.

PROVIDE (4) 5" CONDUITS FROM LC17-WEST VAULT TO LC17-

EAST 480V SWITCHGEAR SECTION. PROVIDE 1-1/2" UNISTRUT

SUPPORT SYSTEM FOR VERTICAL RISERS FROM VAULT.

ROUTE OVERHEAD TO TOP OF LC17-EAST.

EXISTING 12-OUTLET SHORE POWER STATION.

PROVIDE 120V CIRCUITS TO HOT BOX HEATER(S). SEE SITE

CIRCUIT SCHEDULE ON ES605 AND DETAIL C4/ES515.

DUCTBANK FROM LC17 VAULT TO AC-513 AND 34' NORTH OF

AC-513 IS EXISTING, EXTEND FROM END POINT TO MANHOLE

AC-512.

REMOVE EXISTING LC17-EAST NEMA 3R TOP SECTION AND

REPLACE WITH A CUSTOM TOP TO ALLOW CONDUIT ENTRY

FROM THE TOP SIDE. REPLACEMENT TOP SECTION MUST BE

INSTALLED BY A MANUFACTURERS TECHNICIAN.

UTILIZE SPARE 4" CONDUIT IN EXISTING DUCT BANK.

PROVIDE TELCOM CABINET PER DETAIL A5/ES502.

20' 0 20' 40' 1" = 20'

GENERAL NOTES

EL. 9.7 + 12.0

1.

2.

3.

4.

5.

6.

7.

SEE SINGLE LINE DIAGRAMS ON DRAWINGS ES606 TO ES609

AND CONDUIT AND WIRE SCHEDULES ON DRAWINGS ES601 TO

ES604 FOR CONDUIT AND CONDUCTOR SIZES.

SEE DRAWING ES405 TO ES409 FOR ELECTRICAL UTILITY

TUNNEL WORK BELOW THIS ELEVATION.

EXISTING UNDERGROUND ITEMS ARE NOT SHOWN IN EXACT

LOCATIONS OR TO EXACT SCALE. CONSULT CIVIL DRAWINGS

FOR MORE DETAILED UNDERGROUND UTILITY DEPICTIONS.

PERFORM A UFPO BEFORE INSTALLING ANY UNDERGROUND

WORK. VERIFY EXISTING COMPONENTS AND REPORT ANY

CONFLICTS TO THE ENGINEER BEFORE BEGINNING.

SEE PROFILE DRAWING (ES200 SERIES) FOR UNDERGROUND

DUCT CONFIGURATIONS LANDSIDE OF DRY DOCKS.

SEE DRAWING ES518 FOR DUCT BANK CONFIGURATIONS

INDICATED ON THIS DRAWING.

SEE DRAWING ES503 FOR CONDUIT PENETRATION

REQUIREMENTS.

PROVIDE CONDUIT EXPANSION FITTINGS WHEN CROSSING

UTILITY TUNNEL EXPANSION JOINTS.

Am e n dm en t 1

-2 0 -20

CS

A

FE

E

ES

FO

R

CO

NT

IN

UA

TI

O N

PS-LV-S-29

LHE

PS-LV-S-29

LHE

LHE

PS-LV-S-29

LV

LV LV LV LV LV LV

LTLTLTLTLT LT

LTLTLTLTLT LT

UE-LV-S-29

29 29 29 29 UE-LV-S-28

PS-LV-S-2727272727 27

PS-LV-S-3333333333 33

LV 23 LV LV LV LV23 23 23 PS-LV-S-23

LVLV LV LV2525 25 PS-LV-S-25

LV LP1-WCW-3 LV LV LV LV LV3 3 3 3 LP1-WCW-1

TYP

LHE

PS-LV-S-29

LI LI LI LI LI LI

TYP

TYP

LT

LT 33

LHE

LHE

LHE

LHE

LHE

LHEPS-LV-S-29

PS-LV-S-29 PS-LV-S-29 PS-LV-S-29

PS-LV-S-29 PS-LV-S-29

UGE UGE UGE UGE UGE

LY 27 LY 27

LY LY33 33 LY 33

LY 27 LY

LY 33

27 LY

LY

LY LY

LYLY

LP-3Y-8,10 LP-3Y-8,10 LP-3Y-8,10 LP-3Y-8,10 LP-3Y-8,10 LP-3Y-8,10

TYP

TYP

TYP

KEY PLAN KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 2:

P

M

D D

1N L

IG

H

TI

N

G P

LA

N

W

ES

T

ES108

12823915

PLAN NORTH

SCALE: 1" = 20'-0"

LIGHTING PLAN DD1 - WEST

KEYNOTES

PROVIDE BULK HEAD LIGHT AT TOP OF DRY DOCK WALL.

POWER FROM INDICATED PANEL WITH (2) #8 & (1) #10 GND

IN 1" RGC. ROUTE CONDUIT FOR FIXTURE POWER

THROUGH DD1N UTILITY TUNNEL.

PROVIDE BULK HEAD LIGHT AT TOP OF DRY DOCK WALL.

POWER EACH CIRCUIT FROM INDICATED PANEL WITH (2) #

10 & (1) #10 GND IN 1" RGC ROUTE CONDUIT FOR FIXTURE

POWER THROUGH CENTERWALL UTILITY TUNNEL. REFER

TO DETAILS ON DRAWING ES513 FOR FURTHER

CLARIFICATION.

PROVIDE BULK HEAD LIGHT AT TOP OF DRY DOCK WALL.

POWER EACH CIRCUIT FROM INDICATED PANEL WITH (2) #8

& (1) #10 GND IN 1" RGC ROUTE CONDUIT FOR FIXTURE

POWER THROUGH DD1W UTILITY TUNNEL. REFER TO

DRAWING ES105 FOR LP1-WCW PANEL LOCATION.

PROVIDE POLE MOUNTED LIGHT FIXTURE AT SURFACE OF

CENTERWALL. POWER EACH CIRCUIT FROM INDICATED

PANEL WITH (2) #10 & (1) #10 GND IN 1" RGC ROUTE

CONDUIT FOR FIXTURE POWER THROUGH CENTERWALL

UTILITY TUNNEL. REFER TO DETAILS ON DRAWING ES513

FOR FURTHER CLARIFICATION.

POLE MOUNTED LIGHTS MUST BE CONTROLLED TO TURN

ON VIA PHOTOCELL ON FIRST POLE IN CIRCUIT, AND TURN

OFF VIA PROGRAMMED TIMECLOCK. LIGHTING CONTROL

PANEL WITH TIMECLOCK WILL BE ADJACENT TO PANEL

LP-3Y IN A NEMA 4X ENCLOSURE. REFER TO DRAWING

ES512 FOR LIGHTING CONTROLLER DETAIL.

PROVIDE POLE MOUNTED LIGHTING. POWER EACH CIRCUIT

FROM 120/208V AC PANEL LP-3Y LOCATED IN SOUTHWEST

CORNER OF BUILDING 175. PROVIDE (2) #10 & (1) #10 GND IN

1" RGC REFER TO DRAWING ES511 FOR POLE BASE DETAIL.

UNDERGROUND CONDUIT FOR LIGHT POLE POWER IS TO

BE DIRECT-BURIAL A MINIMUM OF 50" BELOW CRANE RAILS.

20' 0 20' 40' 1" = 20'

GENERAL NOTES

1. SEE DRAWING ES514 FOR LUMINAIRE SCHEDULE.

EL. 9.7 + 12.0

Am en dm en t 1

-2 0 -20

CS

A

E

ES

FO

R C

O N

TI

N

U

AT

IO

N

TYP

TYP

TYP

LT LT

LT

LTLTLT

LT

LV LV LV LV

LV

LV LV LVUE-LV-S-28

28 28

UE-LV-S-25 25 25 25

UE-LV-S-20

26262626

UE-LV-S-26

LV LP1-WCW-1 LV LV1 1

LV UE-LV-S-27 LV LV LV27 27 27

LT LTLTLTLT 20 20202020

LILI

TYP

TYP

TYP

LI LI

TYP

UGE UGE UGE

UGE

LY 26 LY

LT

LY 26 LY 26 LY 26

LY LY

LT

LY LY LY LY20 20

20 20 20

LY

LP-3Y-8,10 LP-3Y-8,10 LP-3Y-8,10 LP-3Y-8,10

KEY PLAN KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 3:

P

M

D D

1N L

IG

H

TI

N

G P

LA

N

EA

ST

ES109

12823916

PLAN NORTH

SCALE: 1" = 20'-0"

LIGHTING PLAN DD1 - EAST

KEYNOTES

PROVIDE BULK HEAD LIGHT AT TOP OF DRY DOCK WALL.

POWER EACH CIRCUIT FROM INDICATED PANEL WITH (2) #

10 & (1) #10 GND IN 1" RGC ROUTE CONDUIT FOR FIXTURE

POWER THROUGH DD1N UTILITY TUNNEL.

PROVIDE BULK HEAD LIGHT AT TOP OF DRY DOCK WALL.

POWER EACH CIRCUIT FROM INDICATED PANEL WITH (2) #

10 & (1) #10 GND IN 1" RGC ROUTE CONDUIT FOR FIXTURE

POWER THROUGH CENTERWALL UTILITY TUNNEL.

PROVIDE BULK HEAD LIGHT AT TOP OF DRY DOCK WALL.

POWER EACH CIRCUIT FROM INDICATED PANEL WITH (2) #

10 & (1) #10 GND IN 1" RGC ROUTE CONDUIT FOR FIXTURE

POWER THROUGH DD1W UTILITY TUNNEL. REFER TO

DRAWING ES105 FOR LP1-WCW PANEL LOCATION.

PROVIDE POLE MOUNTED LIGHT FIXTURE AT SURFACE OF

CENTERWALL. POWER EACH CIRCUIT FROM INDICATED

PANEL WITH (2) #10 & (1) #10 GND IN 1" RGC ROUTE

CONDUIT FOR FIXTURE POWER THROUGH CENTERWALL

UTILITY TUNNEL.

POLE MOUNTED LIGHTS MUST BE CONTROLLED TO TURN

ON VIA PHOTOCELL ON FIRST POLE IN CIRCUIT, AND

TURN OFF VIA PROGRAMMED TIMECLOCK. LIGHTING

CONTROL PANEL WITH TIMECLOCK WILL BE ADJACENT

TO PANEL LP-3Y IN A NEMA4X ENCLOSURE. REFER TO

DRAWING ES512 FOR LIGHTING CONTROLLER DETAIL.

PROVIDE POLE MOUNTED LIGHTING. POWER EACH

CIRCUIT FROM 120/208V AC PANEL LP-3Y LOCATED IN

SOUTHWEST CORNER OF BUILDING 175. PROVIDE (2) #10

& (1) #10 GND IN 1" RGC REFER TO DRAWING ES511 FOR

POLE BASE DETAIL. UNDERGROUND CONDUIT FOR LIGHT

POLE POWER IS TO BE DIRECT-BURIAL A MINIMUM OF 50"

BELOW CRANE RAILS.

CIRCUIT TO LIGHTING CONTROLLER IN SUBSTATION 3,

SEE DWG. ES411 FOR LOCATION.

20' 0 20' 40' 1" = 20'

GENERAL NOTES

1. SEE DRAWING ES514 FOR LUMINAIRE SCHEDULE.

EL. 9.7 + 12.0

Am en dm en t 1

-2 0 -20

CS

A

CAssini Cloud

CAssini Line

CAssini Text Box

CAssini Line

CAssini Line

CAssini Line

IP-F

5" POWER CONDUITS

STAINLESS STEEL 1-5/8"

CHANNEL AND 3/8" ROD (TYP)

ES510

C3

NAVD 88 Level 0.05

EL 9.70

CENTERWALL_TUNNEL_FLOOR_01

EL -5.28

GROUND BAR

MISCELLANEOUS CONDUIT

AND LIGHT FIXTURE SUPPORT

STAINLESS STEEL 1-5/8" CHANNEL,

SECURE CABLES WITH CABLE

CLEATS. ROUTE GROUND WIRE

OUTSIDE OF CLEATS, SECURE

WITH TIE-WRAPS(2) 5" CONDUITS TO

MANHOLE BELOW.

AC-518

SPLICE CABLES IN MANHOLE

4" TELCOM CONDUITS, ROUTE

THROUGH AC MANHOLE

CONVERT TO PVC COATED RGC

IP-AA

MANHOLE COVER

DD1W

TUNNEL

AC-510

TYPE 4 MANHOLE,

SEE A4/ES520

(3) 5" CONDUITS

RER IP OUTLET

4" CONCRETE PAD (EXTEND

TO LEVEL BELOW)

GROUND BAR (TYP)

ES510

C3

STAINLESS STEEL

1-5/8" CHANNEL

AND 3/8" ROD

LIGHT

FIXTURE

NAVD 88 Level 0.05

EL 9.70

MISCELLANEOUS

CONDUITS

5" POWER CONDUITS

PUMP_STATION_LOWER_LEVEL_FLOOR_01

EL -3.00

CABLE RACK SUPPORT

STANCHION

8" BLOCK WALL

STAINLESS STEEL

1-5/8" CHANNEL

AND 3/8" ROD

MISCELLANEOUS

CONDUITS 4" TELCOM CONDUITS

EXPANSION ANCHOR

(TYP)

MEDIUM VOLTAGE

CONDUITS

1' - 3"

(TYP)

UTILITY BUILDING

TUNNEL

EL -8.28

CABLE RACK GROUND

WIRE (TYP OF 7) SECURE CLEATS TO RACK WITH 1/4" STAINLESS STEEL

HARDWARE. DRILL 1/4" HOLE IN RACK IN (4) LOCATIONS.

SUPPORT STANCHIONS TO WALL WITH 1/2" EXPANSION ANCHORS

AT 2'-0" (CENTER) ON PRECAST WALLS. SUPPORT WITH 1/2" ROD

THRU - WALL AT 2'-0" CENTERS ON BLOCK WALLS

HEAVY DUTY

STAINLESS STEEL

HINGED CABLE

CLEAT (TYP)

(3) - 500 MCM COPPER

RHW-2 CABLE (TYP)

1' - 8 1/2"

(1) #250 MCM BARE COPPER GND

WIRE FOR SHORE POWER FEEDERS,

(1) #1/0 BARE COPPER GND WIRE FOR

INDUSTRIAL POWER FEEDERS. TIE

WRAP TO CABLE RACK.

NOTE: GROUND WIRE IS COMMON ON

EACH CABLE RACK, CONNECT ALL

GROUND WIRES FROM

SWITCHBOARDS OR POWER

OUTLETS USING COMPRESSION

CONNECTORS.

SUPPORT

STANCHION

ATTACHED TO

WALL

2-1/2" MIN.

(TYP)

1/4"-20

STAINLESS

STEEL BOLT

(TYP)

CABLE RACK

NOTE:

1.

2.

NAVD 88 Level 0.05

EL 9.70

CENTERWALL_TUNNEL_FLOOR_01

EL -5.28

TC1N-S2

2" TELCOM CONDUIT

TO TJB-5

STAINLESS STEEL 1 5/8"

CHANNEL AND 3/8" ROD

EXPANSION

ANCHOR (TYP)

CHAIN MOUNT FIXTURE

LIGHT FIXTURE

MEDIUM VOLTAGE

CONDUITS

GROUND

BAR (TYP)

ES502

A5

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 3:

P

M

U

TI

LI

TY

T U

N N

EL

S

EC

TI

O N

S

ES302

12823946

SCALE: 1/4" = 1'-0" ES102 C4

DDIN NORTH WALL - 2

SCALE: 1/4" = 1'-0" ES104 A2DD1W SOUTH WALL - 1

SCALE: 1/4" = 1'-0" ES403 A5UTILITY TUNNEL EAST

SCALE: 1/4" = 1'-0" ES101 C2CENTER WALL - 3

NOTE: SUPPORT CHANNEL FOR TELCOM BOX NOT SHOWN, SEE DETAIL A5/ES502.

Am en dm en t 1

-2 0 -20

CS

A

A5

ES211

VOLTAGE

REGULATOR,

TYPICAL FOR 3

INTERIOR WALL, TYP

(2) 5" CONDUITS TO

SECTIONALIZER

EXTERIOR WALL

TYP

CABLE TRAY ABOVE,

A4

ES211

A2

ES211

LIGHT FIXTURE

(TYP)

(2) 5"

CONDUITS

TO 15KV

SWITCH8' - 0"

17' - 9"

2' - 10"

2' - 3"

2' - 11"

LM LME

LME LM

GFCI

WP

SL

L

S SL

L

S SL

L

S

GFCI

WP

2 2 2

GND GND

REMOTE CONTROLLER

(TAP CHANGER)

VR-TSS11: LP-3Y-2

VR-TSS12: LP-3Y-5

VR-TSS11: LP-3Y-6

VR-TSS12: LP-3Y-4

(TYP 2)

VR-TSS11: LP-3Y-1

VR-TSS12: LP-3Y-3

(TYP 4)

1 1 1

3' - 0" x 3' - 0" LOUVER, CENTERED (TYP 2)

KEY PLAN KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 3:

P

M

R

EG

U

LA

TO

R

E N

C

LO

SU

R

E

- P

LA

N

V

IE

W

ES401

12823948

PLAN NORTH

SCALE: 3/4" = 1'-0"

REGULATOR ENCLOSURE -

ELECTRICAL PLAN

GENERAL NOTES

PROVIDE 2" CONDUIT BELOW GRADE FOR CONTROL

CABLE TO REMOTE CONTROLLER. STUB UP 6" AFF.

PROVIDE 1-1/2" CONDUIT FOR GROUND WIRE TO VOLTAGE

REGULATOR. ROUTE ON FLOOR WITH UNISTRUT.

PROVIDE A 1/4"x4"x24" COPPER GROUND BAR AT 24" AFF.

ATTACH VOLTAGE REGULATOR GROUNDS AND GROUNDS

FROM EXTERIOR GROUND GROUND GRID WITH DOUBLE

LUG DOUBLE CRIMP CONNECTORS AND DURIUM BRONZE

HARDWARE.

1' 0' 4'2'1' 3/4" = 1'-0"

KEYNOTES

PROVIDE WIRING TO REGULATORS IN A 4-WIRE GROUNDED

WYE CONFIGURATION. SEE DRAWING ES211 FOR FURTHER

CLARIFICATION.

LABEL CABLES AT REGULATOR BUSHINGS, ARRESTORS AND

GROUND BAR PER APPROPRIATE CABLE SPECIFICATIONS.

PROVIDE (3)-20A, 120V CIRCUITS TO EACH VOLTAGE

REGULATOR FROM PANEL LP-3Y (SEE ES411). ROUTE A 3/4"

CONDUIT UNDERGROUND FROM PANEL TO EACH REGULATOR

ENCLOSURE. EACH CIRCUIT MUST BE (2) #12, #12 GND WITH A

SEPARATE NEUTRAL. CIRCUIT AS INDICATED, SEE PANEL

SCHEDULE ON DRAWING ES611.INTERCONNECT SINGLE POLE

SWITCH TO LIGHTING CIRCUIT. INTERIOR CONDUITS MUST BE

SURFACE MOUNTED RGS. OUTLET AND JUNCTION BOXES

MUST BE FS STYLE CAST IRON. DEVICES MUST HAVE

GASKETED WEATHERPROOF COVERS.

SEE LUMINAIRE SCHEDULE ON DRAWING ES514 FOR FIXTURE

TYPES.

1.

2.

3.

4.

1. PRE-FAB MANUFACTURER REFER TO US001 - STRUCTURAL GENERAL NOTES FOR DESIGN CRITERIA

2. PRE-FAB MANUFACTURER TO PROVIDE LIFT POINTS FOR FUTURE RELOCATION OF ENCLOSURE.

3. PRE-FAB ENCLOSURE TO BE UN-INSULATED.

4. PRE-FAB ENCLOSURE TO HAVE A MINIMUM INSIDE CLEAR HEIGHT OF 13' - 0".

5. PRE-FAB ENCLOSURE TO HAVE DECK ANCHOR POINTS AS RECOMMENDED BY THE PRE-FAB MANUFACTURER AND PER THE STRUCTURAL DESIGN CRITERIA. ANCHORAGE TO BE COORDINATED WITH THE PRE-FAB

MANUFACTURER AND STRUCTURAL SLAB.

6. WALL AND ROOF FINISHES TO BE METAL PANEL WITH MARINE GRADE FINISH, WEATHER TIGHT, COLOR

SELECTED BY OWNER.

7. PRE-FAB MANUFACTURER TO PROVIDE TWO 3'-0" x 3'-0" LOUVERS WITH RAIN AND INSECT SCREEN TO ALLOW

FOR CROSS VENTILATION.

8. DOUBLE DOOR TO BE (2) 3'-0"W x 7'-0"H PANELS.

9. REFER TO SPECIFICATION SECTIONS 087100 AND 133419.01 FOR FURTHER DETAILS.

ENCLOSURE NOTES

Am en dm en t 1

-2 0 -20

CS

A

SUBSTATION 3

EXPANSION

7 7

SP-8SP-7

UG

E

3-5B

3-2B

23 241315

13.2 KV VAULT

JB-A

JB-B

JB-D

JB-E

UG

E

UG

E

381 39

AC-502

AC-507

AC-513

SG-7 SG-8

SECT

TSS 11

SECT

TSS 12

TC4TC3 298

TC1297 TC2

UG

E

UG

E

UG

E

UG

E

1151920

UG

E

UG

E

3-7B

3-4B (TIE)

13A/13B (3-18A/3-19A)

12A/12B (3-16A/3-17A)

11A/11B (3-14A/15A)

10A/10B (3-13A)

9A/9B (3-12A)

8A/8B (3-11A)

TRANSITION

7A/7B (TIE)

6A/6B (3-9A)

5A/5B (3-8A)

4A/4B (3-7A)

3A/3B (3-5A/6A)

2A/2B (3-3A/4A)

1A / 1B (3-1A/2A)

SUBSTATION 3A

SUBSTATION 3B

SUBSTATION 3A TRENCH

SUBSTATION 3B TRENCH

UG

E

UGEUGEUGE

UGE

1915 20

SECT. 3-1A

232425

19 20 23 24 25

LP-3Y

EXISTING PANEL AC-11 AND AC-12

VR-TSS11 VR-TSS12

TSS11 TSS12

8 8

LOAD CENTER LC-2

LP-3Y-716

146 17

UG

E

UG

E

UGE

UGE

UGE

UG

E

UG

E

UG

E

UG

E

LP-3Y-5

LP-3Y-2 5

LIGHTING

CONTROLLER

KEY PLAN KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

CHECK GRAPHIC SCALE BEFORE USING

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

GRAPHIC SCALE

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 3:

P

M

EN

LA

R G

ED

P

LA

N

SU

BS

TA

TI

O

N

ES411

12823958

PLAN NORTH

SCALE: 1/8" = 1'-0"

SUBSTATION 3

KEYNOTES

PROVIDE MANHOLE, SEE DETAIL B4/ES516 AND MANHOLE

SCHEDULE ON ES605 FOR SIZE.

PROVIDE JUNCTION BAR IN VAULT TO INTERCONNECT TO 13.2 KV

CIRCUIT, SEE ES606 FOR FURTHER CLARIFICATION .

SPLICE FLEXIBLE CABLES FROM SHORE POWER OUTLETS IN

MANHOLE AC-513.

UTILIZE (4) SPARE 4" CONDUITS IN EXISTING DUCT BANK.

PROVIDE 120V CIRCUIT FOR VOLTAGE REGULATOR REMOTE

CONTROLLER.

CUT CIRCUIT 3-1A IN MANHOLE AC-321. EXTEND CIRCUIT TO

SECTIONALIZER 3-1A, SEE DWG. ES606.

PROVIDE 15 KV, PAD MOUNT VFI SWITCH.

PROVIDE VOLTAGE REGULATOR ENCLOSURE PER DWGS. ES401

AND ES211.

PROVIDE TRANSPORTABLE SUBSTATION ON CONCRETE PAD, SEE

CIVIL DRAWINGS.

PROVIDE 4-WAY DUCT BANK FROM AC-321 TO SECT. 3-1A.

PROVIDE SECTIONALIZER WITH SIDE ACCESS DOORS PER DETAIL

A2/ES510. PROVIDE ON CONCRETE PAD.

PROVIDE (2) 5" CONDUITS UNDERGROUND FROM PAD MOUNT

SWITCH TO VOLTAGE REGULATOR, SEE ES211.

PROVIDE (2) 5" CONDUITS FROM SECTIONALIZER GROUND SLEEVE

TO VOLTAGE REGULATOR, SEE DWG. ES211. MOUNT GROUND

SLEEVE EXPOSED ON CONCRETE PAD, ROUTE CONDUITS

UNDERGOUND INTO BOTTOM OF SLEEVE. SEE DETAIL A2/ES510

FOR SECTIONALIZER CONFIGURATION.

PROVIDE 1" UNDERGROUND CONDUIT BETWEEN SWITCH AND

TRANSFORMER IN TRANSPORTABLE SUBSTATION FOR

OVERTEMPERATURE SWITCH IN TRANSFORMER.

PROVIDE PANEL LP-3Y ON REGULATOR BUILDING. ROUTE TO

EXISTING 208/120V PANEL AC-11 IN BUILDING 175 WITH (4) #6, #10

GND IN A 1" C. PROVIDE 60A/3P BREAKER IN AC-11. ROUTE

CONDUIT UNDERGOUND TO BUILDING EXTERIOR AND ROUTE TO

PANEL OVERHEAD IN BUILDING.

PROVIDE 120V CIRCUIT FOR SCADA UNIT IN SWITCH, (2) #12, #12

GND 3/4" UNDERGOUND CONDUIT.

PROVIDE LIGHTING CONTROLLER FOR EXTERIOR TYPE LI POLE

MOUNTED LIGHTING. SEE DWG. ES108 AND ES109 FOR FIXTURE

LOCATIONS. SEE DETAIL C2/ES512 FOR LIGHTING CONTROLLER

WIRING DIAGRAM.

GENERAL NOTES

4' 0' 4' 8' 12' 16' 1/8" = 1'-0"

ES102

1.

2.

3.

4.

5.

6.

SEE SINGLE LINE DIAGRAMS ON DRAWINGS ES606 TO ES609 AND

CONDUIT AND WIRE SCHEDULES ON DRAWINGS ES601 TO ES604 FOR

CONDUIT AND CONDUCTOR SIZES.

SEE DRAWING ES405 TO ES409 FOR ELECTRICAL UTILITY TUNNEL

WORK BELOW THIS ELEVATION.

EXISTING UNDERGROUND ITEMS ARE NOT SHOWN IN EXACT

LOCATIONS OR TO EXACT SCALE. CONSULT CIVIL DRAWINGS FOR

MORE DETAILED UNDERGROUND UTILITY DEPICTIONS. PERFORM A

UFPO BEFORE INSTALLING ANY UNDERGROUND WORK. VERIFY

EXISTING COMPONENTS AND REPORT ANY CONFLICTS TO THE

ENGINEER BEFORE BEGINNING.

SEE PROFILE DRAWING (ES200 SERIES) FOR UNDERGROUND DUCT

CONFIGURATIONS LANDSIDE OF DRY DOCKS.

SEE DRAWING ES524 FOR DUCT BANK CONFIGURATIONS INDICATED

ON THIS DRAWING.

SEE DRAWING ES503 FOR CONDUIT PENETRATION REQUIREMENTS.

EL + 9.7, + 12.0

SEE ES102 FOR CONTINUATION

Am en dm en t 1

-2 0 -20

CS

A1

AS REQUIRED

2-1/2" C.

PROVIDE CONNECTION BOX: COMBINATION, DISCONNECT WITH

OVERCURRENT PROTECTION AND 200A CONNECTION PLUG AND

SCREW ON CAP. RATING: 200A, NEMA 4X, 480V, 3P, 3W. BASIS OF

DESIGN: RUSSELLSTOLL MAXGARD INTERCONNECTION SYSTEMS

PROVIDE CONNECTION BOX: COMBINATION, DISCONNECT WITH

OVERCURRENT PROTECTION AND 100A CONNECTION PLUG AND

SCREW ON CAP. RATING: 100A, NEMA 4X, 480V, 3P, 3W. BASIS OF

DESIGN: RUSSELLSTOLL MAXGARD INTERCONNECTION SYSTEMS

PROVIDE A 200A MALE PLUG.

PROVIDE 3 FEET OF 600V TYPE SEOW 2/4 (4/C #2) CORD.

PROVIDE A SEALING RING, 2" NPT.

PROVIDE A STRAIN RELIEF WITH KELLEMS GRIP, 2" NPT.

PROVIDE A 1-1/2" ID BUSHING.

PROVIDE 1-1/2" NEMA 4 J-HOOK CABLE SUPPORT.

1-5/8" STAINLESS STEEL SUPPORT CHANNEL, COMPATIBLE

FITTINGS AND HARDWARE (TYP). PROVIDE STAND OFFS PER

DETAIL C3/ES502.

KEYNOTES:

5' - 0"

DECK LEVEL

NAVD 88 Level 0.05

EL 9.70

36" W X 36" D X 48" H

JUNCTION BOX

RELOCATED IP

OUTLET WITH (2)

400A CIRCUITS

EXTEND EXISTING 4"

CONCRETE PAD

4' - 4"

NOTES:

1. MOUNT JUNCTION BOX WHERE EXISTING IP OUTLET WAS LOCATED.

2. SPLICE EXISTING IP OUTLET FEEDERS TO PERMANENT FEEDERS. PERMANENT FEEDERS MUST

EACH BE (3) PRE-TERMINATED, 535 MCM DLO CABLES AND A #2 GND.

3. EXTEND 4" FRE CONDUITS REMOVED DURING DEMOLITION INTO JUNCTION BOX. EXISTING

CONDUITS INTO BOTTOM OF IP OUTLET NOT SHOWN FOR CLARITY.

4. RELOCATE EXISTING IP OUTLET, TIE TO JUNCTION BOX WITH (2) 4" CONDUITS. PROVIDE

CONDUCTORS TO IP OUTLET FROM MANHOLE DC-1069.

SEE NOTE 4

SEE NOTE 3

KEYNO

PROVIDE 12 GAUGE 1-5/8" STAINLESS STEEL CHANNEL SUPPORT ASSEMBLY. PROVIDE FITTINGS AND

HARDWARE , ANCHOR TO DECK WITH (4) 3/8" EXPANSION ANCHORS PER FLOOR FLANGE.

GENERAL NOTES:

1. PROVIDE 45 DEGREE STANDOFF FROM BACK OF EACH VERTICAL 1-5/8" SUPPORT CHANNEL TO DECK.

ATTACH STANDOFF AT 24" ABOVE DECK, SEE DETAIL C3.

2. CONDUIT MUST BE PVC COATED RIGID GALVANIZED STEEL ROUTED TO UTILITY TUNNEL BELOW.

3. SEE COMMUNICATIONS EQUIPMENT SCHEDULE ON DWG. ES609 FOR CABINET SIZES.

RFC-x RFC-xnTCx

TELEPHONE ONLY RFID FIBER FIBER AND TELEPHONE

AS REQUIRED AS REQUIRED

5' - 0"

FC-x

2" C.

2" C. 2" C. 3/4" C.

2" C.

DECK

LEVEL

2" C.

TCx

AS REQUIRED

5' - 0"

PROVIDE 45 DEGREE STANDOFF FROM BACK OF EACH

VERTICAL SUPPORT OF UNISTRUT TO DECK. ATTACH

STANDOFF AT 24" ABOVE DECK.

PROVIDE (2) SPARE 1" CONDUITS FROM EACH MPZ TO

THE UTILITY TUNNEL BELOW.

SEE SITE PLANS AND SCHEDULES FOR SIZE AND

QUANTITY OF CONDUITS AND CONDUCTORS.

(2) SPARE 1"

CONDUITS

MPZ (MINI POWER

ZONE)

ACTIVE CONDUITS TO

UTILITY TUNNEL BELOW

1.

2.

3.

DECK LEVEL

6' - 0"

2' - 0"

TYPICAL STANDOFF

AT VERTICAL

SUPPORT

45 DEGREE ANGLE

BRACKET (TYP)

2' - 0"

1-5/8" STAINLESS STEEL CHANNEL,

COMPATIBLE FITTINGS AND

HARDWARE (TYP)

AS REQUIRED

WHERE REQUIRED: AT ALL EXPOSED LOCATIONS UNDER PIERS WHERE

FRE CONDUIT IS USED.

CONVERT TO PVC COATED RGS CONDUIT WHERE ENTERING A UTILITY

TUNNEL.

CONCRETE ENCASED

DUCTBANK

PVC 40 TO FRE CONDUIT

CONVERSION FITTING

EXPOSED FRE CONDUIT

UNDER PIER

FRE EXPANSION /

DEFLECTION FITTING

1.

2.

#4/0 INSULATED

GROUND WIRE

#535 MCM FLEXIBLE

DLO CABLE (TYP 24)

MOUNTING FRAME

(TYP 2)

#4/0 INSULATED

GROUND WIRE

#535 MCM FLEXIBLE

DLO CABLE (TYP 24)TWB SEALING

BLOCK (TYP)

1' - 4"

1' - 9" 0' - 9" 1' - 9"

ELEVATION VIEW

8" BLOCK WALL

PLAN VIEW

#535 MCM FLEXIBLE

DLO CABLE (TYP 48)

MOUNTING FRAME

(TYP 2)

#4/0 INSULATED

GROUND WIRE (TYP 4)

STAINLESS STEEL

SLEEVE (TYP 2)

NOTES:

1. PROVIDE A THRU-WALL BARRIER SLEEVE SYSTEM FOR DLO CABLES. FOLLOW MANUFACTURER'S

INSTRUCTIONS FOR INSTALLATION.

2. DETAIL SHOWN IS A SLEEVE FOR CABLES TO SHORE POWER OUTLET SP-2. PROVIDE SLEEVE SYSTEM FOR

OTHE INDUSTRIAL POWER OUTLETS, ADJUST SIZE/ QUANTITY OF SLEEVES AND QUANTITY OF OPENINGS FOR

THOSE FEEDERS, SPARE CABLE OPENINGS ARE NOT REQUIRED.

3. PROVIDE A STAINLESS STEEL SLEEVE TO FORM REMAINDER OF OPENING IN BLACK WALL. INSIDE DIMENSIONS OF SLEEVE MUST MATCH INNER COLLAR DIMENSIONS TO ALLOW SUFFICIENT ROOM FOR CABLES TO PASS THRU. SLEEVE SYSTEMS WITH LARGER MOUNTING FRAMES MATCHING WALL THICKNESS ARE ACCEPTABLE.

MOUNTING FRAME

INNER COLLAR (TYP 2)

MOUNTING FRAME

INNER COLLAR (TYP 2)

8" BLOCK WALL

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 3:

P

M

M

IS

C

EL

LA

N

EO

U

S D

ET

AI

LS

ES502

12823962

N.T.S. C2CRANE HOTEL POWER DETAIL

N.T.S. ES101 C5EXISTING IP OUTLET REWORK

N.T.S. A5TELCOM CABINET DETAIL

N.T.S. C3MINI POWER ZONE DETAIL

N.T.S. A2

TYPICAL FRE CONDUIT EXPANSION /

DEFLECTION FITTING

N.T.S. A3TYPICAL CABLE SLEEVE DETAIL

Am e n dm en t 1

-2 0 -20

CS

FUSE DISCONNECTING DEVICE IN LIGHT POLE BASE

O/

TO LUMINAIRE - EXTEND

#12 AWG WIRES FROM

POLE BASE TO LUMINAIRE

IN-LINE WATERPROOF

FUSE HOLDER WITH 10

AMP FUSE

GROUND LUG IN BASE

N

CEILING

GALVANIZED STEEL

FIXTURE CHAIN, #14

LIGHT FIXTURE

FLOOR

REFER TO SHEET

SPECIFIC KEYNOTES

FOR LIGHT FIXTURE

MOUNTING HEIGHTS

DETAIL IS GENERIC, MODIFY FOR

SPECIFIC INSTALLATIONS.

NOTE:

1.

ATTACH CHAIN TO

STAINLESS STEEL

FIXTURE BRACKET

SO THAT THE

FIXTURE HOUSING IS

NOT PENETRATED

WHEN MOUNTING

FIXTURE

CM

CM

CM

C

O

COIL

FROM PANEL

BOARD

PCOFF

AUTO

HAND

PC

NOTES:

1. CONFIRM WITH ACTIVITY PRIOR TO PROGRAMMING.

2. DEVICES SHOWN MUST BE A PRE-PACKEGED LIGHTING CONTROLLER MOUNTED INSIDE A COMMON ENCLOSURE. NEMA 12

FOR INTERIOR, NEMA 4X FOR EXTERIOR

3. DASHED LINES INDICATE FIELD WIRING. L1 AND N FOR 120V LIGHTING CIRCUITS, L1 AND L2 FOR 208V LIGHTING CIRCUITS.

4. LIGHTING CONTROLLER LOCATIONS: 2ND FLOOR OF PUMP STATION (SEE PE107), UTILITY ENCLOSURE (SEE UE107), SITE (SEE

ES411)

TC

TC

HAND-OFF-AUTO

SWITCH. MOUNT

ON CONTACTOR.

LABEL CONTACTOR

"EXTERIOR

LIGHTING"

TIME CLOCK

SEE NOTE BELOW

EXTERIOR WALL MOUNTED

PHOTOCELL (MOUNT ON FIRST

LIGHT POLE OF CIRCUIT)

MECHANICALLY HELD

LIGHTING CONTACTOR WITH

20A MINIMUM CONTACTS

2 WIRE CONTROL MODULE

L1 L2 N

TO LIGHTING

LOADS

LIGHTING CONTROLLER

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 4:

P

M

LI

G

H

TI

N G

D

ET

AI

LS

S H

EE

T

O

F

ES512

12823972

N.T.S. A2

TYPICAL SITE LUMINAIRE WIRING

DIAGRAM

N.T.S. C5

TYPICAL LIGHT FIXTURE HANGING

DETAIL

N.T.S. C2

TYPICAL LIGHTING CONTROLLER

DETAIL

Am e n dm en t 1

-2 0 -20

CS

A

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 4:

P

M

LU

M

IN

AI

R E

SC

H

ED

U

LE

ES514

12823974

LUMINAIRE SCHEDULE

Image TYPE Description LAMP LUMENS WATTS VOLTAGE MOUNTING COMMENTS LHE RUGGED DIE-CAST IMPACT RESISTANT ALUMINIUM HOUSING WITH A HINGED DIE-CAST ALUMINIUM DOOR. OPTICAL CHAMBER SEALED WITH ONE-PIECE SILICONE

GASKET SEAL. UL 1598 WET LOCATION RATED. 4000K LEDS WITH AN INTEGRAL LED ELECTRONIC DRIVER. 120V EMERGENCY BATTERY PACK.

LED 10264 lm 58 W 120 V SURFACE PROVIDE BIRD SPIKES ON TOP OF FIXTURE. DO NOT PENETRATE FIXTURE HOUSING

WHEN INSTALLING FIXTURES.

LI ENCLOSED IP-66 RATED EXTRUDED ALUMINUM HOUSING WITH CONTINUOUS NEMA 4X GASKET. HOUSING FINISHED IN SUPER DURABLE TGIC POLYESTER

POWDER COAT PAINT, 2.5 MIL NOMINAL THICKNESS.

LED 63313 lm 558 W 208V POLE PROVIDE BIRD SPIKES ON TOP OF FIXTURE. DO NOT PENETRATE FIXTURE HOUSING

WHEN INSTALLING FIXTURES.

LJ ENCLOSED IP-66 RATED EXTRUDED ALUMINUM HOUSING WITH CONTINUOUS NEMA 4X GASKET. HOUSING FINISHED IN SUPER DURABLE TGIC POLYESTER

POWDER COAT PAINT, 2.5 MIL NOMINAL THICKNESS.

LED 14890 lm 133 W 120 V POLE INSTALL BIRD SPIKES ON TOP OF FIXTURE

LK ENCLOSED IP-66 RATED EXTRUDED ALUMINUM HOUSING WITH CONTINUOUS NEMA 4X GASKET. HOUSING FINISHED IN SUPER DURABLE TGIC POLYESTER

POWDER COAT PAINT, 2.5 MIL NOMINAL THICKNESS.

LED 13755 lm 133 W 120 V SURFACE INSTALL BIRD SPIKES ON TOP OF FIXTURE

LM ENCLOSED POLYESTER REINFORCED FIBERGLASS AND SELF-EXTINGUISHING PLASTIC HOUSING. WATERTIGHT HOUSING WITH A POLYURETHANE GASKET PROVIDING A SEAMLESS SEAL FOR THE DIFFUSER LENS. COMPLIES WITH NEMA 4X, IP65, IP66 AND IP67 RATINGS. 4000K LEDS

LED 4431 lm 49 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LME ENCLOSED POLYESTER REINFORCED FIBERGLASS AND SELF-EXTINGUISHING PLASTIC HOUSING. WATERTIGHT HOUSING WITH A POLYURETHANE GASKET PROVIDING A SEAMLESS SEAL FOR THE DIFFUSER LENS. COMPLIES WITH NEMA 4X, IP65, IP66 AND IP67 RATINGS. 4000K LEDS WITH A 10-WATT, 120V EMERGENCY

BATTERY PACK.

LED 4431 lm 49 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LN ENCLOSED POLYESTER REINFORCED FIBERGLASS AND SELF-EXTINGUISHING PLASTIC HOUSING. WATERTIGHT HOUSING WITH A POLYURETHANE GASKET PROVIDING A SEAMLESS SEAL FOR THE DIFFUSER LENS. COMPLIES WITH NEMA 4X, IP65, IP66 AND IP67 RATINGS. 4000K LEDS

LED 7000 lm 49 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LNE ENCLOSED POLYESTER REINFORCED FIBERGLASS AND SELF-EXTINGUISHING PLASTIC HOUSING. WATERTIGHT HOUSING WITH A POLYURETHANE GASKET PROVIDING A SEAMLESS SEAL FOR THE DIFFUSER LENS. COMPLIES WITH NEMA 4X, IP65, IP66 AND IP67 RATINGS. 4000K LEDS WITH A 10-WATT, 120V EMERGENCY

BATTERY PACK.

LED 7000 lm 49 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LNE-O ENCLOSED POLYESTER REINFORCED FIBERGLASS AND SELF-EXTINGUISHING PLASTIC HOUSING. WATERTIGHT HOUSING WITH A POLYURETHANE GASKET PROVIDING A SEAMLESS SEAL FOR THE DIFFUSER LENS. COMPLIES WITH NEMA 4X, IP65, IP66 AND IP67 RATINGS. 4000K LEDS WITH A 10-WATT, 120V EMERGENCY BATTERY PACK. INCLUDES INTEGRAL OCCUPANCY SENSOR FOR 50% DIMMING WHEN NOT IN USE.

LED 7000 lm 49 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LP FIBERGLASS HOUSING WITH HIGH IMPACT DIFFUSER AND METAL GEAR TRAY SECURED BY INTERNAL STAINLESS STEEL LATCHES. 4000K LEDS. COMPLIES WITH

NEMA 4X, IP65, IP66, IP67, AND IP69 RATINGS. UP TO 1500 PSI HOSEDOWN.

LED 17864 lm 138 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LPE FIBERGLASS HOUSING WITH HIGH IMPACT DIFFUSER AND METAL GEAR TRAY SECURED BY INTERNAL STAINLESS STEEL LATCHES. 4000K LEDS. COMPLIES WITH NEMA 4X, IP65, IP66, IP67, AND IP69 RATINGS. UP TO 1500 PSI HOSEDOWN. INCLUDES 10-WATT, 120V EMERGENCY BATTERY PACK.

LED 17864 lm 138 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LS FIBERGLASS HOUSING WITH HIGH IMPACT DIFFUSER AND METAL GEAR TRAY SECURED BY INTERNAL STAINLESS STEEL LATCHES. 4000K LEDS. COMPLIES WITH

NEMA 4X, IP65, IP66, IP67, AND IP69 RATINGS. UP TO 1500 PSI HOSEDOWN.

LED 17864 lm 138 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LSE FIBERGLASS HOUSING WITH HIGH IMPACT DIFFUSER AND METAL GEAR TRAY SECURED BY INTERNAL STAINLESS STEEL LATCHES. 4000K LEDS. COMPLIES WITH NEMA 4X, IP65, IP66, IP67, AND IP69 RATINGS. UP TO 1500 PSI HOSEDOWN. INCLUDES 10-WATT, 120V EMERGENCY BATTERY PACK.

LED 17864 lm 138 W 120 V PENDANT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LT ENCLOSED CORROSION RESISTANT ALUMINUM ALLOY HOUSING WITH BAKED POWDER EPOXY/POLYESTER FINISH AND UNIFORM CORROSION PROTECTION. IP66

RATED WITH HIGH TEMPERATURE SILICONE GASKETING.

LED 18544 lm 55 W 120 V POLE, REMOVABLE

DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LV ENCLOSED CORROSION RESISTANT ALUMINUM ALLOY HOUSING WITH BAKED POWDER EPOXY/POLYESTER FINISH AND UNIFORM CORROSION PROTECTION. IP66

RATED WITH HIGH TEMPERATURE SILICONE GASKETING.

LED 18544 lm 55 W 120 V WALL, REMOVABLE

DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LWE ENCLOSED GASKETED STAINLESS STEEL HOUSING. SUBMERSIBLE MARINE GRADE SURFACE MOUNT LINEAR FIXTURE. IP68, UL STD 1598 RATED. INCLDUES

10-WATT, 120V EMERGENCY BATTERY PACK.

LED 1365 lm 49 W 120 V WALL MOUNT DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LY ENCLOSED CORROSION RESISTANT ALUMINUM ALLOY HOUSING WITH BAKED POWDER EPOXY/POLYESTER FINISH AND UNIFORM CORROSION PROTECTION. IP66

RATED WITH HIGH TEMPERATURE SILICONE GASKETING.

LED 7171 lm 55 W 120 V POLE, REMOVABLE

DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

LX2 ENGINEERING-GRADE THERMOPLASTIC HOUSING. RUGGED POLYCARBONATE CLEAR HOUSING LENS. SEALED FIXTURE

AND SEALED BATTERY. WET LOCATION RATED.

LED 120 V/1-10 VA SURFACE/CEILING DO NOT PENETRATE FIXTURE HOUSING WHEN INSTALLING FIXTURE.

Am en dm en t 1

-2 0 -20

CS

ES103 MANHOLES

N

W

S

EAC-509

N

W

S

EAC-510

ES104 MANHOLES

N

W

S

EAC-511

N

W

S

EAC-528 (EX)

N

W

S

EAC-512

ES105 MANHOLES

N

W

S

ELC17 VAULT (EX)

AC-514 DC-D87

S

603,604,605,606,613

E

N

W

S

DC-D4 (EX)

E

N

W

S

AC-303 (EX)

120 121 S

S112

S113

119 118 S 74 75 S

S

S

70 69 S 68 67 S

S

S

EX

114 115

116 117

20 - WAY (5 x 4) 5" C.

S

S

S

S

S114

115 S

S 114

115S

112111 113110

72114 73115

S 116117

S

EX EX EX

EX EX EX

S

S

S

S

S S

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX

EXEX

EX

EX EX

EX EX

S S

EX

EX

EX

EX

EX

EX

EX EX

14 - WAY (7 x 2) 5" C.

EXPOSED

CONDUITS TO

LC17 EAST

3 - WAY (3 x 1) 5" C.

3 - WAY (3 x 1) 5" C.

3 - WAY (3 x 1) 5" C.

4 - WAY (2 x 2) 5" C.

8 - WAY (4 x 2) 5" C.

14 - WAY (4 x 3 x 2) 5" C.

14 - WAY (7 x 2) 5" C.

1" C (MPZ-1WS

TO DP1)

S

S

S 292S

S

S

S

S

1" C (MPZ-1WS

TO DP1)

C13,C14,C15,C26

C21,C25,C36,C37,C38

C1,C2,C4,C6,C8 M1,C18,C19

C7

C31,C32,C33,C34,C40,C43

S S

S

S

SS

S

601,602

EX EX EX EX

EX EX EX

S EX EX EX 601,602

112111 113110S 116117

72114 73115S 292S

14 - WAY (7 x 2) 5" C.

14 - WAY (4 x 3 x 2) 5" C.

20 - WAY (5 x 4) 5" C.

12 - WAY (4 x 3) 4" C.

12 - WAY (4 x 3) 4" C.

C7

SS

603,604,605,606,613 C13,C14,C15,C26 C1,C2,C4,C6,C8 M1,C18,C19

P15

P14P1

P4

EX EX EX EX

EX EX EX EX EX

EXEXEXEX

EX

EX

EX

EX

EX

EX

EX

EX

EX

C21,C25,C36,C37,C38

12 - WAY (4 x 3) 4" C. C7

603,604,605,606,613

C13,C14,C15,C26 C1,C2,C4,C6,C8

M1,C18,C19

M1,C18,C19

C31,C32,C33,C34,C40,C43

603,604,605,606,613

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX C2

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX EX EX EX EX EX EX EX EX

20 - WAY (5 x 4) 5" C.

E

N

W

S

E

N

W

S

C31,C32,C33,C34,C40,C43 C21,C25,C36,C37,C38

N

W

S

E

N

W

S

E

P7

S

S

S

S

S

S

S

S

S

S

S

S

S

S

P5

S

S

S

S

S

S

S

S

S

C1,C2,C4,C6,C8 M1,C18,C19

C31,C32,C33,C34,C40,C43

S

C21,C25,C36,C37,C38

C7

603,604,605,606,613 C13,C14,C15,C26S

C13,C14,C15C5,C7,C10,C12 C21,C22,C23,C25,C38 S

C1,C2,C4,C6 C18,C19,C26

C31,C32,C33,C34,C35 SSSS

603,604,605,606,613

6 - WAY

(3 x 2) 4"C.

M1,C5,C8,C10,C12,C22,C23

C26,C35,C36,C37,C40,C43

S

S

S

20 - WAY (5 x 4) 5" C.

20 - WAY (4 x 5) 5" C.

P7

P6

P3

P2

P8

P9

P3

P2

S

S

S

S

S

P10

P11

P13U

V

P14

P15 P15

P14 P1

P4

20 - WAY (5 x 4) 5" C.

P7

S

S

S

S

S

S

S

S

S

S

S

S

S

S

P5

P4

S P1

P2 P3

P6 P5

P2 P3

S

U V

S P13

S

P9 P8

P11 P10

S

P4 SP1P2 P3

P6 P5P2 P3 S

U VS P13 S

P9 P8P11 P10 S

P4 SP1P2 P3

P6 P5P2 P3 S

U VS P13 S

P9 P8P11 P10 S

12 - WAY (4 x 3) 4" C.

12 - WAY (4 x 3) 4" C.

DC-D85

AC-515

P7

4 - WAY (2 x 2) 5" C.

S

P14 P15

4 - WAY (2 x 2) 5" C.

S

P15

P7

P14

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 4:

P

M

M

AN

H O

LE

F

O

LD

O U

TS

ES518

12823978

GENERAL NOTES

1.

2.

3.

4.

5.

6.

MANHOLE FOLDOUTS ARE NOT TO SCALE, SEE MANHOLE

DETAILS FOR SIZES AND CONFIGURATIONS SEE DWG. ES516.

ALL DUCT BANKS LEAVING MANHOLES MUST BE CONCRETE

ENCASED PER DETAIL A2/ES516.

SEE CONDUIT AND WIRE SCHEDULES ON ES601 TO ES604 FOR

CIRCUIT DESIGNATIONS.

SEE ES200 PROFILE DRAWINGS FOR DUCT BANK ELEVATIONS.

COORDINATE EXACT LOCATION OF ENTRY INTO MANHOLES IN

THE FIELD. PROVIDE DIMENSIONED MANHOLE FOLDOUT

DRAWINGS AT PROJECT CLOSEOUT.

EX = EXISTING CONDUCTORS IN CONDUIT.

CONDUITS FURTHEST FROM MANHOLE ARE THE UPPER

CONDUITS OF THE DUCT BANK. 1

Am en dm en t 1

-2 0

-20

CS

ES406 MANHOLES

ES408 MANHOLES

N

W

S

EAC-309 (EX)

N

W

S

EAC-516

N

W

S

EAC-517

N

W

S

EAC-518 N

W

S

ETC-6

N

W

S

EAC-519

N

W

S

EAC-520

N

W

S

EAC-522

N

W

S

EAC-523

ES411 MANHOLES

N

W

S

EAC-513

N

W

S

EAC-507

N

W

S

EAC-321 (EX)

N

W

S

EAC-525

N

W

S

ETC-1

ES407 MANHOLES

N

W

S

ETC-3

N

W

S

ETC-4

N

W

S

ETC-5

N

W

S

EAC-502

14 25S

N

W

S

EAC-521

102 103

S S

97 98

99 100

S

98 101

99 102

97 100

96 105

S

S

S

124 125 S165 166 S 167 168 S

97 100

S

S

S

105S

S

N

W

S

ETC-2

81,82,83,84,701,702

617,618,619

81,82,83,84,701,702

617,618,619

617,618,619

81,82,83,84,701,702

81,82,83,84,701,702

617,618,619

617,618,619 81,82,83,84, 701,70280,81,82,83,84, 626,701,702

616,617,618,619, 624,625

616,624, S

105 S

S

169 170 S

100 103

S

S

171 172 S

S

173 174 S

S

80,81,82,83,84,626,701,702

616,617,618,619,624,625

614,615,616,617,618,619

79,626

79,80,81,82,83,84,701,702

614,615,624

79,626

614,615,624, 79,626

614,623,625 79,626

614,623,625

S

219 S 220 S

TC2

TC1

SS

S

S

S S

12-WAY (4 x 3) 5" C.

(3) 5" SLEEVES

23 25

S

S

2413 20

EX

EX

EX

14 25S

97100

S

S

S 100

S

S

S S

S S

S S S S

S S 101

100 103

S

S

S S S S S

S S S S

S

S

S

S

EX

EX EX

EX EX

EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX S

EX EX EX

EX EX EX

EX EX

EX EX

S

S

S

S

24 1320

297 TC4

TC3

S

S

S

S

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX

EX EX EX

S EX

EX EX S

S

S

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

S

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX EX EX

EX

EX S

EX

EX

EX

EX EX

EX EX

EX EX S

EX15 19 20

SS2513

S23 23 24 24 S

S

S

N

W

S

ETC-7

614,623,625

S

614,623,625

S

S

614,623,625

297 297 297 297 297

297297297297297297

297 297 297 297

298 298 298 298 298

298298298298298298

298 298 298 298

N

W

S

EAC-524

S

S

3-WAY (3 x 1) 5" C.

3-WAY (3 x 1) 5" C.

3-WAY (3 x 1) 5" C.

9-WAY (3 x 3) 5" C. 12-WAY (3 x 4) 5" C.

(3) 5" SLEEVES

12-WAY (3 x 4) 5" C. 15-WAY (3 x 5)

5" C.

(3) 5" SLEEVES

15-WAY (3 x 5) 5" C.

15-WAY (3 x 5) 5" C.

4-WAY (1 x 4) 4" C.

4-WAY (1 x 4) 4" C.

4-WAY (1 x 4) 4" C.

4-WAY (1 x 4) 4" C.

4-WAY (1 x 4) 4" C.

4-WAY (4 x 1) 4" C.

3-WAY (3 x 1) 5" C.

3-WAY (3 x 1) 5" C.

3-WAY (3 x 1) 5" C.

(3) 5" SLEEVES (3) 5" SLEEVES

6-WAY (3 x 2) 5" C.

6-WAY (3 x 2) 5" C.

9-WAY (3 x 3) 5" C.

4-WAY (1 x 4) 4" C.

4-WAY (1 x 4) 4" C.

4-WAY (1 x 4) 4" C.

3-WAY (3 x 1) 5" C.

(2) 2" C.

(1) 2" SLEEVE

3-WAY (3 x 1) 5" C.

(1) 2" C.

(1) 2" SLEEVE

(1) 2" C.

(1) 2" SLEEVE

(4) 4" C.

614,615,624, 80,626

(2) 2" C.

(1) 2" SLEEVE

S

6-WAY (3 x 2) 5" C.

S

SS

12-WAY (4 x 3) 5" C.

6-WAY (3 x 2) 5" C.

12-WAY (4 x 3) 5" C.

8-WAY (4 x 2) 5" C.

8-WAY (4 x 2) 5" C.

2-WAY (2 x 1) 5" C.

2-WAY (2 x 1) 5" C.

EX

EX

EX

EX

24-WAY (8 x 3) 5" C. 24-WAY (8 x 3)

5" C.

97 9896 99 100

101 102 103 104 105

123122 S S S

S

S

S

S

S

1 1

12" (TYP)

12" (TYP)

12" (TYP)

12" (TYP)

38 39

20 S

S

1 S

S S

S

S S

1538 39 19

1 20 S S

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 4:

P

M

M

AN

H O

LE

F

O

LD

O U

TS

ES519

12823979

GENERAL NOTES

1.

2.

3.

4.

5.

6.

MANHOLE FOLDOUTS ARE NOT TO SCALE, SEE MANHOLE DETAILS ON

DRAWING ES516 FOR SIZES AND CONFIGURATIONS.

ALL DUCT BANKS LEAVING MANHOLES MUST BE CONCRETE ENCASED PER

DETAIL A2/ES516.

SEE CONDUIT AND WIRE SCHEDULES ON ES601 TO ES604 FOR CIRCUIT

DESIGNATIONS.

SEE ES200 PROFILE DRAWINGS FOR DUCT BANK ELEVATIONS. COORDINATE

EXACT LOCATION OF ENTRY INTO MANHOLES IN THE FIELD. PROVIDE

DIMENSIONED MANHOLE FOLDOUT DRAWINGS AT PROJECT CLOSEOUT.

EX = EXISTING CONDUCTORS IN CONDUIT.

CONDUITS FURTHEST FROM MANHOLE ARE THE UPPER CONDUITS OF THE

DUCT BANK.

KEYNOTES

1 PROVIDE CONDUITS AT 12" CENTER TO CENTER.

Am en dm en t 1

-2 0 -20

CS

SHORE POWER OUTLET SCHEDULE

TAG

SP-1

TYPE

16 - 400A OUTLETS

NORTHING, EASTING

SP-2 16 - 400A OUTLETS

SP-3

12 - 400A OUTLETS

DLO CABLE

LENGTH

SP-4

SP-5

SP-6

SP-7

SP-8

SP-9

SP-10 12 - 400A OUTLETS

16 - 400A OUTLETS

16 - 400A OUTLETS

16 - 400A OUTLETS

16 - 400A OUTLETS

16 - 400A OUTLETS

16 - 400A OUTLETS

20'

40'

15'

15'

15'

15'

15'

15'

FIELD VERIFY CABLE LENGTHS BEFORE ORDERING

65'

55'

INDUSTRIAL POWER OUTLET SCHEDULE

TAG

IP-A

IP-B

IP-C

IP-D

IP-E

IP-F

TYPE

2 - 400A OUTLETS

NORTHING, EASTING

2 - 400A OUTLETS

2 - 400A OUTLETS

2 - 400A OUTLETS

2 - 400A OUTLETS

2 - 400A OUTLETS

IP-G 2 - 400A OUTLETS

IP-H 2 - 400A OUTLETS

IP-I 2 - 400A OUTLETS

IP-J 2 - 400A OUTLETS

IP-K 2 - 400A OUTLETS

IP-L 2 - 400A OUTLETS

IP-M 2 - 400A OUTLETS

IP-N 2 - 400A OUTLETS

IP-O 2 - 400A OUTLETS

IP-P 2 - 400A OUTLETS

IP-Q 2 - 400A OUTLETS

IP-R 2 - 400A OUTLETS

IP-S 2 - 400A OUTLETS

IP-T 2 - 400A OUTLETS

IP-U 2 - 400A OUTLETS

IP-V 2 - 400A OUTLETS

IP-W 2 - 400A OUTLETS

IP-X 2 - 400A OUTLETS

IP-Y 2 - 400A OUTLETS

IP-Z 2 - 400A OUTLETS

IP-AA 2 - 400A OUTLETS

IP-BB 2 - 400A OUTLETS

IP-CC 2 - 400A OUTLETS

IP-DD 2 - 400A OUTLETS

DLO CABLE

LENGTH

30'

30'

30'

30'

30'

30'

60'

90'

20'

35'

20'

20'

20'

20'

20'

20'

35'

35'

35'

35'

35'

35'

35'

IP-EE 1 - 400A OUTLETS

IP-FF 1 - 400A OUTLETS

65'

70'

55'

60'

20'

20'

20'

20'

20'

1. FIELD VERIFY CABLE LENGTHS BEFORE ORDERING.

2. 1R = 1-RECEPTACLE CONFIGURATION, 2R = 2-RECEPTACLE

CONFIGURATION, 4R = 4-RECEPTACLE CONFIGURATION. SEE DETAIL

C3/ES510 & C5/ES510.

IP-GG 1 - 400A OUTLETS 70'

CONFIGURATION

2R

2R

2R

2R

2R

2R

2R

2R

4R

4R

4R

4R

4R

4R

4R

4R

4R

4R

2R

2R 1R

1R

1R

AC-400

AC-401

AC-506

AC-524

DC-D7

AC-509

AC-510

AC-511

AC-512

AC-525

AC-517

AC-521

TC-1

TC-2

TC-6

AC-518

AC-519

AC-522

AC-523

CIP

CIP

CIP

CIP

NOTES:

1. SEE DRAWING ES516 FOR MANHOLE SIZES AND TYPES.

2. CIP (CONSTRUCTED-IN-PLACE) MANHOLES MUST BE BUILT

INTO PRECAST WALLS OF THE DRY DOCK. SEE

STRUCTURAL DWGS. YS109, YS110, YS126 AND YS127 FOR

DETAILS. SEE DRAWINGS ES407 AND ES408 FOR MANHOLE

SIZES.

CIP

CIP

CIP

CIP

CIP

CIP

CIP

TC-3

TC-4

TC-5

CIP

CIP

CIP

AC-507

AC-502

AC-508

MANHOLE SCHEDULE

TAG TYPE NORTHING, EASTING

AC-505 1

AC-514 5

DC-D87 5

DC-D89 5

AC-503

AC-504

AC-501 6

AC-516 CIP

AC-527 CIP (SEE A3/UE301)

TC-7 CIP

AC-520 CIP

AC-526 5

DC-D85 4

AC-515 4

KI

TT

ER

Y, M

AI

N E

PO

R

TS

M

O U

TH

N

AV

AL

S H

IP

YA

R D

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

SHEET

NAVFAC DRAWING NO.

OF

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

CA

PI

TA

L I

IM

PR

OV

EM

EN

T

CO

RE

NA

VA

L S

TA

TI

ON

N

OR

FO

LK

, V

IR

GI

NI

A

P-

M

U

LT

I-M

IS

SI

O

N D

R Y

D O

C K

#1

DRAWFORM REVISION: 07 AUG 2018

UNCLASSIFIED

U N C

LA

SS

IF

IE

D

UNCLASSIFIED

LBT/LBL

NBJ

EJA

DSN

JDM

CONSTR. CONTR. NO.

DRW CHKCSADES

SCALE: AS SHOWN

EPROJECT NO.: 1604959

JRC

C

U s er s\ Pu b l ic

\D oc u m en ts \L oc a l_ Re v i t_

Fi le s\ D

RY

D

S W

T R -1

5 9 -E

_C A ss in i.r vt

/1

7/

: 5 4:

P

M

EL

EC

TR

IC

AL

S

C H

ED

U

LE

S

ES605

12823985

ELECTRICAL SITE CIRCUIT SCHEDULE

TAG

ELECTRICAL

DATA PANEL

CIRCUIT

NUMBER

CIRCUIT

BREAKER WIRE/CONDUIT SIZE STARTER DISCONNECT NOTES

ACCU-1 480V/3 - 4000VA MRD 37,39,41 15A - 3P (3) #10, #10 GND, 3/4" C. YES 3,4

ACCU-2 480V/3 - 4000VA MRD 26,28,30 15A - 3P (3) #10, #10 GND, 3/4" C. YES 3,4

AHU-1 480V/3 - 2000VA MRD 20,22,24 15A - 3P (3) #10, #10 GND, 3/4" C. YES 3,4

AHU-1 480V/3 - 2000VA MRD 2,4,6 15A - 3P (3) #10, #10 GND, 3/4" C. YES 3,4

HB1-1 120V/1 - 1000 VA MPZ 1NN 13 20A-1P (2) #10, #10 GND, 3/4" C

HB1-2 120V/1 - 1900 VA MPZ 1NN 3 20A-1P (2) #10, #10 GND, 3/4" C

HB2-1 120V/1 - 1000 VA MPZ 1NN 14 20A-1P (2) #10, #10 GND, 3/4" C

HB2-2 120V/1 - 1000 VA MPZ 1NN 8 20A-1P (2) #10, #10 GND, 3/4" C

HB2-3 120V/1 - 1000 VA MPZ 1NN 11 20A-1P (2) #10, #10 GND, 3/4" C

HB2-4 120V/1 - 1000 VA MPZ 1NN 9 20A-1P (2) #10, #10 GND, 3/4" C

HB3-1 120V/1 - 1900 VA MPZ 1NSW 3 20A-1P (2) #10, #10 GND, 3/4" C

HB3-2 120V/1 - 1900 VA MPZ 1NSW 7 20A-1P (2) #10, #10 GND, 3/4" C

HB4-1 120V/1 - 1900 VA MPZ 1NSW 5 20A-1P (2) #10, #10 GND, 3/4" C

HB4-2 120V/1 - 1900 VA MPZ 1NSW 4 20A-1P (2) #10, #10 GND, 3/4" C

HB5-1 120V/1 - 1900 VA MPZ 1NSW 6 20A-1P (2) #10, #10 GND, 3/4" C

HB6-1 120V/1 - 1900 VA MPZ 1NSW 8 20A-1P (2) #10, #10 GND, 3/4" C

HB7-1 120V/1 - 1900 VA MPZ 1NSW 11 20A-1P (2) #10, #10 GND, 3/4" C

HB7-2 120V/1 - 1900 VA MPZ 1NSW 9 20A-1P (2) #10, #10 GND, 3/4" C

HB8-1 120V/1 - 1900 VA MPZ 1NSE 10 20A-1P (2) #10, #10 GND, 3/4" C

HB8-2 120V/1 - 1900 VA MPZ 1NSE 8 20A-1P (2) #10, #10 GND, 3/4" C

HB9-1 120V/1 - 1900 VA MPZ 1NSE 12 20A-1P (2) #10, #10 GND, 3/4" C

HB10-1 120V/1 - 1900 VA MPZ 1NSW 2 20A-1P (2) #10, #10 GND, 3/4" C

HB11-1 120V/1 - 1900 VA MPZ 1NN 4 20A-1P (2) #10, #10 GND, 3/4" C

HB11-2 120V/1 - 1900 VA MPZ 1NN 5 20A-1P (2) #10, #10 GND, 3/4" C

HB12-1 120V/1 - 1900 VA MPZ 1NSE 2 20A-1P (2) #10, #10 GND, 3/4" C

HB12-2 120V/1 - 1900 VA MPZ 1NSE 7 20A-1P (2) #10, #10 GND, 3/4" C

HB13-1 120V/1 - 1900 VA MPZ 1NSE 6 20A-1P (2) #10, #10 GND, 3/4" C

HB14-1 120V/1 - 1900 VA MPZ 1NSE 4 20A-1P (2) #10, #10 GND, 3/4" C

HB14-2 120V/1 - 1900 VA MPZ 1NSE 9 20A-1P (2) #10, #10 GND, 3/4" C

HB15-1 120V/1 - 1900 VA MPZ 1NSE 5 20A-1P (2) #10, #10 GND, 3/4" C

HB16-1 120V/1 - 1900 VA MPZ 1WS 7 20A-1P (2) #10, #10 GND, 3/4" C

HB16-2 120V/1 - 1900 VA MPZ 1WS 2 20A-1P (2) #10, #10 GND, 3/4" C

HB17-1 120V/1 - 1000 VA MPZ 1WS 4 20A-1P (2) #10, #10 GND, 3/4" C

HB17-2 120V/1 - 1000 VA MPZ 1WS 3 20A-1P (2) #10, #10 GND, 3/4" C

HB17-3 120V/1 - 1000 VA MPZ 1WS 10 20A-1P (2) #10, #10 GND, 3/4" C

HB17-4 120V/1 - 1000 VA MPZ 1WS 12 20A-1P (2) #10, #10 GND, 3/4" C

HB18-1 120V/1 - 1900 VA MPZ 1WS 6 20A-1P (2) #10, #10 GND, 3/4" C

HB18-2 120V/1 - 1900 VA MPZ 1WS 5 20A-1P (2) #10, #10 GND, 3/4" C

HB19-1 120V/1 - 1900 VA MPZ 1NN 6 20A-1P (2) #10, #10 GND, 3/4" C

HB19-2 120V/1 - 1000 VA MPZ-TASW 10 20A-1P (2) #10, #10 GND, 3/4" C

HB20-1 120V/1 - 1900 VA MPZ-TASW 7 20A-1P (2) #10, #10 GND, 3/4" C

HB20-2 120V/1 - 1000 VA MPZ-TASW 3 20A-1P (2) #10, #10 GND, 3/4" C

HB21-1 120V/1 - 1900 VA MPZ-TASW 4 20A-1P (2) #10, #10 GND, 3/4" C

HB21-2 120V/1 - 1000 VA MPZ-TASW 5 20A-1P (2) #10, #10 GND, 3/4" C

HB22-1 120V/1 - 1900 VA MPZ-TASW 6 20A-1P (2) #10, #10 GND, 3/4" C

HB22-1 120V/1 - 1000 VA MPZ-TASW 8 20A-1P (2) #10, #10 GND, 3/4" C

RFC-1N 120V/1 - 100VA MPZ 1NN 7 15A-1P (2) #10, #10 GND, 3/4" C

RFC-2N 120V/1 - 100VA MPZ 1NSW 10 15A-1P (2) #10, #10 GND, 3/4" C

RFC-3N 120V/1 - 100VA MPZ 1NSW 12 15A-1P (2) #10, #10 GND, 3/4" C

RFC-4N 120V/1 - 100VA MPZ 1WS 8 15A-1P (2) #10, #10 GND, 3/4" C

SP-1 480V/3 - 20000VA MRD 31,33,35 30A - 3P (3) #10, #10 GND, 3/4" C. 4

DD-UH-03 120 V/1-0 VA MPZ 1NN 1 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-04 120 V/1-0 VA MPZ 1NN 1 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-05 120 V/1-0 VA MPZ 1NN 2 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-06 120 V/1-0 VA MPZ 1NSE 1 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-07 120 V/1-0 VA MPZ 1NSW 1 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-08 120 V/1-0 VA MPZ 1NSE 3 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-09 120 V/1-0 VA MPZ 1NSW 1 20A-1P (2) #12, #12G IN 3/4"C YES 1

DD-UH-10 120 V/1-0 VA MPZ 1NSE 3 20A-1P (2) #12, #12G IN 3/4"C…