This document is a specification section outlining requirements for a wet pipe sprinkler system as part of a federal construction project to build a partitioned addition to an existing dry dock. Key details include specifications for underground and aboveground piping components, sprinklers, valves, backflow prevention, alarm and supervisory devices, and accessories. It also provides instructions for inspection, installation, testing, training, and closeout of the wet pipe sprinkler system. Submittal requirements and quality assurance measures are defined. The project is to construct additions to Dry Dock 1 at Portsmouth Naval Shipyard in Kittery, Maine to support maintenance and overhaul of Virginia-class submarines.
View the file
Other files
Show 40 more
Latest 50 of 123 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P381 Multi-Mission Drydock #1 eProjects # 1604959 Portsmouth Naval Shipyard, Kittery, ME
SECTION 21 13 13.00 20
WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
04/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 13 (2016; TIA 16-1; TIA 16-2; TIA 16-3 2016;
Errata 17-1; Errata 17-2) Standard for the Installation of Sprinkler Systems
NFPA 24 (2016; ERTA 2016) Standard for the Installation of Private Fire Service Mains and Their Appurtenances
UNDERWRITERS LABORATORIES (UL)
UL 262 (2004; Reprint Oct 2011) Gate Valves for Fire-Protection Service
UL 789 (2004; Reprint May 2017) UL Standard for Safety Indicator Posts for Fire-Protection Service
UL Fire Prot Dir (2012) Fire Protection Equipment Directory
1.2 SYSTEM DESCRIPTION
Design and provide automatic wet pipe fire extinguishing sprinkler systems for complete fire protection coverage throughout the Pump Station, Utility Enclosure, and Utility Tunnel as indicated on the design drawings.
1.3 SPRINKLER SYSTEM DESIGN
Except as modified herein, design automatic wet pipe fire extinguishing sprinkler systems in accordance with the required and advisory provisions of NFPA 13 , including all recommendations and advisory portions, which shall be considered mandatory; this includes advisory provisions listed in the appendices of such standard(s), as though the word "shall" had been substituted for the word "should" wherever it appears. Design system by
SECTION 21 13 13.00 20 Page 1 hydraulic calculations for uniform distribution of water over the design area. Hydraulic calculations shall assume a 12 psi pressure loss for the backflow preventer assembly. Locate sprinklers in a consistent pattern with ceiling grid, lights, and air supply diffusers. Provide sprinklers and piping system layout. All Devices and equipment for fire protection service shall be UL Fire Prot Dir listed or FM APP GUIDE approved for use in wet pipe sprinkler systems.
1.3.1 Location of Sprinklers
Sprinklers in relation to the ceiling and the spacing of sprinklers shall not exceed that permitted by NFPA 13 for ordinary hazard occupancy.
Uniformly space sprinklers on the branch piping. Sprinklers shall provide coverage throughout 100 percent of the structure(s). This includes, but is not limited to, telephone rooms, electrical equipment rooms, boiler rooms, switchgear rooms, transformer rooms, and other electrical and mechanical spaces.
1.3.2 Water Distribution
Distribution shall be uniform throughout the area in which the sprinklers will open. Discharge from individual sprinklers in hydraulically most remote area shall be between 100 percent and 120 percent of the specified density.
1.3.3 Density of Application of Water
Size pipe to provide the specified density when the system is discharging the specified total maximum required flow. Application to horizontal surfaces below the sprinklers shall be as indicated on the contract drawings.
1.3.4 Sprinkler Discharge Area
Area shall be the hydraulically most remote 2500 sq ft Area reductions and increases from NFPA 13 shall not be applied to this area.
1.3.5 Outside Hose Allowances
Hydraulic calculations shall include a hose allowance of 250 gpm for outside hose streams
1.3.6 Water Supply
Base hydraulic calculations on the water supply data shown on the fire protection contract drawings. The sprinkler systems are not to be fed from the fire pumps in the Utility Enclosure fire pump room, as the pumping arrangement is strictly to serve the hose manifold stations.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval.
Partial submittals and submittals not fully complying with the requirements and recommended practices of NFPA 13 and this specification section shall be returned disapproved without review. This contract stipulation is non-negotiable.
SECTION 21 13 13.00 20 Page 2
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Shop Drawings; G
Prepare 22 by 34 inch detail working drawings of sprinklers and piping. Floor plans shall be drawn to a scale not less than 1/8" = 1'-0". Show data essential for proper installation of each system. Show details, plan view, elevations and sections of the systems supply and piping. Show piping schematic of systems supply, devices, valves, pipe and fittings. Show point to point electrical wiring diagrams. Submit drawings signed by a registered fire protection engineer. Provide three copies of the Sprinkler System Shop Drawings, no later than 21 days prior to the start of sprinkler system installation.
SD-03 Product Data
Pipe; G
Fittings; G
Alarm valves; G
Valves, including gate, check, and globe ; G
Sprinklers; G
Pipe hangers and supports; G
Sprinkler Alarm Switches; G
Fire department connections; G
Mechanical couplings; G
Backflow Prevention Assembly; G
Annotate descriptive data to show the specific model, type, and size of each item. Catalog cuts shall also indicate UL Listing/FM Approval and country of manufacture.
SD-05 Design Data
Hydraulic Calculations; G
Submit computer program generated hydraulic calculations to substantiate compliance with hydraulic design requirements.
Calculations shall be performed by computer using software intended specifically for fire protection system design.
Calculations shall include isometric diagram indicating hydraulic nodes and pipe segments.Submit name of software program used.
SD-06 Test Reports
Request to schedule Preliminary Tests; G
SECTION 21 13 13.00 20 Page 3
Preliminary Test Report; G
Provide Three copies of the completed Preliminary Test Report, no later than 7 days after the completion of the Preliminary Tests.
The Preliminary Tests Report shall include both the Contractor's Material and Test Certificate for Underground Piping and the Contractor's Material and Test Certificate for Aboveground Piping. All items in the Preliminary Tests Report shall be signed by the Fire Protection Engineer.
Request to schedule Final Acceptance Test; G
Final Acceptance Test Report; G
Provide Three copies of the completed Final Acceptance Tests Reports, no later than 7 days after the completion of the Final Acceptance Tests. All items in the Final Acceptance Report shall be signed by the Fire Protection Engineer.
SD-07 Certificates
Inspection by Fire Sprinkler Nicet IV Designer; G
Fire Protection Engineer; G
The name and documentation of certification of the proposed Fire Protection Engineer, no later than 14 days after the Notice to Proceed and prior to the submittal of the sprinkler system drawings and hydraulic calculations.
Sprinkler System Installer; G
Submit data showing the Sprinkler System Installer has successfully installed systems of the same type and design as specified herein, Data shall include names and locations of at least two installations where the Contractor, or the subcontractor referred to above, has installed such systems. Indicate type and design of each system and certify that each system has performed satisfactorily in the manner intended for not less than 18 months. Provide NICET certification of the system technician.
Contractor shall submit data along with submittal of the Fire Protection Engineer Qualifications.
SD-10 Operation and Maintenance Data
Operating and Maintenance Instructions
Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA as supplemented and modifies by this specification section.
Provide six manuals in accordance with NFPA 13. The manuals shall include the manufacturer's name, model number, parts list, list of parts and tools that should be kept in stock by the owner for routine maintenance including the name of a local supplier, simplified wiring and controls diagrams, troubleshooting guide, and recommended service organization (including address and telephone number) for each item of equipment. Each service
SECTION 21 13 13.00 20 Page 4 organization submitted shall be capable of providing 4 hour on-site response to a service call on an emergency basis.
SD-11 Closeout Submittals
As-built drawings
As-built shop drawings, at no later than 14 days after completion of the Final Tests. The Sprinkler System Drawings shall be updated to reflect as-built conditions after all related work is completed. Provide electronic drawings in dwg or pdf format.
On-site training
1.5 QUALIFICATIONS
1.5.1 Fire Protection Engineer
A Fire Protection Engineer is a registered professional engineer (P.E.)
who has passed the fire protection engineering written examination administered by the National Council of Examiners for Engineering and Surveys (NCEES) or a registered P.E. in a related engineering discipline with a minimum of 5 years experience, dedicated to fire protection engineering that can be verified with documentation.
1.5.2 Sprinkler System Installer
The Sprinkler System Installer shall be regularly engaged in the installation of the type and complexity of system specified in the Contract documents, and shall have served in a similar capacity for at least three systems that have performed in the manner intended for a period of not less than 6 months. Installation drawings, shop drawings and as-built drawings shall be prepared, by or under the supervision of, an fire sprinkler systems designer who is experienced with the types of works specified herein, and is currently certified by the National Institute for Certification in Engineering Technologies (NICET) as an engineering technician with minimum Level IV certification in Automatic Sprinkler System program, applicable to all fire suppression systems on this project.
1.6 QUALITY ASSURANCE
1.6.1 Material and Equipment Qualifications
Provide materials and equipment that are standard products of manufacturers regularly engaged in the manufacture of such products, which are of a similar material, design and workmanship. Standard products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year use shall include applications of equipment and materials under similar circumstances and of similar size.
The product shall have been for sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2 year period.
1.6.2 Alternative Qualifications
Products having less than a two-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturer's factory or
SECTION 21 13 13.00 20 Page 5 laboratory tests, can be shown.
1.6.3 Manufacturer's Nameplate
Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
1.6.4 Field Fabricated Nameplates
ASTM D709. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified in the technical sections or as indicated on the drawings. Each nameplate inscription shall identify the function and, when applicable, the position.
Nameplates shall be melamine plastic, 0.125 inch thick, white with black center core. Surface shall be matte finish. Corners shall be square.
Accurately align lettering and engrave into the core. Minimum size of nameplates shall be one by 2.5 inches. Lettering shall be a minimum of
0.25 inch high normal block style.
1.7 ACCESSIBILITY
Install all work so that parts requiring periodic inspection, operation, maintenance, and repair are readily accessible. Install concealed valves, expansion joints, controls, dampers, and equipment requiring access, in locations freely accessible through access doors.
1.8 DELIVERY, STORAGE AND HANDLING
All equipment delivered and placed in storage shall be housed in a manner to preclude any damage from the weather, humidity and temperature variations, dirt and dust, or other contaminants. Additionally, all pipes shall either be capped or plugged until installed.
PART 2 PRODUCTS
2.1 UNDERGROUND PIPING COMPONENTS
Pipe shall comply with NFPA 24 . Minimum pipe size shall be 6 inches.
Piping more than 5 feet outside the building walls shall comply with Section 33 11 00 WATER UTILITY DISTRIBUTION PIPING.
2.2 GATE VALVE AND INDICATOR POSTS
Installation shall comply with NFPA 24 . Gate valves for use with indicator post shall conform to UL 262 . Indicator posts shall conform to UL 789 . Provide each indicator post with one coat of primer and two coats of red enamel paint.
2.3 VALVE BOXES
Except where indicator posts are provided, for each buried valve, provide ductile-iron of a suitable size. Provide ductile-iron cover for valve box with the word "WATER" cast on the cover. The box shaft diameter shall be
5.25 inches. Coat ductile-iron boxes with bituminous paint applied to a minimum dry-film thickness of 10 mils.
SECTION 21 13 13.00 20 Page 6
2.4 BURIED UTILITY WARNING AND IDENTIFICATION TAPE
Provide detectable aluminum foil plastic backed tape or detectable magnetic plastic tape manufactured specifically for warning and identification of buried piping. Tape shall be detectable by an electronic detection instrument. Provide tape in rolls, 3 inches minimum width, color coded for the utility involved with warning and identification imprinted in bold block letters continuously and repeatedly over the entire tape length. Warning and identification shall read "CAUTION BURIED WATER PIPING BELOW" or similar wording. Use permanent code and letter coloring unaffected by moisture and other substances contained in trench backfill material.
2.5 ABOVEGROUND PIPING COMPONENTS
All components of the aboveground piping shall fully comply with the requirements and recommended practices of NFPA 13 and this specification section. Aboveground piping shall be steel .
2.5.1 Steel Pipe
Pipe shall be black steel. Pipe shall be minimum Schedule 10 for piping larger than 2 inches, and piping 2 inches and smaller shall be Schedule 40.
Fittings into which sprinklers, sprinkler riser nipples, or drop nipples are threaded shall be welded, threaded, or grooved-end type. Plain-end fittings with mechanical couplings, fittings that use steel gripping devices to bite into the pipe and segmented welded fittings shall not be permitted. Rubber gasketed grooved-end pipe and fittings with mechanical couplings shall be permitted in pipe sizes 1.5 inches and larger.
Fittings, mechanical couplings, and rubber gaskets shall be supplied by the same manufacturer. Sprinkler pipe and fittings shall be metal. G alvanized pipe is prohibited.
2.5.2 Grooved Mechanical Joints and Fittings
Grooved couplings, fittings and grooving tools shall be products of the same manufacturer.
2.5.3 Flexible Sprinkler Hose
The use of flexible sprinkler hose is not permitted.
2.5.4 Sprinklers
Provide nominal 0.75 inch orifice sprinklers. Sprinklers with internal O-rings shall not be used. Sprinklers shall be used in accordance with their listed coverage limitations. Provide Pendent or Upright sprinklers as indicated on the drawings. Sprinklers shall have a brass finish.
Temperature classification shall be as indicated. Sprinklers in high heat areas including attic spaces or in close proximity to unit heaters shall have temperature classification in accordance with NFPA 13 . Extended coverage sprinklers shall not be used. Deflector shall not be more than3 inches below suspended ceilings. Ceiling plates shall not be more than
0.5 inch deep. Ceiling cups shall not be permitted.
2.5.5 Valves
Provide valves of types approved for fire service. Valves shall open by counterclockwise rotation. Provide an OS&Y valve beneath each alarm.
SECTION 21 13 13.00 20 Page 7
Check valves shall be clear opening swing-check type with inspection and access cover plate for sizes 8 inches and larger.
2.5.6 Pipe Supports
Provide Pipe hangers and supports in accordance with NFPA 13 .
2.5.7 Alarm Valves
Provide variable pressure type alarm check valve, standard trim piping, pressure gauges, bypass, retarding chamber, testing valves, main drain, and other components as required for a fully operational system.
2.5.8 Fire Department Connections
Fire department connection shall be projecting type with cast brass body, matching wall escutcheon lettered "Auto Spkr" with a polished brass finish. The connection shall have two inlets with individual self-closing clappers, caps with drip drains and chains. Female inlets shall have 2-1/2 inch diameter American National Fire Hose Connection Screw Threads (NH) per NFPA 1963 and in accordance with the Shipyard Fire Department.
This fire department connection shall serve all fire sprinkler systems serving the Pump Station, Utility Enclosure, and Utility Tunnel.
2.5.9 Backflow Prevention Assembly
Provide listed double check valve assembly backflow preventer, listed for vertical orientation. Each check valve shall have a drain. Backflow prevention assemblies shall have current "Certificate of Approval from the Foundation for Cross-Connection Control and Hydraulic Research, FCCCHR List. Listing of the specific make, model, design, and size in the FCCCHR List shall be acceptable as the required documentation."
2.6 ALARM INITIATING AND SUPERVISORY DEVICES
2.6.1 Sprinkler Alarm Switches
Provide vane type flow switch(es) with circuit opener or closer for the automatic transmittal of an alarm over the facility fire alarm system.
Connection of switch shall be under Section 28 31 63.00 20
ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM
2.6.2 Valve Supervisory (Tamper) Switch
Switch shall be suitable for mounting to the type of control valve to be supervised open. The switch shall be tamper resistant and contain one set of SPDT (Form C) contacts arranged to transfer upon removal of the housing cover or closure of the valve of more than two rotations of the valve stem.
2.7 ACCESSORIES
2.7.1 Sprinkler Cabinet
Provide metal cabinet with extra sprinklers and sprinkler wrench adjacent to each alarm valve. The number and types of extra sprinklers shall be as specified in NFPA 13 .
SECTION 21 13 13.00 20 Page 8
2.7.2 Pipe Escutcheon
Provide split hinge metal plates for piping entering walls, floors, and ceilings in exposed spaces. Provide polished stainless steel plates or chromium-plated finish on copper alloy plates in finished spaces. Provide paint finish on metal plates in unfinished spaces.
PART 3 EXECUTION
3.1 INSPECTION BY FIRE SPRINKLER NICET IV DESIGNER
The Fire Sprinkler Nicet IV Designer shall inspect the sprinkler system periodically during the installation to assure the sprinkler system is being provided and installed in accordance with the contract requirements and the approved sprinkler system submittal(s). The Fire Sprinkler Nicet IV Designer shall attend both the preliminary and final tests, and shall sign the test results. After the preliminary testing has been completed, the Fire Sprinkler Nicet IV Designer, shall certify in writing the system is ready for the final inspections and tests. This report shall document any discrepancies found and what actions will be taken to correct. Any discrepancy noted during the periodic site visits or the preliminary testing shall be brought to the attention of the Contracting Officer in writing, no later than three working days after the discrepancy is discovered.
3.2 UNDERGROUND PIPING INSTALLATION
The methods of fabrication and installation of the underground piping shall fully comply with the requirements and recommended practices of NFPA 13 , NFPA 24 and the contract drawings.
3.3 ABOVEGROUND PIPING INSTALLATION
The methods of fabrication and installation of the aboveground piping shall fully comply with the requirements and recommended practices of NFPA 13 and this specification section.
3.3.1 Piping in Finished Areas
In areas with suspended or dropped ceilings and in areas with concealed spaces above the ceiling, piping shall be concealed above ceilings.
Piping shall be inspected, tested and approved before being concealed.
Risers and similar vertical runs of piping in finished areas shall be concealed.
3.3.2 Pendent Sprinklers
Where sprinklers are installed below suspended or dropped ceilings, drop nipples shall be cut such that sprinkler ceiling plates or escutcheons are of a uniform depth throughout the finished space. The outlet of the reducing coupling shall not extend more than 1 inch below the underside of the ceiling. Pendent sprinklers in suspended ceilings shall be a minimum of 6 inches from ceiling grids.
3.3.3 Pipe Joints
Pipe joints shall conform to NFPA 13 , except as modified herein. Welded joints will be permitted, only if welding operations are performed as required by NFPA 13 at the Contractor's fabrication shop, not at the
SECTION 21 13 13.00 20 Page 9 project construction site. Flanged joints shall be provided where indicated or required by NFPA 13 . Grooved pipe and fittings shall be prepared in accordance with the manufacturer's latest published specification according to pipe material, wall thickness and size.
Grooved couplings, fittings and grooving tools shall be products of the same manufacturer. The diameter of grooves made in the field shall be measured using the method specifically approved by the coupling manufacturer for the intended application. Groove width and dimension of groove from end of pipe shall be measured and recorded for each change in grooving tool setup to verify compliance with coupling manufacturer's tolerances. A representative of the grooved couplings and fittings manufacturer shall conduct at least one onsite inspection of the piping installation to ensure the method of installation is in accordance with the manufacturer's requirements and recommended practices.
3.3.4 Reducers
Reductions in pipe sizes shall be made with one-piece tapered reducing fittings. Bushings are prohibited.
3.3.5 Pipe Penetrations
Cutting structural members for passage of pipes or for pipe-hanger fastenings will not be permitted. Pipes that must penetrate concrete or masonry walls or concrete floors shall be core-drilled and provided with pipe sleeves. Each sleeve shall be Schedule 40 galvanized steel, ductile iron or cast iron pipe and shall extend through its respective wall or floor and be cut flush with each wall surface. Sleeves shall provide required clearance between the pipe and the sleeve per NFPA 13 . The space between the sleeve and the pipe shall be firmly packed with mineral wool insulation. Where pipes penetrate fire walls, fire partitions, or floors, pipes shall be fire stopped in accordance with Section 07 84 00 FIRESTOPPING. In penetrations that are not fire-rated or not a floor penetration, the space between the sleeve and the pipe shall be sealed at both ends with plastic waterproof cement that will dry to a firm but pliable mass or with a mechanically adjustable segmented elastomer seal.
3.3.6 Inspector's Test Connection
Provide test connections approximately 6 feet above the floor for each sprinkler system or portion of each sprinkler system equipped with an alarm device. Provide test connection piping to a drain location that can accept full flow where the discharge will be readily visible and where water may be discharged without property damage. Discharge to floor drains, janitor sinks or similar fixtures shall not be permitted. Provide discharge orifice of same size as corresponding sprinkler orifice. The penetration of the exterior wall shall be no greater than 2 feet above finished grade.
3.3.7 Drains
Main drain piping shall be provided to discharge at a safe point outside the building, approved by the owner. Basement level drainage shall be piped to discharge at a safe point outside the building, approved by the owner.Auxiliary drains shall be provided as required by NFPA 13 .
3.3.8 Installation of Fire Department Connection
Connection shall be mounted on the exterior wall approximately 3 feet
SECTION 21 13 13.00 20 Page 10 above finished grade. The piping between the connection and the check valve shall be provided with an automatic drip in accordance with NFPA 13 and arranged to drain to the outside.
3.3.9 Identification Signs
Signs shall be affixed to each control valve, inspector test valve, main drain, auxiliary drain, test valve, and similar valves as appropriate or as required by NFPA 13 . Valve identification signs shall be minimum 6 inches wide by 2 inches high with enamel baked finish on minimum 18 gauge steel or 0.024 inch aluminum with red letters on a white background or white letters on red background. Hydraulic design data nameplates shall be permanently affixed to each sprinkler riser as specified in NFPA 13 .
3.4 ELECTRICAL WORK
Except as supplemented and modified herein, electric equipment and wiring shall be in accordance with Section 26 20 00 INTERIOR DISTRIBUTION
SYSTEM. 28 31 63.00 20 ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM
3.5 PIPE PAINTING AND COLOR CODE MARKING
Paint and color code mark sprinkler piping system as specified in Section
09 90 00 PAINTS AND COATINGS.
3.6 PRELIMINARY TESTS
The system, including the underground water mains, and the aboveground piping and system components, shall be tested to assure that equipment and components function as intended. The underground and aboveground interior piping systems and attached appurtenances subjected to system working pressure shall be tested in accordance with NFPA 13 and NFPA 24 .
Submit request to schedule Preliminary Tests, no later than 14 days prior to the proposed start of the tests. Upon completion of specified tests, the Contractor shall submit for approval a Preliminary Test Report.
3.6.1 Underground Piping
3.6.1.1 Flushing
Underground piping shall be flushed in accordance with NFPA 24 .
3.6.1.2 Hydrostatic Testing
New underground piping shall be hydrostatically tested in accordance with
NFPA 24 .
3.6.2 Aboveground Piping
3.6.2.1 Hydrostatic Testing
Aboveground piping shall be hydrostatically tested in accordance with
NFPA 13 .
3.7 FINAL ACCEPTANCE TEST
Final Acceptance Test shall begin only when the Preliminary Test Report has been approved. Submit request to schedule Final Acceptance Test, no later than 14 days prior to the proposed start of the tests. Notification
SECTION 21 13 13.00 20 Page 11 shall include a copy of the Contractor's Material & Test Certificates.
The NAVFAC Midlant Fire Protection Engineer must witness the Final Acceptance Test which shall include a complete demonstration of the operation of the system. This shall include operation of control valves and flowing of inspector's test connections to verify operation of associated waterflow alarm switches. After operation of control valves has been completed, the main drain test shall be repeated to assure that control valves are in the open position. In addition, the representative shall have available copies of as-built drawings and certificates of tests previously conducted. The installation shall not be considered accepted until identified discrepancies have been corrected and test documentation is properly completed and received. The Contractor shall submit the Final Acceptance Test Report as specified in the Submittals paragraph.
An experienced technician regularly employed by the system installer shall be present during the inspection. The NAVFAC Midlant Fire Protection Engineer must attend the final inspections and tests. At this inspection, repeat any or all of the required tests as directed. Correct defects in work provided by the Contractor, and make additional tests until the systems comply with contract requirements. Furnish appliances, equipment, electricity, instruments, connecting devices, and personnel for the tests. The Government will furnish water for the tests. The NAVFAC Division, Naval Facilities Engineering Command, Fire Protection Engineer, will witness formal tests and approve systems before they are accepted.
3.8 ON-SITE TRAINING
Submit request to schedule the On-site Training, at least 14 days prior to the start of related training but prior to the final inspections and tests. The sprinkler contractor shall conduct a training course for operating and maintenance personnel as designated by the Contracting Officer. Training shall be provided for a period of 8 hours of normal working time and shall start after the system is functionally complete and after the Final Acceptance Test. The On-Site Training shall cover all of the items contained in the approved Operating and Maintenance Instructions.
-- End of Section --
SECTION 21 13 13.00 20 Page 12
| 21 13 13.00 20 - WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SYSTEM DESCRIPTION |
| 1.3 SPRINKLER SYSTEM DESIGN |
| 1.3.1 Location of Sprinklers |
| 1.3.2 Water Distribution |
| 1.3.3 Density of Application of Water |
| 1.3.4 Sprinkler Discharge Area |
| 1.3.5 Outside Hose Allowances |
| 1.3.6 Water Supply |
| 1.4 SUBMITTALS |
| 1.5 QUALIFICATIONS |
| 1.5.1 Fire Protection Engineer |
| 1.5.2 Sprinkler System Installer |
| 1.6 QUALITY ASSURANCE |
| 1.6.1 Material and Equipment Qualifications |
| 1.6.2 Alternative Qualifications |
| 1.6.3 Manufacturer's Nameplate |
| 1.6.4 Field Fabricated Nameplates |
| 1.7 ACCESSIBILITY |
| 1.8 DELIVERY, STORAGE AND HANDLING |
| PART 2 PRODUCTS |
| 2.1 UNDERGROUND PIPING COMPONENTS |
| 2.2 GATE VALVE AND INDICATOR POSTS |
| 2.3 VALVE BOXES |
| 2.4 BURIED UTILITY WARNING AND IDENTIFICATION TAPE |
| 2.5 ABOVEGROUND PIPING COMPONENTS |
| 2.5.1 Steel Pipe |
| 2.5.2 Grooved Mechanical Joints and Fittings |
| 2.5.3 Flexible Sprinkler Hose |
| 2.5.4 Sprinklers |
| 2.5.5 Valves |
| 2.5.6 Pipe Supports |
| 2.5.7 Alarm Valves |
| 2.5.8 Fire Department Connections |
| 2.5.9 Backflow Prevention Assembly |
| 2.6 ALARM INITIATING AND SUPERVISORY DEVICES |
| 2.6.1 Sprinkler Alarm Switches |
| 2.6.2 Valve Supervisory Tamper Switch |
| 2.7 ACCESSORIES |
| 2.7.1 Sprinkler Cabinet |
| 2.7.2 Pipe Escutcheon |
| PART 3 EXECUTION |
| 3.1 INSPECTION BY FIRE SPRINKLER NICET IV DESIGNER |
| 3.2 UNDERGROUND PIPING INSTALLATION |
| 3.3 ABOVEGROUND PIPING INSTALLATION |
| 3.3.1 Piping in Finished Areas |
| 3.3.2 Pendent Sprinklers |
| 3.3.3 Pipe Joints |
| 3.3.4 Reducers |
| 3.3.5 Pipe Penetrations |
| 3.3.6 Inspector's Test Connection |
| 3.3.7 Drains |
| 3.3.8 Installation of Fire Department Connection |
| 3.3.9 Identification Signs |
| 3.4 ELECTRICAL WORK |
| 3.5 PIPE PAINTING AND COLOR CODE MARKING |
| 3.6 PRELIMINARY TESTS |
| 3.6.1 Underground Piping |
| 3.6.1.1 Flushing |
| 3.6.1.2 Hydrostatic Testing |
| 3.6.2 Aboveground Piping |
| 3.6.2.1 Hydrostatic Testing |
| 3.7 FINAL ACCEPTANCE TEST |
| 3.8 ON-SITE TRAINING |