Specifications 2.pdf
PDF 5 MB Posted
- Attached to
- P-5001 DBB, JOINT AIR DEFENSE OPERATIONS PHASE II, JOINT BASE ANACOSTIA-BOLLING, WASHINGTON, DC
- Solicitation number
- N4008021R3502
About this file
This solicitation is for the construction of a two-story Joint Air Defense Operations Center at Joint Base Anacostia-Bolling in Washington, DC. The project scope includes constructing a concrete slab-on-grade foundation with spread footings and structural steel frame, concrete masonry unit shear walls, roofing system, pavements, utilities, site improvements, passive force protection measures, security fencing, and diverse communication routing. The facility must meet Intelligence Community, Department of Defense, Air Force, and Joint Base design standards, and be designed as permanent construction according to Department of Defense criteria. Special construction requirements include complying with Controlled Space standards and using special exterior finishes. This acquisition is being conducted by the Naval Facilities Engineering Command.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Submitted By: Ahmed Khalil, LEED AP Date: 25 October 2021 Project Manager
Project Manager: Michelle Robertson, PE Date:
NAVFAC Project Manager
Approved By: Date:
eProject NO. 1673850 Contract NO. N40080-17-D-0018
Yousef Nawas, AIA Mechanical:
Sami Klapperick, NCIDQ Plumbing:
Electrical:
David Traxler, PE Jerome Lemens, PE John O’Neil, PE
Architectural:
Interior:
Civil:
Structural:
Stanley Lee, PE Tom Holt, PE Communications: Robert Fauvelle
Geotechnical: Michael Venezia, PE Fire Protection: Michael Owens, PE Specifications: Larry Adams, AIA Cost Estimating: John Adams AT/FP: Brian Horstmann, SE PE Sustainabiity: Elizabeth Floyd Security: Robert, Craig, PE
David Wolfel, RA Acting Design Production Director
SPECIFICATIONS
IFC Submission
25 October 2021
Volume 2 of 2 Divisions 10 - 41
FY22 MCON PROJECT P-5001
JOINT AIR DEFENSE OPERATIONS CENTER
(JADOC) PHASE II
Joint Base Anacostia-Bolling, Washington, DC
PREPARED BY:
Jacobs 1100 North Glebe Road
Suite 500 Arlington, VA 22201
FOUO
FOUO
Construction Solicitation NO. N40080-21-R-3502
28 October 2021
01 November 2021
THIS PAGE LEFT INTENTIONALLY BLANK
FOUO
P-5001 - JADOC PHASE II Work Order No. 1673850 Joint Base Anacostia Bolling, Washington, D.C.
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 07 SEALS PAGE
00 01 15 LIST OF DRAWINGS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 20 00 PRICE AND PAYMENT PROCEDURES
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 30 01.00 23 DESIGN, PROCUREMENT, AND INSTALLATION OF FURNITURE,
FIXTURES, AND EQUIPMENT
01 31 23.13 20 ELECTRONIC CONSTRUCTION AND FACILITY SUPPORT CONTRACT
MANAGEMENT SYSTEM
01 32 17.00 20 COST-LOADED NETWORK ANALYSIS SCHEDULES (NAS)
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 20 QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 46 00 BLAST RESISTANCE
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 58 00 PROJECT IDENTIFICATION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 24.00 20 FACILITY ELECTRONIC OPERATION AND MAINTENANCE SUPPORT
INFORMATION (eOMSI)
01 78 30.00 23 CADD DATA FOR GIS DELIVERABLES
01 91 00.15 20 TOTAL BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
PROJECT TABLE OF CONTENTS Page 1
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 13 53 ELASTOMERIC SHEET WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 36 SPRAY FOAM AIR BARRIERS
07 54 19 POLYVINYL-CHLORIDE ROOFING
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS AND FRAMES
08 14 00 WOOD DOORS
08 31 00 ACCESS DOORS AND PANELS
08 33 23 OVERHEAD COILING DOORS
08 34 59 VAULT DOORS AND DAY GATES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 67 23.13 STANDARD RESINOUS FLOORING
09 68 00 CARPETING
09 69 13 RIGID GRID ACCESS FLOORING
09 90 00 PAINTS AND COATINGS
09 96 00 HIGH-PERFORMANCE COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 39 FOLDING PANEL PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
PROJECT TABLE OF CONTENTS Page 2
DIVISION 13 - SPECIAL CONSTRUCTION
13 48 73 BRACING FOR EQUIPMENT
DIVISION 21 - FIRE SUPPRESSION
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00.00 20 COMMISSIONING OF MECHANICAL AND PLUMBING SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 20 FACILITY GAS PIPING
23 21 13.00 20 LOW TEMPERATURE WATER (LTW) HEATING SYSTEM
23 30 00 HVAC AIR DISTRIBUTION
23 52 43.00 20 LOW PRESSURE WATER HEATING BOILERS (UNDER 800,000 BTU/HR
OUTPUT)
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 82 00.00 20 TERMINAL HEATING UNITS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.21 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS FIRE
AND LIFE SAFETY (F&LS)
25 05 11.23 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMSUTILITY
MONITORING AND CONTROL SYSTEMS (UMCS)
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 16 PUBLIC ADDRESS SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM,
ADDRESSABLE
PROJECT TABLE OF CONTENTS Page 3
DIVISION 31 - EARTHWORK
31 23 00.00 20 EXCAVATION AND FILL
31 63 26.60 HELICAL PILES
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENT
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 31 13.53 HIGH-SECURITY FENCES (CHAIN LINK AND ORNAMENTAL) AND GATES
32 92 19 SEEDING
32 93 00 EXTERIOR PLANTS
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 11 23 NATURAL GAS AND LIQUID PETROLEUM PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 46 13 FOUNDATION DRAINAGE
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 13.19 JIB CRANES
41 22 23.19 MONORAIL HOISTS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
JADOC Phase II Final Submission Work Order No. 1673850
SECTION 00 01 07
SEALS PAGE
11/14
DOCUMENT 00 01 07 Page 1
CIVIL ENGINEER:
Cheuk Ming Lee License Number PE-2011015770 in The State of Missouri Expiration Date: 12/31/2021
ARCHITECT:
Yousef Nawas License Number 001-021847 in The State of Illinois Expiration Date: 11/30/2022
INTERIOR DESIGNER:
Samantha Klapperick License Number 001137 in The Commonwealth of Virginia Expiration Date: 04/30/2022
STRUCTURAL ENGINEER:
Thomas P. Holt License Number 056668 in The Commonwealth of Virginia Expiration Date: 12/31/2022
SECURITY ENGINEER:
Stephanie P. Elliot License Number 54583 in The State of Maryland Expiration Date: 12/31/2022
JADOC Phase II Final Submission Work Order No. 1673850
DOCUMENT 00 01 07 Page 2
LANDSCAPE ARCHITECT:
Jay LeChien License Number 2973 in The State of Texas Expiration Date: 09/30/2021
TELECOMMUNICATIONS ENGINEER:
Robert Fauvelle License Number 128496 in The RCDD Expiration Date: 10/28/2022
FIRE PROTECTION ENGINEER:
Michael Owens License Number 49630 in The State of Maryland Expiration Date: 10/28/2022
ELECTRICAL ENGINEER:
John O'Neil License Number 0402-024557 in The Commonwealth of Virginia Expiration Date: 09/30/23
MECHANICAL ENGINEER:
David P. Traxler License Number 43148 in The State of Maryland Expiration Date: 12/20/2022
DOCUMENT 00 01 15
LIST OF DRAWINGS
02/11, CHG 1: 08/14
PART 1 GENERAL
1.1 SUMMARY
This section lists the drawings for the project pursuant to contract clause "DFARS 252.236-7001, Contract Drawings, Maps and Specifications."
1.2 CONTRACT DRAWINGS
Contract drawings are as follows:
JADOC II SHEET INDEX
SHEET NO. REV. NO. NAVFAC DWG.
NO.
SHEET NAME
GENERAL
G-001 13134470 COVER SHEET
G-002 13134471 SHEET INDEX
G-003 13134472 SHEET INDEX - CONTINUED
G-004 13134473 GENERAL NOTES, GENERAL SYMBOLS, ABBREVIATIONS
LIFE SAFTEY
L-001 13134474 LIFE SAFETY GENERAL NOTES
L-002 13134475 CODE COMPLIANCE SITE PLAN
L-101 13134476 LIFE SAFETY PLAN - FIRST FLOOR
L-102 13134477 LIFE SAFETY PLAN - SECOND FLOOR
SURVEY
VF101 13134478 EXISTING CONDITIONS PLAN
VF102 13134479 SURVEY CONTROL AND UTILITIES STRUCTURE
SCHEDULE
GEOTECHNICAL
B-001 13134480 BORING LOCATION PLAN
DOCUMENT 00 01 15 Page 1
B-002 13134481 BORING LOGS
B-003 13134482 BORING LOGS
B-004 13134483 BORING LOGS
B-005 13134484 BORING LOGS
B-006 13134485 BORING LOGS
B-007 13134486 BORING LOGS
B-008 13134487 BORING LOGS
B-009 13134488 LABORATORY TESTING SUMMARY
CIVIL
C-001 13134489 BMP MATERIAL CRITERIA AND SEQUENCE OF
CONSTRUCTION
C-002 13134490 GENERAL NOTES
C-003 13134491 GENERAL NOTES
C-004 13134492 LEGEND AND ABBREVIATIONS
C-005 13134493 LOCATION MAP, VICINITY MAP AND CONTRACTOR
ACCESS ROUTE
CD101 13134494 DEMOLITION PLAN
CS101 13134495 SITE PLAN
CS102 13134496 LAYOUT PLAN
CS103 13134497 LAYOUT PLAN
CS104 13134498 LAYOUT COORDINATE DATA
CG101 13134499 GRADING PLAN
CG102 13134500 GRADING PLAN
CG103 13134501 EROSION CONTROL PLAN
CG104 13134502 EROSION CONTROL NOTES
CG105 13134503 EROSION CONTROL DETAILS
CG106 13134504 EROSION CONTROL DETAILS
CG107 13134505 EROSION CONTROL DETAILS
CG201 13134506 ROAD PROFILES
DOCUMENT 00 01 15 Page 2
CG202 13134507 ROAD PROFILES
CG301 13134508 BMP TYPICAL SECTIONS
CG302 13134509 BMP ENLARGED PLAN
CG501 13134510 BMP DETAILS
CU101 13134511 UTILITY PLAN
CU201 13134512 SANITARY SEWER LINE PROFILE
CU202 13134513 STORM DRAIN LINE PROFILES
CU203 13134514 STORM DRAIN LINE PROFILES
CU204 13134515 WATER LINE PROFILES
C-501 13134516 SITE DETAILS
C-502 13134517 SITE DETAILS
C-503 13134518 SITE DETAILS
C-504 13134519 FENCE DETAILS
C-505 13134520 FENCE DETAILS
C-506 13134521 FENCE DETAILS
C-507 13134522 FENCE DETAILS
C-508 13134523 FENCE DETAILS
C-509 13134524 FENCE DETAILS
C-510 13134525 STORM SEWER DETAILS
C-511 13134526 STORM SEWER DETAILS
C-512 13134527 SANITARY SEWER DETAILS
C-513 13134528 WATER DETAILS
LANDSCAPE
LS001 13134529 LANDSCAPE GENERAL NOTES
LS002 13134530 LANDSCAPE PLANTING SCHEDULE
LS101 13134531 LANDSCAPE TREE INVENTORY
LS102 13134532 LANDSCAPE TREE PROTECTION PLAN
DOCUMENT 00 01 15 Page 3
LS103 13134533 LANDSCAPE SITE PLAN
LS104 13134534 LANDSCAPE PLANTING LAYOUT
LS105 13134535 LANDSCAPE BMP PLANTING PLAN
LS106 13134536 LANDSCAPE SEEDING PLAN
LS107 13134537 JBAB INSTALLATION LANDSCAPE TREE REPLACEMENT
LOCATION A
LS108 13134538 JBAB INSTALLATION LANDSCAPE TREE REPLACEMENT
LOCATION B
LS109 13134539 JBAB INSTALLATION LANDSCAPE TREE REPLACEMENT
LOCATION C
LS110 13134540 JBAB INSTALLATION LANDSCAPE TREE REPLACEMENT
LOCATION D
LS111 13134541 JBAB INSTALLATION LANDSCAPE TREE REPLACEMENT
LOCATION E
LS501 13134542 LANDSCAPE PLANTING DETAILS
LS502 13134543 LANDSCAPE TREE PROTECTION AND CLEAR ZONE
REQUIREMENTS
LS503 13134544 LANDSCAPE URBAN FORESTRY ADMINISTRATION TREE
REMOVAL PERMIT
STRUCTURAL
S-001 13134545 GENERAL NOTES
S-002 13134546 GENERAL NOTES
S-003 13134547 GENERAL NOTES
SD101 13134548 FOUNDATION DEMOLITION PLAN
SD102 13134549 SECOND FLOOR DEMOLITION PLAN
SD301 13134550 DEMOLITION SECTIONS
S-101 13134551 FIRST FLOOR AND FOUNDATION PLAN
S-102 13134552 SECOND FLOOR FRAMING PLAN
S-103 13134553 ROOF FRAMING PLAN
S-104 13134554 PENTHOUSE ROOF FRAMING PLAN
S-201 13134555 FRAMING ELEVATIONS
S-202 13134556 FRAMING ELEVATIONS
S-301 13134557 SECTIONS
S-401 13134558 ENLARGED PLANS
DOCUMENT 00 01 15 Page 4
S-501 13134559 TYPICAL DETAILS - FOUNDATIONS
S-502 13134560 TYPICAL DETAILS - FOUNDATIONS
S-503 13134561 TYPICAL DETAILS - CONCRETE
S-504 13134562 TYPICAL DETAILS - CONCRETE
S-505 13134563 TYPICAL DETAILS - STEEL
S-506 13134564 TYPICAL DETAILS - DECKING
S-507 13134565 TYPICAL DETAILS - DECKING
S-508 13134566 TYPICAL DETAILS - MASONRY
S-509 13134567 TYPICAL DETAILS - WALLS
S-510 13134568 TYPICAL DETAILS - DEEP FOUNDATIONS
S-511 13134569 TYPICAL DETAILS - MISCELLANEOUS
S-512 13134570 TYPICAL DETAILS - JIB CRANE
ARCHITECTURAL
A-001 13134571 ARCHITECTURAL SYMBOLS, LEGENDS AND NOTES
A-002 13134572 TYPICAL MOUNTING HEIGHTS & ACCESSIBILITY
STANDARDS
A-003 13134573 BUILDING AIR BARRIER ENVELOPE
AD100 13134574 DEMO FLOOR PLANS
AD101 13134575 DEMO ELEVATIONS
A-101 13134576 FIRST FLOOR PLAN
A-102 13134577 SECOND FLOOR PLAN
A-130 13134578 ROOF PLAN
A-131 13134579 UPPER ROOF PLAN
A-151 13134580 FIRST FLOOR REFLECTED CEILING PLAN
A-152 13134581 SECOND FLOOR REFLECTED CEILING PLAN
A-201 13134582 SOUTH EXTERIOR ELEVATION
A-202 13134583 EAST AND WEST EXTERIOR ELEVATIONS
A-301 13134584 BUILDING SECTIONS
DOCUMENT 00 01 15 Page 5
A-302 13134585 BUILDING SECTIONS
A-310 13134586 WALL SECTIONS
A-311 13134587 WALL SECTIONS
A-401 13134588 ENLARGED FLOOR PLANS - RESTROOMS
A-402 13134589 ENLARGED FLOOR PLANS - RESTROOMS
A-405 13134590 ENLARGED STAIR PLANS AND SECTIONS
A-406 13134591 ENLARGED STAIR PLANS AND SECTIONS
A-501 13134592 PLAN EXTERIOR DETAILS
A-510 13134593 SECTION DETAILS
A-511 13134594 SECTION DETAILS
A-512 13134595 EXTERIOR OPENING DETAILS
A-540 13134596 ROOF DETAILS
A-541 13134597 ROOF DETAILS
A-545 13134598 EXTERIOR DETAILS
A-550 13134599 PLAN AND SECTION DETAILS
A-555 13134600 DETAILS - CONTROLLED SPACE
A-556 13134601 PLAN AND SECTION DETAILS
A-560 13134602 STAIR DETAILS
A-565 13134603 ACCESS FLOOR DETAILS
A-601 13134604 DOOR, WINDOW AND LOUVER SCHEDULES AND DETAILS
A-602 13134605 EXTERIOR FINISH SCHEDULE
A-604 13134606 DOOR DETAILS
A-610 13134607 PARTITION TYPES
A-611 13134608 PARTITION TYPES
A-612 13134609 PARTITION TYPES
A-613 13134610 PARTITION TYPES
A-801 13134611 AREA CALCULATION
DOCUMENT 00 01 15 Page 6
A-901 13134612 PERSPECTIVE VIEWS
INTERIORS
I-100 13134613 FIRST FLOOR FURNITURE PLAN
I-101 13134614 SECOND FLOOR FURNITURE PLAN
I-102 13134615 FIRST FLOOR FINISH PLAN
I-103 13134616 FIRST FLOOR CORNER GUARD PLAN
I-104 13134617 SECOND FLOOR FINISH PLAN
I-105 13134618 SECOND FLOOR CORNER GUARD PLAN
I-106 13134619 FIRST FLOOR INTERIOR SIGNAGE PLAN
I-107 13134620 SECOND FLOOR INTERIOR SIGNAGE PLAN
I-108 13134621 FIRST FLOOR INTERIOR ELEVATION PLAN
I-109 13134622 SECOND FLOOR INTERIOR ELEVATION PLAN
I-200 13134623 INTERIOR ELEVATIONS
I-201 13134624 INTERIOR ELEVATIONS
I-202 13134625 INTERIOR ELEVATIONS
I-203 13134626 INTERIOR ELEVATIONS
I-204 13134627 INTERIOR ELEVATIONS
I-205 13134628 INTERIOR ELEVATIONS
I-400 13134629 ENLARGED FURNITURE PLANS
I-401 13134630 ENLARGED FINISH PLANS
I-402 13134631 ENLARGED INTERIOR ELEVATION PLANS
I-500 13134632 SIGNAGE TYPICALS
I-501 13134633 SIGNAGE TYPICALS
I-502 13134634 TYPICAL SIGNAGE MOUNTING HEIGHTS
I-503 13134635 TYPICAL SIGNAGE MOUNTING HEIGHTS
I-504 13134636 MILLWORK DETAILS
I-505 13134637 MILLWORK DETAILS
DOCUMENT 00 01 15 Page 7
I-506 13134638 MILLWORK DETAILS
I-600 13134639 FURNITURE, FIXTURE, & EQUIPMENT SCHEDULES
I-601 13134640 INTERIOR MATERIAL KEY
I-602 13134641 INTERIOR FINISH SCHEDULE
I-603 13134642 INTERIOR SIGNAGE SCHEDULE
I-900 13134643 FURNITURE TYPICALS
FIRE PROTECTION
FX001 13134644 FIRE SUPPRESION GENERAL NOTES
FX101 13134645 FIRE SUPPRESSION PLAN - FIRST FLOOR
FX102 13134646 FIRE SUPPRESSION PLAN - SECOND FLOOR
FX500 13134647 FIRE SUPPRESSION DETAILS
FIRE ALARM
FA001 13134648 FIRE ALARM & MASS NOTIFICATION GENERAL NOTES
FA101 13134649 FIRE ALARM & MASS NOTIFICATION PLAN - FIRST
FLOOR
FA102 13134650 FIRE ALARM & MASS NOTIFICATION PLAN - SECOND
FLOOR
FA500 13134651 FIRE ALARM & MASS NOTIFICATION DETAILS
FA501 13134652 FIRE ALARM & MASS NOTIFICATION MATRIX OF
OPERATIONS
PLUMBING
P-001 13134653 PLUMBING LEGEND AND GENERAL NOTES
P-101 13134654 PLUMBING SANITARY & VENT FLOOR PLAN - FIRST
FLOOR
P-102 13134655 PLUMBING SANITARY & VENT FLOOR PLAN - SECOND
FLOOR
P-103 13134656 PLUMBING ROOF PLAN
P-104 13134657 PLUMBING DOMESTIC WATER FLOOR PLAN - FIRST
FLOOR
P-105 13134658 PLUMBING DOMESTIC WATER FLOOR PLAN - SECOND
FLOOR
P-301 13134659 PLUMBING MECHANICAL ROOM SECTIONS
P-401 13134660 PLUMBING SANITARY & VENT ENLARGED PLANS -
FIRST FLOOR
P-402 13134661 PLUMBING DOMESTIC WATER ENLARGED PLANS -
FIRST FLOOR
DOCUMENT 00 01 15 Page 8
P-403 13134662 PLUMBING ENLARGED PLANS - SECOND FLOOR
P-501 13134663 PLUMBING DETAILS
P-502 13134664 PLUMBING DETAILS
P-601 13134665 PLUMBING SCHEDULES
P-602 13134666 PLUMBING SCHEDULES
P-901 13134667 PLUMBING RISER DIAGRAMS - SANITARY & VENT
P-902 13134668 PLUMBING RISER DIAGRAMS - ENLARGED SANITARY
& VENT
P-903 13134669 PLUMBING RISER DIAGRAMS - DOMESTIC WATER
P-904 13134670 PLUMBING RISER DIAGRAMS - ENLARGED DOMESTIC
WATER
P-905 13134671 PLUMBING RISER DIAGRAMS - STORM
P-906 13134672 PLUMBING RISER DIAGRAMS - NATURAL GAS AND
COMPRESSED AIR
MECHANICAL
M-001 13134673 MECHANICAL LEGEND
MD100 13134674 FIRST FLOOR PLAN DEMO
MH101 13134675 FIRST FLOOR PLAN - HVAC
MH102 13134676 SECOND FLOOR PLAN - HVAC
MH103 13134677 ROOF PLAN - HVAC
MP101 13134678 FIRST FLOOR PLAN - MECHANICAL PIPING
MP102 13134679 SECOND FLOOR PLAN - MECHANICAL PIPING
M-301 13134680 MECHANICAL BUILDING SECTION
M-302 13134681 MECHANICAL BUILDING SECTION
M-401 13134682 ENLARGED MECHANICAL ROOM PLAN
M-501 13134683 MECHANICAL DETAILS
M-502 13134684 MECHANICAL DETAILS
M-503 13134685 MECHANICAL DETAILS
M-601 13134686 MECHANICAL SCHEDULES
M-602 13134687 MECHANICAL SCHEDULES
DOCUMENT 00 01 15 Page 9
M-603 13134688 MECHANICAL SCHEDULES
M-701 13134689 CONTROL DIAGRAMS AND SEQUENCES
M-702 13134690 CONTROL DIAGRAMS AND SEQUENCES
M-703 13134691 CONTROL DIAGRAMS AND SEQUENCES
M-704 13134692 CONTROL DIAGRAMS AND SEQUENCES
M-705 13134693 CONTROL DIAGRAMS AND SEQUENCES
M-706 13134694 CONTROL DIAGRAMS AND SEQUENCES
M-707 13134695 CONTROL DIAGRAMS AND SEQUENCES
M-708 13134696 CONTROL DIAGRAMS AND SEQUENCES
M-709 13134697 CONTROL DIAGRAMS AND SEQUENCES
M-710 13134698 CONTROL DIAGRAMS AND SEQUENCES
M-711 13134699 CONTROL DIAGRAMS AND SEQUENCES
M-712 13134700 BAS NETWORK ARCHITECTURE
M-713 13134701 I/O POINTS
M-714 13134702 I/O POINTS
M-715 13134703 I/O POINTS
M-716 13134704 I/O POINTS
M-717 13134705 I/O POINTS
M-718 13134706 I/O POINTS
M-719 13134707 I/O POINTS
M-720 13134708 I/O POINTS
M-721 13134709 I/O POINTS
M-722 13134710 I/O POINTS
M-723 13134711 THERMOSTAT AND OCCUPANCY SENSOR SCHEDULE
M-724 13134712 UMCS SCHEDULE
M-801 13134713 HEATING HOT WATER FLOW DIAGRAM
M-802 13134714 CHILLED WATER FLOW DIAGRAM
DOCUMENT 00 01 15 Page 10
ELECTRICAL
E-001 13134715 LEGEND AND ABBREVIATIONS
ES100 13134716 ELECTRICAL SITE PLAN
E-101 13134717 FIRST FLOOR PLAN - LIGHTING
E-102 13134718 SECOND FLOOR PLAN - LIGHTING
E-111 13134719 FIRST FLOOR POWER PLAN
E-112 13134720 SECOND FLOOR POWER PLAN
E-113 13134721 ROOF PLAN - POWER
E-401 13134722 1ST FLOOR ENLARGED PLANS
E-402 13134723 2ND FLOOR ENLARGED PLANS
E-501 13134724 LIGHTING SCHEDULES & DETAILS
E-502 13134725 ELECTRICAL DETAILS
E-503 13134726 ELECTRICAL DETAILS
E-600 13134727 ONE-LINE AND RISER DIAGRAM
E-601 13134728 PANEL SCHEDULES
E-602 13134729 PANEL SCHEDULES
E-603 13134730 PANEL SCHEDULES
E-604 13134731 PANEL SCHEDULES
EG100 13134732 LIGHTNING PROTECTION PLAN
TELECOMMUNICATIONS
T-001 13134733 TELECOMMUNICATIONS SYMBOLS, ABBRIVIATIONS
AND GENERAL NOTES
T-100 13134734 TELECOMMUNICATIONS OVERALL SITE PLAN
T-101 13134735 TELECOMMUNICATIONS FIRST FLOOR PLAN
T-102 13134736 TELECOMMUNICATIONS SECOND FLOOR PLAN
T-111 13134737 TELECOMMUNICATIONS EXISTING FIRST FLOOR
T-112 13134738 TELECOMMUNICATIONS EXISTING SECOND FLOOR
T-201 13134739 RACK ELEVATION
DOCUMENT 00 01 15 Page 11
T-202 13134740 RACK ELEVATION
T-203 13134741 RACK ELEVATION
T-204 13134742 RACK ELEVATION
T-205 13134743 RACK ELEVATION
T-401 13134744 ENLARGED PLANS
T-501 13134745 WALL OUTLET DETAILS
T-502 13134746 FLOOR BOX DETAILS
T-503 13134747 PATHWAY DETAILS
T-504 13134748 EQUIPMENT RACK DETAILS
T-505 13134749 BONDING AND GROUNDING DETAILS
T-506 13134750 PBB BONDING DETAILS
T-507 13134751 SITE DUCT BANK AND MAINTENANCE HOLE DETAILS
T-508 13134752 SITE MAINTENANCE HOLE DETAILS
T-601 13134753 PUBLIC ADDRESS SYSTEM ONE-LINE DIAGRAM
T-602 13134754 INTRA-BUILDING BACKBONE ONE-LINE DIAGRAM
T-603 13134755 RACK TO OUTLET ONE-LINE
SECURITY
TY001 13134756 SECURITY LEGEND AND ABBREVIATIONS
TY100 13134757 SITE PLAN - SECURITY
TY101 13134758 JADOC I - SECOND FLOOR - SECURITY DEMOLITION
PLAN
TY111 13134759 FIRST FLOOR PLAN - PHYSICAL SECURITY
TY112 13134760 SECOND FLOOR PLAN - PHYSICAL SECURITY
TY121 13134761 FIRST FLOOR PLAN - ELECTRONIC SECURITY
TY122 13134762 SECOND FLOOR PLAN - ELECTRONIC SECURITY
TY123 13134763 ROOF PLAN - ELECTRONIC SECURITY
TY501 13134764 SECURITY DETAILS
TY502 13134765 SECURITY DETAILS
DOCUMENT 00 01 15 Page 12
TY503 13134766 SECURITY DETAILS
TY504 13134767 ESS DIAGRAMS
TY505 13134768 PHYSICAL SECURITY DETAILS
TY506 13134769 PHYSICAL SECURITY DETAILS
TY507 13134770 PHYSICAL SECURITY DETAILS
TY508 13134771 SECURITY CAMERA FIELDS OF VIEW
-- End of Document --
DOCUMENT 00 01 15 Page 13
THIS PAGE INTENTIONALLY LEFT BLANK
DOCUMENT 00 01 15 Page 14
SECTION 10 14 00.20
INTERIOR SIGNAGE
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 COMM (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
ICC/ANSI A117.1 (2009) Accessible and Usable Buildings and Facilities
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2021) Life Safety Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Detail Drawings; G
SD-03 Product Data
Room Identification And Directional Signage System; G
Stair Signage; G
Exit Door Tactile Sign; G
SECTION 10 14 00.20 Page 1
Door Tags; G
SD-04 Samples
Interior Signage; G
Software; G
Stair Signage; G
Exit Door Tactile Sign; G Door Tags; G
SD-10 Operation and Maintenance Data
Approved Manufacturer's Instructions; G
Protection and Cleaning; G
1.3 EXTRA MATERIALS
Provide 10 extra frames and extra stock of the following: blank plates of each color and size for all sign types included in project. Ten changeable message strips. Provide 50 paper inserts and laser print templates to support end-user printing copy onecopy of the software for user produced signs and inserts after project completion and equipment necessary for removal of signage parts and pieces.
1.4 QUALITY ASSURANCE
1.4.1 Samples
Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: sign types included in project Metal Plaques. Approved samples may be installed in the work, provided each sample is identified and location recorded.
1.4.2 Detail Drawings
Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.
1.4.3 Sign Fabricator
Sign Fabricator to follow room number strategies created by designer. The room numbering system to be reviewed and approved by the Contracting Officer and command end users during the shop drawing phase, and prior to fabrication.
1.5 DELIVERY, STORAGE, AND HANDLING
Package materials to prevent damage and deterioration during shipment, handling, storage and installation. Deliver products to the jobsite in manufacturer's original packaging and store in a clean, dry area in accordance with manufacturer's instructions.
SECTION 10 14 00.20 Page 2
1.6 WARRANTY
Provide manufacturer's warranty to repair or replace defective interior signage materials and workmanship for a period of 2 years from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 ROOM IDENTIFICATION AND DIRECTIONAL SIGNAGE SYSTEM
Provide signs, plaques, directories, and dimensional building letters that are standard products of manufacturers regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letter forms and graphics true and clean.
2.1.1 Panel Sign Systems
Provide direct print acrylic with applied tactile graphics, sign is fabricated of 0.375 inch acrylic in two layers with smooth edge conforming to ANSI Z97.1 . Provide signs that can accept raised copy and Braille with printable message inserts . Provide paper or acetate inserts with a
0.080 inch thick non glare acrylic window to allow sign to be updated.
2.1.2 Standard Room Signs
Provide signs that include tactile letters, symbols and Braille for interior rooms or spaces where the sign is not likely to change over time. Tactile text descriptions are required for pictograms that are provided to identify a permanent room. Examples include interior signs that label restrooms, stairs, room numbers or letters, and room names.
These permanent room signs can include paper inserts for updatable information.
2.1.2.1 Tactile Letters, Symbols and Braille
Provide ADA compliant material per 36 CFR 1191 which is raised 1/32 inch from the first surface, has a minimum 5/8 inch in height and is an ADA acceptable font. The color of the tactile letters is required to contrast with the sign face color per ADA standards. The ADA required Braille has a minimum durometer reading of 90. All raised letters, numbers and symbols are to comply.
2.1.3 Directional Signs
Directional signs provide arrows with messages which point to critical destinations such as departments, offices, or other pertinent destinations. These can be a panel sign system with a series of permanently attached messages or a modular system with updatable inserts.
Directional signs have header panels with applied or direct print messages.
2.1.4 Message Inserts
Provide updatable message inserts covered with a clear matte 0.015 inch vinyl protective overlay. The insert is typeset message laser printed on paper card stock . Provide paper and software with message template for creating text and symbols for computers identified for Government production of paper inserts after project completion. Manufacturer is
SECTION 10 14 00.20 Page 3 required to offer online ordering capabilities to facilitate and expedite ordering packages of replacement, color-coated paper inserts. Provide sliding inserts that slide horizontally exposing different graphic information as identified on the drawings.
2.1.5 Type of Mounting for Signs
Provide surface mounted signs mounted with concealed mechanical fastening through the holders countersunk mounting holes in plaques and mounting screws. Secure inserts in holders with flexible plastic clips . Mount framed plaques with manufacturer's standard (1/6 inch) 1.59 mm thick closed cell vinyl foam with adhesive backing. Adhesive must be transparent, long aging, high tech formulation on two sides of the vinyl foam. Double-faced tape consisting of acrylic adhesive on polyurethane foam used in conjunction with silicone adhesive .
2.1.6 Character Proportions and Heights
Letters and numbers on signs conform to 36 CFR 1191 .
2.2 STAIR SIGNAGE
Provide signs on stairs serving three or more stories with special signage within the enclosure at each floor landing conforming to NFPA 101 .
Indicate the floor level, the terminus of the top and bottom of the stair enclosure, and the identification of the stair enclosure. Also, state the floor level of, and the direction to, exit discharge. Locate the signage inside the enclosure in a position that is visible when the door is in the open or closed position and install in conformance with 36 CFR 1191 .
Provide tactile for floor level designation in accordance with
ICC A117.1 COMM .
2.3 EXIT DOOR TACTILE SIGN
Provide tactile sign with the message EXIT at each exit door that requires an exit sign to conform with NFPA 101 . Sign tactile message is to comply with ICC/ANSI A117.1 .
2.4 DOOR TAGS
Provide one door tag plate for each room entry door. In size as indicated on drawings. Provide room number to match architectural floor plan room number.
2.5 METAL PLAQUES
2.5.1 Cast Metal Plaques
2.5.1.1 Fabrication
Provide cast metal plaques with the logo, emblem and artwork cast in the bas relief technique; fabricated from bronze.
2.5.1.2 Border
Border is flat band straight edge.
SECTION 10 14 00.20 Page 4
2.5.1.3 Finish
Letter Finish satin
Background Finish dark bronze
Background Texture leather
2.5.2 Chemically Etched Metal Plaques
2.5.2.1 Fabrication
Plaque is chemically etched one-piece or photochemically engraved metal sheet or plate stainless steel 0.125 inch thick.
a. Facility Recognition Plaque
Provide and install a Faciltiiy Reocnition Plaque at a location as directed by the Contracting Officer with the following informtion.
(1). Facility Name
(2). Identify any recognition applied to the facility or person for which the facility has been dedicated
(3). Date of occupancy (month/year)
(4). Third Party Certification achieved (if applicable)
(5). Using Activity Commander/ Commanding Officer
(6). Base Commander/ Commanding Officer
(7). NAVFAC Component Commander/ Facility Engineering Component Commanding Officer
(8). Prime Contractor
(9). Architect/ Engineer (The main facility designer)
2.5.2.2 Finish
Single-etched raised areas are silver-tone finish and recessed areas are color filled (black).
2.6 GRAPHICS
Provide signage graphics for modular signs to the following:
2.6.1 Graphic Blast Raised Copy
Background is sandblasted to a uniform depth of 1/32 inch leaving raised text and Braille. Background is factory-finished with polyurethane paint.
SECTION 10 14 00.20 Page 5
2.7 COLOR, FINISH, AND CONTRAST
Provide color as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers. Finish of eggshell, matte, or other non-glare finish for all signs as required in handicapped-accessible buildings.
PART 3 EXECUTION
3.1 PLACEMENT SCHEDULE
Refer to signage schedule in drawings.
3.2 INSTALLATION
Install signs plumb and true and in accordance with approved manufacturer's instructions at locations shown on the detail drawings.
Submit operating instructions outlining the step-by-step procedures required for system operation. The instructions include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Provide each set permanently bound with a hard cover. The following identification must be inscribed on the covers: "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Submit in accordance with Section 01 78 23 OPERATING AND MAINTENANCE DATA. Mounting height and mounting location complies with 36 CFR 1191 . Install required blocking. Do not install signs on doors or other surfaces until finishes on such surfaces have been installed. Signs installed on glass surfaces are installed with matching blank back-up plates in accordance with manufacturer's instructions.
Do not install items that show visual evidence of biological growth.
3.2.1 Anchorage
Provide anchorage in accordance with approved manufacturer's instructions. Anchorage not otherwise specified or shown includes slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Provide exposed anchor and fastener materials compatible with metal to which applied with matching color and finish.
a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.
b. Install signs mounted on metal surfaces with magnetic tape.
c. Install signs mounted on fabric surfaces with hook and loop tape or pin mount.
d. Install signs to workstation panels with panel clips.
3.2.2 Protection and Cleaning
Protect the work against damage during construction. Adjust hardware and electrical equipment for proper operation. Clean glass, frames, and other sign surfaces at completion of signage installation in accordance with the
SECTION 10 14 00.20 Page 6 manufacturer's written instructions.
-- End of Section --
SECTION 10 14 00.20 Page 7
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 10 14 00.20 Page 8
SECTION 10 21 13
TOILET COMPARTMENTS
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A385/A385M (2020) Standard Practice for Providing High-Quality Zinc Coatings (Hot-Dip)
ASTM A666 (2015) Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM D7611/D7611M (2013; E 2014) Standard Practice for Coding Plastic Manufactured Articles for Resin Identification
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 COMM (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-60003 (Basic) Partitions, Toilet, Complete
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
SECTION 10 21 13 Page 1
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings
Installation Drawings; G
SD-03 Product Data
Cleaning and Maintenance Instructions
Stainless Steel
Sound-Deadening Cores
Anchoring Devices and Fasteners
Hardware and Fittings
Brackets
Door Hardware
Toilet Enclosures
Urinal Screens
Finishes; G
Recycled content for stainless steel partitions and screens; S
SD-04 Samples
Colors and Finishes; G
Hardware and Fittings
Anchoring Devices and Fasteners
SD-07 Certificates
Warranty
SD-10 Operation and Maintenance Data
Plastic Identification; G 1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Stainless Steel Partitions
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or
SECTION 10 21 13 Page 2 provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body.
1.4 REGULATORY REQUIREMENTS
Comply with to ICC A117.1 COMM code for access for the handicapped operation of toilet compartment door and hardware.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials in the manufacturer's original unopened packages with the brand, item identification, and project reference clearly marked.
Store components in a dry location that is adequately ventilated; free from dust, water, other contaminants, and damage during delivery, storage, and construction.
1.6 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for a period of one year from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 SYSTEM REQUIREMENTS
Provide a complete and usable toilet partition system, including toilet enclosures, room entrance screens, urinal screens, system of panels, hardware, and support components. Furnish the partition system from a single manufacturer, with a standard product as shown in the most recent catalog data. Submit Fabrication Drawings for toilet partitions and urinal screens consisting of fabrication and assembly details to be performed in the factory. Submit manufacturer's Cleaning and Maintenance Instructions in accordance with Section 01 78 23 OPERATIONS AND
MAINTENANCE DATA.
2.1.1 Plastic Identification
Verify that plastic products to be incorporated into the project are labeled in accordance with ASTM D7611/D7611M . Where products are not labeled, provide product data indicating polymeric information in the Operation and Maintenance Manual.
Type 1 Polyethylene Terephthalate (PET, PETE)
Type 2 High Density Polyethylene (HDPE)
Type 3 Vinyl (Polyvinyl Chloride or PVC)
Type 4 Low Density Polyethylene (LDPE)
Type 5 Polypropylene (PP)
Type 6 Polystyrene (PS)
SECTION 10 21 13 Page 3
Type 1 Polyethylene Terephthalate (PET, PETE)
Type 7 Other. Use of this code indicates that the package in question is made with a resin other than the six listed above, or is made of more than one resin listed above, and used in a multi-layer combination.
2.2 MATERIALS
2.2.1 Stainless Steel Sheet (Finish 4)
Provide stainless steel sheet conforming to ASTM A666, 300 series commercial stainless steel sheet suitable for exposed applications with a Flame Spread Index of 0 and a Smoke Developed Index of 0. Provide smooth material, without creases or ripples. Provide face sheet of minimum of
0.048 inch ((18 gauge) thickness. Provide with No. 4 finish.
2.2.2 Sound-Deadening Cores
Provide sound deadening consisting of treated kraft paper honeycomb cores with a cell size of not more than 1 inch. Provide resin-material content weighing not less than 11 percent of the finished core weight. Face expanded cores on both sides with kraft paper.
2.2.3 Anchoring Devices and Fasteners
Provide steel anchoring devices and fasteners hot-dipped galvanized after fabrication, in conformance with ASTM A385/A385M and ASTM A123/A123M .
Conceal all galvanized anchoring devices.
2.2.4 Brackets
Provide two-ear panel wall brackets, T-style, 1 inch stock. Provide stirrup style panel-to-pilaster brackets.
2.2.5 Hardware and Fittings
2.2.5.1 General Requirements
Provide hardware for the toilet partition system that complies with CID A-A-60003 for the specified type and style of partitions. Provide hardware finish highly resistant to alkalis, urine, and other common toilet room acids. Comply with 36 CFR 1191 of latching devices and hinges for handicap compartments; provide stainless steel devices and hinges with door latches that operate without either tight grasping or twisting of the wrist of the operator. Submit three samples of each item, including anchoring devices and fasteners. Approved hardware samples may be installed in the work if properly identified.
Material Conformance Standard
Stainless sheet steel ASTM A666
Stainless steel castings ASTM A743/A743M
SECTION 10 21 13 Page 4
2.2.5.2 Finishes
a. Provide stainless steel with a No. 4 finish.
b. Provide exposed fasteners that match the hardware and fittings.
2.2.6 Door Hardware
2.2.6.1 Hinges
Provide adjustable hinges to hold in-swinging doors open at any angle up to 90 degrees and outswinging doors up to 10 degrees. Provide self-lubricating hinges with the indicated swing. Provide hinges that and have the following type of return movement:
a. Gravity return movement
2.2.6.2 Latch and Pull
Provide latch and pull that is a combination rubber-faced door strike and keeper equipped with emergency access. Compliant with all federal ADA guidelines at accessible compartments.
2.2.6.3 Coat Hooks
Provide coat hooks that are combination units with hooks and rubber tipped pins.
2.3 PARTITION PANELS AND DOORS
Fabricate partition panels, and pilasters of materials and construction listed:
Provide stainless steel partition panels and doors in finished thickness of no less than 1 inch and pilasters no less than 1-1/4 inches, both with face sheets no less than 0.038 inch. .
Provide stainless steel toilet partitions and screens with recycled content of 50 percent minimum. Provide data identifying percentage of recycled content for stainless steel partitions and screens
2.3.1 Toilet Enclosures
Provide toilet enclosures that comply with CID A-A-60003 , Type I, Style B, ceiling hung . Furnish width, length, and height of toilet enclosures as shown. Finish surface of panels are stainless steel (Finish 4); water resistant; graffiti resistant; non-absorbent radius beveled edges.
Reinforce panels indicated to receive toilet paper holders or grab bars for mounting of the items required, and provide cut outs for through partition toilet accessories. Provide grab bars to withstand a bending stress, shear stress, shear force, and a tensile force induced by 250 lbf.
Grab bars cannot rotate within their fittings.
2.3.2 Urinal Screens
Provide urinal screens that comply with CID A-A-60003 , Type III, Style F, wall hung. Provide finish for surface of screens as stainless steel (Finish 4); water resistant; graffiti resistant; non-absorbent with radius beveled edges; with manufacturer's standard post design of materials
SECTION 10 21 13 Page 5 matching the thickness and construction of pilasters. Furnish width and height of urinal screens as shown. Provide thickness to match toilet compartment panel construction. Secure wall hung urinal screens with 42 inches long, continuous flanges. Fabricate screens from the same types of panels and pilasters as the toilet partitions. Use corrosion-resistant steel fittings and fasteners.
2.4 CEILING-HUNG PARTITIONS
Provide pilasters in size indicated that are manufacturer's standard corrosion resistant anchoring assemblies complete with leveling adjustment nuts at pilasters for connection to structural support above finished ceiling. Design anchoring device to transmit the strain and loading on the pilaster directly to the structural support above without putting strain or loading on the finished ceiling. Provide sleeves or caps at tops of pilasters to conceal anchorage.
2.5 HARDWARE
Provide hardware for the toilet partition system that complies with CID A-A-60003 for the specified type and style of partitions. Provide hardware pre-drilled by manufacturer. Use a hardware finish that is highly resistant to alkalis, urine, and other common toilet room acids.
Hardware includes: stainless steel hinges, as specified, adjustable for door close positioning; nylon bearings; stainless steel door latch;
stainless steel door strike and keeper with rubber bumper; and stainless steel coat hook and bumper. Provide latching devices and hinges for handicap compartments complying with 36 CFR 1191 and stainless steel door latches that operate without either tight grasping or twisting of the wrist of the operator. Use stainless steel, tamper proof type screws and bolts. Wall mounting brackets are continuous, full height, stainless steel, in accordance with toilet compartment manufacturer's instructions.
2.6 COLORS AND FINISHES
2.6.1 Colors
Provide color as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers.
Submit three samples showing color and a finished edge on two adjacent sides and core construction, each not less than 12 inch square.
2.6.2 Finishes
2.6.2.1 Finishes No. 1 Through No. 3
Provide partitions, panels, screen, and door finishes that comply with CID A-A-60003 finished with Stainless Steel (Finish 2).
PART 3 EXECUTION
3.1 PREPARATION
Take field measurements prior to the preparation of drawing and fabrication to ensure proper fits. Verify that field measurements, surfaces, substrates and conditions are as required, and ready to receive work. Verify correct spacing of plumbing fixtures. Verify correct location of built in framing, anchorage, and bracing. Report in writing
SECTION 10 21 13 Page 6 to Contracting Officer prevailing conditions that adversely affect satisfactory execution of the work of this section. Do not proceed with work until unsatisfactory conditions have been corrected.
3.2 METAL PARTITION FABRICATION
a. Fabricate metal partition panels, doors, screens, and pilasters required for the project from galvanized-steel face sheets with formed edges. Laminate face sheets via pressure to the sound-deadening core with edges sealed with a continuous locking strip and corners mitered and welded. Ground all welds smooth. Provide concealed reinforcement for installation of hardware, fittings, and accessories. Surface of face sheets must be , free from wave, warp, or buckle.
b. Before application of an enamel coating system, solvent-clean galvanized-steel surfaces to remove processing compounds, oils, and other contaminants harmful to coating-system adhesion. After cleaning,coat the surfaces with a metal-pretreatment phosphate coating. After pretreatment, finish exposed galvanized-steel surfaces with a baked-enamel coating system as specified.
c. Provide an enamel coating system consisting of a factory-applied baked acrylic enamel coating system. Provide a coating system that is a durable, washable, stain-resistant, and mar-resistant finish.
3.3 INSTALLATION
Do not install items that show visual evidence of biological growth.
Install partitions rigid, straight, plumb, and level, with the panels centered between the fixtures. Provide a panel clearance of not more than 1/2 inch and secure the panels to walls and pilasters with continuous full height wall brackets. Locate wall brackets so that holes for wall bolts occur in masonry or tile joints. Secure panels to pilasters with brackets matching the wall brackets. Provide for adjustment due to minor floor variations. Locate head rail joints at pilaster center lines. Install adjacent components for consistency of line and plane. Equip each door with hinges, one door latch, and one coat hook and bumper. Align hardware to uniform clearance at vertical edges of doors.
a. Secure panels to hollow plastered walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Provide toggle bolts with a load-carrying strength of not less than 600 pounds per anchor.
b. Secure panels to ceramic tile on hollow plastered walls or hollow concrete-masonry walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Provide toggle bolts with a load-carrying strength of not less than 600 pounds per anchor.
c. Secure panels to solid masonry or concrete with lead or brass expansion shields designed for use with not less than 1/4-20 screws, with a shield length of not less than 1-1/2 inches. Provide expansion shields with a load-carrying strength of not less than 600 pounds per anchor.
d. Submit Installation Drawings for toilet partitions, room entrance screens, and urinal screens showing plans, elevations, details of construction, hardware, reinforcing and blocking, fittings, mountings
SECTION 10 21 13 Page 7 and escutcheons. Indicate on drawings the type of partition, location, mounting height, cutouts, and reinforcement required for toilet-room accessories.
3.4 CEILING-HUNG PARTITIONS
Secure pilasters to the structural support above with the anchorage device specified. Make all leveling devices readily accessible for leveling, plumbing, and tightening the installation. Level the bottoms of doors with bottoms of pilasters when doors are in a closed position.
3.5 FINAL ADJUSTMENT
After completion of the installation, make final adjustments to the pilaster-leveling devices, door hardware, and other working parts of the partition assembly. Doors have a uniform vertical edge clearance of approximately 3/16 inch and rest open at approximately 30 degrees when unlatched.
3.6 CLEANING
Touch up baked enamel and powder coat finish with the same color of paint that was used for the finish. Clean all surfaces and adjacent surfaces soiled as a result of the work, in an approved manner compliant with the manufacturer's recommended cleaning and protection from damage procedures until accepted. Remove all equipment, tools, surplus materials, and work debris from the site.
-- End of Section --
SECTION 10 21 13 Page 8
SECTION 10 22 39
FOLDING PANEL PARTITIONS
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM C423 (2009a) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E90 (2009; R2016) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
ASTM E336 (2020) Standard Test Method for Measurement of Airborne Sound Attenuation between Rooms in Buildings
ASTM E413 (2016) Classification for Rating Sound Insulation
ASTM E557 (2012; R 2020) Standard Guide for Architectural Design and Installation Practices for Sound Isolation between Spaces Separated by Operable Partitions
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of…
This is the start of the file's text. The full file is on GovTribe.