Ty6-00.pdf

PDF 137 KB Posted

Attached to
Restack of the William J. Green Federal Building
Solicitation number
GS-03-P-16-AZ-C-7004
Issued by

About this file

Drawing Ty6-00

View the file

Other files

File Type Posted
Amendment_0007.pdf PDF
Ta4.26_-_02_Enlarged_Plans_-_Conference_Room_05.pdf PDF
Amendment_0006.pdf PDF
Flow_Test.pdf PDF
23_0900_INSTRUMENTATION_AND_CONTROL_FOR_HVAC._-_Add__2.pdf PDF
S4-02_-_ENLARGED_PARTIAL_PLANS.pdf PDF
Amendment_0005.pdf PDF
Specification_-_Table_of_Contents.pdf PDF
10_2240_Folding_Glass-Panel_Partitions.pdf PDF
MS-502.pdf PDF
09_5113_acoustical_panel_ceilings.pdf PDF
23_2113_HYDRONIC_PIPING_-_Add__2.pdf PDF
MP-405.pdf PDF
01_1030_TELECOMMUNICATIONS_SYSTEMS_OVERVIEW.pdf PDF
08_8713_Window_Film_Type_01.pdf PDF
01_ARCHITECTURAL_-_Addendum_02.pdf PDF
Addendum_No_02_-_Cover_Sheet.pdf PDF
09_3033_stone_tiling.pdf PDF
10_1423_Panel_Signage.pdf PDF
MD-124.pdf PDF
MP-103_2.pdf PDF
M-001.pdf PDF
09_6813_tile_carpeting.pdf PDF
S3-01_-_TYPICAL_DETAILS.pdf PDF
MP-104.pdf PDF
MS-501.pdf PDF
10_2226_Operable_Partitions.pdf PDF
MD-123.pdf PDF
08_8713_Window_Film_Type_02.pdf PDF
09_3000_ceramic_tile.pdf PDF
10_2241_Vertically_Folding_Panel_Doors.pdf PDF
MD103.pdf PDF
MD501.pdf PDF
Pre-Alteration_Asbestos_Assessment.pdf PDF
Specification_-_23_0529_HANGERS_AND_SUPPORTS_FOR_HVAC_PIPING_AND_EQUIPMENT-Addendum__1.pdf PDF
Specification_-_09_6513_RESILIENT_BASE_AND_ACCESSORIES.pdf PDF
Specification_-_01_1000_SUMMARY.pdf PDF
MH104.pdf PDF
Amendment_0004.pdf PDF
Construction_Sequencing_Diagrams.pdf PDF
Addendum_No_01_-_Cover_Sheet.pdf PDF
01_ARCHITECTURAL_-_Addendum_01.pdf PDF
MH103.pdf PDF
Specification_-_01_2400_OPTIONS.pdf PDF
Specification_-_Table_of_Contents.pdf PDF
Specification_-_09_5113_ACOUSTICAL_PANEL_CEILINGS.pdf PDF
MD104.pdf PDF
Amendment_0003.pdf PDF
Amendment_0002.pdf PDF
02_STRUCTURAL.pdf PDF
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WORK NOTES:

SERVER

SWITCH

RACK MOUNTED

STATION PATCH PANEL

FURNISHED AND INSTALLED

SECURITY SECURITY CONTRACTOR.

ASSOCIATED FIBER OPTIC PATH

PANEL, FIBER CONVERTER AND

CODE DISTRIBUTION UNIT, NOT

SHOWN, FURNISHED AND

INSTALLED BY OTHERS (TYPICAL)

SWITCH IN

TELECOM

ROOMS

RACK MOUNTED

FIBER OPTIC

PATCH PANEL

FIBER OPTIC

PATCH CORDS

PATCH

CORDS. SEE

NOTE 2

(TYPICAL)

RACK MOUNTED

FIBER OPTIC

PATCH PANEL

MCR SWITCH

FIBER OPTIC

PATCH CORDS

TYPICAL TELECOM ROOM

MOE NETWORK (DATA

CENTER/SERVER) ROOM

CAT-6A

PATCH

CORD (S)

REFER TO

NETWORK

DRAWINGS FOR

MORE

INFORMATION

AND

CONNECTIVITY

DETAILS

4" HORIZONTAL SLEEVE

FURNISHED AND INSTALLED

BY OTHERS (TYPICAL)

CABLING OUT

TO

DOORS/ALARM

POINTS. REFER

TO FLOORS

PLANS FOR

MORE INFO.Access Control Panel

ACCESS CONTROL

PANEL

1. DRAWING SHOW CONNECTION OF ACCESS CONTROL AND INTRUSION ALARM INTERFACE EQUIPMENT

INTO TECHNOLOGY INFRASTRUCTURE AND IP NETWORK.

2. ALL PATCH CORDS WITHIN THE TELECOM ROOM TO BE INSTALLED BY CABLING CONTRACTOR. FINAL

PATCH CORD CONNECTION TO EACH CONTROL PANEL TO BE INSTALLED BY THE SECURITY

CONTRACTOR.

3. FOR ALL CABLING FROM THE TELECOM ROOM OUT TO THE PERIPHERAL DEVICES SHALL BE PLENUM

RATED. A 10' SERVICE LOOP WILL BE NEATLY COILED AT THE CEILING AND SECURED WITHIN CLOSE

PROXIMITY OF THE 4" X 4" JUNCTION BOX. CAUTION WILL BE TAKEN TO INSURE THAT TY-WRAPS ARE

NOT OVER TIGHTENED AND THAT TY-WRAPS DO NOT CRIMP OR DEFORM THE CABLE JACKET

4. ALL CONTROL PANEL CONNECTIVITY (PHYSICAL AND LOGICAL) WILL BE COORDINATED BETWEEN

SUBSYSTEM PROVIDER AND NETWORK INTEGRATOR

5. COORDINATION OF CABLE ROUTING AND FINAL CONNECTION TO BE DONE BY CABLING

CONTRACTOR, SECURITY CONTRACTOR, AND THE CLARIENT GROUP.

SERVER

IP CAMERA

POE SWITCH

RACK MOUNTED

CAT 6A STATION PATCH PANEL

IP CAMERA FURNISHED

AND INSTALLED by

SECURITY CONTRACTOR

(TYPICAL)

SEE NOTE

NOTE 2 & 7

(TYPICAL)SEE NOTE 3 & 4

(TYPICAL)

FURNISHED AND INSTALLED

SECURITY SECURITY CONTRACTOR.

ASSOCIATED FIBER OPTIC PATH

PANEL, FIBER CONVERTER AND

CODE DISTRIBUTION UNIT, NOT

SHOWN, FURNISHED AND

INSTALLED BY OTHERS (TYPICAL)

POE SWITCH IN

TELECOM ROOMS

RACK MOUNTED

FIBER OPTIC

PATCH PANEL

FIBER OPTIC

PATCH CORDS

WORK NOTES:

1. DRAWING SHOW CONNECTION OF VIDEO SURVEILLANCE INTERFACE EQUIPMENT AND IP CAMERAS

INTO TECHNOLOGY INFRASTRUCTURE AND IP NETWORK.

2. ALL PATCH CORDS WITHIN IDF TO BE INSTALLED BY CABLING CONTRACTOR. FINAL PATCH CORD

CONNECTION TO EACH CAMERA TO BE INSTALLED BY THE SECURITY CONTRACTOR.

3. FOR ALL IN-CEILING MOUNTED CAMERAS THE TERMINATED STATION CABLE WILL SECURED WITH

PLENUM RATED TY-WRAPS. A 20' SERVICE LOOP WILL BE NEATLY COILED AND SECURED WITHIN

CLOSE PROXIMITY OF CABLE TERMINATION. CAUTION WILL BE TAKEN TO INSURE THAT TY-WRAPS

ARE NOT OVER TIGHTENED AND THAT TY-WRAPS DO NOT CRIMP OR DEFORM THE CABLE JACKET

4. FOR ALL PENDANT-MOUNTED CAMERAS CABLE WILL BE RUN THROUGH PENDANT CONDUIT WITH

JACK TERMINATED AND LEFT INSIDE CAMERA ASSEMBLY BACK-BOX

5. ALL DEVICE CONNECTIVITY (PHYSICAL AND LOGICAL) WILL BE COORDINATED BETWEEN SUBSYSTEM

PROVIDER AND NETWORK INTEGRATOR

6. ALL HORIZONTAL STATION CABLE WILL BE PLENUM RATED

7. COORDINATION OF CABLE ROUTING AND FINAL CONNECTION TO BE DONE BY CABLING

CONTRACTOR, SECURITY CONTRACTOR, AND THE CLARIENT GROUP.

CAT-6A PATCH

CORDS. SEE

NOTE 2 & 7

(TYPICAL)

RACK MOUNTED

FIBER OPTIC

PATCH PANEL

MOE SWITCH

FIBER OPTIC

PATCH CORDS

(1) CAT-6A

PATCH CORD

A. CAT 6 STATION CABLE DISTANCE

NOT TO EXCEED 290 FEET

EXCLUDING PATCH CORDS.

B. IF STATION CABLE EXCEEDS 290

FEET IP EXTENDERS (BALUMNS)

ARE TO BE USED.

TYPICAL TELECOM ROOM

MOE NETWORK (DATA

CENTER/SERVER) ROOM

CAT-6

PATCH

CORD (S)

REFER TO

NETWORK

DRAWINGS FOR

MORE

INFORMATION

AND

CONNECTIVITY

DETAILS

RACK MOUNTED

FIBER OPTIC

PATCH PANEL

4" HORIZONTAL SLEEVE

FURNISHED AND INSTALLED

BY OTHERS (TYPICAL)

N

PROPERTY OF THE UNITED

STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Do not remove this notice.

Properly destroy or return documents when no longer needed.

(SBU)

SENSITIVE BUT UNCLASSIFIED

OVERALL

© 2015 Erdy McHenry Architecture, LLC

DRAWN BY:

Erdy McHenry Architecture, LLC 915 North Orianna Street Philadelphia, Pennsylvania 19123 ph: 215.925.7000 fax: 215.925.1990 web: http://www.em-arc.com

Architect: SCOTT A. ERDY, AIA

DAVID S. MCHENRY, AIA

emArchitectureemArchitectureemArchitectureemArchitecture

SCALE:

PROJECT NO:

DATE:

SHEET NUMBER:

P lo tte d:

KEY PLAN

Ty6.00

Line Diagrams

1158.00Author

03.24.2016

600 Arch Street

Philadelphia, PA 19107

Green Federal BuildingGreen Federal BuildingGreen Federal BuildingGreen Federal Building ConsolidationConsolidationConsolidationConsolidation

Program + Strategy Consultant Studio Hillier 190 Witherspoon Street Princeton NJ 08542

Greenman - Petersen, Inc. (GPI) 50 Glenmaura National BLVD.

Suite 102 Scranton, PA 18505

Cerami & Associates 404 Fifth Avenue New York, NY 10018

TCT Cost Consultants, LLC 1090 Vermont Avenue NW Suite 230 Washington, DC 20005

Weidlinger Associates, INC 1825 K Street Avenue NW Suite 350 Washington, DC 20006

Antis Veterans Engineering and Technical Services 2074 Cobblestone Lane Suite 850 Reston, VA 20191

Structural Engineer

MEP Engineer

Acoustical Consultant

Cost Specialist

Security + Blast

Praxis Building Solutions, LLC 2401 Walnut Street Suite 102 Philadelphia, PA 19103

Green Building Consultant

Beam, Ltd 428 West Waverly Road Glenside, PA 19038

Lighting Consultant

GSA Project Data William J. Green Federal Building GSA Project #: VPA00027 GSA Building #: PA0277 GSA Contract #: GS-03P-14-AZ-C-0020 GSA Solicitation #: GS-03P-15-AZ-C-1020

The Clarient Group, LLC 630 9th Ave Suite 1012 New York, NY 10036

Telecom/Audiovisual/Security

Drawing Issue Date Core & Shell Package 05/06/2016

Sheets
Ty6.00 - Line Diagrams

File details come from the government source that posted it. Updated .