4 Kacey Court • Mechanicsburg, PA 17055-5596 • (717) 766-4500 • FAX (717) 766-3999 1337 Veterans Memorial Drive • Jessup, PA 18434 • (570) 291-0030 • FAX (570) 291-0035 www.cocciardi.com
May 31, 2016
Mr. Mark Miller, RA Associate Erdy-McHenry Architecture, LLC 915 North Orianna Street Philadelphia, PA 19123
RE: Pre-Alteration Asbestos Assessment, Review and Remediation Design Green Federal Building Consolidation Project Cocciardi Project No. 150057
Dear Mr. Miller:
Cocciardi and Associates, Inc. (Cocciardi) was contracted by Erdy-McHenry Architecture, LLC to provide inspection, document review and remediation design services relative to Asbestos Containing Materials (ACM) anticipated to be impacted during the Green Federal Building Consolidation Project in Philadelphia, Pennsylvania. Enclosed in this project binder are the following:
Section 1: A final report of the pre-alteration asbestos building inspection and corresponding document review.
Section 2: Project specifications for the remediation of identified
ACM.
Section 3: Drawing Markups to accompany project specifications.
CERTIFICATION:
The information contained in this report is believed to be accurate and true to the best knowledge of the inspector(s). Findings and recommendations for this investigation are based on the observations of the conditions, as they existed at that time. The inspector(s) and Cocciardi and Associates, Inc. assumes no liability for financial or health consequences due to actions or lack of actions taken by the client as a result of this inspection.
Michael Baltrusaitis, CHMM, CSP Senior Professional Cocciardi and Associates, Inc.
Cody Youshock Safety, Health & Environmental Technologist Cocciardi and Associates, Inc.
http://www.cocciardi.com/
Section 1
A final report of the pre-alteration asbestos building inspection and corresponding document review.
Provided To:
Erdy-McHenry Architecture, LLC Pre-Alteration Asbestos Assessment, Review and Remediation Design Green Federal Building Consolidation Project Cocciardi Project No. 150057
4 Kacey Court • Mechanicsburg, PA 17055-5596 • (717) 766-4500 • FAX (717) 766-3999 1337 Veterans Memorial Drive • Jessup, PA 18434 • (570) 291-0030 • FAX (570) 291-0035 www.cocciardi.com
May 31, 2016
Mr. Mark Miller, RA Associate Erdy-McHenry Architecture, LLC 915 North Orianna Street Philadelphia, PA 19123
RE: William J. Green Federal Building 600 Arch Street, Philadelphia, PA 19106 Pre-Alteration Asbestos Assessment and Documentation Review Cocciardi Project No. 150057
Dear Mr. Miller:
The following report is provided to document the Pre-Alteration Asbestos Assessment and Review conducted in designated areas of the William J. Green Federal Building located in Philadelphia, Pennsylvania.
BACKGROUND:
Cocciardi and Associates, Inc. (Cocciardi) was contracted by Erdy-McHenry Architecture, LLC.
(em Architecture) to perform a Pre-Alteration Asbestos Assessment and Documentation Review at the above-mentioned structure to facilitate planned renovations within various areas throughout the facility. The assessment was requested to meet requirements of the U.S.
General Service Administration (GSA) policy in addition to federal, state and local regulations, where applicable and as outlined below:
U.S. Environmental Protection Agency (EPA):
o National Emission Standards for Hazardous Air Pollutants (NESHAP), 40CFR61 o Asbestos Hazard and Emergency Response Act (AHERA), 40CFR763
U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) o Asbestos in Construction, 29CFR1926.1101 o Asbestos in General Industry, 29CFR1910.1001
City of Philadelphia, Department of Public Health o Asbestos Control Regulation
The scope of the project was limited to the surfaces, materials and components that are to be potentially impacted by the proposed project, as designated in provided scope of work documents and corresponding project drawings.
Mr. Mark Miller, RA May 31, 2016
Specifically, Cocciardi performed the following activities under the scope of this project:
Document review of existing ACM and environmental inspection reports. Documents provided to Cocciardi included:
1. “Asbestos-Containing Building Materials Survey Report for the William J. Green Jr. Federal Building, Philadelphia, Pennsylvania”; Tidewater, Inc.; September 2011.
2. “Limited Asbestos Survey Report for William J. Green Building 10th Floor”;
Langan Engineering and Environmental Services, Inc.; July 10, 2014.
Limited building inspection of accessible areas scheduled to be included in the renovation project. The inspection activities were completed by Pennsylvania Department of Labor and Industry (PA DOLI) Asbestos Building Inspectors and City of Philadelphia Department of Public Health Asbestos Investigators. Due to the current occupancy of the building, inspection methods were limited to non-destructive measures with invasiveness limited to access hatches, lifting of ceiling tiles and carpeting in accessible areas.
Copies of the above reports are found in Appendix A of this report.
Recommendations regarding handling of these materials are provided in this document and are based on applicable federal, state, and local regulations established by OSHA, EPA, the Pennsylvania Department of Environmental Protection (PA DEP), PA DOLI, and the City of Philadelphia Department of Public Health.
The William J. Green Federal Building was constructed in 1974, and is currently used by various governmental agencies for office space. The building is comprised of 10 levels with over 800,000 square feet of floor area. The building adjoins the James Byrne U.S. Courthouse and is located at 601 Market Street in Philadelphia, Pennsylvania. The above-referenced Building Consolidation Project will include demolition/renovation of building and architectural components in addition to impacting mechanical/HVAC and electrical systems in floors 1 through 9 of the building.
ACTIVITIES:
During the timeframe of December 2015 to April 2016, Cocciardi performed the above document review and onsite inspections. These activities were conducted by PA DOLI Asbestos Building Inspectors/City of Philadelphia Air Management Services Asbestos Investigators, Mr.
Cody Youshock (PA DOLI 050339/AMS AIC15-00028) and Mr. Lynn Stutzman (PA DOLI 030480/AMS AC-0640), with assistance by the following PA DOLI Asbestos Building Inspectors:
Dominick DeFazio, PA DOLI No. 040641 Michael Baltrusaitis, PA DOLI No. 032659 John Noullet, PA DOLI 053825
Applicable Licenses can be found in Appendix B of this report.
Cocciardi personnel performed a visual and tactile review of the designated areas utilizing select invasive measures as necessary. An assessment of the suspect ACM was conducted during the inspection, which included classification of material by EPA National Emission Standards for Hazardous Air Pollutants (NESHAP) category (Regulated Asbestos Containing Material [RACM], Category I and Category II exempt materials), friability, physical assessment, and quantity.
Friability Conditions:
Friable - “Friable” material in a building means that the material, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure, and includes previously non-friable material after such previously non-friable material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure.
Non-Friable - “Non-Friable” means material in a building which, when dry, may not be crumbled, pulverized, or reduced to powder by hand pressure.
EPA NESHAP Categories are defined as follows:
1. Category I Non-Friable ACM (CAT I): Asbestos containing packing, gaskets, floor covering, and asphalt roofing products containing more than one percent (1%) asbestos.
2. Category II Non-Friable ACM (CAT II): Any material, excluding Category I non-friable asbestos containing material, containing more than one percent (1%) asbestos. Material, that when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
3. Regulated Asbestos Containing Material (RACM): Friable asbestos material, Category I non-friable asbestos containing material that has become friable, Category I non-friable asbestos material that will be or has been subject to sanding, grinding, cutting, or abrading.
Category II non-friable asbestos containing material that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition.
EPA Physical Assessment Factors:
Good - Less than 10% area damage
Fair - More than 10%, but less than 25% area damage
Poor - More than 25% area damage
The following confirmed/presumed ACMs were identified outside of the renovation/alteration scope of work:
Mirror Glue/Mastic (10th Floor) Pipe Insulation and associated Mudded Fittings/Elbows
Rough Plaster (limited quantity in basement) Gray Sink Insulation Popcorn Ceiling (Linkway from Green and Byrne Building) Elevator Brake Shoes (presumed)
The following suspect components were determined to be non-ACM through laboratory analysis:
Wall Plaster (Skim/Base Coats) Gypsum Board/Drywall (and Joint Compound) Block Mortar Fiberglass Insulation Joint Sealant Brown Metal Duct Insulation Floor Leveling Compound Tape Glue on Duct Insulation Joint Tape on Duct Seams Soundproofing Square Blocks Duct Seam Caulking Various Ceiling Tiles Various 12” x 12” Floor Tiles not listed in Table I Various Cove Base Moldings (with Mastics) Gray Spray-on Fireproofing Tile Grout Tan Duct Putty
After onsite observations and upon review of existing asbestos survey documentation, a summary of confirmed ACM identified during the inspection that may be impacted by the proposed renovations, including results of sample collection and analysis, where applicable, is provided in Table I.
Table I Analytical Results: Asbestos Building Survey
William J. Green Federal Building Philadelphia, Pennsylvania
Homogeneous Material Description Location Quantity (1)
NESHAP
Category Friability Condition Result Classification
Assorted Floor Tile (12” x 12”) a.) Square Beige b.) Off-White w/ Gray Streaks c.) Beige w/ White and Brown Dots d.) Tan w/ White and Brown Streaks e.) Off-White w/ Green Streaks f.) Black w/ White and Gray Streaks g.) Light Gray Mottled h.) Dark Gray Mottled i.) Dark Blue w/ Beige Streaks
1st Floor 2,120 SF
CAT I Non- Friable Good
2.2% - 28.6%
CH
Confirmed
ACM
2nd Floor 320 SF 3rd Floor 260 SF 4th Floor 3,400 SF 5th Floor 280 SF 6th Floor 1,200 SF 7th Floor 1,500 SF 8th Floor 120 SF 9th Floor ---
Mastic *Majority located directly under carpet **Some located under floor tiles
1st Floor 2,120 SF
CAT I Non- Friable Good
1.8% - 5.0%
CH
Confirmed
ACM
2nd Floor 16,840 SF 3rd Floor 40,660 SF 4th Floor 37,100 SF 5th Floor 49,375 SF 6th Floor 57,890 SF 7th Floor 31,925 SF 8th Floor 56,790 SF 9th Floor 55,150 SF
Transite Paneling over Infloor Trench Ducts
1st Floor ---
CAT II Non- Friable Good NA PACM
2nd Floor 700 SF 3rd Floor 1,400 SF 4th Floor 740 SF 5th Floor 1,400 SF 6th Floor 1,400 SF 7th Floor 1,400 SF 8th Floor 1,400 SF 9th Floor 1,400 SF
Table I Notes:
SF: Square Feet LF: Linear Feet NA: Not Analyzed
PACM: Presumed Asbestos Containing Material CH: Chrysotile (Type of Asbestos)
CAT I: Category I Non-Friable Asbestos Containing Material CAT II: Category II Non-Friable Asbestos Containing Material Note 1: These quantities include areas that may be impacted by the proposed renovations outlined in Appendices A and B. Additional ACM may exist in other locations of the facility.
CONCLUSIONS:
Under the scope of the asbestos inspection activities for the William J. Green Federal Building, Cocciardi identified the following:
C-1: The asbestos pre-renovation inspection conducted in accordance with OSHA and EPA requirements identified the following confirmed/presumed ACM:
Material Location Quantity
Assorted 12” x 12” Floor Tiles Throughout Floors 1-9 9,200 SF
Floor Tile Mastic Throughout Floors 1-9 347,850 SF
Transite Panel (Infloor Duct Trench) Throughout Floors 1-9 9,840 SF
RECOMMENDATIONS:
R-1: Asbestos abatement activities are recommended prior to any repair, renovation, or demolition activities which would disturb the matrix of confirmed ACM (identified in C-1).
It is recommended that any asbestos activity be performed in accordance with applicable EPA, OSHA, PA DEP, and City of Philadelphia regulatory requirements. In order to comply with these requirements, the following is recommended:
1. Written EPA notification of demolition/renovation ten (10) working days prior to asbestos related activities, as required by the National Emission Standards for Hazardous Airborne Pollutants (NESHAP) of the Clean Air Act.
2. Development of a written Asbestos Abatement Project Design Specification, designating abatement work practices and control measures to reduce airborne fiber concentrations, waste disposal requirements, and air sample collection and analysis requirements including the final clearance (re-occupancy) criteria.
3. Selection of a licensed asbestos contractor for the performance of asbestos response activities.
4. Air sample collection and analysis subsequent to asbestos abatement activities in compliance with project design requirements for the re-occupancy by non-protected individuals.
R-2: In the event that the project is modified and will expand to other locations not included in this survey, or will impact suspect materials originally outside of the project scope, an additional survey may be necessary to confirm ACM quantities and additional testing of suspect materials may be required.
R-3: Notify contractors for this project of the location and extent of ACM within the building.
Provide a copy of this report to any contractor or employee performing renovation work within this area.
CERTIFICATION:
The information contained in this report is believed to be accurate and true to the best knowledge of the inspector(s). Findings and recommendations for this investigation are based on the observations of the conditions, as they existed at that time. The inspector(s) and Cocciardi and Associates, Inc. assumes no liability for financial or health consequences due to actions or lack of actions taken by the client as a result of this inspection.
Sincerely, Michael Baltrusaitis, CHMM, CSP Senior Professional Cocciardi and Associates, Inc.
Cody Youshock Safety, Health, and Environmental Technologist Cocciardi and Associates, Inc.
cc: file Attachments
Appendix A
Copies of the reports
Provided To:
Erdy-McHenry Architecture, LLC William J. Green Federal Building 600 Arch Street, Philadelphia, PA 19106 Pre-Alteration Asbestos Assessment and Documentation Review Cocciardi Project No. 150057
LIMITED ASBESTOS SURVEY REPORT
for
Prepared For:
Prepared By:
Vijay Patel Senior Associate
July 10, 2014 220073901
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
TABLE OF CONTENTS
Page No.
ACRONYMS............................................................................................................................... i
EXECUTIVE SUMMARY
1.0 INTRODUCTION
2.0 SITE DESCRIPTION
3.0 ASBESTOS CONTAINING MATERIALS
3.1 Terminology
3.2 Observations and Findings
4.0 CONCLUSIONS AND RECOMMENDATION
4.1 Asbestos Containing Materials .............................Error! Bookmark not defined.
5.0 ASSUMPTIONS, LIMITATIONS AND EXCEPTIONS
TABLES
Table 1 Summary of Asbestos Survey Findings Table 2 Bulk Asbestos Sample Analysis Results
DRAWINGS
L1 Limits of the 10th floor spaces surveyed ASL-1 Asbestos sampling locations 10th Floor
APPENDICES
Appendix A Laboratory Test Results and Chain of Custody Documentations Appendix B Appendix C September 2011 Asbestos Containing Building Materials Survey Report
Limited Asbestos Survey Report (10th Floor) July 2, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
ACRONYMS
USEPA United States Environmental Protection Agency
AHERA Asbestos Hazard Emergency Response Act
OSHA Occupational Safety and Health Administration
CFR Code of Federal Regulation
EPA United States Environmental Protection Agency
HEPA High Efficiency Particulate Air
NESHAPS National Standards for Hazardous Air Pollutants
PLM Polarized Light Microscopy
TEM Transmission Electron Microscopy
ACM Asbestos-Containing Materials
SF Square Feet
LF Linear Feet
M Meter
M2 Square meter
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
EXECUTIVE SUMMARY
Langan Engineering and Environmental Services, Inc. has prepared this Limited Asbestos
Containing Materials (Asbestos) Survey Report to identify the presence/absence of asbestos containing materials (ACM) in select spaces on the 10th floor of the William J. Green Federal
Building, located at 600 Arch Street, Philadelphia, PA. The limits of the areas surveyed are shown on Drawing L1. The limits of the asbestos survey were based on the 100% submission
Architectural Drawing A100, dated April 11, 2014.
PROJECT INFORMATION:
Region:
EPA Region 3 (Mid- Atlantic)
Client Name: US General Administration
Building Number: PA00277PA 220073901
Building Name:
William J. Green Federal Building Manager/Phone No.:
Vijay Patel / 201-398-4511
Construction Date: 1975 Email: vpatel@langan.com
Gross Square Footage:
1,752,000 gross square foot
Property Address: 31 Hopkins Plaza
Floor Number: Basement, 1 thru 10 Property Town, County, State:
Philadelphia, PA 19106
Property Use: Public Service Survey Dates: June 17, 18, 19, & 26, 2014
The following summ of ACM identified in the building spaces surveyed:
Material Assumed
ACM
ESTIMATED
QUANTITIES
Remnant of old mastic under carpet/leveling compound
ACM 28,700 SF 2,666 m2
Various floor tiles/mastic (underlying wall to wall carpet)
ACM 5,100 SF 474 m2
Various floor tiles/mastic (exposed) ACM 3,800 SF 353 m2
Wooden door insulation* (Approximately 100 Doors)
Assumed
ACM
2,100 SF 74 m2
Mastic daubs underlying wall mirrors* Assumed
ACM
800 SF 195 m2
Suspect materials within metal electrical conduits and panels (i.e. wires, insulation, Transite, etc.)*
Assumed
ACM
3,000 LF 914 m
* - Assumed ACM in lieu of live electricity, destructive survey and testing.
SF- square feet; LF- linear feet; m2 square meter; m- meter.
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
1.0 INTRODUCTION
Langan Engineering and Environmental Services, Inc. has prepared this Limited
Asbestos Containing Materials (Asbestos) Survey Report to identify the presence/absence of asbestos containing materials (ACM) within select spaces on the
10th floor of the William J. Green Federal Building, located at 600 Arch Street, Philadelphia, PA. The purpose of this survey was to prepare an inventory of ACM so they could be appropriately segregated, removed and disposed as part of the remediation process prior to renovations.
The following presents our observations, copy of reports reviewed, laboratory test results of samples collected, plans showing sampling locations, and an itemized inventory of ACM identified in the spaces surveyed.
2.0 SITE DESCRIPTION
The William J. Green Federal Building is located at 600 Arch Street, Philadelphia, PA
19106 and is utilized as public service building. The Property is currently owned by the
General Services Administration (GSA). The property is improved by an approximately
1,752,000 square feet ten (10) stories building with a basement. The subject building is steel framed high-rise structure with glass façade.
3.0 ASBESTOS CONTAINING MATERIALS
3.1 Terminology
Suspect Asbestos-Containing Materials
Asbestos was used in certain types of construction and building materials. Until a material is examined using light microscopy or a similar technique, the building material is considered as a suspect asbestos-containing material. A few examples of these materials include floor tiles, ceiling panels, thermal system insulation, fireproofing insulation, roofing materials, etc. Any suspect ACM of unknown asbestos content (that is not tested) should be handled as if it were an asbestos containing material.
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
Asbestos Containing Material
A material with an asbestos concentration greater than one percent by weight is considered to be asbestos-containing by the United States Environmental
Protection Agency (USEPA). Thus, a material which contains asbestos in materials that do not contain asbestos or asbestos is detected in concentrations less than one percent by weight.
Friable Asbestos Containing Material
A friable material is one that can be easily crumbled, pulverized, or reduced to powder by hand or mechanical pressure. This characteristic of a building material is directly linked to the potential of the material to release asbestos fibers into the air.
3.2 Observations and Findings
The field survey of the subject building was conducted on June 17, 18, 19, and
26, 2014 by Sanjay Patel, an USEPA and Pennsylvania Department of
Labor accredited asbestos inspector and City of Philadelphia certified asbestos investigator.
Prior to our site visit, we reviewed the September 2011 Asbestos Containing
Building Materials Survey Report prepared by Tidewater, Inc. The report identified collection and analysis of 126 bulk samples from the building. Of these
126 samples, only four samples were collected from the DEA space. The report documented presence of the following ACM in the building: Various floor tiles/mastic, pop-corn ceiling, and pipe insulation. The report did not provide sampling location plan and was not clear with respect to the locations of ACM and presumed ACM. A copy of this report is included in Appendix C.
Suspect materials observed during the survey were documented, assessed, quantified, and sampled as necessary. The following suspect materials and their
ACM were identified in the building spaces surveyed:
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
SUSPECT ACM RESULTS:
ACM OR NON-ACM
Remnants of old mastic under carpet/leveling compound
ACM
12" Square beige floor tiles and mastic
FT: ACM
MA:ACM
12" square spackled gray floor tiles and mastic FT: Non-ACM
MA: ACM
12" Square spackled off white floor tiles and mastic FT: Non -ACM
MA: ACM
12" Square mottled light gray floor tiles and mastic FT: Non -ACM
MA: ACM
12" Square mottled beige floor tiles and mastic FT: Non -ACM
MA: ACM
12" Square black floor tiles and mastic FT: Non -ACM
MA: ACM
12" Square grit design dark gray floor tiles and mastic FT: Non -ACM
MA: ACM
12" Square stripe dark brown floor tiles and mastic
FT: ACM
MA:ACM
Wall plaster (2 Layers) L1:Non-ACM L2: Non-ACM
Gypsum board Non-ACM
Gypsum board joint compound Non-ACM
Cinderblock mortar Non-ACM
Fiberglass pipe insulation end/joint sealant Non-ACM
Brown metal duct insulation Non-ACM
Floor leveling compound under wall-to-wall carpet Non-ACM panels Non-ACM
Tape glue on the metal duct fiberglass insulation Non-ACM
Glue associated with carpet above the floor tiles Non-ACM
Metal duct seam joint tape Non-ACM
Sink undercoating Non-ACM
Soundproofing square blocks Non-ACM
Black floor covering Non-ACM
Fiberglass insulation glue inside the induction unit Non-ACM
Metal duct seam caulking Non-ACM
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
SUSPECT ACM
RESULTS:
ACM OR NON-ACM
Raised floor support mastic Non-ACM
Glue associated with black rubber wall panels Non-ACM
12" Square multicolor floor tiles and mastic FT: Non-ACM MA: Non-ACM BB: Non-ACM GL: Non-ACM BB: Non-ACM GL: Non-ACM BB: Non-ACM GL: Non-ACM and associated glue BB: Non-ACM GL: Non-ACM BB: Non-ACM GL: Non-ACM BB: Non-ACM GL: Non-ACM
During the survey, Langan inspector collected seventy-four (74) samples of suspect materials. Samples were analyzed using polarized light microscopy
(PLM). Samples were analyzed by layers, resulting one hundred and one (101) samples. The details of asbestos survey findings are provided in Table 1 and the analytical test results are summarized in Table 2.
Due to building occupancy, live electricity and in lieu of destructive means of access, suspect materials associated with electrical components, wooden door insulation, and wall mirror mastic are assumed to be ACM.
A visual survey was also performed in limited spaces on the 9th floor above the suspended ceilings where plumbing connections are proposed. No suspect
ACM pipe insulation was found in the areas surveyed.
600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
4.0 CONCLUSIONS AND RECOMMENDATION
Non-friable asbestos-containing materials were identified in the spaces surveyed on the subject 10th floor. Refer to Table 1 for the summary of asbestos survey findings.
All identified ACM/assumed ACM which would be impacted by planned renovations/demolition must be properly removed prior to initiating such activities. The removal and disposal of ACM must be performed by a licensed asbestos handling contractor. The City of Philadelphia Asbestos Control Regulations (ACR), and the
Pennsylvania Department of labor and Industry (PADLI) regulations apply to all friable asbestos abatement projects. A material that is now friable or will become friable as a result of renovation/demolition activities is subject to appropriate ACR, PADLI, and
National Emission Standards for Hazardous Air Pollutants (NESHAP) regulations and requirements.
Proper notifications must be filed with the US-EPA, PADOL, PADOH, and other regulatory agencies prior to performing such activities. An independent asbestos project inspector licensed by the City of Philadelphia, must be retained to monitor the abatement project.
All confirmed and assumed ACM in the buildings that is to be left in place should be managed in good condition under an Operations and Management (O & M) plan. The purpose and objective of the O & M Plan is to maintain the assumed, assumed or known asbestos containing materials in good condition, prevent future release of asbestos fibers, and minimize exposure of all building occupants to asbestos fibers.
5.0 ASSUMPTIONS, LIMITATIONS AND EXCEPTIONS
The conclusions and recommendations presented in this report are professional current regulatory requirements. These conclusions and recommendations are intended exclusively for the purpose stated herein, at the site indicated, and for the project indicated.
It is important to recognize that even the most comprehensive scope of services may fail to detect all ACM that may be associated with the property. Therefore, Langan
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
ACM associated with the property have been identified, and no expressed or implied representation or warranty is included or intended in our report, except that our services were performed, within the limits prescribed by our client, with the customary thoroughness and competence of our profession.
Destructive means of survey will be necessary to ascertain the presence/absence of
ACM in wooden doors and electrical components/light fixtures. Any suspect material that is not listed in this report must be assumed as ACM until confirmed otherwise via laboratory testing.
\\langan.com\data\PH\data9\220073901\Office Data\Reports\Environmental\10th Floor Limited Asbestos Survey\Asbestos
Report.doc
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
TABLES
Material Location Inspection
Results Notes/Comments
Remnant of old mastic under carpet/leveling compound
Scattered locations on the 10th Floor ACM 28,700 SF 2,666 m2 --
Various floor tiles and mastic under carpet Scattered locations on the 10th Floor ACM 5,100 SF 474 m2 -- Various floor tiles and mastic exposed Scattered locations on the 10th Floor ACM 3,800 SF 353 m2 --
Mirror glue/mastic Gymnasium Assumed ACM 800 SF 74 m2
Most of the walls in the Gymnasium were covered with mirrors. Suspect glue/mastic may exist behind the mirrors. In lieu of destructive testing the mastic/glue behing the mirrors is assumed to be
ACM.
Wooden door insulation Throughout surveyed area Assumed ACM 2,100 SF 195 m2
Approximately 100 wooden doors were observed.
Suspect insulation may exist within the wooden doors. In lieu of destructive testing, the wood doors are assumed to contain ACM insulation.
Suspect materials within metal electrical conduits, panels and light fixtures (i.e. wires, insulation, transite elements, etc.)
Throughout surveyed area Assumed ACM 5,000 LF 1,524 m
Due to live electricity suspect wires and transite elements are assumed to be ACM.
Wall plaster (2 Layers) Scattered locations throughout Non-ACM -- -- -- -- -- Gypsum board Scattered locations throughout Non-ACM -- -- -- -- --
Gypsum board joint compound Scattered locations throughout Non-ACM -- -- -- -- -- Cinderblock mortar Scattered locations throughout Non-ACM -- -- -- -- --
Fiberglass pipe insulation end/joint sealant Scattered locations throughout Non-ACM -- -- -- -- -- Brown metal duct insulation Scattered locations throughout Non-ACM -- -- -- -- --
Floor leveling compound under wall-to-wall carpet Scattered locations throughout Non-ACM -- -- -- -- --
Scattered locations throughout Non-ACM -- -- -- -- --
Tape glue on the metal duct fiberglass insulation Scattered locations throughout Non-ACM -- -- -- -- --
Glue associated with carpet above the floor tiles Scattered locations throughout Non-ACM -- -- -- -- --
Metal duct seam joint tape Scattered locations throughout Non-ACM -- -- -- -- -- Sink undercoating Scattered locations throughout Non-ACM -- -- -- -- --
Soundproofing square blocks Big mechanical room by elevators Non-ACM -- -- -- -- -- Black floor covering Base room Non-ACM -- -- -- -- --
Fiberglass insulation glue inside the induction unit Scattered locations throughout Non-ACM -- -- -- -- --
Metal duct seam caulking Scattered locations throughout Non-ACM -- -- -- -- -- Raised floor support mastic Crypto room and base room Non-ACM -- -- -- -- --
Glue associated with black rubber wall panels Gymnasium Non-ACM -- -- -- -- --
Materials identified to be ACM
TABLE 1 - SUMMARY OF ASBESTOS SURVEY FINDINGS
WILLIAM J. GREEN BUILDING (10TH FLOOR)
600 ARCH STREET, PHILADELPHIA, PA
Estimated Quantity of ACM or Assumed ACM to be Impacted
Materials identified to be non-ACM
Material Location Inspection
Results Notes/Comments
TABLE 1 - SUMMARY OF ASBESTOS SURVEY FINDINGS
WILLIAM J. GREEN BUILDING (10TH FLOOR)
600 ARCH STREET, PHILADELPHIA, PA
Estimated Quantity of ACM or Assumed ACM to be Impacted
12" Square multicolor floor tiles and mastic VOIP room and backside room in the vault Non-ACM -- -- -- -- --
Scattered locations throughout Non-ACM -- -- -- -- --
Scattered locations throughout Non-ACM -- -- -- -- --glue Scattered locations throughout Non-ACM -- -- -- -- --
Scattered locations throughout Non-ACM -- -- -- -- --
Scattered locations throughout Non-ACM -- -- -- -- --
Warehouse - 2nd floor Non-ACM -- -- -- -- --
WP - 1 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
WP - 2 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
WP - 3 4 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
WP - 4 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
WP - 5 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
WP - 6 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
WP - 7 Wall Plaster (Two layers) 10th Floor L1: Non-ACM L2: Non-ACM
ND --
RMA - 1 - A Remnants of mastic under carpet Training room Non-ACM ND --
RMA - 1 - B Remnants of mastic under carpet Chief counsel room Non-ACM ND --
RMA - 1 - C Remnants of mastic under carpet Administration space ACM CHRY 3.0% --
SHT - 1 - A Gypsum board File room/mail room Non-ACM ND --
SHT - 1 - B Gypsum board Group 6 space Non-ACM ND --
SHJC - 1 - A Gypsum board joint compound File room/mail room Non-ACM ND --
SHJC - 1 - B Gypsum board joint compound Group 6 space Non-ACM ND --
CMOR - 1 - A Cinderblock mortar Space 10403 Non-ACM ND --
CMOR - 1 - B Cinderblock mortar Space 10251 Non-ACM ND --
FGPIS - 1 - A
Fiberglass pipe insulation end/joint sealant Corridor by mechanical room Non-ACM ND --
FGPIS - 1 - B
Fiberglass pipe insulation end/joint sealant Corridor by mechanical room Non-ACM ND --
DTI - 1 - A Metal duct insulation Space by women restroom and staircase
Non-ACM ND --
DTI - 1 - B Metal duct insulation Space by women restroom and staircase
Non-ACM ND --
LC - 1 - A Floor leveling compound Administration space Non-ACM ND --
LC - 1 - B Floor leveling compound File room/mail room Non-ACM ND --
CPP - 1 - A
panels
Training room Non-ACM ND --
CPP - 1 - B
panels
Room next to Break room
Non-ACM ND --
DTG - 1 - A Fiberglass insulation tape on metal ducts File room/mail room Non-ACM ND --
DTG - 1 - B Fiberglass insulation tape on metal ducts Group 7 space Non-ACM ND --
CG - 1 - A Carpet glue File room/mail room Non-ACM ND --
CG - 1 - B Carpet glue Special group space Non-ACM ND --
TABLE 2 - BULK SAMPLING ANALYSIS RESULTS
WILLIAM J. GREEN BUILDING (10TH FLOOR)
600 ARCH STREET, PHILADELPHIA, PA
SAMPLE ID
DESCRIPTION OF HOMOGENEOUS
MATERIAL
SAMPLE LOCATION
ACM or Non-
ACM
RESULTS
PLM/PLM-NOB TEM
DSM - 1 - A Metal duct seam joint tape Space by women restroom and staircase
Non-ACM ND --
DSM - 1 - B Metal duct seam joint tape Space by women restroom and staircase
Non-ACM ND --
SU - 1 - A Sink undercoating - Gray Interrogation room Non-ACM ND --
SU - 1 - B Sink undercoating - Gray Break room Non-ACM ND --
SPS - 1 - A Sound proofing square block Big mechanical room by elevators Non-ACM ND --
SPS - 1 - B Sound proofing square block Big mechanical room by elevators Non-ACM ND --
FC - 1 - A Black floor covering Base room Non-ACM ND --
FC - 1 - B Black floor covering Base room Non-ACM ND --
IUIG - 1 - A
Glue associated with fiberglass induction unit insulation Training room Non-ACM ND --
IUIG - 1 - B
Glue associated with fiberglass induction unit insulation Administration space Non-ACM ND --
DTC - 1 - A Metal duct seam caulking Corridor by Group 2 space/Near men room Non-ACM ND --
DTC - 1 - B Metal duct seam caulking Corridor by Group 2 space/Near men room Non-ACM ND --
RSFM - 1 - A Raised floor support mastic Base room Non-ACM ND --
RSFM - 1 - B Raised floor support mastic Base room Non-ACM ND --
WPG - 1 - A
Glue associated with black rubber wall panels Gymnasium Non-ACM ND --
WPG - 1 - B
Glue associated with black rubber wall panels Gymnasium Non-ACM ND --
FT - 1 - A 12-inch square beige floor tiles File room/mail room FT:ACM CHRY 4.0% --
FT - 1 - A
Mastic associated with 12-inch square beige floor tiles File room/mail room MA: ACM CHRY 5.0% --
FT - 1 - B
12-inch square beige floor tiles and mastic Group 6 space
FT: NA/PS
MA: NA/PS
FT: NA/PS
MA: NA/PS
FT - 2 - A
12-inch square multi color floor tiles and mastic VOIP Room
FT: Non-ACM MA: Non-ACM
ND --
FT - 2 - B
12-inch square multi color floor tiles and mastic Room next to VOIP room FT: Non-ACM MA: Non-ACM
ND --
FT - 3 - A
12-inch square spackled gray floor tiles and mastic Vault room
FT: Non-ACM
MA: ACM
CHRY 3.0% --
FT - 3 - B
12-inch square spackled gray floor tiles and mastic Vault room
FT: Non-ACM
MA: ACM
FT: ND
MA: NA/PS
FT - 4 - A
12-inch square spackled off white floor tiles and mastic Special support - File room FT: Non-ACM
MA: ACM
CHRY 3.0% --
FT - 4 - B
12-inch square spackled off white floor tiles and mastic Special support space
FT: Non-ACM
MA: ACM
FT: ND
MA: NA/PS
FT - 5 - A
12-inch square mottled light gray floor tiles and mastic Room across Group 6 entrance door FT: Non-ACM
MA: ACM
CHRY 3.0% --
FT - 5 - B
12-inch square mottled light gray floor tiles and mastic Room across Group 6 entrance door FT: Non-ACM
MA: ACM
FT: ND
MA: NA/PS
FT - 6 - A
12-inch square mottled light beige floor tiles and mastic Hallway by freight elevators FT: Non-ACM
MA: ACM
CHRY 2.0% --
FT - 6 - B
12-inch square mottled light beige floor tiles and mastic Hallway by freight elevators FT: Non-ACM
MA: ACM
FT: ND
MA: NA/PS
FT - 7 - A
12-inch square black floor tiles and mastic Corridors on sides
FT: Non-ACM
MA: ACM
CHRY 3.0% --
FT - 7 - B
12-inch square black floor tiles and mastic Corridors on sides
FT: Non-ACM
MA: ACM
FT: ND
MA: NA/PS
FT - 8 - A
12-inch square grit design dark gray floor tiles and mastic Corridors on sides
FT: Non-ACM
MA: ACM
CHRY 2.0%
FT - 8 - B
12-inch square grit design dark gray floor tiles and mastic Corridors on sides
FT: Non-ACM
MA: ACM
FT: ND
MA: NA/PS
FT - 9 - A
12-inch square striped dark brown floor tiles Center corridor by elevators
FT: ACM CHRY 2.0% --
FT - 9 - A
Mastic associated with 12-inch square striped dark brown floor tiles Center corridor by elevators
MA: ACM CHRY 2.0% --
FT - 9 - B
12-inch square striped dark brown floor tiles and mastic Center corridor by elevators
FT: NA/PS
MA: NA/PS
FT: NA/PS
MA: NA/PS
BB - 1 - A
associated glue
Training room BB: Non-ACM GL: Non-ACM
ND --
BB - 1 - B
associated glue
Room by training room
BB: Non-ACM GL: Non-ACM
ND --
BB - 2 - A
associated glue
File room/mail room BB: Non-ACM GL: Non-ACM
ND --
BB - 2 - B
associated glue
Administration space BB: Non-ACM GL: Non-ACM
ND --
BB - 3 - A
associated glue
Base room BB: Non-ACM GL: Non-ACM
ND --
BB - 3 - B
associated glue
Base room BB: Non-ACM GL: Non-ACM
ND --
BB - 4 - A
associated glue
VOIP Room BB: Non-ACM GL: Non-ACM
ND --
BB - 4 - B
associated glue
Vault room BB: Non-ACM GL: Non-ACM
ND --
BB - 5 - A
associated glue
Intel group Non-ACM ND --
BB - 5 - B
associated glue
Intel group Non-ACM ND --
BB - 6 - A
associated glue
Room across Group 6 entrance door
Non-ACM ND --
BB - 6 - B
associated glue
Room across Group 6 entrance door
Non-ACM ND --
Concentrations in weight percent.
NA/PS = Not Analyzed/Positive Stop
PLM = Polarized Light Microscopy
BB = Baseboard Molding
GL = Glue
NOB = Non-friable Organically Bound
TEM = Transmission Electron Microscopy
A material with asbestos content greater than one percent (>1.0%) is considered as an asbestos-containing material (ACM).
CHRY = Chrysotile Asbestos
FT = Floor Tile
MA = Mastic
600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
DRAWINGS
Limited Asbestos Survey Report (10th Floor) July 10, 2014 William J. Green Building 600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
A P P E N D I X A
Laboratory Test Results and Chain of Custody
600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
A P P E N D I X B and Laboratory Accreditations
600 Arch Street Philadelphia, Pennsylvania Langan Project No. 220073901
A P P E N D I X C
September 2011 Asbestos Containing Building Materials Survey Report
Asbestos-Containing Building Materials Survey Report
William J. Green Jr. Federal Building Philadelphia, Pennsylvania
Prepared For:
Asbestos-Containing Building Materials Survey Report
William J. Green Jr. Federal Building – GSA Facility PA0277BG 600 Arch Street
Philadelphia, Pennsylvania 19106
Prepared For:
Prepared By:
– Facility WV0226ZZ - 244 Needy Road, Matinsburg West
Asbestos Survey Report - Facility PA0277BG
General Services Administration Facility – PA0277BG
600 Arch Street, Philadelphia, Pennsylvania
TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY
2.0 INTRODUCTION
2.1 Facility Description
3.0 SCOPE OF WORK
3.1 Limitations
4.0 ASBESTOS SURVEY METHODOLOGY
4.1 Records Review
4.2 Inspection and Sampling Procedures
4.3 Laboratory Analysis
4.4 Confined Spaces / Inaccessible Areas, Spaces and Materials
4.5 Health Hazard Assessment
4.6 Deliverables
4.6.1Asbestos Report 4.6.2Management Plans and Data Record Disk 4.6.3Inspection Documentation
5.0 SURVEY FINDINGS AND DISCUSSION
5.1 Survey Chronology
5.2 Records Review
5.3 Confined Spaces / Inaccessible Areas, Spaces and Materials
5.4 Assumed / Presumed Asbestos-Containing Materials
5.5 Laboratory Results
5.6 Discussion
6.0 COST ESTIMATE
Appendix A: Detailed Inventory of Results by room and floor Appendix B: Sketches / Drawings Appendix C: Photographic Log Appendix D: Laboratory Reports
INSPECTION SUMMARY and REVIEW
GSA Facility PA0277BG
TWI – 1006-027
Facility PA0277BG – William J. Green, Jr. Federal Building, Philadelphia, Pennsylvania Tidewater Project Number – 1006-027
Records for on-site review, anecdotal and personal knowledge of the facility were provided during the pre-inspection conference and during the inspection. Records reviewed include the following:
Records Review
February 9, 1996 - Fax Transmittal documenting Asbestos Sampling at the Byrne /Green Buildings. Roy F.
Weston, Inc. West Chester, Pennsylvania.
March 18, 1997 – Transmittal Letter documenting floor tile results from 8th and 9th floors. Cape Environmental Management, Inc., Exton Pennsylvania.
August 21, 1997 - Letter Report – Asbestos-Containing Materials (ACM) Sampling in the Custodial Storage Room located on the Basement Floor. Cape Environmental Management, Inc., Exton Pennsylvania.
August 19, 2009 – Letter Report – Pre-Renovation Asbestos, Lead Based Paint and Other Regulated Materials Inspection Report, Green Federal Building Child Center Renovation. Hygienetics Environmental Services, Inc.
Cherry Hill New Jersey.
Any documents provided prior to and at the time of the inspection may not be a complete inventory of all available documents, and therefore should not be considered comprehensive regarding renovations, remediation, and monitoring programs.
No confined spaces were identified during the inspection. An inaccessible space was identified as the plenum above the main lobby ceiling. Several areas were inspected for access hatches none were located. Visual inspection through the vent covers indicates a tan duct mastic materials is present in the space. This material is not as Presumed or PACM in this report.
Inaccessible Spaces
1. Tan Duct Mastic – HA046
Presumed Materials Identified
2. 12”x12” Off White Mottled Tile – HA050
3. 12”x12” Light Grey Mottled Tile – HA051
4. 12”x12” Dark Grey Mottled Tile- HA052
5. Mastic a/w HA014 – HA066
6. Mastic a/w HA026 – HA073
7. Mastic a/w HA031 – HA074
8. Mastic a/w HA036 – HA077
9. Mastic a/w HA045 – HA080
10. Mastic a/w HA053 – HA086
11. Mastic a/w HA054 – HA087
12. Mastic a/w HA055 – HA088
13. Mastic a/w HA057 – HA089
These materials have been designated as presumed because they were inaccessible or the inspector(s) were asked by GSA personnel not to sample because of the location of the materials, or the location of the sample.
Current Cost estimate, attached below for your review, is $531,006.75. Presumed items make up $101,495.00..
Cost Estimate Review
1. The largest portion of the cost estimate is confirmed items.
Discussion / Conclusions
1. No further action is recommended.
Recommendations for Additional Investigation
INSPECTION SUMMAY and REVIEW
– Facility WV0226ZZ - 244 Needy Road, Matinsburg GSA Facility PA0277BG
TWI – 1006-027
Based on the results of this inspection, the following cost estimate has been developed for the removal and disposal of confirmed and assumed/presumed asbestos-containing building materials. These unit prices are based on current industry standard costs for projects of similar scale and scope. The cost estimate includes containment, removal, transportation, and disposal of the materials. The cost estimate also includes costs associated with typical testing and monitoring during the abatement work, up to and including final clearance testing and visual certification of the abatement work area. A 15% contingency has been included as a line item to account for unforeseen conditions and inaccessible materials not identified by this inspection.
Cost Estimate
Material Type Quantity Unit Removal Cost per
Unit Total
12" x 12" Vinyl Floor Tile (Positive/Confirmed)
80,334 SF $2.50 $200,835.00
12" x 12" Vinyl Floor Tile (Presumed)
3,778 SF $2.50 $9,445.00
Duct Mastic (Presumed) 15,000 LF $2.50 $37,500.00
Linoleum Flooring (Presumed) 200 SF $3.25 $650.00
Mastic (Presumed) 21,560 SF $2.50 $53,900.00
Mastic (Positive/Confirmed) 22,422 SF $2.50 $56,055.00
Mudded Fittings 19 EA $22.00 $418.00
Pipe Insulation 385 LF $15.00 $5,775.00
Pipe Insulation Mastic 337 LF $2.50 $842.50
Plaster 2,550 SF $16.00 $40,800.00
Sink Insulation 1,576 SF $35.00 $55,160.00
Subtotal $461,380.50
15% Contingency $69,207.08
Grand Total $530,587.58
– Facility WV0226ZZ - 244 Needy Road, Matinsburg West 1
Asbestos Survey Report - Facility PA0277BG
General Services Administration Facility – PA0277BG
600 Arch Street, Philadelphia, Pennsylvania
1.0 EXECUTIVE SUMMARY
As part of the Asbestos Survey Program for PA0277BG, William J. Green Jr. Federal Building, Philadelphia Pennsylvania, records were reviewed for additional information during the inspection, and bulk samples were collected for analysis. Copies of all field notes, photos, chain-of-custody forms, and laboratory results are included as appendices of this report.
In general, the building, its materials of construction, and building systems were observed to be generally in good condition. Some materials were found in poor condition in the building. They are listed in the inventory. Limited asbestos-containing materials were identified in detail in the body of this report.
Based on the results of this inspection, the following cost estimate has been developed for the removal and disposal of confirmed and assumed/presumed asbestos-containing building materials.
These unit prices are based on current industry standard costs for projects of similar scale and scope. The cost estimate includes containment, removal, transportation, and disposal of the materials. The cost estimate also includes costs associated with typical testing and monitoring during the abatement work, up to and including final clearance testing and visual certification of the abatement work area. A 15% contingency has been included as a line item to account for unforeseen conditions and inaccessible materials not identified by this inspection.
Material Type Quantity Unit Removal Cost per Unit Total
12" x 12" Vinyl Floor Tile (Positive/Confirmed) 80,334 SF $2.50 $200,835.00
12" x 12" Vinyl Floor Tile (Presumed) 3,778 SF $2.50 $9,445.00
Duct Mastic (Presumed) 15,000 LF $2.50 $37,500.00 Linoleum Flooring (Presumed) 200 SF $3.25 $650.00 Mastic (Presumed) 21,560 SF $2.50 $53,900.00 Mastic (Positive/Confirmed) 22,422 SF $2.50 $56,055.00 Mudded Fittings 19 EA $22.00 $418.00 Pipe Insulation 385 LF $15.00 $5,775.00 Pipe Insulation Mastic 337 LF $2.50 $842.50 Plaster 2,550 SF $16.00 $40,800.00 Sink Insulation 1,576 SF $35.00 $55,160.00
Subtotal $461,380.50
15% Contingency $69,207.08
Grand Total $530,587.58 This cost estimate does not include: Elevator Brake Shoes or Roofing Materials
– Facility WV0226ZZ - 244 Needy Road, Matinsburg West 2
Asbestos Survey Report - Facility PA0277BG
General Services Administration Facility – PA0277BG
600 Arch Street, Philadelphia, Pennsylvania
2.0 Introduction
Tidewater, Inc. (Tidewater) was retained by the General Services Administration (GSA) to generate full-service Asbestos Survey Programs (ASPs) for federally-owned facilities under GSA control in the Mid-Atlantic Region. The Mid-Atlantic Region encompasses the States of Delaware, Maryland (excluding Montgomery and Prince George’s Counties), Pennsylvania, Virginia (excluding the cities of Alexandria and Falls Church, and Arlington, Fairfax, Loudoun, and Prince William Counties), West Virginia, and southern New Jersey. The facilities consist of approximately 10.6 million square feet of building space in 54 separate buildings in six states. The buildings to be inspected vary in location, age, size, and use. They have varying asbestos inspection and abatement histories, and varying tenants. Tenants include, but are not limited to, any federal agency, each with varying space functions and security.
The GSA is responsible for identifying and controlling environmental safety and health hazards that may exist on federally-owned or leased property under GSA control. In compliance with GSA policy, operations, processes or materials that have been identified as potential hazards must be evaluated. Recommended abatement actions are formulated and referred to the responsible office for implementation. Within the scope of GSA responsibility is the response to hazards and potential hazards caused by asbestos-containing materials (ACM).
US Department of Labor, Occupational Safety and Health Administration (OSHA) require in both its General Industry Standard (29 Code of Federal Regulations (CFR) Part 1910.1001) and its Construction Standard (29 CFR Part 26.1101) that building/facility owners determine the presence, location and quantity of ACM and presumed ACM at the worksite. GSA’s Public Building Service (PBS) Asbestos Policy (Attachment A) requires that these requirements be met by conducting visual inspections of ACM every five years and updating surveys accordingly. In addition, the Federal Accounting Standards Advisory Board Technical Bulletin 2006-01, Recognition and Measurement of Asbestos Related Clean-up Costs (Attachment B) requires the reporting of liabilities and related expenses arising from all asbestos-related clean-up efforts, and not just those from asbestos that requires immediate clean-up.
2.1 Facility Description
As part of this program, Tidewater conducted a detailed asbestos inspection of GSA facility PA0277BG, William J. Green Jr. Federal Building, located at 600 Arch Street in Philadelphia, Pennsylvania between the 9th of March, 2010, and the 11th of March, 2010. A follow up inspection was performed on June 20th 2011. The William J. Green Jr. Federal Building facility consists of one ten-story structure with a two penthouses, and a basement with a garage, constructed in 1966. The structure is basically a combination of reinforced concrete and masonry bearing-wall structure. The total square enclosed footage is approximately 848,755 square feet.
Information regarding the construction and maintenance history for the facility was provided by Mr.
John Kleaver, and Ms. Melissa Condran, from GSA.