IF A DIMENSION IS GREATER
THAN 2'-0", SUPPORT ELBOW
FROM STRUCTURE ABOVE
MAX. LENGTH OF
FLEX DUCT 5'-0"
NON-KINKED
SUPPLY DUCT
ROUND OR
RECTANGULAR
MAIN OR BRANCH
DUCT
DRAW BAND BUCKLEY TYPE ATMD
FITTING (OR EQUAL)
PROVIDE A TYPICAL DUCT TAKEOFF WHERE FLEX EXCEEDS
7'-0" (MAX. LENGTH)
CEILING TYPE VARIES.
REFER TO ARCHITECTURAL
PLANS FOR CEILING TYPE.
FLEX DUCT
NON- RESTRICTIVE 90 ELBOW
"THERMAFLEX" FLEX-FLOW
OR EQUAL. INSTALL AT ALL
ROUND NECK DIFFUSERS
DRAW BAND ON DIFFUSER
NECK
ROUND NECK
OR NECK
ADAPTOR
SUPPLY AIR DIFFUSER WITH ROUND NECK & O.B.D.
MOUNTING DETAIL VARIES. REFER TO ARCH. FOR
CEILING TYPE AND DIFFUSER MANUFACTURER FOR
MOUNTING REQUIREMENTS
NOTE:
1. INSULATED FLEXIBLE DUCT - SHALL BE PRESTRETCHED BEFORE INSTALL.
2. DIAMETER TO BE EQUAL TO DIFFUSER INLET SIZE UNLESS OTHERWISE NOTED.
HYDRONIC
COIL MV
MV
P/T
CO
CO
P/T
DRAIN PAN (COOLING
ONLY)
CONDENSATE TRAP SEAL
(COOLING ONLY)
SUPPLY PIPING (SEE PLANS
FOR SIZE)
RETURN PIPING (SEE PLANS
FOR SIZE)
MV
NOTES:
1.UNIONS (OR FLANGED BODY) INDICATED TO PERMIT REMOVAL OF CONTROL VALVES. PROVIDE
REDUCERS AS REQUIRED.
2.PROVIDE DRAIN VALVES AT LOW POINTS OF ALL COIL HEADERS, INCLUDING DRAIN HEADERS, SAME SIZE AS COIL OUTLET SIZES BUT NOT LESS THAN 3/8".
3.ALL RUNOUTS SHALL BE SAME SIZE AS COIL CONNECTIONS.
4. LOCATE PIPE UNIONS AND ARRANGE PIPING TO FACILITATE COIL REMOVAL.
MAIN SUPPLY, RETURN, OR EXHAUST DUCT(LO OR
MEDIUM PRESSURE)
DISTANCE (1/4)x
DUCT WIDTH;
101.6(4")
MINIMUM
VOLUME DAMPER
(TYPICAL)
RECTANGULAR BRANCH
TAKE-OFF DUCT
45° ENTRY FITTING
CONCAL DUCT
TAKE-OFF
FITTING
BELLMOUTH DUCT TAKE-
OFF FITTING
VOLUME DAMPER (TYPICAL)
ROUND BRANCH TAKE OFF DUCT (TYPICAL)
NOTES:
1. SPIN-IN DUCT TAKE OFF FITTINGS MAY BE USED IN LIEU OF CONICAL OR BELLMOUTH
FITTING ONLY WHERE MAIN DUCT DIMENSIONS ARE NOT SUFFICIENT TO ALLOW THE
USE OF A CONICAL OR BELLMOUTH
2. SEAL ALL TAKE-OFF AND OTHER FITTINGS AIR TIGHT AS PER SPECIFICATION.
3. FABRICATE BRANCH DUCT TAKE-OFF FITTING PER LATEST EDITION OF DUCT
CONSTRUCTION MANUAL, AS INDICATED ON PLANS, OR AS DESCRIBED IN
SPECIFICATIONS.
4. APPLIES TO SUPPLY AND EXHAUST RUNOUTS TO GRILLES, REGISTERS, AND
DIFFUSERS.
DUCT DIMENSION
UP TO 457 (18")
482(189")- 1524(60")
1549(61")- 2438(96")
OVER 2438(96")
HANGER
TYPE
A
B
C
D
ROD DIA.
25.4(1") STRAP
7.94(5/16")
9.53(3/8")
12.7(1/2")
ANGLE SIZE
36.1x36.1x3.18(1-1/2"x1-1/2"x1/8")
36.1x36.1x3.18(1-1/2"x1-1/2"x3/16")
50.8x50.8x8.35(2"x2"x1/4")
SPACING MAX
24.38(8'-0")
12.19(4'-0")
24.38(8'-0")
24.38(8'-0")
MAX. SIDE
SHEET METAL SCREW,
RIVET OR BOLT TO BOTH
SIDES OF DUCT NUT AND WASHER AT END
OF SCREW
BRACING ANGLES,
SEE NOTES.
HANGER ROD
SECURE THE
STRUCTURE ABOVE AS
RECOMMENDED
25.4(1")x16 GA. GALV.
IRON STRAP OR ALUM.
MAX. SIDE
TYPE A TYPE B,C,D
24.8(8FT.) MAX. HANGER SPACING, ALSO
PROVIDE 3 HANGERS AT EACH TAKE OFF OR
BRANCH.
24.8(8FT.) MAX. HANGER SPACING
NOTES:
1. FOR SEVERAL DUCTS ON ONE HANGER, TYPE B,C OR D MAY BE USED. SIZE OF HANGER SHALL
BE SELECTED ON SUM OF DUCT WIDTHS EQUAL TO MAX. WIDTH OF DUCT SCHEDULE.
2. DO NOT ATTACH HANGERS TO ROOF DECK OR BOTTOM.
TTTTTTTT
FS FS
CHS-P PIPING
CHR-P PIPING
CWR PIPING
CWS PIPING
CONDENSER
BARRELL
EVAPORATOR
BARRELL
TUBE PULL
CLEARANCE
HOSE BIBB DRAIN
VALVE (N.C.)
4" CONCRETE
HOUSEKEEPING PAD
VIBRATION ISOLATORS AS
SPECIFIED
NOTES:
1. PIPE DROPS TO AND FROM CHILLER AND CONDENSER
BARRELLS SHALL BE INSTALLED TO FACILITATE
REMOVAL OF TUBE PULLS.
2. SEE PLANS FOR EXACT LOCATION OF CHILLER PIPE
CONNECTIONS.
FLOW SWITCH
(TYP.)
PRESSURE
GAUGE (TYP.)
CENTRIFUGAL VFD
COMPRESSOR
BUTTERFLY
VALVE (TYP.)
THERMOMETER
TEMPURATURE
SENSOR (TYP.)
UNION (TYP.)
FLEXIBLE PIPE
CONNECTION (TYP.)
MOTORIZED
CONTROL
VALVE (TYP.)
UNION (TYPICAL)
CHEMICAL SHOT FEEDER
TANK
PUMP DISCHARGE PIPING
PUMP SUCTION PIPING
FLOW
1" 1"
CHECK VALVE
CALIBRATED BALANCING AND
SHUT-OFF VALVE
DRAIN VALVE
WITH HOSE
END
SHUT-OFF VALVE (TYPICAL)
FLOOR
ADJUSTABLE LEGS
FLANGES
FLEX CONN
PIPE HANGER
CHRV
CHRVCHRV
1-1/4"
CONDENSATION
TRAP
CHRV
1-1/4"
CHRV
3/4" 3/4"
1-1/2" 1-1/2"
1-1/2"
1-1/2"
1-1/2"
EVAPORATOR
CONDENSER
(3/4")
DUAL RELIEF VALVE
BY CHILLER MF'G
EXTERIOR WALL
APPROVED VENT FITTING
CHRV
(3/4")
ROOF
(M
IN
CHRV
1-1/2"
1-1/2"
CH
CHILLER REFRIGERANT RELIEF VENT QUANTITY, SIZE AND CONFIGURATION MAY DIFFER, VERIFY WITH
CHILLER MANUFACTURER.
1.
NOTES:
PIPE HANGER
FLANGES
FLEX CONN
CONDENSATION
TRAP
FLANGES
FLEX CONN
CONDENSATION
TRAP
CH
CH
PIPE HANGER
1-1/4"
CHRV
3/4"
1-1/2"FLANGES
FLEX CONN
CONDENSATION
TRAP
CH
PIPE HANGER
CHRV
1-1/4"
SECTION THRU PIPE
NOTE:
1.PROVIDE WEATHER RESISTANT LABELING ON EXTERIOR OF JACKET IDENTIFYING PIPES AS BEING "ELECTRICALLY TRACED" WITH VOLTAGE INDICATED.
2. IF THESE DETAILS CONFLICTS WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS - THEN COMPLY WITH THE MANUFACTURERS INSTRUCTIONS.
THERMOSTAT WITH AMBIENT AIR
SENSOR SET ON AT 35°F
PIPE INSULATION & ALUMINUM
FOIL TAPE NOT SHOWN
HEAT TRACE CABLE
EVENLY DISTRIBUTED
ALONG PIPE PIPE STRAPS
1'-6"
VALVE
SELF REGULATING
TYPE HEAT TRACE
CABLE
WATER TIGHT CONTROL BOX
TO POWER SUPPLY AT
DISCONNECT SWITCH
CONTRACTOR
HEAT TRACE CABLE
END CAP
WATERPROOF
JACKET OVER
INSULATION
ALUMINUM FOIL TAPE
SELF REGULATING HEAT TRACE CABLE
PIPE STRAPS AT APPROX. 18" INTERVALS
PIPE INSULATION & ALUMINUM FOIL TAPE
NOT SHOWN
INSTALLATION DETAIL INSTALLATION AT VALVESHEAT TRACE CONTROL BOX DIAGRAM
NO
PIPE INSULATION
HOT- COLD JOINT
1. DEPTH OF SEAL SHALL BE EQUAL TO THE NEGATIVE PRESSURE IN DRAIN PAN.
SEE NOTE #1.
DEPTH OF SEAL
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE
DRAIN PAN
AIR GAP 1" MIN.
NOTES:
PITCH DOWN TO DRAIN
CLEAN OUT UNIT DRAIN PAN
DRAW-THRU SIPHONAGE DISTANCE.
SEE NOTE #2.
2. DISTANCE OF SIPHONAGE SHALL BE 1 1/2 TIMES THE NEGATIVE PRESSURE IN THE DRAIN PAN.
SPLASH BLOCK OR INDIRECT WASTE
CLEAN OUT
LONG-RADIUS ELBOW
THERMOMETER
STRAINER WITH BLOW-OFF VALVE
FLEXIBLE CONNECTOR
SHUT-OFF VALVE
CHECK VALVE
3/4" DRAIN FROM SPILL PAN TO NEAREST FLOOR DRAIN
HORIZONTAL SPLIT CASE PUMP
INERTIA BASE ON (4) SPRING VIBRATION ISOLATORS
HOUSEKEEPING PAD
PUMP SUCTION
PIPING
PUMP DISCHARGE PIPING
SPRING HANGER PIPE SUPPORT (TYP.)
COMBINATION BALANCING/ SHUT-OFF VALVE
PRESSURE GAUGE MANIFOLD W/ GAUGE COCKS
PIPE SUPPORT
FLOOR
N
PROPERTY OF THE UNITED
STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Do not remove this notice.
Properly destroy or return documents when no longer needed.
(SBU)
SENSITIVE BUT UNCLASSIFIED
WEST EAST
© 2015 Erdy McHenry Architecture, LLC
DRAWN BY:
Erdy McHenry Architecture, LLC 915 North Orianna Street Philadelphia, Pennsylvania 19123 ph: 215.925.7000 fax: 215.925.1990 web: http://www.em-arc.com
Architect: SCOTT A. ERDY, AIA
DAVID S. MCHENRY, AIA
emArchitecture
SCALE:
PROJECT NO:
DATE:
SHEET NUMBER:
P lo tte d:
KEY PLAN
As indicated
MS501
MECHANICAL DETAILS
1158.00/SCR-2015216.00DLA
05-06-16
600 Arch Street
Philadelphia, PA 19107
GREEN FEDERAL BUILDING
CONSOLIDATION
Program + Strategy Consultant Studio Hillier 190 Witherspoon Street Princeton, NJ 08542
Greenman - Pedersen, Inc. (GPI) 50 Glenmaura National Blvd.
Suite 102 Scranton, PA 18505
Cerami & Associates 404 Fifth Avenue New York, NY 10018
TCT Cost Consultants, LLC 1090 Vermont Avenue NW Suite 230 Washington, DC 20005
Weidlinger Associates, INC 1825 K Street Avenue NW Suite 350 Washington, DC 20006
Antis Veterans Engineering adn Technical Services 2074 Cobblestone Lane Suite 850 Reston, VA 20191
Structural Engineer
MEP Engineer
Acoustical Consultant
Cost Specialist
Security + Blast
Praxis Building Solutions, LLC 2401 Walnut Street Suite 102 Philadelphia, PA 19103
Green Building Consultant
Beam, Ltd 428 West Waverly Road Glenside, PA 19038
Lighting Consultant
GSA Project Data William J. Green Federal Building GSA Project #: VPA00027 GSA Building #: PA0277 GSA Contract #: GS-03P-14-AZ-C-0020 GSA Solicitation #: GS-03P-15-AZ-C-1020
Core & Shell Package 05-06-16
NTS1 SUPPLY AIR DIFFUSER DETAIL (SIDE TAP)
NTS2 HYDRONIC COIL PIPING DETAIL - 2-WAY CONTROL VALVE
NTS3 BRANCH TAKE-OFF DETAIL
NTS4 DUCT HANGERS
NTS10 WATER COOLED CHILLER PIPING DETAIL
NTS8 CHEMICAL SHOT FEEDER PIPING
NTS9 CHILLER VENT PIPING DETAIL
NTS5 HEAT TRACING DETAILS
NTS6 DRAW-THRU CONDENSATE DRAIN TRAP DETAIL
NTS7 HORIZONTAL SPLIT CASE PUMP DETAIL
Revision Number Drawing Issue Date
1 Issued for Addendum 02 06-10-16
| Sheets |
| MS501 - MECHANICAL DETAILS |