EVAPORATOR
CONDENSER
EVAPORATOR
CONDENSER
EVAPORATOR
CONDENSER
EVAPORATOR
CONDENSER
K
J
H
G
16 17 18 19 20
LOWER BOILER
ROOM
LOWER
CHILLER
ROOM
RELOCATE
EQUIPMENT AND
REMOVE PAD
TEMPORARILY
REMOVE
MEZZANINE
STAIRS AS
REQUIRED
INCREASE
EXISTING
4'-10"WIDE x
7'-0"HIGH DOOR
OPENING
CHILLER
BUNDLE
SECTION
LOWERED FROM
MEZZANINE
LEVEL
EXISTING
BOILER AND
CONCRETE PAD
EXISTING HIGH
VOLTAGE AND
PIPE CURB
TO REMAIN
EXISTING
MEZZANINE
STAIRS TO
REMAIN.
NOTE:
SEE CHILLER ROOM PHASING PLANS FOR EQUIPMENT INSTALLATION.
UP
L
K
2018 19
MEZZANINE
FAN ROOM
BOILER
ROOM
MEZZANINE
BOILER ROOM
EXISTING REMOVABLE
11'-6"WIDE x
20'-0"HIGH LOUVER
FOR EQUIPMENT
TRANSPORT
CHILLER BUNDLE
SECTION CRANED
IN FROM 6TH
STREET
DN.
EXISTING
HOT/CHILLED
WATER PIPING
EXISTING RUNOUT
TO FCU ABOVE
EXISTING RUNOUT
TO FCU ABOVE
EXISTING FAN COIL
UNIT (FCU)
EXISTING FAN COIL
UNIT (FCU)
FLOOR TO BE
RENOVATED
EXISTING CEILING 9'-0"
EXISTING
HOT/CHILLED
WATER PIPING
EXISTING PIPING
FLOOR BEING
RENOVATED
EXISTING FAN COIL
UNIT (FCU)
INSTALL NEW
PIPING LOOP
NEW PIPING
RUNOUTS TO
NEW FCU
EXISTING RUNOUT
TO FCU TO BE
CAPPED
EXISTING
HOT/CHILLED
WATER
PIPING
NEW FCU
EXISTING PIPING
FLOOR BEING
RENOVATED
EXISTING FAN COIL
UNIT (FCU)
NEW PIPING LOOP
NEW PIPING TO
NEW FCU
EXISTING RUNOUT
TO FCU
NEW FCU
REMOVE EXISTING FAN
COIL UNIT AND CAP
RUNOUT.
EXISTING
HOT/CHILLED
WATER PIPING
TO BE REMOVED
EXISTING PIPING
COMPLETED
FLOOR
RENOVATION
EXISTING FAN COIL UNIT
(FCU) FED BY NEW PIPING
SYSTEM UNTIL FLOOR IS
RENOVATED
INSUBSEQUENT PHASE
INSTALL NEW
PIPING LOOP
NEW (FCU)
NEW PIPING TO
NEW FCU
NOTE:
WHEN THIS FLOOR IS RENOVATED,
CLOSE ISOLATION VALVES ON
FLOOR BELOW, REMOVE FCU, AND
CAP RUNOUT.
CAPPED
HOT/CHILLED
WATER PIPING
REMOVE
PIPING WHEN
ASSOCIATED
FLOOR IS
RENOVATED
N
PROPERTY OF THE UNITED
STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Do not remove this notice.
Properly destroy or return documents when no longer needed.
(SBU)
SENSITIVE BUT UNCLASSIFIED
OVERALL
© 2015 Erdy McHenry Architecture, LLC
DRAWN BY:
Erdy McHenry Architecture, LLC 915 North Orianna Street Philadelphia, Pennsylvania 19123 ph: 215.925.7000 fax: 215.925.1990 web: http://www.em-arc.com
Architect: SCOTT A. ERDY, AIA
DAVID S. MCHENRY, AIA
emArchitecture
SCALE:
PROJECT NO:
DATE:
SHEET NUMBER:
P lo tte d:
KEY PLAN
As indicated
MD501
SCHEMATICS AND
INSTALL PATH
1158.00/SCR-2015216.00DLA
05-06-16
600 Arch Street
Philadelphia, PA 19107
GREEN FEDERAL BUILDING
CONSOLIDATION
Program + Strategy Consultant Studio Hillier 190 Witherspoon Street Princeton, NJ 08542
Greenman - Pedersen, Inc. (GPI) 50 Glenmaura National Blvd.
Suite 102 Scranton, PA 18505
Cerami & Associates 404 Fifth Avenue New York, NY 10018
TCT Cost Consultants, LLC 1090 Vermont Avenue NW Suite 230 Washington, DC 20005
Weidlinger Associates, INC 1825 K Street Avenue NW Suite 350 Washington, DC 20006
Antis Veterans Engineering adn Technical Services 2074 Cobblestone Lane Suite 850 Reston, VA 20191
Structural Engineer
MEP Engineer
Acoustical Consultant
Cost Specialist
Security + Blast
Praxis Building Solutions, LLC 2401 Walnut Street Suite 102 Philadelphia, PA 19103
Green Building Consultant
Beam, Ltd 428 West Waverly Road Glenside, PA 19038
Lighting Consultant
GSA Project Data William J. Green Federal Building GSA Project #: VPA00027 GSA Building #: PA0277 GSA Contract #: GS-03P-14-AZ-C-0020 GSA Solicitation #: GS-03P-15-AZ-C-1020
Core & Shell Package 05-06-16
PHASING CONCEPT PERIMETER PIPING
A. PHASING FOR PIPE MAIN REMOVAL/INSTALLATION SHALL OCCUR AS
FOLLOWS TO ACCOMMODATE PROJECT PHASING:
1. REMOVE EXISTING FLOOR MOUNTED FAN COIL UNIT ON
FLOOR CURRENTLY BEING RENOVATED. SEAL ALL FLOOR
PENETRATIONS LEFT BY THE PIPE REMOVAL TO MATCH
SURROUNDINGS.
2. INSTALL NEW PIPING LOOP MAINS AND NEW FAN COIL
UNIT ON RENOVATED FLOOR.
a. WHERE FLOOR ABOVE IS TO BE RENOVATED IN
A SUBSEQUENT PHASE: DISCONNECT EACH
EXISTING FAN COIL UNIT RUNOUT FROM THE
EXISTING FLOOR MOUNTED FAN COIL UNIT
LOCATED ON THE FLOOR ABOVE.
RECONNECT THE SAME FAN COIL UNIT TO
THE NEW PIPING LOOPS. PROVIDE NEW ISOLATION
SHUTOFF VALVES IN THE CEILING FOR EACH
RUNOUT TO THE FAN COIL ABOVE.
b. INSTALL TEMPORARY BOOSTER PUMP LOCATED IN
CORE AHU MECHANICAL ROOM TO PROVIDE INCREASED
FLOW UNTIL THE FLOOR ABOVE IS RENOVATED (REMOVE
BOOSTER PUMP WHEN FLOOR ABOVE IS RENOVATED).
3. ONCE ALL EXISTING PIPE RUNOUTS HAVE BEEN
DISCONNECTED FROM EXISTING PIPE LOOPS, THE EXISTING
PIPE LOOPS AND ALL APPURTENANCES SHALL BE REMOVED.
4. ON FLOORS WHERE EXISTING AREAS ARE NOT RENOVATED,
CONNECT NEW PIPING SYSTEM TO EXISTING PIPING WHERE
RENOVATED AREAS MEET EXISTING AREAS TO REMAIN.
Scale: 1/8" = 1'-0"6 CHILLER INSTALL PATH
Scale: 1/8" = 1'-0"5 CHILLER INSTALL PATH - ROOF Scale: 1/4" = 1'-0"1 PIPE PHASING SCHEMATIC - EXISTING CONDITIONS
Scale: 1/4" = 1'-0"2 PIPE PHASING SCHEMATIC - STEP 1 (NEW WORK/ TEMPORARY TIE-IN
Scale: 1/4" = 1'-0"3 PIPE PHASING SCHEMATIC - STEP 2 (DEMOLITION) Scale: 1/4" = 1'-0"4 PIPE PHASING SCHEMATIC - FINAL LAYOUT
NOTE:
1. THE PROPOSED PERIMETER PIPING PHASING CONCEPT IS INTENDED
TO REPRESENT ONE SUGGESTED APPROACH FOR THE POSSIBLE
PHASING AT THE RENOVATED SPACES WHILE ALLOWING THE PIPING TO
SERVE THE OCCUPIED SPACES.
2. THE ULTIMATE MEANS AND METHOD TO PERFORM THIS WORK IS THAT
OF THE INSTALLING CONTRACTOR. ANY APPROCH SHALL PRESENT AS
LITTLE OF DISTURBANCE TO THE OCCUPANTS IN THE ADJACENT SPACES
AND FLOORS AND ALLOWED BY THE TENANTS AND GSA.
Revision Number Drawing Issue Date
1 Core & Shell Addendum #1 06-03-16
| Sheets |
| MD103 - DEMOLITION LEVEL 2 HVAC FLOOR PLAN - WEST |
| MD104 - DEMOLITION LEVEL 2 HVAC FLOOR PLAN - EAST |
| MD501 - SCHEMATICS AND INSTALL PATH |
| MH103 - LEVEL 2 - HVAC FLOOR PLAN - WEST |
| MH104 - LEVEL 2 - HVAC FLOOR PLAN - EAST |
File details come from the government source that posted it. Updated .