This document is a specification section outlining requirements for vinyl wall coverings in a dormitory repair project. The section specifies vinyl wall coverings must meet ASTM fire testing standards and lists seven approved manufacturers. It requires a minimum backing weight of 33-36 ounces per linear yard and a width of 36 inches for wainscot installation. Samples must be submitted for approval and mockups built to demonstrate quality. Installation must follow manufacturer's instructions and produce tight seams without edges lifted or curled. Extra materials must be provided for future repairs.
Added Specification (noted in Ameded Table of Contents).
View the file
Other files for this federal contract opportunity
Show all 41
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT 01 FA4626-XX-X-XXXX
Repair Dormitory 655
NZAS 04-1042
WALL COVERINGS 097200 - 1
SECTION 09 72 00 - WALL COVERINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 PROHIBITED MATERIALS
A. Asbestos-containing materials are prohibitied.
1.3 SUMMARY
A. Section Includes:
1. Vinyl wall covering.
1.4 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.5 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include data on physical characteristics, durability, fade resistance, and fire-test-response characteristics.
B. Shop Drawings: Show location and extent of each wall-covering type. Indicate seams and termination points.
C. Samples: For each type of wall covering and for each color, pattern, texture, and finish specified, full width by 36-inch- (914-mm-) long in size.
1. Wall-Covering Sample: From same production run to be used for the Work, with specified treatments applied. Mark top and face of fabric.
D. Product Schedule: For wall coverings. Use same designations indicated on Drawings.
NZAS 04-1042
WALL COVERINGS 097200 - 2
1.6 INFORMATIONAL SUBMITTALS
A. Qualification Data: For testing agency.
B. Product Test Reports: For each wall covering, for tests performed by a qualified testing agency.
1.7 CLOSEOUT SUBMITTALS
A. Maintenance Data: For wall coverings to include in maintenance manuals.
1.8 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Wall-Covering Materials: For each type, color, texture, and finish, full width by length to equal to percent of amount installed.
1.9 QUALITY ASSURANCE
A. Mockups: Build mockups to verify selections made under Sample submittals and to demonstrate aesthetic effects and to set quality standards for installation.
1. Build mockups for each type of wall covering on each substrate required. Comply with requirements in ASTM F1141 for appearance shading characteristics.
2. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing.
3. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
1.10 FIELD CONDITIONS
A. Environmental Limitations: Do not deliver or install wall coverings until spaces are enclosed and weathertight, wet work in spaces is complete and dry, work above ceilings is complete, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at levels intended for occupants after Project completion during the remainder of the construction period.
B. Lighting: Do not install wall covering until lighting that matches conditions intended for occupants after Project completion is provided on the surfaces to receive wall covering.
NZAS 04-1042
WALL COVERINGS 097200 - 3
C. Ventilation: Provide continuous ventilation during installation and for not less than the time recommended by wall-covering manufacturer for full drying or curing.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Test-Response Characteristics: As determined by testing identical wall coverings applied with identical adhesives to substrates according to test method indicated below by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Surface-Burning Characteristics: Comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
a. Flame-Spread Index: 25 or less.
b. Smoke-Developed Index: 450 or less.
2. Fire-Growth Contribution: No flashover and heat and smoke release according to
NFPA 265.
2.2 VINYL WALL COVERING (VWC)
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. DesignTex Inc.
2. Fidelity Wallcoverings Inc.
3. Gilford Inc.
4. Knoll, Inc.
5. Koroseal.
6. MDC.
7. U.S. Vinyl Wallcovering Corporation.
B. Description: Provide products in rolls from same production run and complying with the following:
1. FS CCC-W-408D and CFFA-W-101-D for Type III, Heavy-Duty products.
C. Total Weight: 33-36 ounces per linear yard, minium, excluding coatings.
D. Width: 36” minimum for wainscot installation.
E. Backing: Paper backed, manufacturer’s standard.
F. Repeat: Random.
NZAS 04-1042
WALL COVERINGS 097200 - 4
G. Stain-Resistant Coating: manufacturer’s standard.
H. Colors, Textures, and Patterns: As selected by Contracting Officer from manufacturer's full range.
2.3 ACCESSORIES
A. Adhesive: Mildew-resistant, nonstaining adhesive, for use with specific wall covering and substrate application indicated and as recommended in writing by wall-covering manufacturer.
B. Seam Tape: As recommended in writing by wall-covering manufacturer.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Installer present, for compliance with requirements for levelness, wall plumbness, maximum moisture content, and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Comply with manufacturer's written instructions for surface preparation.
B. Clean substrates of substances that could impair bond of wall covering, including dirt, oil, grease, mold, mildew, and incompatible primers.
C. Prepare substrates to achieve a smooth, dry, clean, structurally sound surface free of flaking, unsound coatings, cracks, and defects.
1. Moisture Content: Maximum of 5 percent on new plaster, concrete, and concrete masonry units when tested with an electronic moisture meter.
2. Plaster: Allow new plaster to cure. Neutralize areas of high alkalinity. Prime with primer recommended in writing by primer/sealer manufacturer and wall-covering manufacturer.
3. Metals: If not factory primed, clean and apply primer recommended in writing by primer/sealer manufacturer and wall-covering manufacturer.
4. Gypsum Board: Prime with primer as recommended in writing by primer/sealer manufacturer and wall-covering manufacturer.
5. Painted Surfaces: Treat areas susceptible to pigment bleeding.
NZAS 04-1042
WALL COVERINGS 097200 - 5
D. Check painted surfaces for pigment bleeding. Sand gloss, semigloss, and eggshell finish with fine sandpaper.
E. Remove hardware and hardware accessories, electrical plates and covers, light fixture trims, and similar items.
F. Acclimatize wall-covering materials by removing them from packaging in the installation areas not less than 24 hours before installation.
3.3 WALL-COVERING INSTALLATION
A. Comply with wall-covering manufacturers' written installation instructions applicable to products and applications indicated.
B. Cut wall-covering strips in roll number sequence. Change the roll numbers at partition breaks and corners.
C. Install strips in same order as cut from roll.
1. For solid-color, even-texture, or random-match wall coverings, reverse every other strip.
D. Install wall covering without lifted or curling edges and without visible shrinkage.
E. Match pattern 36” above the finish floor.
F. Install seams vertical and plumb at least 6 inches (150 mm) from outside corners and 3 inches (75 mm) from inside corners unless a change of pattern or color exists at corner.
Horizontal seams are not permitted.
G. Trim edges and seams for color uniformity, pattern match, and tight closure. Butt seams without overlaps or gaps between strips.
H. Fully bond wall covering to substrate. Remove air bubbles, wrinkles, blisters, and other defects.
3.4 CLEANING
A. Remove excess adhesive at seams, perimeter edges, and adjacent surfaces.
B. Use cleaning methods recommended in writing by wall-covering manufacturer.
C. Replace strips that cannot be cleaned.
D. Reinstall hardware and hardware accessories, electrical plates and covers, light fixture trims, and similar items.
NZAS 04-1042
WALL COVERINGS 097200 - 6
END OF SECTION 09 72 00