Attach_2_Specifications_Repair_Dorm_655_Part_4.pdf

PDF 4 MB Posted

Attached to
Malmstrom AFB Multiple Award Task Order Contract (MATOC) Federal contract opportunity
Solicitation number
FA462619RA014
Issued by
Department of the Air Force Global Strike Command

About this file

This document provides details for a multiple award task order contract (MATOC) solicitation issued by the Department of the Air Force Global Strike Command. The solicitation seeks proposals for various facility support services at Malmstrom Air Force Base. Offerors must submit proposals by May 15, 2019 for evaluation. The MATOC will make awards to multiple vendors who will then compete for individual task orders over a five year period. Task orders will cover requirements such as custodial services, pest control, waste management, and fire protection. The total value of services ordered under the MATOC is estimated at $50 million.

Attach 2 Initial Task Order Specifications Part 4

View the file

Other files for this federal contract opportunity

Other files attached to Malmstrom AFB Multiple Award Task Order Contract (MATOC), newest first.
File Type Posted
Q&A__5.docx DOCX document
Specifications_-_Table_of_contents_(Amended).pdf PDF
Q&A__4_Attachment_1_-_Cabinet_Bottom.pdf PDF
Q&A__4.pdf PDF
Q&A__4_Attachment_2_-_09_72_00_FL_-_Wall_Coverings.pdf PDF
Amendment_1_FA462619RA0140001.pdf PDF
Addendum__1.pdf PDF
Q&A__3_Attachment_1_-_Irrigation_mainline_as-builts.PDF PDF
Q&A__3.docx DOCX document
PreProposal_SiteVisit_Minutes.pdf PDF
Pre-Proposal_Conference_Sign-in_Roster.pdf PDF
Q&A__2.docx DOCX document
Q&A__2_Attachment_1_-_Asbestos_Survey.pdf PDF
Q&A__2_Attachment_3_-_Drawing_M1.4_Bid_Docs_-_MAFB_Dorm_655.pdf PDF
Q&A__2_Attachment_2_-_08_14_16_FL_-_FLUSH_WOOD_DOORS.pdf PDF
Attach_6_Drawing_M1.3.pdf PDF
Q&A__1.docx DOCX document
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_2.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_8.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_6.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_7.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_3.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_4.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_5.pdf PDF
Attach_2_Specifications_Repair_Dorm_655_Part_2.pdf PDF
Attach_6_Drawing_FULL_Set_Repair_Dorm_655_Part_1.0.pdf PDF
Attach_9_Subcontractor_Consent_Rev_1.doc DOC document
Attach_1_MATOC_Statement_of_Work_Rev2.doc DOC document
Attach_5__Schedule_of_Drawings_Repair_Dorm_655.doc DOC document
Attach_8_Past_Performance_Questionaire_Rev1.docx DOCX document
Attach_4_Full_Submittal_Schedule_Repair_Dorm_655.xls XLS spreadsheet
Attach_14_MATOC_Task_Order_Procedures_Rev4.docx DOCX document
Attach_10_On-Off_Ramp_Procedures_Rev1.docx DOCX document
Attach_7_Installation_Perimeter_Access_Control.pdf PDF
Attach_2_Specifications_Repair_Dorm_655_Part_1.pdf PDF
Attach_3_Bid_Schedule_Repair_Dorm_655.xlsx XLSX spreadsheet
Attach_2_Specifications_Repair_Dorm_655_Part_3.pdf PDF
Attach_11_SECTION_L_Rev1.docx DOCX document
Attach_12_SECTION_M_Revision_5.docx DOCX document
Solicitation_-_FA462619RA014.pdf PDF
Attach_13_Wage_Determinations.docx DOCX document
Show all 41

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

���������������������
������������������������������
��������������������������
������������������������������
��� ��������������!" �
�����������#�������� ����
����������������������
�����������$���������������
����������������������
����������
����#����&��'
����������������������������$
������(���$��������!)���
���������������������
����&��'����#�� ��!" �
������������,�'$-������/
����#����������!
���&��������������
���������!�����������
���#�����#�����������������
.��� ��������(��#�������$
���0�# �����$���������������
���������$���!/���������������
����������#���������������
����������1���&�2�����
������������������������
���������������������
�������������������
���#����������� ��������
,����'�����!
������������345�����������
����&�#��������������������

�46������������������7����

345���������������345
������0������������������!
%���������������������������
� �� �����������
����������������������!

8���������������������

���������9:����������������$
�������������������������$
��������������$���������
:����&��$���� �����������
�����������������!

;<==>?@AB?C>@?<DE?FG

HIJKLAMNOP?QPRSBD>?PREDD>?B>TUJHUI

VGWGXBYIKZRSBD>?PREDD>?B>TUJHUU[ZIKZ

VMB?P\]̂ZZ_Ì [̀ÌÎ aBF<D\]bZK_̀UH[Z̀bJc<Y\]bZK_̀UH[̂HJI E?AP=?PA\dddGM<==>?@AB?e>=PGFBf ghiijklmnk ojiphqhir ��s:�,�:� !

tuvwxyz{|w} ~�}�yz{|w} �w��}����u�

�����������������������������#���#���!�,���������������������� ��
.�����6/��.�����+/!"&�����������������������!�����������5&��

��������8�����

�������.
/������������������������
�������.+/������������
�������.5/,���������
�������"���������
��:��&��'�����$����3������
�������

��:��&��'�����$����3-�

������
�������

��:��&��'�����$����3� �����

��:��&��'�����$����3��� ����� ����� ���������������� �3�� ���� ��� "�� �������3 �0

�+*��656

�+*���3 �+*����6 �+*���3� �+*���33 �+*���3�

�+*���34 �+*���3� �+*����4 �+*���6�

��,5 ��3��� ��:"1- ��:"1-3 ��:"1-3!

��:"1- ��8���

�+0�03�

FA4626-19-R-A014

mossb Highlight mossb Highlight

����0+�� ����1+2�3%����(���� ������������2�3%����(���� 3����*4�+������.

5 � ���������(�������67�� �������8� -. *#+��3 9$$�':#�;&����� ���#<9'��� /'�����'�3 ���=��%���2 �3%����(����%���

���������5�����'����� ����>*&� 5+!

�&8 �&������������� &� �&7����

��?����������6 5����& ���������-���A����

���������B������'�����

��=�����A����� 5������<

�%������<C��

-��A� D �9�

-�A=�� /=5A' �

������8������������(���.�� ����6�������������� ��4#'�(����� ���%��"9'�������� ���3������(��������( �%������8��.��������� D ���.�E(������.

4$$$F������

������8����������

-����%�����?������%��6

�����5����<

A��� ��������

=%�����C���

GHIIJKLMNK

OJIPHQHIR

)B/' )/� < !"#$$

&�S!

6$$�>

$�8#>84$

FA4626-19-R-A014

������������������������
���������
������������������������
���� �������������������
��!������������"
�����
��������$%&'
(����������
���������(
����+������(
������
��!�����(��������0
��
��!��������
�������
����������������
����������

1� � ���2�����

�)�������������������
#��)��)������������������
�����������������

1� � ���2������

�����1�

���"1��)�����

�������!�#��)����������
��3���������������

1�� ���2���� 4����*��

�����1�

5�#���� ���� 1�

1 �������'������

1��)*�/$--����������� ����

������������
������������)����������
�����"+������
�#������
���������������������
�������������)�����!������(

��!����$", .$%&' 6����0#�!� ���������(� �������7����)��������

8��))����������������
����������()�������� ��

�� �#��)� �9��!����������

+)�����������������)�
���������(���������(����
��������(��)���#���
��������)���������������
#�)�����3��������

2��)�)����������� �������� �

�������������������
����������6�7"+)����������)����
�#����������(�
�����������(����
�����������������"
+)����:������������#��)�)�
���������������
�����
���������������
��!���������0�����
�������0����)������

;<==>?@AB?

C>=D<E<=F ��G�����

� ����5� ��

'��H*��0--%9

-%�$9��-

626-19-R-

A001FA4626-19-R-A001

�����0��������� �����"� 0����������������������������

1������1����2��0��%���

�3�1��*4 �1(3

��������������5677

������84

��5.,,���������������"����0��%�������������� ������ .97���0��%� ���"������� ���������#3� ������� ��� ��������0��%�����������������"�

����������������5677���� � �������0���������!��������!��������

3���������� ������84���"������ ������������&����������!'�������#�������84��� ��������!����������0������ �� ��������������!���������#��������������������!��������0���

�� ��5.,,������������������ ���������84���

@ABBCDEFGD

HCBIAJABK

�*L2� *2� # ��5.,, ��������"������������������1����

��5677(����� �

��M����,,7:

,7-.:-+, &'()*+,-&.+/0/+1,/(2-

/2&*,&(3.'

456789:6;<58=>?@=@A= B>C@DEF>GHIHGCG>DFJKG=HGLKDH>MM@C@KD>NCG>DFJKG=HG=>OPH>MMHMCK@DQGH>FHQ>I>Q@COR

S.+T12/+1U

VWHG>NNM@=HDF@KDX@CYMKKG 4:Z[\]̂ ?5_4[5];?:̀ [a]bca5_==?Za_==d4Z5==e

.2f/'(2S.2,1U gH=IHG>CAGHB>DEH 5̀hCK456hic6hCKa_h9e

;A=@M@COB>DEH jICK_̀kB;lDKDmQKDMHDF@DEn_6hic̀5h9e=>?@=@A=

-/o21U/2oU/2.+/'+*/,'1,/2o-

7KNC>EH 5a7b9DK=@D>Nl5ZRp7b9=>?@=@A= q>?@=@A=DA=PHGKJMHW@QHF ;r̀566lbA>Nrs9tFù _:CKC>Nl4_\MHCHQCKGFl4_\QKDCGKN[=KD@CKG=KMANHF q>?@=@A=N@DHNHDECY 6̀ap=c46l666JCRe458̂ vl̀R̀4==w

VIHG>C@KD=KMHF 8W>@N>PNH>FrCONH:c9N>FF8eKGrCONHac9N>FFxLgmC>II@DE@F>NNKXHMX@CYrCONHa c9N>FFxeQKDDHQC@KDFKDNO

2(,/0/+1,/(21&&U/12+.+/'+*/,(*,&*,+/'+*/,-y-,12)1')12).z&12-/(221+-

{89VACKACB>C@DEF 58=>?@=@A=IHG{89L5a7JANNX>WHGHQC@J@HMb9KACIACLIKXHGN@=@CHM

{89QAGGHDClrC>DM>GMX@CYVDH gKC>NKJ{89F|8A?@N@>GO}KXHG~5Rp8=>?@=@A= gG>DFJKG=HG c�J>A?@N@>GO}KXHGCKC>N~p66=8L{89IKXHG~58=>?@=A=e gKC>N{89QAGGHDC~Z8=>?@=@A=

{89QAGGHDClrC>DM>GMX@CYVIC@KD>N gKC>NKJ{89F|8A?@N@>GO}KXHG~\8=>?@=@A= gG>DFJKG=HG cKIC@KD>NCG>DFJKG=HG;r̀45789e

0*2+,/(2'.U1�(*,&*,+/'+*/,-y-,12)1')12).z&12-/(2

8NNBHN>OF 58n 6̀7b9GHF@F@C@WHLiKG=9QKDC>QCFLGH�A@GHFIKXHGADN@=@CHMFKAGQH

&(3.'(*,&*,+/'+*/,-

8A?@N@>GO}KXHGVACIACFcCXK �>QYKACIAC@FG>CHM>Cp66=8n5a7b9lJ@NCHGHMlGHEAN>CHMl>DMIKXHGN@=@CHML

KACIACFe =>?@=@A=G@IINHQKNC>EH~:66=7II

�1,,.'�/20('S1,/(2 x>CCHGO9Y>GEHG 9AGGHDCN@=@CHMJNK>CQY>GEHGJKGFH>NHMNH>M>Q@MP>CCHG@HF iNK>C9Y>GEH 5ZRp7b9

9Y>GE@DE9AGGHDC 5RZ8=>?@=@A=lDK>A?@N@>GONK>MFL4RZ8DK=@D>NX@CY6Rp8KDH>QY8A?@N@>GOKACIAC q>?@=@A=x>CCHGO9>I>Q@CO 458Y=>?@=@A=F@<H@DCHGD>NCKQ>P@DHCL p̀8Y=>?@=@A=F@<H>NNKXHMlGH�A@GHF=KMHNx8ggm98xs�?CHGD>Nx>CCHGO9>P@DHC

+(SS*2/+1,/(2&(',-

8{{c8DDADQ@>CKG}KGCe i@?HMP>AMG>CHna\66PIFLJKGAFHX@CY;r5\65�VB;r̀:aa8DDADQ@>CKGF cBHJHGCK@DM@W@MA>NIGKMAQC@DFC>NN>C@KD@DFCGAQC@KDFJKGQ>I>Q@C@HF>DMX@G@DEM@FC>DQHFeR

;rBr5\5m5 i@?HMP>AMG>CHn_:66PIFL:R64=c56JCRe=>?@=@A=M@FC>DQHLJKGAFHX@CY;87�b

7K@QH�W>QA>C@KDrOFCH=

9V{acb@>NHG[9@COqKMANH}KGCe i@?HMP>AMG>CHna\66PIFLJKGAFHX@CY;rbsb@E@C>N9K==AD@Q>CKGqKMANHKG;r9g�x

9@COqKMANH

�4crHGW@QHIKGCKGFHG@>NIG@DCHG i@?HMP>AMG>CHn_:66PIFL:=c56JCRe=>?@=@A=M@FC>DQHLJKGAFHX@CY

IKGCe rHGW@QH[}GKEG>==@DE}9cAF@DÊ @DMKXF_pKG_\eLKGJKGFHG@>N@DIACIG@DCHG

2.,3('�&(',-rC>DM>GM}GKCKQKNu46�=c̀ l̀666JCRL:R5=@NHFe=>?@=@A=M@FC>DQHPHCXHHDDKMHFl

=@D@=@A=5\8̂ vX@GHFc6R6\4==we

9Vq4l9Vq5c;>GG@DECKD;r

}>DHNCK}>DHNDHCXKG�l

BHMADM>DCb9sBe

Br5̀5}GKCKQKNAICK56=c::JCReCOI@Q>NNOJKGQKDDHQC@KDCKH?CHGD>N=KMH=

&1*)'1,. S1z/S/*S+1&1+/,12+. S1z/S/*S2.,3('�2().-

{HCXKG�̂ @G@DE}>G>=HCHGF _:66

c=>?@=@A=N@DHGHF@FC>DQH~:\6 a\66

KY=Fe 5a66

5pa

5pa

5pa

466Di

556Di aZ6Di

:\6Di

���������� ��
������������������������������
��������
������� �
����
���������
�������
�������
����������������
����
�����������������
����
�������
����
����
������
�����'�������

0+*1)2)*3 45678957: ; <4=>??

8@@ABCCDEFBGHAB8FDAI:JKLAJFMDKBF

NJOP<G4Q??RS

?RT>STU?

Harrington Signal Inc.

2519 4th Avenue, Moline, Illinois 61265

P.O. Box 590, Moline, Illinois 61266-0590

Phone: (800) 577-5758 Local: (309) 762-0731 Fax: (309) 762-8215

Internet: www.harringtonfire.com

HARRINGTON

FIRE ALARM

SIGNAL INC . HS-3644

LCD Annuncuator

Features

Meets NFPA 72 requirements

UL 864 and CSFM listed

80-character (4x20) backlit LCD

Six common system status lights:

Alarm (red), Supervisory (yellow), Trouble (yellow), Monitor

(yellow),mAC On (green), and Ground Fault (yellow)

Four system hotkeys for Ack, Silence, Reset, and Lamp

Test

Access-controlled Silence and Reset hotkeys require the keyswitch to be in the “enable” position

Four sets of scroll keys for Alarm, Supervisory, Trouble and Monitor

Up to eight HS-3644 annunciators can be connected to the HS-3100/ 3200 or HS-3030 Fire Alarm Control Panel

User-programmable supervision addresses (eight options)

Suitable for flush mounting into a standard five gang device box or surface mounting with optional back box

Description The HS-3644 LCD Annunciator allows you to monitor and control compatible Fire Alarm Control Panels from anywhere within your facility. Up to eight HS-

3644's, each set to a unique user-programmable

ID, can be connected to each FACP. A single HS-

3644 can be as far as 9000 feet from the control panel.

The HS-3644 display follows the display of the FACP to which it is connected allowing immediate action from wherever these units are installed. The on-board system hotkeys provide quick access to

Lamp Test and Acknowledge functions, but require the key switch to be used when accessing Silence or Reset functions.

In addition to the textual LCD, the HS-3644 incorporates six system status LEDs that offer a quick overview of system status. Monitored conditions include: Alarm, Supervisory, Trouble, Monitor, AC On, and Ground Fault.

The HS-3644 connects to a HS-3100/3200 or HS-

3030 using the FACPs annunciator port.

Connection between the HS-3644 and the HS-3030 requires the use of the HS-3109-3 communications board in the HS-3030 in order to drive Port 3.

Ordering Information

Doc#HFS-0019.1

09/11/08

Model Number Part Number Description

HS-3644R

HS-3644BB

LCD Annunciator, flush mount, Red

Flush mount back box for HS-3644R, Red

222-0064

222-0070

FA4626-19-R-A001FA4626-19-R-

A001 mossb Highlight

HS-3644

mossb Highlight

HS-3644R

HS-3644BB

LCD Annunciator, flush mount, Red Flush mount back box for HS-3644R, Red mossb Highlight 222-0064 mossb Highlight 222-0070 hove Highlight

Engineering specificaion Electrical Specifications

Voltage 16 28 VDC, power limited

Max. input voltage ripple 3.0VP-P

Standby current draw 30 mA

Maximum/alarm current 70 mA

Environmental Specifications

Operating Temperatures 32F - 120F / 0C - 49C

Humidity 85% RH non-condensing (max.)

Physical Dimensions

HS-3644 (trim plate) 4.5” (H) x 10” (W)

10.2cm (H) x 25.4cm (W)

HS-3644-SM 4.5” (H) x 10” (W) x 2 1/2 “ (H)

10.2cm (H) x 25.4cm (W) x 6.4cm (H)

Connections

Maximum Distance 9000 ft. (2700m) 12 AWG

Communication/Power Wire 12 to 22 AWG non-shielded twisted pair (two twisted pair required)

Note: Harrington recommends that the HS-3644 be powered from the fire panel. If an external power supply is used, the following conditions must be met:

The power supply must be regulated, filtered, power limited, and UL listed for Fire applications.

To ensure proper communications, the negative of the power supply must be connected to the Aux Power negative of the fire panel.

The external power supply must be mounted no further than 10ft (3m) from the FACP.

To connect the HS-3644 annunciator HS-3030 FACP, a communications board must be in the HS-3030 (Model

# HS-3109-3)

HARRINGTON

FIRE ALARM

SIGNAL INC . HS-3644

LCD Annuncuator

Doc#HFS-0019.1

09/11/08

FA4626-19-

R-A014 hove Highlight hove Highlight hove Highlight

HARRINGTON

FIRE ALARM

SIGNAL INC .

NOTICE: The information contained in this document is intended only as a summary and is subject to change without notice. The products described have specific instructional/installation documentation, which covers various technical, approval, code, limitation and liability information. Copies of this documentation along with any general prod-uct warning and limitation documents, which also contain important information, are provided with the product and are also available from Harrington Signal Inc. The information con-tained in all of these documents should be considered before specifying or using the products. Any example applications shown are subject to the most current enforced local/nation-al codes, standards, approvals, certifications, and/or the authority having jurisdiction. All of these resources, as well as t he specific manufacturer of any shown or mentioned related equipment, should be consulted prior to any implementation. For further information or assistance concerning the products, contact Harrington Signal Inc. Harrington Signal Inc.

reserves the right to change any and all documentation without notice. Quality manufactured for Harrington Signal Inc. by Secutron.

HS-3644

LCD Annuncuator

(Powered by external PS)

(Powered by FACP)

HS3644 Wiring Diagram

HS3644 wiring diagram

HS3030 wiring diagram

HS3030 wiring

Doc#HFS-0019.1

09/11/08 hove Rectangle

Arrow

DF-60734:A8 • 10/23/2015 — Page 1 of 6

ECC-50/100(E)

Emergency Command Center

Emergency Communications

DF-60734:A8 • C-200

General Firelite’s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications, or both. The Primary Operating Con-soles (POCs)deliver 50 or 100 watts of audio power for distri-bution to up to eight speaker circuits (i.e. zones). The ECC-50/ 100(E) comes standard with a single speaker circuit and a built-in 25Vrms, 50 watt amplifier. A secondary 50 watt ampli-fier (ECC-50W-25/70V) can be added for single speaker circuit backup or to increase system capacity to two speaker circuits and an additional 50 watts of audio power. An optional ECC- CE6 module added to the ECC-50/100(E) will upgrade the system to a maximum of eight speaker circuit outputs. All speaker output circuits can be wired in either Style Y (Class B) or Style Z (Class A) configuration. The ECC-50/100(E) has fourteen field programmable messages (up to 60 seconds each), built-in field configurable pre- and post-announce tone generators and a fully supervised Notification Appliance Cir-cuit (NAC) with 2.0 amps of synchronized NAC power. The ECC-50/100(E) includes three built-in Form-C relay contacts, (AC power, trouble and MNS active) a NAC follower input for triggering the on board NAC circuit and 500mA special appli-cation power. A built-in power supply with switch mode tech-nology delivers operational power to the panel and an onboard battery charger supports charging up to 26AH batteries (ECC cabinet holds up to 18AH batteries).

For fire protection applications, the ECC-50/100(E) is an adjunct (slave) to any UL listed FACP, providing reverse polar-ity or contact closure; can be used as a stand-alone unit for non-fire applications. For seamless integration between fire and mass notification, the ECC-50/100(E) can be directly acti-vated via serial communication between the MS-9600(UD)LS or MS-9200UDLS. Activation of the ECC-50/100(E) via other FACPs uses the eight on board Command Input Circuits (CMDs). Two of the eight CMD circuits (CMD 1 & CMD 2) can be individually field programmed for activation by an FACP Notification Appliance Circuit reverse polarity and all eight can be activated by a contact closure. In addition, the ECC-50/ 100(E) can be activated from a building's Private Branch Exchange (PBX) with the integral night ring feature.

All ECC-50/100(E) programming is done by using a simple, built-in programming utility accessed from any laptop. For added flexibility, the ECC-50/100(E) supports both 25Vrms and 70.7Vrms speaker output operation. By adding a 70V transformer conversion module (ECC-XRM-70V) or an addi-tional 70.7 volt secondary amplifier (ECC-50W-25/70V) the system supports 70.7 volt speaker devices.

The ECC-50/100(E) can expand in order to accommodate larger or more complex installations. To add more control and increase system capacity, any combination of up to eight external remote consoles (including the ECC-LOC, ECC-RPU, and ECC-RM) and up to eight distributed audio amplifiers (including the ECC-50DA(E), ECC-50BDA and ECC-125- DA(E) can be connected on the external data bus and audio riser data bus to create a fully integrated command center. A fully loaded system supports up to 1100 watts of total audio power and up to 24 speaker circuit outputs.

TYPICAL APPLICATIONS

Features

• UL Listed to UL 2572 Communication (Control Units Mass

Notification Systems) and UL 864 (emergency voice evacu-ation for fire)

• Modular design for system flexibility and easy expansion

• Removable terminal blocks for ease of servicing and mod-ule replacement

• 50 watts of 25V audio power (expandable to 100 watts)

RMS

• 2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for System Sensor, Wheelock or Gen-tex protocols

• Optional 70.7VRMS conversion transformer available for the primary amplifier. (Note that speaker wiring continues to be supervised in standby, alarm and when background music is playing with this optional transformer installed)

• Eight Command Input Circuits to activate messages 1 to 8:

– CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or contact closures

– CMD3-CMD8 are activated by contact closures

• Speaker Circuits

– Single Style Y (Class B) or Style Z (Class A) speaker Cir-cuit

• Schools • Healthcare Facilities • Factories

• Theaters • Military facilities • Restaurants

• Auditoriums • Places of Worship • Office Buildings

• Dormitories mossb Highlight 50 watts of 25V audio power (expandable to 100 watts)

RMS

mossb Highlight 2 amp Notification Appliance Circuit (NAC) output mossb Highlight Optional 70.7VRMS conversion transformer available for the primary amplifier mossb Highlight CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or contact closures mossb Highlight CMD3-CMD8 are activated by contact closures mossb

Single Style Y (Class B) or Style Z (Class A) speaker Circuit

Page 2 of 6 — DF-60734:A8 • 10/23/2015

– Two Style Y (Class B) or Style Z (Class A) speaker cir-cuits (with optional ECC-50W-25/70V Audio Amplifier installed)

– Eight Style Y (Class B) or Style Z (Class A) speaker cir-cuits (with optional ECC-50W-25/70V and ECC-CE6 installed)

• 520Hz square wave tones available, which can be uploaded to the ECC-50/100 to meet NFPA Low Frequency requirements (Refer to the Device Compatibility Document 15384 for listed compatible speakers.)

• ECC-50/100(E) can be controlled by an FACP via the ANN/ ACS (EIA-485) link. Compatible FACPs include the MS- 9600(UD)LS and MS-9200UDLS

• Certified for seismic applications when used with the appro-priate seismic mounting kit

• Integral supervised microphone

• Microphone time-out feature which reverts back to prere-corded message if emergency page exceeds the pro-grammed time

• 14 recorded messages

• Field-selectable message and custom message recording capability using the local microphone, a USB port, or an external audio input

• External Audio Input can be used for background music

• Up to 60 second message duration for all messages

• Integral tone generators field selectable for multiple tone types

• Powered by integral AC power supply or batteries during AC fail

• Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss

• Piezo sounder for local trouble

• 100 event history log

• Three Form-C relays:

– AC Power Loss Relay - TB1

– System Trouble Relay - TB2

– MNS Active - TB3

• 500mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable FACPs and End-of-Line power supervision relays

• System Status LEDs (Refer to “Controls and Indicators” in product manual LS10001-000FL-E.)

• Integral Dress Panel

• Optional TR-CE semi-flush trim ring

• Any combination of up to eight (8) external remote con-soles:

– Optional ECC-RM Remote Microphone (includes cabinet) See DF-60760.

– Optional ECC-RPU Remote Page Unit (includes cabinet) See DF-60761.

– Optional ECC-LOC Local operator console (includes cab-inet) See DF-60762.

• Any combination of up to eight (8) distributed audio amplifi-ers:

• Optional ECC-50DA(E) distributed amplifier, 50 watts. See

DF-60763.

• Optional ECC-125DA(E) distributed amplifier, 125 watts.

See DF-60763.

• Optional ECC-50BDA distributed amplifier with backup, 100 watts.See DF-60760.

Optional Internal Expansion Modules ECC-CE6: Circuit Expander Module provides connections for up to six Style Z (Class A) or Style Y (Class B) speaker cir-cuits. Circuits are configured through the web-based program-ming utility.

ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier.

ECC-50W-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier.

ECC-XRM-70V: 70V Transformer Conversion Module. Con-verts the ECC-50/100(E) primary amplifier to a 70V output.

This transformer mounts directly to the ECC-50/100(E) main control board by two metal brackets.

Control and Indicators

PUSH BUTTON CONTROLS

• All Call • Message Select 1-14

• MNS Control • Diagnostic Select

• System Control • Trouble Silence

• Speaker Select 1-24 • Console Lamp Test mossb Highlight 520Hz square wave tones available, which can be uploaded to the ECC-50/100 mossb Highlight 14 recorded messages mossb Highlight 500mA (0.5A) Special Application mossb Highlight Any combination of up to eight (8) external remote consoles:

mossb Highlight Optional ECC-LOC Local operator console (includes cabinet) See DF-60762.

mossb Highlight Any combination of up to eight (8) distributed audio amplifiers:

mossb Highlight Optional ECC-50DA(E) distributed amplifier, 50 watts. See

DF-60763.

DF-60734:A8 • 10/23/2015 — Page 3 of 6 horns/strobes

Speaker Circuits

TB20 & TB21

NAC Circuit

TB19

Internal options

ECC-CE6 circuit expander

ECC50W-25/70V

optional amplifier

ECC-FFT firefighter telephone remote consoles

ECC-LOC

local operator console

ECC-RPU

remote paging unit

ECC-RM

remote microphone

TB4

TB12

TB22

distributed audio external battery charger - J7

ECC-50DA 50W

remote amplifier

ECC-125DA 125W

remote amplifier

CHG-120F charger CHG-75 charger

ECC-50/100(E) Emergency Command Center (Possible Configurations)

ECC-50BDA 50W

remote amplifier

Page 4 of 6 — DF-60734:A8 • 10/23/2015

LED Status Indicators (visible with door closed)

LED Indicators (visible with door and dress panel open)

• Speaker Volume Control Fault (yellow).

• Option Card Fault (yellow).

• Amplifier Over Current Fault (yellow).

Product Line Information ECC-50/100: (Primary Operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacuation system, integral microphone, built in tone generator and 14 recordable messages.

ECC-50/100E: Export version (Primary Operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacua-tion system, integral microphone, built in tone generator and 14 recordable messages. (240 VAC, 50Hz).

ECC-CE6: Speaker Circuit/Zone Expander Module.

ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier.

ECC-50W-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier.

ECC-XRM-70V: 70V Transformer Conversion Module. Con-verts the ECC-50/100(E) primary amplifier to a 70V output.

This transformer mounts directly to the ECC-50/100(E) main control board by two metal brackets.

ECC-LOC: Local Operator Console (Complete user interface), Please refer to the data sheet DF-60762 for more information.

ECC-RPU: Remote Page Unit Hand held microphone, 14 message buttons. Please refer to the data sheet DF-60761 for more information.

ECC-RM: Remote Microphone only. Please refer to the data sheet DF-60760 for more information.

ECC-50DA: Distributed (Remote) Audio Amplifier, 50 watts.

Please refer to the data sheet DF-60763 for more information.

ECC-50DAE: Export version. Distributed (Remote) Audio Amplifier, 50 watts. (240 VAC, 50Hz). Please refer to the data sheet DF-60763 for more information.

ECC-125DA: Distributed (Remote) Audio Amplifier, 125 watts.

Please refer to the data sheet DF-60763 for more information.

ECC-125DAE: Export version. Distributed (Remote) Audio Amplifier, 125 watts. (240 VAC, 50Hz). Please refer to the data sheet DF-60763 for more information.

ECC-50BDA: Distributed (Remote) Audio Amplifier with back up, 50 watts/100 watts at 25Vrms or 70Vrms. Please refer to the data sheet DF-60763 for more information.

ECC-50WBU: Expander card for ECC-50BDA remote amplifier for 100 watt primary / 50 watt back up operation.Please refer to the data sheet DF-60763 for more information.

ECC-CE4: Distributed Audio Speaker Circuit/Zone expander module.

ECC-FFT: Fire Fighter Telephone System. Please refer to the data sheet DF-60765 for more information.

ECC-RTZM: Remote Telephone Zone Module. Allows for secure access to the ECC via cell phone or remote telephone means; not UL listed.Please refer to the data sheet DF-60785 for more information.

SEISKIT-COMMENC: Seismic kit for the ECC-50/100.

Includes battery bracket for two 12 AH or 18 AH batteries.

FPJ-F: Remote Phone Jack.

FHS-F: Fire Fighters Remote Handset.

FHSC-RF: Fire Fighters Handset Cabinet Recessed.

FHSC-SF: Fire Fighters Handset Cabinet Surface Mount

MMF-301: Addressable Mini-Monitor Module.

I300: SLC Line Isolation Module.

TR-CE: Optional Trim Ring.

THUMBLTCH: Optional Thumb Latch. (Non UL-Listed).

CHG-75: 25 to 75 ampere-hours (AH) External Battery Charger.

CHG-120F: 25-120 ampere-hours (AH) External Battery Charger.

ECC-MICROPHONE: Replacement Microphone only.

BAT-1270: Battery,12 volt,7.0 AH (Two required).

BAT-12120: Battery,12 volt,12.0 AH (Two required).

BAT-12180: Battery,12 volt, 18.0 AH (Two required).

Wiring Requirements See product manual, part number LS10001-000FL-E for detailed wiring requirements.

Total System Capacity: (ECC-50/100(E) only)

• Total Built-in Audio Power: 50 Watts.

• Total Expandable Audio Power: 100 Watts.

• Total Built-in Speaker Circuits: 2.

• Total Expandable Speaker Circuits: 8.

• Audio Message Max Time Duration: 60 seconds.

• External Audio Input: 1.

Total System Capacity: (Fully Loaded System)

• Total Distributed Audio Power: 1100 Watts.

• Total Speaker Circuits Per System: 24.

• Total Remote Consoles Supported: 8.

• Total Distributed Audio Amplifiers Supported: 8.

Fire System Active (green) LOC/RPU/RM 1-8 Active (green)

MNS Control (green) Main Console Fault (yellow)

System Control (green) AC Power (green)

System in Use (green) Ground Fault (yellow)

Speaker Zone 1-24 Active (green)

Charger Fault (yellow)

Speaker Zone 1-24 Fault (yellow)

Battery Fault (yellow)

OK to Page (green) Data Bus Fault (yellow)

Microphone Trouble (yellow) NAC Fault (yellow)

Message 1-8 Active (red) NAC Active (green)

Message 1-8 Fault (yellow) System Trouble (yellow)

Remote Amplifier 1-8 Fault (yellow)

Audio Riser Fault (yellow)

LOC/RPU/RM 1-8 Fault (yellow)

DF-60734:A8 • 10/23/2015 — Page 5 of 6

Electrical Specifications

PRIMARY (AC) POWER (TB15)

ECC-50/100: 120 VAC, 60 Hz, 3.5 amps.

ECC-50/100E: 240 VAC, 50 Hz, 2.0 amps.

Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation.

SECONDARY POWER (BATTERY) CHARGING CIR-

CUIT (J7)

• Supports lead-acid batteries only.

• Float charge voltage at 27.3V

• Maximum charge current: 1.0 Amp

• Maximum battery charge capability: 2.8 Amps, 26AH (ECC cabinet holds max. 18AH battery).

• Minimum Battery size:12 Amp Hour.

AC LOSS RELAY CONTACT RATING (TB3)

• 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).

FORM C - TROUBLE RELAY CONTACT RATING (TB2)

• 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive).

MNS ACTIVE RELAY CONTACT RATING (TB1)

• 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).

NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT

RATING (TB19)

• One (1) Style Y (Class B) or Style Z (Class A) circuit.

• Power-limited circuitry, (Class 2) supervised.

• Nominal operating voltage: 24 VDC.

• Maximum signaling current for special application power:

2.0A.

• Maximum signaling current for regulated power: 200mA.

• Maximum wiring impedance: 1Ω.

• Current limit: fuse-less, electronic, power-limited.

• End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required for Style Y (Class B) operation.

Refer to the Device Compatibility Document 15384 for listed compatible devices.

NAC FOLLOWER OUTPUT REMOTE SYNC (TB18)

• Connections for FACP NAC synchronization trigger signal.

• Output terminals: pass-through to other system compo-nents.

• Trigger input voltage: 9 to 32 VDC, 24 VDC rated.

• Input current draw in Alarm condition: 10 mA at rated volt-age.

SPECIAL APPLICATION POWER (AUX. POWER)

(TB17)

• 500 mA @ 24 VDC.

• Used for powering addressable modules and associated End-of-Line power supervision relays.

Power-limited circuitry. Refer to the Device Compatibility Doc-ument 15384 for a list of compatible devices.

SPEAKER VOLUME CONTROL OVERRIDE (TB23)

• Style Y (Class B) or Style Z (Class A) circuit.

• Special application power.

• Power-limited circuitry, supervised.

• Nominal operating voltage: 24 VDC.

• Maximum signaling current: 0.25 amps.

• Current limit: fuse-less, electronic, power-limited.

• End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required for Style Y (Class B) operation.

Speaker Circuits

• Primary Speaker Circuit (TB20)

• Secondary Speaker Circuit (TB21) (with optional amplifier only).

– Circuit can be wired Style Y (Class B) or Style Z (Class A).

– Power-limited circuitry.

– Normal Operating Voltage: 25 VRMS @ 2 amps max and maximum Load Impedance of 12.5Ω (70.7 VRMS @ 700 mA max. with maximum load Impedance of 100Ω opera-tion possible by plugging optional ECC-XRM-70V conver-sion transformer into J12 of the main control board).

– Output Power: 50 watts (10 watts when background music is employed).

– Frequency Range: 400Hz - 4,000Hz.

– Maximum total capacitance for each speaker circuit: 250 µF.

– End-of-Line Resistor required for Style Y circuit: 15 KΩ, 1 watt (P/N: ELR-15K).

Command Input Circuits (alarm polari-ties shown) CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Ter-minals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices down stream.

CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Ter-minals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices downstream.

CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for con-tact closure only.

CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for con-tact closure only.

CMD5 - TB7 Terminals 1(+) & 2(-) are input terminals for con-tact closure only.

CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for con-tact closure only.

CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for con-tact closure only.

CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for con-tact closure only.

• Power-limited and supervised circuitry.

• Normal Operating Voltage Range: 10.5 VDC - 29 VDC;

(Maximum Voltage: 29 VDC).

• NAC Reverse Polarity Current (requires End-of-Line Resis-tor from NAC): 1.6 mA maximum.

• Contact Closure Operation Current (requires 4.7KΩ, ½ watt End-of-Line Resistor P/N 27072): 6.6 mA maximum.

• Maximum Wiring Impedance CMD1 - CMD8 (Contact Clo-sure Operation): 200Ω.

NOTE: When the system is programmed for Mass Notification, CMD1and CMD2 will be programmed for Reverse Polarity only.

See manual P/N LS10001-000FL-E for more details.

MAXIMUM INPUT IMPEDANCE:

• CMD1 & CMD2 (Reverse Polarity Operation): 20KΩ.

• CMD1 - CMD8 (Contact Closure Operation): 4.75KΩ.

NIGHT RING INPUT - TB16, TERMINALS 1 (+) & 2 (-)

• Contact closure input.

• Isolated, non-supervised.

• Operation current: 3.8 mA, maximum.

Page 6 of 6 — DF-60734:A8 • 10/23/2015

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.

www.firelite.com

Fire-Lite® Alarms is a registered trademark of Honeywell International Inc.

©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Assembled in the USA

• Maximum wiring impedance: 30KΩ.

• Minimum isolation withstand voltage: 1500 VRMS.

EXTERNAL OPERATOR INTERFACE POWER OUTPUT

(TB24)

• Non-resettable power for external operator interface com-ponents.

• Power-limited circuitry, non-supervised.

• Nominal operating voltage: 24 VDC.

• Maximum output current: 0.80 amps.

• Current limit: fuse-less, electronic, power-limited circuit.

EXTERNAL DATA BUS (EIA-485) (TB12)

• Data connections for external operator interface components.

• Redundant transceiver circuitry for Class A operability.

• Power-limited circuitry, supervised.

• Maximum wiring impedance: 13.2Ω

FACP DATA BUS (EIA-485) (TB13)

• Dedicated connection to FACP serial bus.

• Output terminals: pass-through to other system components.

• Isolated, supervised.

• Minimum isolation withstand voltage: 1500 VRMS.

• Maximum wiring impedance: 40Ω (ANN-BUS), 26Ω (ACS-BUS).

• External Audio Riser (TB22).

• Style Y (Class B) or Style Z (Class A) audio connections to external operator interface components.

• Power-limited circuitry, supervised.

• Audio signal level: 3.85 V, maximum.

• Frequency range: 400 Hz - 4 KHz RMS.

• Frequency range (ECC-50/125DA): 800Hz - 2KHz RMS.

ELECTRICAL SPECIFICATIONS DISPLAY BOARD

EXTERNAL AUDIO INPUT (TB5)

• Input Impedance: 8.5KΩ nominal @1KHz

• Input Voltage: 700 mV rms maximum

• Input Current: 0.1 mA maximum @ 700 mV

NOTE: Some laptops/personal computers only provide an audio output for headphones. It may be necessary to adjust the head-phone output level for proper recording of voice messages.

ECC-CE6 Circuit Expander Module Specifications

• Power-limited circuitry.

• Up to six (6) circuits on the ECC-CE6 can be wired as Style Y (Class B) or Style Z (Class A).

• Normal Operating Voltage for Speaker Circuits: 25 VRMS @ 2.0 amps max. (Maximum Load Impedance of 12.5Ω).

• 70.0 VRMS @ 700 mA max. with maximum Load Imped-ance of 100Ω operation possible for the primary circuit by plugging in an optional ECC-XRM-70V conversion trans-former into J12 of the main control board. The same opera-tion is possible for the optional 50W amplifier by selecting the ECC-50W-70V model.

• Speaker circuit wiring is supervised during standby, back-ground music, and alarm.

• Output Power: 50 watts total; Frequency Range: 400Hz - 4,000Hz.

• Maximum total capacitance: 250 µF. (Note that the total capacitance for the speaker outputs must not exceed the maximum of 250 µF).

• End-of-Line Resistor required for Style Y (Class B) speaker circuit: 15 KΩ, 1 watt (P/N: ELR-15K) TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP provides programmed speaker control.

Cabinet Specifications

• Backbox: 19.0"(48.26 cm) high x 16.65"(42.29 cm) wide x

5.20"(13.23 cm) deep.

• Door: 19.26” (48.92 cm) high x 16.82”(42.73 cm) wide x 0.12”(0.30 cm) deep.

• Trim Ring (TR-CE): 22.00” (55.88 cm) high x 19.65” (49.91

cm) wide.

Shipping Specifications Base Unit Weight: 27.85 lbs (12.63 kg).

Temperature and Humidity ranges This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com-ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.

Agency Listings and Approvals The listings and approvals below apply to the basic ECC-50/ 100(E) control panel. In some cases, certain modules may not be listed by certain approval agencies or listing may be in pro-cess. Consult factory for latest listing status.

• UL/ULC Listed S2424.

• Compliant with UFC 4-021-01.

• CSFM: 7300-0075:0226.

• NYC Fire Dept.Certificate of Approval: #6152.

• FM Approved.

Standards and Codes The ECC-50/100(E) complies with the following UL Standards, NFPA 72, International Building Codes, and California Building Codes.

• UL 864.

• UL 2572.

• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seis-mic).

• CBC 2007 (Seismic)

'(()('*+(,-./,0+'123456-+ 7-85/.0+94:03;;30,84+<8./=640

����������������>? ����@A@�����������!�

B'(()('*+94:03;;30,84+ 94:0-/.0,84:

����>����>�����C�C�D��E���� E� C����F��&��G������� C� �����G�� �� ���>�����@����>&��H�� G���&&���� ��� ��%�����>����>��&�E� C��� �� ���>�����@����&����

������I����%��J����������>�����@����K��E���
L��������������>�����&���������&����%

MNO'PQRSTUVVUTWXRYURZY[W\WR]YX̂YT_WSYZ̀aWb̀YcdSTYèY ZXR̀YWRYUbbX\ZURb̀Y[WT_YfghiYjkYURZYVXbUVYX\ZWRURb̀Sl mn83-5+o3p8/0+q+r8/40,4s �% �E������� ��F�$���������C �I ����C%

�% J�&�t�����C��$�����$����
��&F���C�
E��C����

��CF��G�

�I������&�����F�����������I������C�C��$�%��
������&����H����@!u�C�������$����I��EC�����&�E��
���>����>�%������

�% v�C��� ���>����>���� ������w������w�CGC �&��C� ��C��I���I���$% mxB++r8/40,4s+08+3+myz+{p:06= �% J�&�t�� ���C��$C����&� ���>�����@����&����

������I����������F��

��$������C�t���|�}�CEFF�����
���@!~����H�&�����&����C������C��C�C��$�%��
�% ��H�����>����>���t������C������C���C���������
C�F��%��v�C��������������������>����>������
���>�����@����&����
������I�����I���H�
����E�����
��I������G�F��C%

E��� ���>����>�� �� ���C ������C�$� ����H� �|!}� L�����C ��$C���&�t���F��t��EC�G%

�% J�E�� �����CF��G��I���E����� ���>����>�%����

mxm++r8/40,4s+08+3+��z+{p:06=

v�����>����>��$����I��EC����������w�CGC�&����&EC�I��
&�E����������E�
����$������>���#JK���w�

����C���&��%

�% J�&�t�� ���C��$C����&� ���>�����@����&����

������I�����������F�
��$���C�t���|�}�����
C������C����t��|�}����@!u�C������C�|CEFF�����$������
>����>�}�����$��|�}���A@��~����H�C������C�
|CEFF�����$������C���&���I��
��}��C�C��$�%�

E������C���&���I�

��������
��CC�C�EC��H�$��
|�}�L!������FC��EC%��v�C����EC��H������@��u�C�
��%

Sb\̀[ [W\̀YbVUc�

�,s/-6+B++�6=8�,4s+0�6+{.-6���,-6+(;3=2

�̀ al

��������h�i

��k cXdRTWR]Y_XV̀S

�,s/-6+m++r8/40,4s+0�6+'(()('* cXdRTWR]Y_XV̀S ���YTXYh�Y bXRR̀bTWXR

( %)*+,�-./�#00!0#1�23/4�-./�5-6,72885�*,5-6))/7�*,� 5-/9��(��:,5-6))�./67/4�;<��2,�-./�#00!0#1�*,-2����2,� -./�#00!=������>6*,�?2,-42)�@2647A�@/*,+�?64/8B)�,2-� -2�@/,7�6,C�9*,5(

&( �/?B4/�-./�#00!0#1�-2�-./�5-6,72885�D*-.�-./�/*+.-�

EFG�H&!&��5?4/D5�94/3*2B5)C�4/>23/7(��I./�@2--2>�

/,7�28�-./�#00!0#1�D*))�>2B,-�2,�-./�-46,5824>/4� @46?J/-(���//�"*+B4/&(�

=( K2B-/�-./�7*59)6C�?6@)/�B,7/4�-./�#00!0#1(����

LMNONPQ

�9/6J/45�?6,�@/�D*4/7�*,�/*-./4�0)655�%�E�-C)/�RG�24�

0)655S�E�-C)/�TG(��0*4?B*-5�64/�?2,8*+B4/7�-.42B+.�-./�

D/@!@65/7�942+46>>*,+�B-*)*-C(��U5/�28�-./�5/?2,764C�

?*4?B*-5�4/VB*4/5�-./�29-*2,6)�5/?2,764C�6>9)*8*/4�

#00!=�W!�=�X�Y(��%))�?*4?B*-5�64/�5B9/43*5/7�6,7�92D/4!

)*>*-/7(��W./,�6))�D*4*,+�*5�?2>9)/-/A�4/5-24/�%0�92D/4� 6,7�4/?2,,/?-�@6--/4*/5(���//�"*+B4/=(�

ZZ������������

_̀ ab cddefd\egdh ijklmnnZoiàZp̂qZ]êrstZZ klmjuvook wNQxOyzLzz{P|}~��NPQz}�yz�O~P|��O�yOz�O~��y} ijklmnnZl�vZp�qZ]e�r]�tZ klmjuvook l�vZp�qZ�se��Z�̀�kZj�lk

��m��̀l

��mkkik wNQxOyz�zz��xP}NPQz}�yz�������z�z�O~P|��O�yO

�v�jlij�Z�vǹk ov�Z��e��Zk��̀�k ì��lZpsqZlvlmn

�v�jlij�Z�vǹk ov�Z��e��Zk��̀�k

¡]ZlvZg]Z �vjj̀�livj wNQxOyz¢zz£¤y~�yOzMNONPQ

¥l¦ǹZ§ZpdnmkkZhqZdi���il c̈_Z�̀©�i�̀uZov�Z ¥l¦ǹZªZeZdnmkkZ\Zvjn¦ ]̂«¬Z]Z�mll¬ gr®c̈_e]̂«

¥�ìnu gv�̀ �eni�il̀uZpdnmkkZ�q¬Z ¥��̀�aik̀u

DF-60763:B • 8/25/14 — Page 1 of 4

ECC-50DA(E)

ECC-125DA(E), ECC-50BDA

Distributed Audio Amplifiers

Distributed Audio Amplifiers

DF-60763:B

General The ECC-50DA(E), ECC-50BDA, and ECC-125DA(E) are intelligent 50 watt, 100 watt, and 125 watt amplifiers that are used with the ECC-50/100(E) Emergency Command Center.

These distributed audio amplifiers amplify an audio message for distribution throughout a facility when additional audio power is required. They are designed as self-contained units and can be conveniently installed near an area of protection to reduce wiring demands for speaker circuit outputs.

Each ECC-50DA(E) is capable of producing 50 watts of total power and includes four built-in, fully supervised speaker cir-cuits/zones. The ECC125DA(E) is capable of producing 125 watts of total power with four built-in, fully supervised speaker circuits/zones. Both amplifiers are expandable to include eight speaker circuits when an optional ECC-CE4 module is installed.

For installations that require survivability, the ECC-50BDA pro-vides 50 watts or 100 watts of primary power along with 50 watts of backup power and comes standard with eight built-in, fully supervised speaker circuits/zones.

Any combination of up to eight, ECC-50DA(E)s, ECC-50BDAs, or ECC-125DA(E)s can be connected to the ECC-50/100(E) to provide a total output of 1100 watts of audio power and up to 24 speaker circuit outputs. These distributed audio amplifiers are wired to the data bus and the Audio-Riser bus of the ECC- 50/100(E) primary operating console. They have their own power supplies with built-in battery charger and are both fully supervised by the ECC-50/100(E) for any trouble conditions.

Features

• The ECC-50DA(E) and ECC-125DA(E) units come stan-dard with four onboard fully supervised speaker circuit zones, and are expandable to eight circuits when an optional ECC-CE4 module is added.

• The ECC-50BDA includes eight onboard fully supervised speaker circuits/zones.

• Any combination of up to eight ECC-50DA(E)s, ECC- 50BDAs, or ECC-125DA(E)s per system can be used with the ECC-50/100(E) for a total of 1100 watts of audio power and 24 speaker circuit outputs.

• The ECC-50BDA can be used in the following configura-tions:

– 50 Watts primary / 50 Watts back up

– 100 watts primary / No back up

– 100 watts primary / 50 Watts backup (Optional ECC-

50BU required)

• Supports both Class A (Style Z) and Class B (Style Y) wiring.

• Easy setup and configuration by using a simple, built-in web based programming utility on the ECC-50/100(E).

• UL2572 (Communication and Control Units Mass Notifi-cation Systems). UL 864 (Emergency Voice Evacuation for Fire).

• Built-in power supply and battery charger that supports up to 35AH. (For batteries larger than 18 AH, use the BB-26 or BB-55F Battery Box.)

• ECC-50DA(E) and ECC-50BDA are field selectable for 25Vrms or or 70.7Vrms of operation.

• Sturdy, scratch resistant cabinet.

SOME SUITABLE APPLICATIONS

Installation The ECC-50DA(E), ECC-50BDA, and ECC-125DA(E) can be surface or flush mounted.

Compatibility The ECC-50DA(E), ECC-50DA and ECC-125DA(E) are only compatible with the ECC-50/100(E) Emergency Command Center System.

Electrical Specifications

PRIMARY AC POWER:

• ECC-50DA: 120VAC, 60Hz, 1200mA (max).

• ECC-50DAE: 240VAC, 50Hz, 600mA (max).

• ECC-50BDA: 120VAC, 60Hz, 2470mA (max).

• ECC-125DA: 120VAC, 60Hz, 2200mA (max).

• ECC-125DAE: 240VAC, 50Hz, 1250mA (max).

SPEAKER POWER:

• ECC-50DA(E): 50 watts primary only (25Vrms or

70.7Vrms).

• Schools • Healthcare Facilities • Factories

• Theaters • Military Facilities • Restaurants

• Auditoriums • Places of Worship • Office Buildings

• Dormitories mossb

ECC-50DA(E)

Page 2 of 4 — DF-60763:B • 8/25/14

• ECC-50BDA: 50 watts primary & 50 watts back up (25Vrms or 70.7Vrms); 100 watts primary only (25Vrms or 70.7Vrms); 100 watts primary & 50 watts back up (25Vrms or 70.7Vrms) (ECC-50WBU installed).

• ECC-125DA(E): 125 watts primary only (25Vrms).

SPEAKER OUTPUTS

• ECC-50DA(E): Four (4) supervised Class B (Style Y) or

Class A (Style Z). outputs. (Expandable to eight with ECC-

CE4).

• ECC-50BDA: (8) supervised Class B (Style Y) or Class A (Style Z). outputs.

• ECC-125DA(E): Four (4) supervised Class B (Style Y) or Class A (Style Z). outputs. (Expandable to eight with ECC-

CE4).

SECONDARY POWER (BATTERY) CHARGING CIRCUIT

• Supports lead acid batteries only.

• Battery charge capability: 7AH to 35AH.

(The ECC-50DA(E), ECC-BDA and the ECC-125DA(E) cabi-net only support up to 18AH. For batteries larger than 18AH, use the BB-26 or the BB-55F battery box. A minimum of 35AH is allowed per system.

Other Accessories BB-26: Battery cabinet used to mount up to two 26AH Batter-ies (BAT-12260).

BB-55F: Battery cabinet used to mount up to two 55AH Batter-ies (BAT-12250).

Product Line Information (Ordering Information) ECC-50DA: Distributed (Remote) Audio Amplifier, 50 watts.

ECC-50BDA: Distributed (Remote) Audio Amplifier with back up, 50 watts/100 watts at 25Vrms or 70Vrms.

ECC-125DA: Distributed (Remote) Audio Amplifier.

ECC-50DAE: Export version, Distributed (Remote) Audio Amplifier, 50 watts, 240 VAC, 50 Hz.

ECC-125DAE: Export version, Distributed (Remote) Audio Amplifier, 125 watts, 240 VAC, 50 Hz.

ECC-50/100: (Primary operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacuation system, Integral microphone, built in tone generator and 14 recordable messages. Please refer to the data sheet DF-60734 for more information.

ECC-50/100E: Export version (Primary operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacua-tion system, Integral microphone, built in tone generator and 14 recordable messages. 240 VAC, 50 Hz. Please refer to the data sheet DF-60734 for more information.

ECC-CE6: Speaker Circuit/Zone Expander Module.

ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier.

ECC-50W-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier.

ECC-XRM-70V: 70V Transformer conversion module for 70V operation.

ECC-LOC: Local Operator Console (Complete user interface), Please refer to the data sheet DF-60762 for more information.

ECC-RPU: Remote Page Unit Hand held microphone, 14 message buttons. Please refer to the data sheet DF-60761 for more information.

ECC-RM: Remote Microphone only. Please refer to the data sheet DF-60760 for more information.

ECC-FFT: Fire Fighter Telephone System. Please refer to the data sheet DF-60765 for more information.

FPJ-F: Remote Phone Jack.

FHS-F: Fire Fighters Remote Handset.

FHSC-RF: Fire Fighters Handset Cabinet Recessed.

FHSC-SF: Fire Fighters Handset Cabinet Surface Mount.

MMF-301: Addressable Mini-Monitor Module.

I300: SLC Line Isolation Module.

TR-CE: Optional Trim Ring.

CHG-75: 25 to 75 ampere-hours (AH) external battery charger.

CHG-120F: 25-120 ampere-hours (AH) external battery charger.

ECC-MICROPHONE: Replacement microphone only.

THUMBLTCH: Optional Thumb Latch. (Non-UL Listed).

BAT-1270: Battery, 12volt, 7.0AH (Two required).

BAT-12120: Battery,12volt,12.0AH (Two required).

BAT-12180: Battery,12volt, 18.0AH (Two required).

BAT-1260: Battery, 12volt, 26.0AH (Two required).

Optional Modules ECC-CE4: Circuit Expander Module provides connections for up to four Style Z (Class A) or four Style Y (Class B) speaker circuits. Circuits are configured through the web-based pro-gramming utility on the ECC-50/100(E).

ECC-50WBU: Expander card for ECC-50BDA remote amplifier for 100 watt primary / 50 watt back up operation.

Wiring Requirements

See Product manual part number: LS10027-000FL-E for detailed wiring requirements.

Cabinet Specifications 16" W x 26.25" H x 4.125" D (40.64cm W x 66.68cm H x 10.48cm D).

Shipping Specifications ECC-50DA Weight: 25.8 lbs (11.7kg)

ECC-50DA(E) Weight: 25.8 lbs (11.7kg)

ECC-125DA Weight: 24.3 lbs (11.02kg)

ECC-125DA(E) Weight: 24.3 lbs (11.02kg)

ECC-50BDA Weight: 28 lbs (12 kg)

ECC-50WBU Weight: 3 lbs (1 kg)

DF-60763:B • 8/25/14 — Page 3 of 4 horns/strobes

Speaker Circuits

TB20 & TB21

NAC Circuit

TB19

Internal options

ECC-CE6 circuit expander

ECC-50W-25/70V optional amplifier

ECC-FFT firefighter telephone remote consoles

ECC-LOC

local operator console

ECC-RPU

remote paging unit

ECC-RM

remote microphone

TB4

TB12

TB22distributed audioexternal battery charger - J7

ECC-50DA 50W

remote amplifier

ECC-125DA 125W

remote amplifier CHG-120F charger

CHG-75 charger

ECC-50/100(E) Emergency Command Center (Possible Configurations)

ECC-50BDA 50W

remote amplifier

Page 4 of 4 — DF-60763:B • 8/25/14

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.

www.firelite.com

©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Made in the U.S. A.

Temperature and Humidity ranges This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com-ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.

Agency Listings and Approvals The listings and approvals below apply to the basic ECC-50/ 100(E) Fire emergency voice evacuation system. In some cases, certain modules may not be listed by certain approval agencies or listing may be in process. Consult factory for latest listing status.

• UL Listed S2424.

• FDNY: COA #6152.

Standards and Codes The ECC-50/100 system complies with the following UL Stan-dards and with NFPA 72 Fire Alarm system requirements.

UL 864.

UL 2572

CSFM

��
�������������

,-.-/01

234567789:;5<=5>?5@AB<@?>C594D@B45:>E45;?<B5B3>B5<=5F@D8

A>B<GC45H<B35B3456778IJKLJJM6N56D4OE4?FP57@DD>?Q574?B4O

R@O5R<O45AO@B4FB<@?5>AAC<F>B<@?=S5TB5<=5A>OB5@R5B345R>D<CP5@R54UB4O?>C

O4D@B45F@?=@C4=5B3>B5>CC@H=5R@O54UB4?Q<?E5B3456778IJKLJJM6N

Q<=AC>P5>?Q5F@?BO@C5B@5O4D@B45C@F>B<@?=5H<B3<?5>5GV<CQ<?ES TB5<=

3@V=4Q5<?5>5F>G<?4B5H<B35>5W4P4Q5@O5>?5@AB<@?>C5B3VDG5C@FW5B@

C<D<B5>FF4==5B@5XV>C<R<4Q5A4O=@??4CS5

YZ�677�[�\]̂_̀ab�c�da]̀e�]̂f]_g�hZ�̂��̂b�c�̀�_e]�̂
daee�̂ceZ�e_�̂d�hacZ�be��_e]i�e�eZ�cjce�fg�f�e�̀jk
lmm*lmmh��]̂�_�̂d�dg��b_�ce�i�geZ�ch��n�g_]g_a]ec
djb�hg�cc]̂�eZ�f]_g�hZ�̂�ochacZ�e�e�̀ndaee�̂klc�̂
�bb�bd�̂��]epeZ�qeZdaee�̂�̂eZ�[�\_�̂d�ac�be��_e]�

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .