Drawings_56-99.pdf
PDF 45 MB Posted
- Attached to
- DENA 332037 Eielson Roof Replacement Federal contract opportunity
- Solicitation number
- 140P2026R0087
About this file
This is a construction design documentation package containing architectural and structural drawings for the rehabilitation of the Eielson Visitor Center at Denali National Park and Preserve. The project, designated DENA 332037, involves comprehensive roof replacement and interior modifications.
The scope of work includes demolition of existing penthouse structures, metal deck infills at skylight and mechanical openings, selective interior framing modifications, and exterior stair infill. Structural work involves removal of cold-formed steel (CFS) shear walls, removal of existing skylight enclosures, and installation of new metal deck (Verco PLN3-32, 18 gauge roof deck) with associated steel framing connections. Interior work encompasses new CFS wall framing, suspended gypsum board and acoustical tile ceilings with seismic bracing per ASCE 7, casework modifications including interactive display counters and finned-tube cabinet replacements, and flooring transitions. The project incorporates fire suppression system modifications including replacement of selective piping sections and recharged glycol solution per UL 2901 standards, mechanical system relocations to accommodate structural changes, and ADA accessibility compliance throughout. Design standards reference the 2024 International Building Code with snow loads of 258 PSF (LRFD) and wind speeds of 110 MPH (ultimate design). Special inspections are required for structural steel welding, bolting, and fabrication per AISC 360-16 standards. The documentation includes detailed schedules for door hardware, room finishes, casework materials, and ceiling assemblies, with design prepared by Design Alaska (Architecture/Engineering) and structural engineering by a registered professional engineer in Alaska.
View the file
Other files for this federal contract opportunity
Show all 49
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E
B C
D
A
F
K - L SIMILAR
G H
I J
AC
B
D
E
F
G
H
LEGEND
SKYLIGHT INFILL IDENTIFICATION
J
I
L
K
A. PHOTOS SHOW EXISTING CONDITIONS AT TIME OF SITE
VISIT.
EXISTING CONDITIONS NOTES
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A710
INTERIOR PHOTOS -
SKYLIGHTS
JB
20 JUL 2026
1" = 20'-0"A710
1 SKYLIGHT INFILL PHOTO MAP
0'
GRAPHICS SCALE: 1" = 20'-0"
10'-0" 20'-0" 40'-0"
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
T
20-JUL-2026
A. PHOTOS SHOW EXISTING CONDITIONS AT TIME OF SITE
VISIT.
EXISTING CONDITIONS NOTES
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A711
INTERIOR PHOTOS -
EXISTING CONDITIONS
JB
20 JUL 2026
NOT TO SCALEA711
4 PHOTO - INTERIOR WOOD RAMP TO CONCRETE TRANSITION
NOT TO SCALEA711
3 PHOTO - INTERIOR EXISTING INTERACTIVE DISPLAYS
NOT TO SCALEA711
2 PHOTO - VIEWING AREA
NOT TO SCALEA711
1 PHOTO - FIN TUBE CABINET COVERS
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
A. PHOTOS SHOW EXISTING CONDITIONS AT TIME OF SITE
VISIT.
EXISTING CONDITIONS NOTES
NOT TO SCALEA712
1 PHOTO - EXTERIOR PRECAST CONCRETE SILLS - TYPE 1
NOT TO SCALEA712
4 PHOTO - EXTERIOR MASONRY CRACKS
NOT TO SCALEA712
2 PHOTO - EXTERIOR CONCRETE WINDOW SILL - TYPE 2
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A712
EXTERIOR PHOTOS -
EXISTING CONDITIONS
JB
20 JUL 2026
NOT TO SCALEA712
3 PHOTO - EXTERIOR SIGNAGE
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
A. SEE A0 SHEETS FOR ASSEMBLY TAG LEGEND.
B. SEE A5 SHEETS FOR EXTERIOR ASSEMBLIES AND
DETAILS.
C. PROVIDE FINISHES TO FULL HEIGHT OF WALL UNLESS
NOTED OTHERWISE.
D. SEE MATERIAL SCHEDULE FOR CASEWORK FINISHES.
E. SEE SPECS FOR CASEWORK FINISHES NOT OTHERWISE
NOTED.
F. FINISH EXPOSED SURFACES OF CASEWORK, OUTSIDE
AND INSIDE.
G. SEE SPECS FOR CASEWORK HARDWARE, NOT SHOWN.
INTERIOR DETAIL NOTES
PROVIDE LATERAL
BRACING AT HINGE
LOCATIONS
HINGE SIDE
STRIKE SIDE
PROVIDE LATERAL
BRACING AT STRIKE
LOCATIONS
SEE DETAIL FOR
LATERAL BRACING
SEE DETAIL FOR
OPENINGS LESS
THAN 4'-0"
A810
G A
P
/2
M
IN
FASTEN GYPSUM BOARD TO STUD.
FASTENERS TO TRACK PROHIBITED.
MAINTAIN 1/2" GAP BETWEEN TOP OF
GYPSUM AND STRUCTURE ABOVE
SEALANT
GYPSUM
J BEAD
PROVIDE DEFLECTION TRACK AT NON
BEARING STUD WALLS EXTENDING TO
STRUCTURE ABOVE UNLESS NOTED
OTHERWISE.
MAINTAIN 1/2” GAP BETWEEN
TOP OF STUD AND TRACK ABOVE
G A
P
/2
M
IN
INSTALL DEFLECTION TRACK PER
MANUFACTURERS RECOMMENDATIONS
PER
ASSEMBLY
TYPE
/2
M
IN
GYPSUM BOARD(S)
NOT SHOWN THIS SIDE
FOR GRAPHIC CLARITY
GYPSUM BOARD(S)
PER ASSEMBLY
TYPE
PROVIDE CONTINUOUS BRIDGING BAR
AT TOP-MOST STUD KNOCK-OUT.
BRIDGING BAR NOT REQUIRED AT
WALLS WITH GYPSUM BOARD FROM
FLOOR TO STRUCTURE ABOVE. TYPICAL BOTTOM TRACK WITH
MECHANICAL FASTENERS AT 12"
OC, UNLESS NOTED OTHERWISE
HEADER TRACK TO MATCH
STUD SIZE AND GAUGE
TYPICAL WALL STUDS
TYPICAL WALL INFILL STUDS
SILL TRACK TO MATCH
STUD SIZE AND GAUGE
NOTE:
SEE STRUCTURAL FOR LOAD BEARING CONDITIONS.
SEE DETAIL
FOR DOOR
OPENINGS
CUT AND BEND EACH END
OF HEAD. (3) #10 SELF-
TAPPING SCREWS TO JAMB.
KING STUD WITH NESTED
TRACK TO MATCH STUD
SIZE AND GAUGE. STITCH
TOGETHER WITH (2) #10
TEK SCREWS AT 12" OC
CARPET PER ROOM
SCHEDULE
TRANSITION STRIP PER
SPECSTILE PER ROOM SCHEDULE
CEMENTITIOUS BOND
COAT AS SPECIFIED
EQ EQ
TILE TO CARPET
EQ EQ
NEATLY TRIMMED
BUTT-JOINT
ALIGN
RESILIENT TO RESILIENT
BUTT JOINT AT CHANGE OF
DIRECTION OR COLOR
RESILIENT FLOORING
PER ROOM SCHEDULE
TRANSITION STRIP PER SPECS
CARPET PER
ROOM SCHEDULE
EQ EQ
CARPET TO RESILIENT
1. SEE ROOM SCHEDULE FOR FLOORING FINISHES
2. SEE DOOR SCHEDULE FOR HARDWARE GROUPS. SEE
SPECIFICATIONS FOR DOOR THRESHOLD
5. SEE SPECIFICATIONS FOR FLOOR UNDERLAYMENT
WHERE REQUIRED
6. ALIGN CENTER OF DOOR THRESHOLD WITH CENTER OF
DOOR UNLESS FINISH PLAN INDICATES OTHERWISE
4. SEE DETAIL FOR LEVEL CHANGES
RESILIENT
FLOORING PER
ROOM SCHEDULE
FLOORING TRANSITION NOTES:
DOOR WHERE OCCURS
DOOR WHERE OCCURS
DOOR WHERE OCCURS
EXISTING CONCRETE
FLOORING WHERE
OCCURS
TRANSITION STRIP PER SPECS
FLOORING PER
ROOM SCHEDULE
EQ EQ
WOOD TO CONCRETE
DOOR WHERE OCCURS
A830
SEE PHOTO: 4
A711
SIZE PER MATERIAL SCHEDULE
CONCEALED PIVOTING ROD
HINGE
SCREWDRIVER OPERATED LATCH
MOUNTING HOLES
PER ASSEMBLY TYPE
ACCESS PANEL DOOR
FRAME
14"
/2
1"
HARDWOOD NOSING
EXISTING SILL TO REMAIN
RSL-1 PER MATERIAL SCHEDULE
EXISTING 1/2" UNDERLAYMENT OVER EXISTING
3/4" SUBFLOOR REPLACE AS REQUIRED TO
ACCOMMODATE NEW WORK
EXISTING FLOOR JOISTS
PROVIDE WD-3 PER MATERIAL SCHEDULE
1/2" HARDWOOD VENEER PLYWOOD RISER
3/4" PLYWOOD SUBFLOOR
EXISTING 2X STRINGER @ 3'-0" O.C
INTERIOR DETAIL LEGEND
EXISTING CONSTRUCTION
78910
A812
2'-0" 10" 2'-8" 10" 5'-4" 9" 2'-8" 9" 4'-10" 8" 2'-11" 8" 5'-1"
H E
IG
H
T S
P E
R C
E
IL
IN
G
P L A
N
FIELD VERIFY ALL
DIMENSIONS. NEW
CEILING TO MATCH
EXISTING LOCATION
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A810
INTERIOR DETAILS
JB
20 JUL 2026
1" = 1'-0"A810
INTERIOR FRAMING DETAIL - NON LOAD
BEARING DOOR OPENING
3" = 1'-0"A810
INTERIOR FRAMING DETAIL - PARTITION
DEFLECTION ATTACHMENT
1" = 1'-0"A810
INTERIOR FRAMING DETAIL - NON LOAD
BEARING OPENING LESS THAN 4'-0"
12" = 1'-0"A810
1 INTERIOR DETAIL - FINISH - FLOORING TRANSITIONS
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"
0'
GRAPHICS SCALE: 1" = 1'-0"
6" 1'-0" 2'-0"
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
0'
GRAPHICS SCALE: 1" = 1'-0"
6" 1'-0" 2'-0"
6" = 1'-0"A810
6 INTERIOR DETAIL - ACCESS PANEL
0'
GRAPHICS SCALE: 12" = 1'-0"
1/2" 1" 2"
0'
GRAPHICS SCALE: 6" = 1'-0"
1" 2" 4"
1 1/2" = 1'-0"A810
2 INTERIOR DETAIL - STAIRS - VIEWING
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
T
20-JUL-2026
1/2" = 1'-0"A810
7 BUILDING SECTION - VIEWING 102
0'
GRAPHICS SCALE: 1/2" = 1'-0"
1'-0" 2'-0" 4'-0"
A. SEE A810 FOR INTERIOR DETAIL NOTES.
INTERIOR DETAIL NOTES
PER PLAN
FLEXIBLE SEALANT OR
TAPE
WHERE ASSEMBLY IS
RATED STC 40 OR
GREATER, CONTINUE STC
RATED ASSEMBLY TO
INSIDE FACE OF EXTERIOR
SHEATHING AT EXTERIOR
ASSEMBLY
EXTERIOR ASSEMBLY PER
ASSEMBLY TYPES
INSIDE FACE OF EXTERIOR
SHEATHING
PER PLAN
THE BELOW DIAGRAM DESCRIBES PRIORITIES
DETERMINING THE CONTINUITY OF STC RATED
ASSEMBLIES.
HIGH PRIORITY- EQUAL TO OR GREATER THAN 40 STC
LOW PRIORITY - LESS THAN 40 STC.
SEE ASSEMBLY TYPES FOR CONSTRUCTION.
SEE FLOOR PLANS FOR LOCATION OF ASSEMBLIES.
SEE ASSEMBLY TYPES FOR STC RATINGS.
PER PLAN
PER PLAN
PER PLAN
LOW PRIORITY
ASSEMBLY
CONTINUE HIGH
PRIORITY ASSEMBLY
WHERE ABUTTING LOW
PRIORITY ASSEMBLY
ALIGN FINISHES UNLESS
NOTED OTHERWISE
HIGH PRIORITY
ASSEMBLY
PER PLAN
PER PLAN
HIGH PRIORITY
ASSEMBLY
SHEATHING SEPARATION
NOT REQUIRED WHERE
HIGH PRIORITY ASSEMBLY
ABUTS HIGH PRIORITY
ASSEMBLY
DOOR FRAME PER DOOR SCHEDULE
DOOR PER DOOR SCHEDULE
CONTINUOUS SEALANT
PER ASSEMBLY TYPE
FINISHES PER ROOM AND DOOR SCHEDULE
CONTINUOUS GASKET WHERE
INDICATED BY HARDWARE SCHEDULE
AT DOORS REQUIRING LESS THAN STC 40,
FILL FRAME WITH 10 LB MINERAL WOOL
SEE DETAIL FOR
TYPICAL FRAMING
A810
FRAME PER DOOR
SCHEDULE
METAL FRAME ANCHOR
DOOR PER DOOR SCHEDULE
CONTINUOUS SEALANT
FINISHES PER ROOM
AND DOOR SCHEDULE
PER
ASSEMBLY
TYPE
CONTINUOUS GASKET
AT STC 33 OR GREATER
AT DOORS REQUIRING LESS
THAN STC 40, FILL FRAME
WITH 10 LB MINERAL WOOL
DOOR PER DOOR SCHEDULE
FINISHES PER ROOM
AND DOOR SCHEDULES
DOOR JAMB AND JAMB GASKET
BEYOND
SEE FINISH PLAN FOR FLOOR
FINISH TRANSITIONS
DOOR BOTTOM WHERE
INDICATED BY HARDWARE
SCHEDULE
MAINTAIN ACOUSTIC
ASSEMBLY AT SILL PER DOOR
SCHEDULE
THRESHOLD WHERE INDICATED
BY HARDWARE SCHEDULE
A811
PROVIDE CONTINUOUS AIR TIGHT SEAL
AT WALL TERMINATION TO METAL DECK
AND ENTIRE WALL PERIMETER.
CONTINUOUS ACOUSTICAL SEALANT TO
ACCOMMODATE STRUCTURAL DEFLECTION
METAL DECK PER STRUCTURAL
NOTCH GYPSUM BOARD TO FIT METAL DECK
PROFILE WITH GAP SIZED TO ACCOMMODATE
STRUCTURAL DEFLECTION.
WHERE METAL DECK FLUTES
ARE PARALLEL TO WALL
ASSEMBLY, SEE DETAIL
FRICTION FIT FIBERGLASS BATT
INSULATION TO FILL CAVITY
WHERE METAL DECK FLUTES
ARE NOT PARALLEL TO WALL
ASSEMBLY, SEE DETAIL
CONTINUOUS ACOUSTICAL SEALANT
FILL CAVITY WITH CONTINUOUS
ACOUSTICAL SEALANT TO ACCOMMODATE
STRUCTURAL DEFLECTION
PROVIDE CONTINUOUS AIR TIGHT SEAL
AT WALL TERMINATION TO METAL DECK
AND ENTIRE WALL PERIMETER.
20 GAUGE METAL CLOSURE PLATE.
SPAN METAL DECK FLUTE COMPLETELY
TO PROVIDE CONTINUOUS SEAL
1" MIN, TYP
TYP
1" MIN
METAL DECK PER STRUCTURAL
PER
ASSEMBLY
TYPE
PER
ASSEMBLY
TYPE
FOR TYPICAL
ANNOTATION
SEE DETAIL
A810
AIR TIGHT SEAL
AS REQ'D FOR
A811
3" = 1'-0"A811
INTERIOR ACOUSTIC DETAIL - PARTITION DEFLECTION
ATTACHMENT - NOT PARALLEL TO FLUTES
3" = 1'-0"A811
INTERIOR ACOUSTIC DETAIL - PARTITION DEFLECTION
ATTACHMENT - PARALLEL TO FLUTES
1" = 1'-0"A811
INTERIOR ACOUSTIC DETAIL - ASSEMBLY
PRIORITY - EXTERIOR
1" = 1'-0"A811
INTERIOR ACOUSTIC DETAIL - ASSEMBLY
PRIORITY - INTERIOR
3" = 1'-0"A811
6 INTERIOR ACOUSTIC DETAIL - DOOR JAMB
3" = 1'-0"A811
3 INTERIOR ACOUSTIC DETAIL - DOOR HEAD
3" = 1'-0"A811
5 INTERIOR ACOUSTIC DETAIL - DOOR SILL
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A811
INTERIOR DETAILS -
ACOUSTIC
JB
20 JUL 2026
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"
0'
GRAPHICS SCALE: 1" = 1'-0"
6" 1'-0" 2'-0"
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"0'
GRAPHICS SCALE: 1" = 1'-0"
6" 1'-0" 2'-0"
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
UNATTACHED WALLS
3/4" MIN AT
MIN
2"
8" MAX
M A
X
SPREADER BAR
WITHIN 8" OF WALL
AT CEILINGS
GREATER THAN
2,500 SF
EDGE OF WALL
PLUMB WITHIN 1:6
PERIMETER
SUPPORT WIRE
WALL MOULDING
BEAM OR CROSS TEE
ASCE 7 SECTION 13.5.6.2.2 MANDATES THAT CEILING AREAS GREATER
THAN 2,500 SF MUST HAVE SEISMIC SEPARATION JOINTS,
CLOSURE ANGLES, AND HORIZONTAL RESTRAINTS. THIS MEANS 2"
MOLDING, PERIMETER SPACER BARS – AND IF THE AREA IS GREATER
THAN 1,000 SF LATERAL FORCE BRACING.
8 GA HANGER WIRE AT
4'-0" EACH WAY
10 GA 4-WAY DIAGONAL
BRACE WIRES AT 45
DEGREES TO STRUCTURE
ABOVE AT 12'-0" ON
CENTER EACH WAY
1 1/2" CARRYING CHANNELS
AT 4'-0" ON CENTER
7/8" FURRING CHANNELS
AT 2'-0" ON CENTER
GYPSUM BOARD(S) PER
ASSEMBLY TYPE
NOTE:
NO FRAMING OR HANGERS
TO BE IN CONTACT WITH
MECHANICAL OR
ELECTRICAL EQUIPMENT 2
PER ASSEMBLY TYPE
BEAD AND TRIM
PER ASSEMBLY TYPE
MAX
8"
ON CENTER
4'-0"
WALL
CROSS RUNNER WITH
3/4" MIN CLEARANCE
FROM PERIMETER
WALLS
MAIN RUNNER WITH
3/8" MIN CLEARANCE
FROM PERIMETER
WALLS
WRAP SUSPENSION
WIRE TIGHTLY AROUND
ITSELF A MINIMUM OF
THREE FULL TURNS
WITHIN A 3" LENGTH
SEISMIC PERIMETER CLIP
SECTION VIEW
PROVIDE 12 GAUGE MINIMUM SUSPENSION WIRES
3/8" MIN
AT CONTRACTORS OPTION:
PROVIDE COUNTER-SLOPING SUSPENSION WIRES
IN LIEU OF A SINGLE SUSPENSION WIRE WHERE
SLOPE GREATER THAN 1:6 REQUIRED
SLOPE SUSPENSION WIRE NOT MORE
THAN 1:6 OUT OF PLUMB
NOTE:
SEE DETAIL FOR SUSPENDED CEILINGS NOT
SURROUNDED BY WALLS OR SOFFITS LATERALLY
BRACED TO THE STRUCTURE ABOVE
A812
ATTACH SCREW THRU
SLOT
WALL
ALLOW 3/4" MIN FREE AXIAL MOVEMENT
(OMIT PINS) AT REMAINING WALLS.
ALL OTHER PINNED END ANNOTATION
REMAINS APPLICABLE TO FREE END
PINNED END
SECTION VIEW
FREE END
SECTION VIEW
SEE DETAIL FOR TYPICAL ANNOTATION
A812
WALL
8" MAX
CENTER
4'-0" ON
SPACER BAR 8" MAX FROM PERIMETER
ATTACH SCREW THRU
SLOT
PERIMETER 12 GA.
HANGER WIRE
PIN RUNNER TO PERIMETER CLOSURE AT
TWO ADJACENT ENDS OF WALL
3/8" MIN
12 GA VERTICAL WIRE HANGER
4'-0" ON CENTER MAX ATTACHED
PRIOR TO SETTING STRUT
(4) 12 GA SPLAY WIRES IN PLANE
OF TEES. SPACE 12'-0" ON CENTER
NO FURTHER THAN 6'-0" FROM
WALL. CONNECT TO MAIN TEE
WITHIN 2" OF INTERSECTION
EMT CONDUIT COMPRESSION STRUT
12'-0" ON CENTER EACH WAY
6'-0" MAXIMUM FROM WALL
• 1/2" DIAMETER UP TO 6'-0",
• 3/4" DIAMETER TO 8'-6",
• 1" DIAMETER UP TO 10'-0"
SLOT END OF TUBE
TO FIT OVER TEE
MAIN TEE
CROSS TEE
EXTEND COMPRESSION STRUT
TIGHT BETWEEN MAIN TEE AND
STRUCTURE ABOVE. SECURE
SEGMENTS TOGETHER WITH 4"
MINIMUM OVERLAP.
SUPPORT ENDS OF RUNNERS WITHIN 8" OF SURROUNDING PERIMETER WALL OR CEILING DISCONTINUITY.
LOOP WIRES AND TWIST 3 TIMES AROUND ITSELF WITHIN 3". WIRES TO BE PLUMB WITHIN 1 IN 6.
BRACING MEMBERS SHALL BE SPACED A MINIMUM OF 6 INCHES FROM ALL HORIZONTAL
PIPING OR DUCT WORK THAT IS NOT PROVIDED WITH BRACING RESTRAINTS
WALL
PINNED END
SECTION VIEW
FREE END
SECTION VIEW
COMPRESSION STRUT PER ENLARGED
AXONOMETRIC DETAIL
SEE DETAIL FOR TYPICAL ANNOTATION
A812
WALL
SPLAY WIRES PER ENLARGED
AXONOMETRIC DETAIL
VERTICAL WIRE HANGER PER
ENLARGED AXONOMETRIC DETAIL
M
IN4
ENLARGED
AXONOMETRIC DETAIL
T Y P
IC
A L
45° M A X
NOT TO SCALE
6'-0" MAX
NOT TO SCALE
12'-0" ON CENTER
COMPRESSION STRUT PER ENLARGED
AXONOMETRIC DETAIL
MAX
8"
SPLAY WIRES PER ENLARGED
AXONOMETRIC DETAIL
VERTICAL WIRE HANGER PER
ENLARGED AXONOMETRIC DETAIL
3/4" MIN
3/8" MIN
PIN RUNNER TO PERIMETER CLOSURE AT
TWO ADJACENT ENDS OF WALL
ATTACH SCREW THRU
SLOT
WD-2 PER MATERIAL
SCHEDULE ON METAL
CARRIER AND
HANGERS
SEE DETAIL
FOR CEILINGS
AT BULKHEAD
A812
ACT-1 PER MATERIAL
SCHEDULE
SEE DETAIL FOR
SUSPENDED ACT
AT WALL SIMILAR
A812
WD-2 PER MATERIAL
SCHEDULE ON METAL
CARRIER AND
HANGERS
SEE DETAIL
FOR CEILINGS
AT BULKHEAD
A812
EXISTING STEEL STUD
BULKHEAD BRACED TO
UNDERSIDE OF
STRUCTURE
INTERIOR DETAIL LEGEND
EXISTING CONSTRUCTION
3/4" = 1'-0"A812
2 INTERIOR CEILING DETAIL - SUSPENDED GYPSUM BOARD
3" = 1'-0"A812
1 INTERIOR CEILING DETAIL - SUSPENDED ACT AT WALL
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A812
INTERIOR DETAILS - CEILING
JB
20 JUL 2026
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8" 1 1/2" = 1'-0"A812
3 INTERIOR DETAIL - CEILING - BULKHEAD
1 1/2" = 1'-0"A812
INTERIOR DETAIL - CEILING - SEISMIC REQUIREMENTS FOR
SUSPENDED ACT EQUAL TO OR LESS THAN 144 SF
1 1/2" = 1'-0"A812
INTERIOR DETAIL - CEILING - SEISMIC REQUIREMENTS FOR SUSPENDED ACT GREATER THAN 144 SF AND LESS
THAN OR EQUAL TO 1000 SF
1 1/2" = 1'-0"A812
5 INTERIOR DETAIL - CEILING - SEISMIC REQUIREMENTS FOR SUSPENDED ACT GREATER THAN 1000 SF AND LESS THAN OR EQUAL TO 2500 SF
0'
GRAPHICS SCALE: 3/4" = 1'-0"
6" 1'-0" 2'-0" 0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4" 0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
1 1/2" = 1'-0"A812
7 INTERIOR DETAIL - CEILING - SUSPENDED LINEAR WOOD AND ACT ELEVATION TRANSITION
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
1 1/2" = 1'-0"A812
8 INTERIOR DETAIL - CEILING - LINEAR WOOD CEILING BULKHEAD
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
MIN. 1'-10 5/8", MAX. 4'-2"
VARIES (SEE ENLARGED PLAN)
EXISTING BRACKET TO REMAIN
EXISTING TUBE STEEL SUPPORT RAILS TO REMAIN
1/2" SLD-1 AS SCHEDULED
1/2" SLD-1 AS SCHEDULED
LAMINATED CURVED PLYWOOD BUILD-UP, PROVIDE
THICKNESS AS REQUIRED
1 1/4" PLYWOOD BUILD-UP, FASTEN AS REQUIRED
EXISTING
EXISTING GRAPHIC MURAL, FASTENERS AND
SUBSTRATE TO REMAIN
EXISTING GRAPHIC MURAL, FASTENERS
AND SUBSTRATE TO REMAIN
VARIES
ADA MAX REACH = 25"
1'-10" MAX
EXISTING
FOR TYPICAL
ANNOTATION SEE
A820
REINSTALL SALVAGED POSTCARD UNIT
1'-1"
/2
POSTCARD POCKET PLAN
VARIES
SEE
VARIES
EXISTING
FOR TYPICAL
ANNOTATION SEE
A820
SALVAGED 1/2" LAMINATED SAFETY
GLASS TO BE REINSTALLED
TO ACCESS CASE INTERIOR LIFT
GLASS OUT WITH GLASS MOVING
SUCTION CUPS
EXISTING BRACKET AND TUBE STEEL
SUPPORT RAILS TO REMAIN BEYOND
1/2" SLD-1 AS SCHEDULED
REMOVABLE PANEL TO ACCESS
INTERNAL LIGHT
WHITE TRANSLUCENT ACRYLIC, ALL
INTERIOR SIDES
INTERNAL LIGHT
VENTILATION PATH
A820
A820
/4
2'-10 1/4"
EXHIBIT ITEMS BELOW
COUNTER, SLD-1 AS SCHEDULED
INSET DISPLAY CASE PER 3
A820
2'-10 1/4"
EXHIBIT ITEMS BELOW
COUNTER, SLD-1 AS SCHEDULED
INSET DISPLAY CASE PER 3
A820
/4
EXISTING
FOR TYPICAL
ANNOTATION SEE
A820
EXISTING MOBILE CART BELOW
MODIFY SUBSTRATE AND SLD-1 AS
REQUIRED TO ACCOMMODATE
MOBILE CARTS BELOW
INTERIOR DETAIL LEGEND
EXISTING CONSTRUCTION
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A820
INTERIOR DETAILS -
CASEWORK
JB
20 JUL 2026
1 1/2" = 1'-0"A820
1 INTERIOR DETAIL - CASEWORK - INTERACTIVE COUNTER - TUNDRA DISCOVERY AREA - TYPICAL 1 1/2" = 1'-0"A820
2 INTERIOR DETAIL - CASEWORK - INTERACTIVE COUNTER - TUNDRA DISCOVERY AREA - POSTCARDS 1 1/2" = 1'-0"A820
3 INTERIOR DETAIL - CASEWORK - INTERACTIVE COUNTER - TUNDRA DISCOVERY AREA - INSET DISPLAY CASE
3" = 1'-0"A820
5 INTERIOR DETAIL - CASEWORK - INTERACTIVE COUNTER - TUNDRA DISCOVERY AREA - INSULATION EXHIBIT 3" = 1'-0"A820
6 INTERIOR DETAIL - CASEWORK - INTERACTIVE COUNTER - TUNDRA DISCOVERY AREA- BITE MARKS EXHIBIT 1 1/2" = 1'-0"A820
4 INTERIOR DETAIL - CASEWORK - INTERACTIVE COUNTER - TUNDRA DISCOVERY AREA - MOBILE CARTS
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4" 0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4" 0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4" 0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8" 0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
PROVIDE GREEN BIOFIBER COMPOSITE
BOARD, CHAMFER EDGES, CLEAR FINISH
EXISTING FRAMING TO REMAIN
EXISTING METAL TRIM
PROVIDE 1X BIRCH AT BASE, STAINED
PROVIDE METAL TRIM TO MATCH
EXISTING
UPPER COUNTER BEYOND
PROVIDE BIRCH VENEER PLYWOOD, STAINED
PROVIDE GYPSUM BOARD
EXISTING FRAMING TO REMAIN
PROVIDE GYPSUM BOARD
PROVIDE 1X BIRCH AT BASE, STAINED
PROVIDE METAL TRIM TO MATCH EXISTING
PROVIDE METAL TRIM TO MATCH EXISTING
/4
SEE DIAGRAM FOR
WINDOW SILL
3/4"
FINISH PER MATERIAL
SCHEDULE
3/4" MIN PLYWOOD
SUBSTRATE
FINISH PER ROOM SCHEDULE
1/4" MIN RADIUSED EDGE
CONTINUOUS SEALANT
WALL PER
ASSEMBLY
TYPES
FINISH PER
ROOM
SCHEDULE
A821
SIMILAR
EQ
E Q
EXTEND INTERIOR SILL
BEYOND WINDOW A
DISTANCE EQUAL TO
SILL HEIGHT
A821
EXTENDED SILL
INTERIOR DETAIL LEGEND
EXISTING CONSTRUCTION
EXISTING WINDOW SILL
EXISTING RADIANT HEATING
EXISTING STEEL STUD BLOCKING
EXISTING METAL ANGLES AS
HEAD RUNNER
PERFORATED METAL CHANNEL
EXISTING COMPOSITE PANEL
EXISTING
EXISTING WOOD RAIL
EXISTING GRAVITY CLEAT
EXISTING GRAVITY CLEAT
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A821
INTERIOR DETAILS -
CASEWORK
JB
20 JUL 2026
1 1/2" = 1'-0"A821
1 INTERIOR DETAIL - CASEWORK - INFORMATION DESK - AT UPPER COUNTER
1 1/2" = 1'-0"A821
2 INTERIOR DETAIL - CASEWORK - INFORMATION DESK - AT LOWER COUNTER
6" = 1'-0"A821
INTERIOR DETAIL - FINISH - WINDOW SILL -
BULLNOSE
3" = 1'-0"A821
INTERIOR DETAIL - FINISH - PARTIAL HEIGHT
WALL CAP
1" = 1'-0"A821
4 INTERIOR DETAIL - FINISH - WINDOW SILL ELEVATIONS
0'
GRAPHICS SCALE: 3" = 1'-0"
2" 4" 8"0'
GRAPHICS SCALE: 6" = 1'-0"
1" 2" 4"
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
0'
GRAPHICS SCALE: 1" = 1'-0"
6" 1'-0" 2'-0"
1 1/2" = 1'-0"A821
3 INTERIOR DETAIL - CASEWORK - FIN TUBE COVER
0'
GRAPHICS SCALE: 1 1/2" = 1'-0"
4" 8" 1'-4"
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
A. SEE A700 FOR ACCESSORY AND FIXTURE TYPES
INTERIOR ACCESSIBILITY
DETAIL NOTESFLOOR SURFACES SHALL BE STABLE,
FIRM, AND SLIP RESISTANT.
CARPET AND/OR CARPET TILE SHALL BE
SECURELY ATTACHED AND SHALL HAVE A
FIRM CUSHION, PAD, BACKING, OR SHALL
HAVE NO CUSHION OR PAD.
CARPET AND/OR CARPET TILE SHALL
HAVE A LEVEL LOOP, TEXTURED LOOP,
LEVEL CUT PILE, OR LEVEL CUT/UNCUT
PILE TEXTURE.
THE PILE SHALL BE 1/2" MAXIMUM IN
HEIGHT.
EXPOSED EDGES OF CARPET SHALL BE
FASTENED TO THE FLOOR AND SHALL
HAVE TRIM ALONG THE ENTIRE LENGTH
OF THE EXPOSED EDGE.
OPENINGS IN FLOOR SURFACES SHALL
BE OF A SIZE THAT DOES NOT PERMIT
THE PASSAGE OF A 1/2" DIAMETER
SPHERE.
ELONGATED OPENINGS SHALL BE
PLACED SUCH THAT THE LONG
DIMENSION IS PERPENDICULAR TO THE
PROMINENT DIRECTION OF TRAVEL.
/2
M
A X
SECTION VIEW
PLAN VIEW
/2
M
A X
DIMENSION
LONG
D O
M
IN
A N
D
IR
E C
T
IO
N
O F
T R
A V
E L
FLOOR SURFACE CHANGES IN LEVEL OF
1/4" MAX SHALL BE PERMITTED TO BE
VERTICAL.
CHANGES IN LEVEL OF GREATER THAN
1/4" IN HEIGHT AND NOT MORE THAN 1/2"
MAX IN HEIGHT SHALL BE BEVELED WITH
A SLOPE NOT STEEPER THAN 1:2.
CHANGES IN LEVEL OF GREATER THAN
1/2" IN HEIGHT SHALL COMPLY WITH
REQUIREMENTS OF RAMPS.
SECTION VIEWS
M A
X
/4
M A
X
/2
/4
T
O
/2
60" MIN
EXISTING - PLAN VIEW - CIRCULAR
60" MIN
M
IN
M
IN
MIN
12"36" MIN
MIN
12"
M
IN
EXISTING - PLAN VIEW - T-SHAPED
TURNING SPACES SHALL BE
PERMITTED TO OVERLAP
WITH CLEAR FLOOR SPACES,
CLEARANCES AT FIXTURES,
AND MANEUVERING
CLEARANCES AT DOORS,
UNLESS NOTED OTHERWISE.
CHANGES IN LEVEL ARE NOT
PERMITTED WITHIN THE
TURNING SPACE WITH THE
EXCEPTION OF SLOPES NO
GREATER THAN 1:48.
FLOOR SURFACES
OF TURNING SPACES
SHALL COMPLY WITH
DETAIL:
BASE
SEE DETAIL FOR
KNEE AND TOE
CLEARANCES:
ARM
DOORS SHALL BE
PERMITTED TO SWING INTO
TURNING SPACES, UNLESS
NOTED OTHERWISE.
M A
X
OVERLAP AT
KNEE AND TOE
CLEARANCES
PERMITTED
ONLY AT
SHADED AREA,
TYPICAL.
OVERLAP AT
KNEE AND TOE
CLEARANCES
PERMITTED
ONLY AT
EITHER THE
END OF THE
BASE OR ONE
ARM, TYPICAL.
A830
A830
CLEAR FLOOR SPACE SHALL
BE PERMITTED TO INCLUDE
KNEE AND TOE CLEARANCE
PER DETAIL:
A830
FLOOR SURFACES
OF CLEAR FLOOR
SPACES SHALL
COMPLY WITH DETAIL:
A830
CHANGES IN LEVEL ARE NOT PERMITTED
WITHIN THE CLEAR FLOOR SPACE WITH THE
EXCEPTION OF SLOPES NO GREATER THAN 1:48.
UNLESS NOTED OTHERWISE, CLEAR FLOOR SPACES
SHALL BE POSITIONED FOR EITHER FORWARD OR
PARALLEL APPROACH TO AN ELEMENT.
ONE FULL, UNOBSTRUCTED SIDE OF THE CLEAR FLOOR
SPACE SHALL ADJOIN OR OVERLAP AN ACCESSIBLE
ROUTE OR ADJOIN ANOTHER CLEAR FLOOR SPACE.
IF A CLEAR FLOOR SPACE IS IN AN ALCOVE OR OTHERWISE
CONFINED ON ALL OR PART OF THREE SIDES, ADDITIONAL
MANEUVERING CLEARANCES FOR PARALLEL AND FORWARD
APPROACH SHALL BE PROVIDED, AS APPLICABLE.
WHERE THE CLEAR FLOOR SPACE IS POSITIONED FOR A
PARALLEL APPROACH, THE ALCOVE SHALL BE 60 INCHES
MINIMUM IN WIDTH WHERE THE DEPTH EXCEEDS 15 INCHES.
WHERE THE CLEAR FLOOR SPACE IS POSITIONED FOR A
FORWARD APPROACH, THE ALCOVE SHALL BE 36 INCHES
MINIMUM IN WIDTH WHERE THE DEPTH EXCEEDS 24 INCHES.
FORWARD APPROACH
AT ALCOVE
PARALLEL APPROACH
AT ALCOVE
M A
X
M A
X
36" MIN 60" MIN
CLEAR FLOOR
OR GROUND
SPACE
48" MIN
M
IN
WHERE SPACE BENEATH AN ELEMENT IS
INCLUDED AS PART OF CLEAR FLOOR SPACE AT
AN ELEMENT, CLEARANCE AT AN ELEMENT, OR
A TURNING SPACE, THE SPACE SHALL COMPLY
WITH KNEE AND TOE CLEARANCES.
ADDITIONAL SPACE SHALL NOT BE
PROHIBITED BENEATH AN ELEMENT, BUT
SHALL NOT BE CONSIDERED AS PART OF THE
CLEAR FLOOR SPACE OR TURNING SPACE.
SPACE BENEATH AN ELEMENT BETWEEN THE
FLOOR AND 9" ABOVE THE FLOOR SHALL BE
CONSIDERED TOE CLEARANCE AND SHALL
COMPLY WITH KNEE AND TOE CLEARANCES.
TOE CLEARANCE SHALL BE PERMITTED TO
EXTEND 25" MAXIMUM UNDER AN ELEMENT.
WHERE TOE CLEARANCE IS REQUIRED AT AN
ELEMENT AS PART OF A CLEAR FLOOR
SPACE, THE TOE CLEARANCE SHALL EXTEND
17" MINIMUM BENEATH THE ELEMENT.
SPACE EXTENDING GREATER THAN 6" BEYOND
THE AVAILABLE KNEE CLEARANCE AT 9" ABOVE
THE FLOOR SHALL NOT BE CONSIDERED TOE
CLEARANCE.
TOE CLEARANCE SHALL BE 30" MINIMUM IN WIDTH.
SPACE BENEATH AN ELEMENT BETWEEN 9" AND
27" ABOVE THE FLOOR SHALL BE CONSIDERED
KNEE CLEARANCE.
KNEE CLEARANCE SHALL BE PERMITTED TO
EXTEND 25" MAXIMUM UNDER AN ELEMENT AT
9" ABOVE THE FLOOR.
WHERE KNEE CLEARANCE IS REQUIRED
BENEATH AN ELEMENT AS PART OF A CLEAR
FLOOR SPACE, THE KNEE CLEARANCE SHALL
BE 11" MINIMUM IN DEPTH AT 9" ABOVE THE
FLOOR, AND 8" MINIMUM IN DEPTH AT 27"
ABOVE THE FLOOR.
BETWEEN 9" AND 27 " ABOVE THE FLOOR, THE
KNEE CLEARANCE SHALL BE PERMITTED TO BE
REDUCED AT A RATE OF 1" IN DEPTH FOR EACH
6" IN HEIGHT.
KNEE CLEARANCE SHALL BE 30" MINIMUM IN WIDTH.
PLAN VIEW
KNEE CLEARANCES
SIDE VIEW
TOE CLEARANCES
6" MAX
M
IN
M
IN
11" MIN
8" MIN
PLAN VIEW
TOE CLEARANCES
M
IN
17"-25"
ELEMENT ABOVE
CLEAR FLOOR SPACE
SIDE VIEW
KNEE CLEARANCES
M
IN
25" MAX
ELEMENT ABOVE
CLEAR FLOOR SPACE
OBJECTS WITH
LEADING EDGES
MORE THAN 27" AND
NOT MORE THAN 80"
ABOVE THE FLOOR
SHALL PROTRUDE
4" MAXIMUM
HORIZONTALLY
INTO THE
CIRCULATION PATH.
HANDRAILS SHALL
BE PERMITTED TO
PROTRUDE 4 1/2"
MAX.
OBJECTS ON POSTS OR PYLONS SHALL BE PERMITTED TO
OVERHANG 12" MAXIMUM WHERE MORE THAN 27" AND NOT
MORE THAN 80" ABOVE THE FLOOR.
SLOPING PORTIONS OF HANDRAILS BETWEEN THE TOP AND
BOTTOM RISER OF STAIRS AND ABOVE THE RAMP RUN SHALL
NOT BE REQUIRED TO COMPLY WITH POST MOUNTED OBJECT
REQUIREMENTS BELOW.
VERTICAL CLEARANCE
SHALL BE 80" MINIMUM.
DOOR CLOSERS AND
DOOR STOPS SHALL BE
PERMITTED TO BE 78"
MINIMUM ABOVE FLOOR.
PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR
WIDTH REQUIRED FOR ACCESSIBLE ROUTES.
x x
O R
E Q
T O
4" MAX
LIMITS OF PROTRUDING OBJECTS
x
REDUCED VERTICAL CLEARANCE
x > OR EQ TO 12"
12" MAX 12" MAX
OBJECT
OBJECT
M A
X
RAILS OR OTHER
BARRIERS SHALL BE
PROVIDED WHERE THE
VERTICAL CLEARANCE
IS LESS THAN 80".
THE LEADING EDGE OF
SUCH RAILS OR
BARRIER SHALL BE
LOCATED 27" MAXIMUM
ABOVE THE FLOOR.
A N
D
M A
X x > 12"
OBJECT
POSTS OR
PYLONS
12" MAX12" MAX<
POST-MOUNTED PROTRUDING OBJECTS
POST-MOUNTED PROTRUDING OBJECTS
FORWARD REACH
FORWARD REACH WHERE UNOB-
STRUCTED OR WHERE OBSTRU-
CTION IS LESS THAN 20".
FORWARD REACH
FORWARD REACH WHERE
OBSTRUCTION IS GREATER THAN
20" AND LESS THAN 25".
M
IN
M A
X
M A
X
25 MAX
20 MIN
M
A X
A T
E X
IS
T
IN
G
E L
E M
E N
T S
M A
X
M A
X
M
IN
MAX
10".
M A
X
M A
X
MAX
24".
SIDE REACH
SIDE REACH WHERE UNOBSTRU-
CTED OR WHERE OBSTRUCTION
IS 10" OR LESS.
SIDE REACH
SIDE REACH WHERE OBSTRUCTION
IS GREATER THAN 10" AND LESS
THAN 24".
OBSTRUCTION
(e.g. COUNTERTOP)
REACH LIMIT (e.g. WALL)
PLAN VIEW - FRONT APPROACH
CLEAR FLOOR
SPACE PER DETAIL
MAX
20".
OBSTRUCTION
(WHERE OCCURS)
REACH LIMIT
OBSTRUCTION
REACH LIMIT
OBSTRUCTION
(e.g. CASEWORK)
REACH LIMIT
(e.g. WALL)
PLAN VIEW - PARALLEL APPROACH
CLEAR
FLOOR
SPACE
OBSTRUCTION
(WHERE
OCCURS)
REACH LIMIT
OBSTRUCTION
REACH LIMIT
EXTEND CLEAR FLOOR SPACE BENEATH
OBSTRUCTION FOR A DISTANCE NOT
LESS THAN THE REQUIRED REACH DEPTH
OVER THE OBSTRUCTION.
A830
CLEAR FLOOR
SPACE REQUIRED
PER DETAIL:
OPERABLE PARTS SHALL BE PLACED
WITHIN ONE OR MORE OF THE REACH
RANGES SPECIFIED PER DETAIL:
OPERABLE PARTS SHALL BE OPERABLE WITH ONE
HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
PINCHING, OR TWISTING OF THE WRIST.
THE FORCE REQUIRED TO ACTIVATE OPERABLE
PARTS SHALL BE 5 POUNDS MAXIMUM.
A830
A830
60" MIN
6" MIN
M
IN9
"TOE SPACE
TOILET
PARTITION
WHERE
OCCURS
12" MIN 24" MIN
M
IN
39" - 41"
7"-9"
M
IN
M
IN
60" MIN
M A
X
6" MAX
16" - 18"
1'-6"
M
IN
36" MIN
.5
M
IN
PLAN VIEW FRONT VIEW SIDE VIEW
FIXTURE PER
MECHANICAL
CLEAR
FLOOR
SPACE
GRAB BARS
AMBUL-
17" - 19"
ATORY
M
IN
M A
X
M
IN
M
IN
T O
C O
N T
R O
L S
M A
X
MIN
8"
MAX
6"
M
IN9
17" MIN
M
IN
INSULATED HOT
WATER & DRAIN
PIPES WITH
ACCESS AS
REQUIRED.
THE DIP OF THE
OVERFLOW
SHALL NOT BE
CONSIDERED IN
DETERMINING
KNEE AND TOE
CLEARANCES
SIDE VIEWPLAN VIEW
EQ EQ
PROVIDE A CLEAR FLOOR SPACE
POSITIONED FOR A FORWARD
APPROACH PER DETAIL:
PROVIDE KNEE AND TOE
CLEARANCES PER DETAIL:
A830
A830
17" - 19"
M
IN
M A
X
M
IN
M
IN
35"-37"
GRAB BARS
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:2 :0
P M
C U s e rs tl m D o c u m e n ts
A R C H
C E N T R A L te h y a S J K .r v t
TLM
JAC A830
INTERIOR DETAILS -
ACCESSIBILITY
JB
20 JUL 2026
NOT TO SCALEA830
INTERIOR DETAIL - ACCESSIBILITY - ABA
2004 SECT 302 - FLOOR SURFACES
NOT TO SCALEA830
INTERIOR DETAIL - ACCESSIBILITY - ABA
2004 SECT 303 - CHANGES IN LEVEL
NOT TO SCALEA830
INTERIOR DETAIL - ACCESSIBILITY - ABA
2004 SECT 304 - TURNING SPACE
NOT TO SCALEA830
4 INTERIOR DETAIL - ACCESSIBILITY - ABA 2004 SECT 305 - CLEAR FLOOR SPACE
NOT TO SCALEA830
5 INTERIOR DETAIL - ACCESSIBILITY - ABA 2004 SECT 306 - KNEE AND TOE CLEARANCES
NOT TO SCALEA830
6 INTERIOR DETAIL - ACCESSIBILITY - ABA 2004 SECT 307 - PROTRUDING OBJECTS
NOT TO SCALEA830
7 INTERIOR DETAIL - ACCESSIBILITY - ABA 2004 SECT 308 - REACH RANGES
NOT TO SCALEA830
INTERIOR DETAIL - ACCESSIBILITY - ABA
2004 SECT 309 - OPERABLE PARTS
1/2" = 1'-0"A830
9 INTERIOR DETAIL - ACCESSIBILITY - ABA 2004 SECT 604 - WATER CLOSET
1/2" = 1'-0"A830
INTERIOR DETAIL - ACCESSIBILITY - ABA
2004 SECT 606 - LAVATORY
0'
GRAPHICS SCALE: 1/2" = 1'-0"
1'-0" 2'-0" 4'-0" 0'
GRAPHICS SCALE: 1/2" = 1'-0"
1'-0" 2'-0" 4'-0"
1/2" = 1'-0"A830
INTERIOR DETAIL - ACCESSIBILITY - ABA
2004 SECTION 604 - AMBULATORY
ACCESSIBLE TOILET COMPARTMENT
0'
GRAPHICS SCALE: 1/2" = 1'-0"
1'-0" 2'-0" 4'-0"
A K
AF AL
T S
T A
E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S
I G N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESSIONAL
ARC
H
IT
E C
GENERAL STRUCTURAL NOTES
F. STEEL DECK
1. STEEL DECK INSTALLATION SHALL COMPLY WITH ALL MANUFACTURER'S REQUIREMENTS AND THE STEEL
DECK INSTITUTE'S SPECIFICATIONS FOR FABRICATION AND ERECTION.
2. WELDING OF STEEL DECK IS TO BE DONE BY CERTIFIED WELDERS EXPERIENCED IN WELDING LIGHT GAUGE
STEEL DECK.
3. BUILDING SYSTEMS & EQUIPMENT HUNG FROM STEEL DECK SHALL BE LIMITED TO SUSPENDED ACOUSTICAL
CEILINGS AND LIGHTWEIGHT DUCT WORK UNLESS SPECIFICALLY APPROVED BY THE STRUCTURAL
ENGINEER.
G. GENERAL
1. CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS TO MATCH NEW CONSTRUCTION TO
EXISTING CONSTRUCTION.
2. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO: BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION VISITS TO THE SITE
INCLUDE INSPECTION OF THESE ITEMS.)
3. STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND ARE INTENDED TO BE USED WITH ARCHITECTURAL, CIVIL, MECHANICAL, AND ELECTRICAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE REQUIREMENTS FROM THESE DISCIPLINES INTO THEIR SHOP DRAWINGS AND WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
5. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOADS SHALL NOT EXCEED THE LISTED DESIGN SNOW LOAD OF THE ROOF OR THE LIVE LOAD OF ELEVATED FLOORS.
6. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL WITH THE APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO
CONSTRUCTION.
7. DO NOT USE SCALED DIMENSIONS TAKEN FROM STRUCTURAL DRAWINGS. CONTACT CONTRACTING OFFICER
IF DIMENSIONAL INFORMATION IS MISSING.
8. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL OF A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALASKA.B. CONCRETE
1. GENERAL:
A. ALL CAST-IN-PLACE CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF 4,500 PSI.
B. CONCRETE SHALL MEET ALL REQUIREMENTS OF ACI 301 SPECIFICATION FOR STRUCTURAL CONCRETE BUILDINGS.
C. ALL PERMANENTLY EXPOSED CONCRETE EDGES TO BE CHAMFERED 3/4", UNO.
D. PROVIDE SLEEVES FOR ALL UTILITY OPENINGS.
E. DIMENSIONS SHOWN ON DRAWING SHALL SUPERSEDE THOSE SHOWN ON GENERAL NOTES.
2. REINFORCING:
A. REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 60, UNLESS OTHERWISE NOTED, EXCEPT #3 BARS
WHICH MAY BE GRADE 40. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185.
B. DETAIL REINFORCING BARS IN ACCORDANCE WITH THE ACI DETAILING MANUAL AND THE ACI BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE, LATEST EDITION.
C. HORIZONTAL FOUNDATION AND WALL REINFORCING SHALL BE CONTINUOUS AROUND CORNERS AND
INTERSECTIONS; PROVIDE CORNER BARS.
D. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORCING AT POSITIONS SHOWN ON THE DRAWINGS.
PROVIDE SUFFICIENT TIE BARS TO SUPPORT ALL REINFORCING.
E. DO NOT CUT ANY REINFORCEMENT AT OPENINGS.
F. UNLESS A REINFORCING SPLICE, CLEAR DISTANCE BETWEEN REINFORCING SHALL NOT BE LESS THAN 1.5 BAR
DIAMETERS NOR LESS THAN 1 1/2''.
G. MINIMUM LAP SPLICE LENGTHS FOR REINFORCING BARS SHALL BE AS FOLLOWS:
a. SPLICES WITH 12” OR MORE OF FRESH CONCRETE PLACED BENEATH: 80 BAR DIAMETERS
b. ALL OTHER SPLICES: 62 BAR DIAMETERS
H. PROVIDE REINFORCEMENT COVER AS FOLLOWS (ACI 7.7), UNLESS NOTED OTHERWISE ON DRAWINGS:
a. CONCRETE POURED AGAINST EARTH ..................... 3" ±3/8"
b. CONCRETE NOT POURED AGAINST EARTH: ........... 1 1/2" ±3/8"
c. CONCRETE SLABS ON GRADE .................................. PLACE REINFORCING AT SLAB MID-DEPTH
C. STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL WIDE FLANGE MEMBERS AND CHANNELS SHALL BE A992 (Fy = 50 KSI).
2. SQUARE/RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500 GRADE C (Fy = 50 KSI).
3. ANGLES, PLATES, AND BARS SHALL BE ASTM A572 (Fy = 50 KSI).
4. ALL STRUCTURAL STEEL SHALL BE DETAILED AND FABRICATED IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC
STEEL CONSTRUCTION MANUAL.
5. BOLTED CONNECTIONS SHALL BE ACCOMPLISHED WITH HIGH-STRENGTH BOLTS CONFORMING TO ASTM A325 IN
STANDARD HOLES UNLESS NOTED OTHERWISE.
6. ALL BOLTED CONNECTIONS SHALL BE PRE-TENSIONED UNLESS NOTED OTHERWISE.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF ALL ERECTION PROCEDURES AND SEQUENCES WITH
REGARD TO TEMPERATURE DIFFERENTIALS.
8. WELDING SHALL BE PERFORMED WITH E70XX ELECTRODES. WELDING SHALL BE DONE BY QUALIFIED WELDERS AND
SHALL CONFORM TO THE AWS D1.1 STRUCTURAL WELDING CODE-STEEL, LATEST EDITION. ALL WELDS ARE INTENDED TO
BE CONTINUOUS UNLESS NOTED OTHERWISE.
9. FIELD WELDS NOTED THROUGHOUT THE CONTRACT DOCUMENTS ARE ACCEPTABLE LOCATIONS FOR FIELD WELDING AT
THE CONTRACTOR'S OPTION. FIELD WELDS MAY BE PERFORMED IN THE SHOP.
A. DESIGN CRITERIA
ALL NEW WORK SHOWN HAS BEEN DESIGNED TO FOLLOWING:
1. BUILDING CODE........................................................................................ 2024 IBC (INTERNATIONAL BUILDING CODE)
2024 IEBC (INTERNATIONAL EXISTING BUILDING CODE)
RISK CATEGORY...................................................................................... II
2. DEAD LOADS
ROOF VEGETATED AREA*......................................................... 80.5 PSF
*NOTE: SUPERIMPOSED DEAD LOAD LISTED, STRUCTURE SELF-WEIGHT & METAL DECK NOT INCLUDED.
3. SNOW LOADS
NEW AND REPLACED ELEMENTS:
GROUND SNOW LOAD Pg-LRFD..................................... 258 PSF GROUND SNOW LOAD Pg-ASD...................................... 181 PSF FLAT ROOF SNOW LOAD Pf-LRFD................................. 258 PSF FLAT ROOF SNOW LOAD Pf-ASD................................... 181 PSF SNOW EXPOSURE FACTOR Ce................................... N/A SNOW LOAD IMPORTANCE FACTOR Is...................... N/A THERMAL FACTOR Ct................................................... N/A
WINTER WIND PARAMETER W2.................................. N/A
EXISTING ELEMENTS (VISITOR CENTER & UTILITY BUILDING)
GROUND SNOW LOAD Pf-ASD ..................................... 140 PSF (PER 2005 AS-BUILTS)
4. LIVE LOADS (PER 2005 AS-BUILTS)
MECHANICAL ROOMS............................................................... 125 PSF ALL OTHER AREAS.................................................................... 100 PSF
5. RAIN LOADS
RAIN LOAD INTENSITY i............................................................ 2.64 IN/HR
6. WIND LOADS
ULTIMATE DESIGN WIND SPEED VULT..................................... 110 MPH
NOMINAL DESIGN WIND SPEED VASD...................................... 85 MPH
EXPOSURE.................................................................................. C INTERNAL PRESSURE COEFFICIENT GCpi.............................. 0.18
7. EQUIPMENT SEISMIC LOADS
IMPORTANCE FACTOR Ie............................................................ 1.0
SEISMIC DESIGN CATEGORY.................................................... D
SITE CLASS.................................................................................. C BASIC SEISMIC FORCE RESISTING SYSTEM........................... ORDINARY STEEL MOMENT FRAMES
RESPONSE MODIFICATION FACTOR R.................................... 3.5
OVER STRENGTH FACTOR FOR THE BUILDING Ω0 ............... 3.0
SS................................................................................................... 1.59 S1................................................................................................... 0.67 SDS................................................................................................. 1.11 SD1................................................................................................. 0.61
E. POST-INSTALLED ANCHORS
POST-INSTALLED ANCHORS SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE:
CONCRETE
ADHESIVE ANCHORS:
• INTERIOR: HILTI HIT-RE 500 V3 OR RED HEAD C6+, ASTM F1554 GRADE
36 THREADED ROD
• EXTERIOR: HILTI HIT-RE 500 V3 OR RED HEAD C6+, 304 OR 316
STAINLESS THREADED ROD
SCREW ANCHORS
• INTERIOR: HILTI KH-EZ OR SIMPSON TITEN HD
• EXTERIOR: SIMPSON TITEN HD, 316 STAINLESS
1. INSTALL POST-INSTALLED ANCHORS ONLY AS INDICATED ON THE DRAWINGS.
2. THE CONTRACTOR MAY NOT USE SUBSTITUTES FOR THE POST-INSTALLED ANCHORS.
3. SEE DRAWINGS FOR ANCHOR TYPE, SIZE, AND EMBEDMENT DEPTHS. INSTALL ANCHORS AS OUTLINED IN
MANUFACTURER'S SPECIFICATIONS AND ICC REPORTS. UTILIZE PROPER DRILL TYPE, BIT SIZE, AND HOLE
CLEANING, DRIVING OR TIGHTENING TECHNIQUES, UNLESS NOTED OTHERWISE.
D. COLD FORMED METAL FRAMING
1. MATERIAL USED TO MANUFACTURE COLD FORMED METAL FRAMING SHALL MEET THE MINIMUM REQUIREMENTS LISTED
BELOW:
A. 43 MIL (18 GAUGE) AND LIGHTER: ASTM C955, GRADE 33 (Fy = 33 KSI) B. 54 MIL (16 GAUGE) AND HEAVIER: ASTM C955, GRADE 50 (Fy = 50 KSI)
2. ALL STRUCTURAL MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITH THE AMERICAN IRON AND STEEL (AISI) "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS," LATEST EDITION W/
SUPPLEMENTS
3. ACCESSORIES: PROVIDE ALL ACCESSORIES INCLUDING, BUT NOT NECESSARILY LIMITED TO TRACKS, CLIPS, WEB STIFFENERS, BRIDGING, ANCHORS, FASTENING DEVICES, RESILIENT CLIPS, AND OTHER ACCESSORIES REQUIRED FOR A COMPLETE AND PROPER INSTALLATION, AND AS RECOMMENDED BY THE MANUFACTURER FOR THE STEEL MEMBER.
4. FASTENING OF COMPONENTS SHALL BE WITH SELF-DRILLING SCREWS. SCREWS SHALL BE OF SUFFICIENT SIZE TO ENSURE THE STRENGTH OF THE CONNECTION. WIRE TYING OF COMPONENTS SHALL NOT BE PERMITTED. SCREW
FASTENERS TO TREATED WOOD SHALL BE STAINLESS STEEL.
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:0 :0
P M
C R e v it
B a c k u p s S T R U N P S A L L te s s a Y T S T Z .r v t
TAA
PSB S001
STRUCTURAL GENERAL NOTES
TAA
20 JUL 2026
+16 -24 +16 -43 +16 -56 +16 -76 +24 -26 +24 -32
POS NEG POS NEG POS NEG POS NEG POS NEG POS NEG
ZONE 1' ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
COMPONENTS AND CLADDING ULTIMATE DESIGN PRESSURE IN PSF FOR EFFECTIVE AREA OF 0-10 SF ARE LISTED
(SEE FIG 30.4-1 THROUGH 30.4-7, ASCE 7-22)
LOWER PRESSURES USING LARGER EFFECTIVE AREAS AS DEFINED BY ASCE 7-22 ARE PERMITTED
LISTED PRESSURES CAN BE CONVERTED TO ASD LOADS BY APPLYING A LOAD FACTOR OF 0.6
WIND LOADING ZONE PRESSURES
A K
AF AL
T S
TA
E O
49 TH
S
Patrick S. Brandon
SE 141370
D E S
I G N
A L
A S
K A
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
R
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:0 :0
P M
C R e v it
B a c k u p s S T R U N P S A L L te s s a Y T S T Z .r v t
TAA
PSB S002
SPECIAL INSPECTIONS
TAA
20 JUL 2026
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCYSYSTEM OR MATERIAL
INSPECTION
REMARKS
PERIODIC: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING
PERFORMED.
CONTINUOUS: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED.
THE FOLLOWING STRUCTURAL ITEMS REQUIRE SPECIAL INSPECTION PER IBC SECTIONS 1704-1707.
SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR INSPECTION AND TESTING THAT ARE NOT PART OF SPECIAL INSPECTIONS.
SPECIAL INSPECTIONS
WPS FOLLOWED PLAN FOR
ENVIRONMENTAL CONDITIONS
AISC 360-16: TABLE N5.4-2 X
WIND SPEED WITHIN LIMITS, PRECIPITATION
AND TEMPERATURE
NO WELDING OVER CRACKED TACK
WELDS
AISC 360-16: TABLE N5.4-2 X
CONTROL AND HANDLING OF
WELDING CONSUMABLES
AISC 360-16: TABLE N5.4-2 X
ITEMS INCLUDE: PACKAGING AND EXPOSURE
CONTROL
FASTENERS ARE PRETENSIONED IN
ACCORDANCE WITH THE RCSC
SPECIFICATION, PROGRESSING
SYSTEMATICALLY FROM THE MOST
RIGID POINT TOWARD THE FREE
EDGES
AISC 360-16: TABLE N5.6-2 X
JOINT BROUGHT TO SNUG-TIGHT
CONDITION PRIOR TO THE
PRETENSIONING OPERATION
1705.2.1
RCSC SPECIFICATION FOR
STRUCTURAL JOINTS
BOLTS SECTION 9
AISC 306-16: TABLE N5.6-2
AISC 360: SECT. N5.6a
X
ALL CONNECTIONS INSPECTED AND VERIFIED
SNUG
DURING BOLTING/WELDING
FIT-UP OF FILLET AND GROOVE
WELDS
AISC 360-16: TABLE N5.4-1 X
JOINT PREPARATIONS, DIMENSIONS,
CLEANLINESS, TACKING, BACKING TYPE AND
FIT
MATERIAL IDENTIFICATION AISC 360-16: TABLE N5.4-1 X TYPE/GRADE
MANUFACTURER CERTIFICATIONS
FOR WELDING CONSUMABLES
AVAILABLE
AISC 360-16: TABLE N5.4-1 X
WPS AVAILABLE AISC 360-16: TABLE N5.4-1 X
WELDER QUALIFICATION RECORDS
AND CONTINUITY RECORDS
AISC 360-16: TABLE N5.4-1 X
CORRECT BOLTING PROCEDURE
AND FASTENERS SELECTED FOR
JOINT DETAIL
AISC 360-16: TABLE N5.6-1 X
GRADE, TYPE, BOLT LENGTH, IF THREADS
ARE TO BE EXCLUDED FROM SHEAR PLANE
FASTENERS MARKED IN
ACCORDANCE WITH ASTM
REQUIREMENTS
AISC 306-16: TABLE N5.6-1
RCSC SPECIFICATION FOR
STRUCTURAL JOINTS
FIGURE C-2.1
X
MANUFACTURER'S CERTIFICATIONS
AVAILABLE FOR FASTENER
MATERIALS
1705.2.1
AISC 360-16: TABLE N5.6-1 X
PRIOR TO BOLTING/WELDING
FABRICATORS
1704.2.5
1704.2.5.1
AISC 360-16: N6 X
SPECIAL INSPECTION IS REQUIRED FOR
STRUCTURAL LOAD-BEARING MEMBERS AND
ASSEMBLIES FABRICATED ON THE PREMISES
OF A FABRICATOR'S SHOP
NOTE: SPECIAL INSPECTION IS NOT
REQUIRED WHERE THE WORK IS DONE ON
THE PREMISES OF A FABRICATOR
REGISTERED AND APPROVED TO PERFORM
SUCH WORK WITHOUT SPECIAL INSPECTION
FABRICATORS
DIVISION #05 - STRUCTURAL STEEL
INSTALLATION OF ROOF DECKING 1705.1.1 ICC EVALUATION REPORT X
SPECIAL INSPECTIONS APPLY TO DECKING
TYPE, DEPTH AND GAUGE, POWER
ACTUATED FASTENERS, SCREWS,
PROPRIETARY SIDE SEAM ATTACHMENTS,
BUTTON PUNCHES, AND SHEAR
CONNECTORS
METAL DECK AND DIAPHRAGM
DIVISION #05 - OTHER METALS
HIGH STRENGTH BOLTING:
PRETENSIONED AND SLIP-CRITICAL
JOINT HIGH-STRENGTH BOLT
INSTALLATION USING
TURN-OF-THE-NUT METHOD WITH
MATCH MARKING, TWIST-OFF BOLT,
OR DIRECT TENSION INDICATOR
METHOD
1705.2.1
RCSC SPECIFICATION FOR
STRUCTURAL JOINTS
USING ASTM A325 OR A490
BOLTS SECTION 9
AISC 360, SECTION M2.5,
N5.6b, TABLE N5.6-2
X
ALL CONNECTIONS INSPECTED AFTER
SNUGGING AND AGAIN AFTER
PRETENSIONING
NO PROHIBITED WELDS HAVE BEEN
ADDED WITHOUT THE APPROVAL OF
THE EOR
AISC 360-16: TABLE N5.4-3 X
REPAIR ACTIVITIES AISC 360-16: TABLE N5.4-3 X
BACKING REMOVED AND WELD TABS
REMOVED
AISC 360-16: TABLE N5.4-3 X REMOVE TABS IF REQUIRED
ARC STRIKES AISC 360-16: TABLE N5.4-3 X
WELDS MEET VISUAL ACCEPTANCE
CRITERIA
AISC 360-16: N5.4, TABLE
N5.4-3
X
SIZE, LENGTH, AND LOCATION OF
WELDS
AISC 360-16: TABLE N5.4-3 X
WELDS CLEANED AISC 360-16: TABLE N5.4-3 X
DOCUMENT ACCEPTANCE OR
REJECTION OF BOLTED
CONNECTIONS OR WELDED JOINT
OR MEMBER
1705.2.1
AISC 360-16: TABLE N5.6-3,
TABLE N5.4-3
X
AFTER BOLTING/WELDING
DIVISION #05 - STRUCTURAL STEEL, CONTINUED
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE OR STANDARD
REFERENCE
FREQUENCYSYSTEM OR MATERIAL
INSPECTION
REMARKS
SPECIAL INSPECTIONS, CONTINUED
A NOMINAL CLEARANCE OF NOT
LESS THAN 3" HAS BEEN PROVIDED
BETWEEN FIRE PROTECTION
SPRINKLER SYSTEM DROPS &
SPRIGS AND: STRUCTURAL
MEMBERS NOT USED TO SUPPORT
THE SPRINKLERS, EQUIPMENT
ATTACHED TO THE BUILDING
STRUCTURE, AND OTHER SYSTEMS'
PIPING
1705.13.6.6 X
CLEARANCES LESS THAN 3" MAY BE SHOWN
ACCEPTABLE IF THE CONTRACTOR'S
ENGINEER CAN SHOW THAT THE PROVISIONS
OF ASCE 7 SECTION 13.2.4 ARE MET.
EXCEPTION: SPRINKLERS INSTALLED USING
FLEXIBLE SPRINKLER HOSE NEED NOT MEET
THE INSTALLED CLEARANCE REQUIREMENT
OF THIS SECTION
AUTOMATIC FIRE SPRINKLER SYSTEMS
NON-STRUCTURAL SPECIAL INSPECTIONS
A K
AF AL
T S
TA
E O
49 TH
S
Patrick S. Brandon
SE 141370
D E S
I G N
A L
A S
K A
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
A
B C D E F G H J
K L
M N
XA
XB
XC
XD
XE X1
X2
X3
X4
S110
S110
TYP (3)
SIDES
S110
W 10x22
W 10x22
C
X30
C
X30
C
X30 C X
. 8
C 10X30
Pip e4
STD
W x1
S110 3
S110
SIM
SIM
W x
W x
W x
W x
W x
W x
W x
W21x44
W 8x15
W 8x15
C10X30 C10X30 C10X30 C10X30 C10X30 C10X30 C10X30
S110
S110
S110
S110
OPP
S110
OPP
(E) SKYLIGHT ENCLOSURE TO BE REMOVED DOWN TO METAL DECK
MAINTAIN (E) FRAMING BELOW DECK
TYP (16) LOCATIONS
HSS4X4X1/4
HSS5X5X1/4
HSS5X5X1/4
W8X31, TYP
W8X31, TYP
HSS4X4X1/4
HSS4X4X1/4
S111
48' - 0"
/4
11' - 10"
S110
C10X30
DEMOLITION LEGEND
MEMBER/ITEM TO BE DEMOLISHED
EXISTING TO REMAIN
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:0 :0
P M
C R e v it
B a c k u p s S T R U N P S A L L te s s a Y T S T Z .r v t
TAA
PSB S100
ROOF DEMOLITION PLAN
TBT
20 JUL 2026
1/8" = 1'-0"S100
1 DEMOLITION PLAN
GENERAL NOTES
1. CONTRACTOR MAY USE (E) STRUCTURAL STEEL FRAMING FOR NEW WORK.
0'
GRAPHICS SCALE: 1/8" = 1'-0"
4' - 0" 8' - 0" 16' - 0"
A K
AF AL
T S
TA
E O
49 TH
S
Patrick S. Brandon
SE 141370
D E S
I G N
A L
A S
K A
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
X1 X2
UPPER ROOF
3742'-9"
BOD
VARIES
SAWCUT PRECAST CONCRETE WALL
AND STEEL COLUMNS TO (E) BOTTOM
OF DECK ELEVATION AND MATCH
EXISTING 1/4"/FT ROOF SLOPE
S110
DEMO PENTHOUSE METAL DECK
DEMO HSS COLUMNS TO LOWER
ROOF T.O.S., (4) 3/4" BOLTS AT
BASE PLATE TOP AND BOTTOM
(TYP)
DEMO PENTHOUSE STEEL
ABOVE ADJACENT
LOWER ROOF T.O.S.
REMOVE PIPE WELDED TO
UNDERSIDE OF BEAMS
NOTE:
CONTRACTOR TO DESIGN & CONSTRUCT TEMPORARY SHORING OF
(E) CONCRETE RETAINING WALL PRIOR TO DEMOLITION & REMOVE
ONLY AFTER NEW ROOF STRUCTURE & DECKING IS COMPLETE.
DEMO TO MATCH TOP OF
ADJACENT CHANNEL SAWCUT PRECAST
CONCRETE WALL AND STEEL
COLUMNS TO MATCH
EXISTING 1/4"/FT ROOF SLOPE
UPPER ROOF
3742'-9"
UPPER ROOF
3742'-9"
REMOVE CFS SHEAR WALL
CUT LEG OF ANGLE OFF TO BE
FLUSH WITH OTHER LEG OR
REMOVE COMPLETELY
DEMO HSS TO LOWER ROOF TOS
DEMO CFS WALL TO TOP OF METAL DECK
PATCH HOLE IN
METAL DECK
NOTE:
SEE ARCH PLANS FOR WALL LOCATIONS
DEMO 1"⌀ ROD BRACING AND
GUSSET PLATES FLUSH TO
LOWER ROOF T.O.S
DEMO PENTHOUSE STEEL ABOVE
ADJACENT LOWER ROOF T.O.S.
UPPER ROOF
3742'-9"
BOD
VARIES
DEMO PENTHOUSE METAL DECK
SAWCUT PRECAST CONCRETE WALL
AND STEEL COLUMNS TO (E) BOTTOM
OF DECK ELEVATION AND MATCH
EXISTING 1/4"/FT ROOF SLOPE
S110
NOTE:
CONTRACTOR TO DESIGN & CONSTRUCT TEMPORARY SHORING OF
(E) CONCRETE RETAINING WALL PRIOR TO DEMOLITION & REMOVE
ONLY AFTER NEW ROOF STRUCTURE & DECKING IS COMPLETE.
S110
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:0 :0
P M
C R e v it
B a c k u p s S T R U N P S A L L te s s a Y T S T Z .r v t
TAA
PSB S110
DEMOLITION DETAILS
TBT
20 JUL 2026
3/4" = 1'-0"S110
1 MECHANICAL PENTHOUSE - DEMO SECTION
1" = 1'-0"S110
2 DEMO PCC PANEL WALL - ROOF STEP DETAIL
1" = 1'-0"S110
3 DEMO PENTHOUSE CFS SHEAR WALL
1" = 1'-0"S110
6 DEMO ROOF MOUNTED CFS WALL AND HSS
3/4" = 1'-0"S110
5 DEMO BRACING AT WEST PENTHOUSE
3/4" = 1'-0"S110
4 WEST PENTHOUSE - DEMO SECTION
0'
GRAPHICS SCALE: 3/4" = 1'-0"
0' - 6" 1' - 0" 2' - 0"
0'
GRAPHICS SCALE: 1" = 1'-0"
0' - 6" 1' - 0" 2' - 0"
A K
AF AL
T S
TA
E O
49 TH
S
Patrick S. Brandon
SE 141370
D E S
I G N
A L
A S
K A
R E
G
IS
T
ERED
STRUCTURAL
EN
G
IN
E E
DEMOLISH CMU WALLS, CFS
FRAMING, AND HSS SUPPORTS,
EXTENT PER ARCH
DEMOLISH (E) CONCRETE STAIR &
STRUCTURAL STEEL STRINGERS
(BEYOND)
STAIR DEMOLITION BEYOND
BUILDING FOOTPRINT PER
LANDSCAPE
DEMOLISH (E) ICF WALL, EXTENT PER PLAN
SAW CUT WALL TO 14" ABOVE (E) GRADE
DEMOLISH (E) STONE WALL ATOP ICF WALL, SEE
CIVIL DRAWINGS FOR SALVAGE NOTES
DEMOLISH (E) ICF WALL TO ADJACENT GRADE
DETACH STRINGER
FROM GIRDER
SAWCUT CONCRETE
ANCHORS AS REQUIRED TO
REMOVE STAIR ASSEMBLY
DEMOLISH COMPLETE
UPPER STAIR ASSEMBLY
T.O. ICF WALL
3734' - 2"
(E) ICF WALL TO REMAIN
(E) ROOF DECK TO REMAIN
DEMO EXTERIOR STAIRS PER LANDSCAPE
1ST FLOOR
3728' - 0"
DEMO (E) ICF WALL TO 1'-6" ABOVE
FINISHED FLOOR TO MATCH ADJACENT (E)
PIER FOUNDATION
M N
S111
STAIR DEMOLITION BEYOND
BUILDING FOOTPRINT PER ARCH
REUSE (E) HSS POST FOR
INFILL WHERE POSSIBLE
3' - 6"
(VIF)
13' - 3"
DEMO (E) ICF WALL SEE ISO FOR EXTENTS
DEMOLISH (E) MANSARD ROOF
AS REQUIRED FOR DEMO (E)
MASONRY VENEER
165633
TECH. REVIEW:
DATE:
DESIGNED: SUB SHEET NO.
SHEET
DRAWING NO.
OF
TITLE OF SHEET
PMIS
NO.
REHABILITATION OF THE EIELSON VISITOR CENTER
DENALI NATIONAL PARK AND PRESERVE
A/E FIRM:
PRIME:
DESIGN ALASKA,
601 COLLEGE RD,
FAIRBANKS,
AK 99701
907.452.1241
AECC511
R E V
IT
227793A
332037A
332037C7
:0 :1
P M
C R e v it
B a c k u p s S T R U N P S A L L te s s a Y T S T Z .r v t
TAA
PSB S111
DEMOLITION DETAILS
PSB
20 JUL 2026
S111
3 STAIR INFILL - DEMOLITION ISOMETRIC
3/4" = 1'-0"S111
2 STAIR DEMOLITION SECTION
1/2" = 1'-0"S111
1 STAIR DEMOLITION PLAN
0'
GRAPHICS SCALE: 3/4" = 1'-0"
0' - 6" 1' - 0" 2' - 0"
0'
GRA…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .