DRAFT_B2_03.13_Certificate_of_Conformity_2RGA031447.pdf

PDF 555 KB Posted

Attached to
SLAC CUIR SP1 Master Substation Annex Building Construction
Solicitation number
SLAC_RFP_368509
Issued by

About this file

This document is a Declaration of Conformity certifying compliance with IEEE standards for electrical equipment manufactured by ABB.

The apparatus described is a SafeGear medium voltage, metal-clad, air-insulated switchgear rated for 15 kilovolts with a 3000-ampere capacity and 50-kiloampere short-circuit rating. The switchgear is designated as Type 2B with a 30-cycle rating and operates at 60 hertz frequency. Key electrical ratings include a lightning impulse withstand voltage of 95 kilovolts, power-frequency withstand voltage of 36 kilovolts, rated peak withstand current of 130 kiloamperes, and rated short-time withstand current of 50 kiloamperes with a 2-second duration. The internal arc duration rating is 0.5 seconds.

The declaration documents comprehensive type tests performed according to IEEE C37.20.2-2015 and IEEE C37.20.7-2007 standards, including power frequency withstand voltage, lightning impulse withstand voltage, bus-bar insulation, continuous current, momentary and short-time withstand current testing on primary and ground buses, mechanical endurance, insulating material qualification, coating qualification, and internal arc testing. Testing was conducted by accredited laboratories including LAPEM (Irapuato, Mexico), ABB Inc. (Lake Mary, Florida), and KEMA Laboratories (Chalfont, Pennsylvania). The document is dated 12.20.2023 and issued by ABB's Technology Center in Mebane, North Carolina, which maintains ISO 9001:2015 certification.

View the file

Other files

File Type Posted
DRAFT_B2_02_RFP_Section_B_(Supplies or Services and Price_Costs.pdf PDF
DRAFT_B2_03.14_FGC_Warranty_Certificate.pdf PDF
DRAFT_B2_03.11_Installation_Operation_and_Maintenance_Manuals.pdf PDF
DRAFT_B2_08.1_WD_CA20260018_17SEPT26_Mod_08.pdf PDF
DRAFT_B2_03.07_RPC-DEMO_Metal_Plates_Location_SKETCH_08.12.2026.pdf PDF
DRAFT_B2_10.2_Section_L_Attachment_B_SLAC_Question&Answer_Log_(RFI).pdf PDF
DRAFT_B2_10.1_Section_L_Attachment_A_Proposal_Breakdown_Sheet.pdf PDF
DRAFT_B2_03.04_CUIR_Subproject_1_Power_Outages_and_Linac_Downtime_Plan.pdf PDF
DRAFT_B2_03.08_00_Appendix_I_Technical_Data_Submittal.pdf PDF
DRAFT_B2_05.1_Fixed_Price_Construction_March2024.pdf PDF
DRAFT_B2_09.1_Reps_and_Certs_Supplement.pdf PDF
DRAFT_B2_08.7_Final_Inspection_Report.pdf PDF
DRAFT_B2_08.4_Small_Business_Subcontracting_Plan_Form.pdf PDF
DRAFT_B2_08.8_Construction_Subcontracts_Final_Release.pdf PDF
DRAFT_B2_03.00_RFP_Section_C_(Specifications_SOW).pdf PDF
DRAFT_B2_03.02_MSS_B016_Expansion_100pct Combined_Plans.pdf PDF
DRAFT_B2_00_Cover_Letter.pdf PDF
DRAFT_B2_03.01_SOW_CUIR-SW-0203.pdf PDF
DRAFT_B2_08.3_SF1413.pdf PDF
DRAFT_B2_11_Section_M_Evaluation_Methodology.pdf PDF
DRAFT_B2_03.12_Certified_Test Reports_SWGR9_SWGR8.pdf PDF
DRAFT_B2_08.5_SubcontractorFormSQF.pdf PDF
DRAFT_B2_03.06_Department_of_Energy_(DOE)_Order_414.1E_Quality_Assurance.pdf PDF
DRAFT_B2_03.10_As-Built_SWGR9_SWGR8.pdf PDF
DRAFT_B2_08.6_NTP_Submittal_Checklist.pdf PDF
DRAFT_B2_08.2_Injury_Illness_Prevention_Plan_Acknowledgement_Form_IIPP.pdf PDF
DRAFT_B2_06_RFP_Section_H_(Special_TsCs).pdf PDF
DRAFT_B2_05.0_RFP_Section_G_(General_TsCs).pdf PDF
DRAFT_B2_01_RFP_Section_A_(Subcontract_Form).pdf PDF
DRAFT_B2_03.03_Commissioning_Plan.pdf PDF
DRAFT_B2_10.0_Section_L_Instruction_to_Offerors.pdf PDF
DRAFT_B2_03.05_CUIR's_Quality_Requirements_for_Subcontractors.pdf PDF
DRAFT_B2_04_RFP_Section_F_(Deliveries Performance).pdf PDF
DRAFT_B2_03.09_01_Packaging_Procedure_1VAM-T0004-020086_MV_Switchgear_Shipping_Preparation-2.pdf PDF
DRAFT_B2_07_RFP_Section_I_(Specific Subcontract Clauses).pdf PDF
DRAFT_B2_09.0_RFP_Section_K_(Rep and Certs).pdf PDF
DRAFT_B2_08.0_RFP_Section_J_(List of Attachments).pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Declaration of Conformity 2RGA031447 according to IEEE Standards UL File # E143324

Apparatus: Medium Voltage, Metal-clad, Air Insulated switchgear type SafeGear

Identification: SafeGear 15kV, 3000A, 50kA, Type 2B, 30Cycle

Ratings: Rated voltage: 15 Rated lightning impulse withstand voltage: 95 Rated power-frequency withstand voltage: 36 Rated frequency: 60 Rated normal current (busbar): 3000 Rated normal current (breaker): 3000 Rated peak withstand current: 130 Rated short time withstand current: 50 Rated duration of short-circuit: 2 Accessibility Type 2B Internal arc duration 0.5 kV kV kV Hz A A kA kA s sec

The assigned reports document type tests, which were carried out according to the below mentioned standards:

Type tests Test according to Test reports No. / Date Issued by

Power frequency withstand voltage test:

IEEE C37.20.2-2015

Subclause: 6.2.1.1

K3421-98I-2021/2021 LAPEM Irapuato, Gto.

Lightning Impulse withstand voltage test:

IEEE C37.20.2-2015

Subclause: 6.2.1.2

BIL-20141120-LMA/2014 ABB Inc. Lake Mary, FL.

Test for bus-bar Insulation, bus joint Insulation, and bus tap Insulation

IEEE C37.20.2-2015

Subclause: 6.2.1.3

K3421-98F-2021 /2021 LAPEM Irapuato, Gto.

Continuous current IEEE C37.20.2 -2015 Subclause: 6.2.2

CC-20180406-LMA/2018 ABB Inc. Lake Mary, FL.

Momentary withstand current on primary bus and connections

IEEE C37.20.2-2015

Subclause: 6.2.3.1

K3422-046A-2021/2021, K3421-98H-2021/2021.

LAPEM Irapuato, Gto.

Momentary withstand current on Ground bus

IEEE C37.20.2 - 2015

Subclause: 6.2.3.2

K3422-046B-2021/2021, K3421-98G-2021/2021.

LAPEM Irapuato, Gto.

Short time withstand current on primary bus and connections:

IEEE C37.20.2 - 2015

Subclause: 6.2.4.1

K3422-046A-2021/2021 K3421-98H-2021/2021

LAPEM Irapuato, Gto.

Short time withstand current on Ground bus:

IEEE C37.20.2 - 2015

Subclause: 6.2.4.2

K3422-046B-2021/2021 K3421-98G-2021/ 2021

LAPEM Irapuato, Gto.

Mechanical Endurance IEEE C37.20.2 – 2015, Subclause: 6.2.6

ME-20161031-LM-A/

ABB Inc. Lake Mary, FL.

Tests for Insulating materials

IEEE C37.20.2 – 2015,

Subclause: 6.2.7

2RGA030877 / 2021 ABB S.L.P, Mexico

Coating qualification tests IEEE C37.20.2 – 2015, Subclause: 6.2.8

2RGA030879 / 2021 ABB S.L.P, Mexico

Internal arc test IEEE C37.20.7 – 2007, Section 5-6

17126-B1 / 2017 17126-B3 / 2017 17180-B /2017 18122-B /2018

KEMA Chalfont, PA

KEMA Laboratories Chalfont is accredited according to DIN EN ISO/IEC 17025.

LAPEM is accredited according to DIN EN ISO/IEC 17025.

ABB Lake Mary,Florida, USA was an ABB Internal ISO 9001 Certified lab.

ABB Mebane, North Carolina, USA is accredited test lab according to DIN EN ISO/IEC 17025 & UL DAP ABB S.L.P. Mexico is an ABB Internal ISO 9001 Certified lab.

ABB Florence, South Carolina, USA is an ABB Internal ISO 9001 Certified lab.

ABB Dalmine, Italy is an accredited test lab according to ISO/IEC 17025.

Date of issue:

12.20.2023

Quality management:

Diego Pena

Technology Center:

Babu Sankar

Manufacturer address: 6801, Industrial drive, Mebane, North Carolina 27302. ISO 9001: 2015 certified.

Telephone 919 563 5561

Web address: www.abb.com/mediumvoltage