DRAFT_B2_03.10_As-Built_SWGR9_SWGR8.pdf

PDF 13 MB Posted

Attached to
SLAC CUIR SP1 Master Substation Annex Building Construction
Solicitation number
SLAC_RFP_368509
Issued by

About this file

This file is a collection of technical drawings, specifications, and bill of materials for an ABB SafeGear indoor switchgear assembly designated as SWGR-9, a 15kV, 3000A, 50kA, 3-phase, 3-wire, 60Hz medium-voltage switchgear system intended for installation at SLAC National Accelerator Laboratory.

The switchgear configuration includes nine operational cubicles (Cubicles 01-09) plus one remote panel cubicle (Cubicle 10), totaling approximately 326 inches in length with a main bus rating of 3000A at 12.47kV and a withstand current of 50kA. The system comprises multiple circuit breakers with varying ratings: four 1200A ADVAC drawout breakers (Model 4, 15kV, 50kA, 3-cycle), four 2000A breakers, and three 3000A breakers, all UL-recognized and equipped with 125VDC motors and coils. The electrical bill of materials specifies current transformers (multi-ratio SAB-1 and SAB-2 types with 2000/300-5A and 3000/300-5A configurations), potential transformers (12.47kV-120V, 110kV BIL), protective relays (SEL-751 feeders relays with arc-sense capability and SEL-587Z high-impedance differential protection), metering devices (SEL-735 power quality meters in multiple locations), and extensive terminal blocks, wire harnesses, fuses, and control devices. The system features porcelain bushings, epoxy-coated breaker primary bushings rated to 63kA, fiber-optic arc-flash sensors, and a real-time automation controller (SEL-3350) with Ethernet switching capability. The switchgear is designed for IEEE Type 2B indoor, gasketed construction with rodent-proof filtered louvers, light-gray galvanized exterior, and internal epoxy coating, scheduled to ship with breakers separately and not pre-installed. Documentation indicates the unit was released for fabrication on February 8, 2024, with revisions through August 14, 2025, and requires compliance with CSA 22.2 No. 31 certification alongside UL labeling.

View the file

Other files

File Type Posted
DRAFT_B2_02_RFP_Section_B_(Supplies or Services and Price_Costs.pdf PDF
DRAFT_B2_03.14_FGC_Warranty_Certificate.pdf PDF
DRAFT_B2_03.11_Installation_Operation_and_Maintenance_Manuals.pdf PDF
DRAFT_B2_08.1_WD_CA20260018_17SEPT26_Mod_08.pdf PDF
DRAFT_B2_03.07_RPC-DEMO_Metal_Plates_Location_SKETCH_08.12.2026.pdf PDF
DRAFT_B2_10.2_Section_L_Attachment_B_SLAC_Question&Answer_Log_(RFI).pdf PDF
DRAFT_B2_10.1_Section_L_Attachment_A_Proposal_Breakdown_Sheet.pdf PDF
DRAFT_B2_03.04_CUIR_Subproject_1_Power_Outages_and_Linac_Downtime_Plan.pdf PDF
DRAFT_B2_03.08_00_Appendix_I_Technical_Data_Submittal.pdf PDF
DRAFT_B2_05.1_Fixed_Price_Construction_March2024.pdf PDF
DRAFT_B2_09.1_Reps_and_Certs_Supplement.pdf PDF
DRAFT_B2_08.7_Final_Inspection_Report.pdf PDF
DRAFT_B2_08.4_Small_Business_Subcontracting_Plan_Form.pdf PDF
DRAFT_B2_08.8_Construction_Subcontracts_Final_Release.pdf PDF
DRAFT_B2_03.00_RFP_Section_C_(Specifications_SOW).pdf PDF
DRAFT_B2_03.02_MSS_B016_Expansion_100pct Combined_Plans.pdf PDF
DRAFT_B2_00_Cover_Letter.pdf PDF
DRAFT_B2_03.01_SOW_CUIR-SW-0203.pdf PDF
DRAFT_B2_08.3_SF1413.pdf PDF
DRAFT_B2_11_Section_M_Evaluation_Methodology.pdf PDF
DRAFT_B2_03.12_Certified_Test Reports_SWGR9_SWGR8.pdf PDF
DRAFT_B2_08.5_SubcontractorFormSQF.pdf PDF
DRAFT_B2_03.06_Department_of_Energy_(DOE)_Order_414.1E_Quality_Assurance.pdf PDF
DRAFT_B2_08.6_NTP_Submittal_Checklist.pdf PDF
DRAFT_B2_03.13_Certificate_of_Conformity_2RGA031447.pdf PDF
DRAFT_B2_08.2_Injury_Illness_Prevention_Plan_Acknowledgement_Form_IIPP.pdf PDF
DRAFT_B2_06_RFP_Section_H_(Special_TsCs).pdf PDF
DRAFT_B2_05.0_RFP_Section_G_(General_TsCs).pdf PDF
DRAFT_B2_01_RFP_Section_A_(Subcontract_Form).pdf PDF
DRAFT_B2_03.03_Commissioning_Plan.pdf PDF
DRAFT_B2_10.0_Section_L_Instruction_to_Offerors.pdf PDF
DRAFT_B2_03.05_CUIR's_Quality_Requirements_for_Subcontractors.pdf PDF
DRAFT_B2_04_RFP_Section_F_(Deliveries Performance).pdf PDF
DRAFT_B2_03.09_01_Packaging_Procedure_1VAM-T0004-020086_MV_Switchgear_Shipping_Preparation-2.pdf PDF
DRAFT_B2_07_RFP_Section_I_(Specific Subcontract Clauses).pdf PDF
DRAFT_B2_09.0_RFP_Section_K_(Rep and Certs).pdf PDF
DRAFT_B2_08.0_RFP_Section_J_(List of Attachments).pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAFEGEAR JOB SPECIFICATION

Drawing No: Status:

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV 1173

Date: Date: Rev:

Rev. GENERAL INFORMATION

Sold To: FGC CONSTRUCTION LLC For: SLAC NATIONAL ACCELERATOR LAB

4916 E BROADWAY 2575 SAND HILL ROAD M/S 1

MADISON, WI 53716 MENLO PARK, CA 94025

UL Label: X IBC Cert: Nuclear Cert:

CSA 22.2, no. 31 Certification with cUL Label

Product Type:

A/R Arc Duration Time:

Rated Voltage:

System Voltage:

Main Bus Rating:

kA Rating:

System Source Type:

Freq:

Construction:

Environmental:

Seismic Reinforced: Ip=1.0

Paint Finish:

Special Color:

Undercoating:

Mimic Bus:

Swgr Breakers CT's PT's

Cert Prod Test Reports: X X X X

Cert of Conformance:

Customer Visit: Inspection Test

1VAL314911A0000

2/8/24

ANSI 61-light gray exterior galvalum interior

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

2/8/24

10 Cycle

1VALCS03149A01

3000 A

12.47kV

CBC 2019

3 Phase Wye - Solid Ground

A01

50kA

15kV

SafeGear IEEE Type 2B

Indoor Gasketed Doors/Filters

RELEASED

60 Hz

Rodent proof

None

CS03149

Sheet 1 of 4

DRAFT

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV 1173

Date: Date: Rev:

1VAL314911A0000

2/8/24

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

2/8/24

1VALCS03149A01A01

RELEASED

CS03149

Rev. MECHANICAL INFORMATION

Frame Construction

Match & Line:

Ref. S.O.

Frame Depth:

Plenum Required:

Enclosure Vent:

Rear Access:

Frame Hrdwr:

Channel Sills:

Floor Plates: X

Breaker Compartment Cable Compartment

Bkr Pri Bushing: Cable Entry:

Bkr Sec. Plug: Ground Sensors: X

TOC Switch: Surge Arrestors:

Bkr Shutters: Cable Lug Boots: X

Bkr Kirk Lock: Cable Supports: X

Bkr Door Tr/Cl PB: Gnd Studs:

Front Door Construction Heater Guards:

Front Door Hrdwr: Bus Compartment

Front Door Padlck: X Bus Plating:

Front Door Gasket: X Bus Hardware:

Front Door Stop: X Main Bus Sup'ts:

RH Hinged Cub 1: Riser Sup'ts:

SmartRack: Neutral Bus: GroundedAll MV Doors

Polyester

All Doors

Grade 5 (Zinc Chromate) Steel

Dual

8 Pole

External Strapping

92 inches

Epoxy

Screened Louvers (Rodent Proof)

Porcelain

Silver

Grade 5 (Zinc Chromate) Steel

None

Full Height Hinged Panel - Padlocked

Standard HG

Top & Bottom

None

MPL-Pull Handle

Grounded Metal

Sheet 2 of 4

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV 1173

Date: Date: Rev:

1VAL314911A0000

2/8/24

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

2/8/24

1VALCS03149A01A01

RELEASED

CS03149

Rev. ELECTRICAL INFORMATION

Wire Markers:

C.T. Wire Size:

P.T. Wire Size:

Chg/Close Wire Size:

Trip Wire Size:

AC/DC Ctrl Bus Size:

Control Lugs:

Terminal Blocks:

Interior Dev. NP:

Wire Spare Cont:

Spare Term Pt's:

Wire Duct Required:

Arc Flash Fiber Optic Cable: X

Rev. PROJECT NOTES

1.

2.

3.

1 6

DRAWOUT CIRCUIT BREAKERS ARE CAPABLE OF BEING LOCKED, WITH UP TO THREE

PADLOCKS, IN EITHER THE TEST OR THE DISCONNECT POSITIONS. PADLOCKING

PREVENTS RACKING UNTIL ALL LOCKS ARE REMOVED.

LOCKING FORKS ARE NOT RECOMMENDED, ESPECIALLY IN DOUBLE-WIRE

CONNECTION POINTS BECAUSE THEY ARE PRONE TO COME LOOSE. ABB STANDARD

PRACTICE IS TO USE RING TONGUE LUGS.

THE DEVICE IDENTIFIER USED IN HARNESSES ADOPTS THE MOUNTING LOCATION

IDENTIFICATION WHERE USED HENCE PLUS (+) WILL BE USED FOR THE MOUNTING

LOCATIONS.

Yes

No

20%

#10 AWG SIS

#8 AWG SIS

GROUND BUS EXTENSIONS ARE REQUIRED IN THE REAR CABLE COMPARTMENTS.

Phoenix Contact (ABB Standard)

Insulated Ring Tongue

Engraved Plastic Adhesive

ADVAC CKT BKR ACCESSORIES INCLUDE: RACKING HANDLE ASSEMBLY, LIFTING HOOK

ASSEMBLY, MANUAL CHARGING HANDLE

KEEP MAIN BUS FOR CUBICLE 01 SEPARATED FROM THE REST OF THE LINE UP, LIKE

WE SHOWED IN SINGLE LINE

#14 AWG SIS

Standard - Destination

#14 AWG SIS

#14 AWG SIS

Sheet 3 of 4

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV 1173

Date: Date: Rev:

1VAL314911A0000

2/8/24

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

2/8/24

1VALCS03149A01A01

RELEASED

CS03149

Rev. PROJECT NOTES

2 7.

3 8.

EXTRA BOTTOM ENTRY CABLE PROVISION NEEDED IN CUBICLE 01.

ALL BREAKERS MUST SHIP SEPARATELY AND NOT INSTALLED

Sheet 4 of 4

ELECTRICAL BILL OF MATERIAL

Drawing No: Sold To: Status:

1VAL314911B0000 FGC CONSTRUCTION LLC

Shop Order No.: Line Item No. 4916 E BROADWAY Serial No.:

CS03149 A01 MADISON, WI 53716 1VALCS03149A01

Engineer: Checked: For: Cust P.O.:

AAM ESV SLAC 1173 LVC LVC LVC LVC LVC

Date: Date: 2575 SAND HILL ROAD M/S 1 Rev:

2/8/24 8/14/25 MENLO PARK, CA 94025 9

PC. ABB ORDER NO. TOTAL FUNCTION / TYPE MFR. RATINGS DEV. PU. SAP SHIP

NO. QTY. CODE NO. CODE OPER LOOSE 1 2 3 4 5 6 7 8 9 10

BREAKER & ACCESSORIES

CB0001 AA4K1777XX000U0 4 ADVAC; 4 - Model 4; A - Drawout; K1 - 15kV, 1200A, 50kA, 3 Cycle; Cap Swtcng:1030A C2

6kA PEAK 0.6 kHz; Charge Motor:7 - 125VDC; Close Coil:7 - 125VDC; Open Coil:7 - 125VDC;

Second Open Coil:X - None (Dual Secondary Disconnect); Under Volt:X – None (Dual Secondary Disconnect); Button Color:0 - Standard (ANSI); Button Protection:0 - None; UL:U - UL Recognized; Ground Cont:0 - Ground pad stainless steel

ABB D52 11 1 1 1 1

CB0002 AA4K2777XX000U0 4 Circuit Breaker, Catalog # AA4K2777XX000U0; ADVAC; 4 - Model 4; A - Drawout; K2 - 15kV, 2000A, 50kA, 3 Cycle; Cap Swtcng:1030A C2 6kA PEAK 0.6 kHz; Charge Motor:7 - 125VDC;

Close Coil:7 - 125VDC; Open Coil:7 - 125VDC; Second Open Coil:X - None (Dual Secondary Disconnect); Under Volt:X – None (Dual Secondary Disconnect); Button Color:0 - Standard (ANSI); Button Protection:0 - None; UL:U - UL Recognized; Ground Cont:0 - Ground pad stainless steel

ABB A52 11 1 1 1 1

CB0003 AA4K3777XX000U0 3 ADVAC; 4 - Model 4; A - Drawout; K3 - 15kV, 3000A, 50kA, 3 Cycle; Cap Swtcng:1030A C2 6kA PEAK 0.6 kHz; Charge Motor:7 - 125VDC; Close Coil:7 - 125VDC; Open Coil:7 - 125VDC;

Second Open Coil:X - None (Dual Secondary Disconnect); Under Volt:X – None (Dual Secondary Disconnect); Button Color:0 - Standard (ANSI); Button Protection:0 - None; UL:U - UL Recognized; Ground Cont:0 - Ground pad stainless steel

IL A52 11 1 1 1

CONVENIENCE DEVICES

0043 279010J00 36 Heater, Strip, 300W, 230V, Oper @ 120vAC IS GH.2 - GH.1 - AH.2 -

AH.1

11 4 4 4 4 4 4 4 4 4

0061 111009-00 9 KT0 111 (NC) Thermostat, Setting Range 32 to 140 Deg F, SPST, For use with Heating Elements

Stego CR 7 1 1 1 1 1 1 1 1 1

8 0082 279033H00 1 Duplex Outlet, GFCI, Brown, 20A, 120V CR 7 1 8 0083 279041B00 1 Single Gang Drawn Handy Box, 4.0 H x 2.125 W, 1-7/8" Deep, 1/2" Knockout CR 7 1 8 0084 58C16 1 Cover, Handy Box, GFCI Recept, Steel CR 7 1

BREAKER COMP'T ACCESS

0162 923A329G22-M 48 Current Transformer, Multi-Ratio CT, Type SAB-1, 3.5" Wide, 1200/2000A Bkr., 2000 / 300-5A, C200, With Mylar Insert

IP DC - DA - AD - AB 11 12 12 12 12

0168 923A330G08-M 51 Current Transformer, Multi-Ratio CT, Type SAB-2, 3.5" Wide, 3000A Bkr., 3000 / 300-5A, C200, With Mylar Insert

IP DD - AD - AC - AB - AA 11 9 9 6 6 9 6 6

0170 923A330G10-M 6 Current Transformer, Multi-Ratio CT, Type SAB-2, 3.5" Wide, 3000A Bkr., 5000 / 500-5A, C200, With Mylar Insert

IP AD 11 3 3

0254 54876BE 24 Copper Two-Hole Lug - Straight Long Barrel - max 35KV, 500 kcmil Wire, 1/2" Bolt Size, 1 3/4" Hole Spacing, Tin Plated Blind End, Brown 87

T&B HY - HW 11 6 6 6 6

BREAKER CONTROL / IND

0311 2438D 22 Switch, Control, Series 24, (1)t, (1)c ES PK - PJ - PI - PH - PG -

PF - PE - PD - PC - PB -

PA

270 7 1 1 2 2 1 2 2 11

0343 MRL125DLR-MPLLRD 22 Indicating Lamp, Type Series 16, Red LED, With Red Cap C3 Controls PKR - PJR - PIR - PHR -

PGR - PFR - PER -

PDR - PCR - PBR -

PAR

882 7 1 1 2 2 1 2 2 11

0344 MRL125DLG-MPLLGN 22 Indicating Lamp, Series 16, Green LED, With Green Cap C3 Controls PKG - PJG - PIG - PHG

- PGG - PFG - PEG -

PDG - PCG - PBG -

PAG

882 7 1 1 2 2 1 2 2 11

0490 774B430G20 20 Switch, Test, FT-1, 10P, (6) Current, (4) Potential, Black Handles. (C-C C-C C-C P P P P) IF PMA - PFA - PDA -

PCA - PBA - PAA

126 7 1 1 1 4 2 2 5 2 2

0497 FT4A14T06BN4068 3 Switch, Test, FT-14, 14P, (8) Current, (6) Potential, (14) Black Handles, Screw Terminals, Black Cover, Configuration: (C-C C-C C-C C-C P P P P P P)

IF PFA 906 7 1 1 1

PROTECTIVE RELAYS

0501 751#MTW9 8 Feeder Protection Relay, SEL-751; Catalog #: 751301ACA1A7085BC30; Advance Features:

Arc Sense; User Interface: English; Front Panel: 5-inch Color Touchscreen With 4 Pushbuttons;

Slot A: Power Supply 110–250 Vdc, 110–240 Vac, 50/60 Hz; 2 DI, 3 DO, 125 Vdc/Vac Digital Input Voltage; Slot B: Ethernet/Rear Serial Options; Single 10/100BASE-T Ethernet, EIA-232 Rear, (No Fiber ST); IEC 61850 Protocol: Yes; DNP3 Protocol: Yes; IEC 60870-5-103 Protocol:

No; EtherNet/IP Protocol: No; Slot C: 4 DI / 4 DO Fast High Current Hybrid (Form A), 125 Vdc/Vac Digital Input Voltage; Slot D: 4 DI / 4 DO Electromechanical (Form A), 125 Vdc/Vac Digital Input Voltage; Slot E: Vsync (300 Vac) / Vbat (300 Vdc) / 4 Arc-Flash Detection Inputs;

Slot Z: 3-Phase AC Voltage (300 Vac), 5 Amp Phase, 5 Amp Neutral; Conformal Coat: No

SL PF - PD 931 7 2 2 2 2

20F PNLLPT 20F 20F 30T 20F

LVC

RELEASED

C U B I C L E

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2025 ABB. All rights reserved.

LVC

BPT

LVC

12F 12F

LVC

12F 12F

30M LPT 30M

Sheet 1 of 4

1VAL314911B0000 FGC CONSTRUCTION LLC

Shop Order No.: Line Item No. 4916 E BROADWAY Serial No.:

CS03149 A01 MADISON, WI 53716 1VALCS03149A01

Engineer: Checked: For: Cust P.O.:

AAM ESV SLAC 1173 LVC LVC LVC LVC LVC

Date: Date: 2575 SAND HILL ROAD M/S 1 Rev:

2/8/24 8/14/25 MENLO PARK, CA 94025 9

PC. ABB ORDER NO. TOTAL FUNCTION / TYPE MFR. RATINGS DEV. PU. SAP SHIP

NO. QTY. CODE NO. CODE OPER LOOSE 1 2 3 4 5 6 7 8 9 10

20F PNLLPT 20F 20F 30T 20F

LVC

RELEASED

C U B I C L E

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2025 ABB. All rights reserved.

LVC

BPT

LVC

12F 12F

LVC

12F 12F

30M LPT 30M

0503 751#MJ4K 3 Feeder Protection Relay, SEL-751; Catalog #: 751301ACA1A7085AC30; Advance Features:

Arc Sense; User Interface: English; Front Panel: 5-inch Color Touchscreen With 8 Pushbuttons;

Slot A: Power Supply 110–250 Vdc, 110–240 Vac, 50/60 Hz; 2 DI, 3 DO, 125 Vdc/Vac Digital Input Voltage; Slot B: Ethernet/Rear Serial Options; Single 10/100BASE-T Ethernet, EIA-232 Rear, (No Fiber ST); IEC 61850 Protocol: Yes; DNP3 Protocol: Yes; IEC 60870-5-103 Protocol:

No; EtherNet/IP Protocol: No; Slot C: 4 DI / 4 DO Fast High Current Hybrid (Form A), 125 Vdc/Vac Digital Input Voltage; Slot D: 4 DI / 4 DO Electromechanical (Form A), 125 Vdc/Vac Digital Input Voltage; Slot E: Vsync (300 Vac) / Vbat (300 Vdc) / 4 Arc-Flash Detection Inputs;

Slot Z: 3-Phase AC Voltage (300 Vac), 5 Amp Phase, 5 Amp Neutral; Conformal Coat: No

SL PF - PD 931 7 1 1 1

0504 0587Z0X335322XX 1 SEL-587Z High-Impedance Differential Protection Firmware: Standard Conformal Coat: None Power Supply; Control Input Voltage: 48/125 Vdc or 125 Vac; 125 Vdc Energy-Clamping MOVs: 4 MOVs 8400J, 1500V Secondary Input Current 5 Amp Phase Mounting: Horizontal Panel Mount Communications Port EIA-232 Front and EIA-485 Rear Port Communications Protocol: Standard plus Modbus® RTU

SL PF 927 7 1

0516 7802D 11 Relay, Lockout, Type LOR, Man Reset, (4)NO-(4)NC, 120 VAC / 125 VDC ES PL - PH 84 7 1 1 2 2 1 2 2 0521 7815D 1 Relay, Lockout, Type LOR, Man Reset, (15) Decks, (30)NO-(30)NC, 120VAC / 125VDC ES PH 85 7 1

METERING DEVICES

0701 735#6J4G 11 SEL-735 Power Quality and Revenue Meter with Color Touchscreen Catalog #:

0735LX20944CXXA4XX16201XX; Enclosure Type: None; Metering: Form 9 (Four-Wire Wye; 3 PT's, 3 CT's ); Slot A: Power Supply 110-240 Vac 50/60 Hz, 110-250 Vdc, Control Input Voltage 125 Vdc or Vac; Slot B: (Ethernet) Single 10/100BASE-T; Slot B: (Rear Serial Port) EIA-232; Slot C Communications: None; Slot D I/O : 4 DI / 4 DO Solid-State (KYZ); Current Class: CL2/10/20, Optimized for Low-End Accuracy; System Frequency: 60Hz.; Software Bundle: None; Front-Panel Labeling: ANSI; Conformal Coat: No; Standard Front Nameplate:

Yes.

SL PM - PD - PC - PB - PA 931 7 1 1 4 5

CIRCUIT PROTECTIVE DEVICES

0752 ATDR15 48 Fuse, Class CC, Time Delay, 15A, 600vAc/300vDc IC CDB - CDA - CAB -

CAA

7 4 2 4 2 8 8 4 8 8

0762 2CDS271337R0457 9 Circuit Breaker, Type SU200M, 1 Pole, K Charac., UL489, 15A, 10kA, 277 VAC, 50/60 Hz. IW CRS 7 1 1 1 1 1 1 1 1 1

0774 2CDS272337R0557 1 Circuit Breaker, Type SU200M, 2 Pole, K Charac., UL489, 40A, 10kA, 240 VAC, 50/60 Hz. IW CRZ 7 1

3 0782 2CSM299912R1801 26 Fuse Holder, Series E 90, 2 Pole, Class CC Fuses, Type Code E 92/30 CC, 30A, 600V AC/DC, 50/60 Hz.

IW CD - CA 7 2 1 3 1 4 4 3 4 4

3 0783 2CSM299932R1801 25 Fuse Holder, Series E 90, 3 Pole, Class CC Fuses, Type Code E 93/30 CC, 30A, 600V AC/DC, 50/60 Hz.

IW CDR - CD - CA - CAF 7 2 2 2 5 2 2 6 2 2

0786 ATQR10 9 Fuse, Class CC, Time Delay, 10A, 600VAC IC CDR - CAR 7 6 3

0787 ATQR1 70 Fuse, Class CC, Time Delay, 1A, 600VAC IC CDC - CAI - CAH - CAG

- CAF - CAE - CAD -

CAC

7 6 8 12 6 6 20 6 6

0796 2CDS272517R0557 1 Circuit Breaker, Type S200UDC, 2 Pole, 40A, 14kA, 125VDC IW CRX 1024 7 1

POTENTIAL TRANSFORMERS

0815 7525A71G28 9 Potential Transformer, Type VIZ-11, (1) fuse swgr style. 12470-120V, 110kV BIL IP DP - AP 11 6 3 0822 50C5225G03 9 Fuse, PT Primary, Construction Type: Ferrule, Type 15CLPT-.5, Dimensions (L x D): 12.6" x

1.6", Clip Centers, 0.5, 15.5kV.

CH DF - AF 11 6 3

0823 400450D00 18 Fuse Clip, Size B, (2) per Fuse IS DF - AF 11 12 6

BUSHINGS

1119 931666K03 9 Porcelain Bushing, Main Bus, 3000A. Order (1) Per Interframe Split IS MB 11 1 1 1 1 1 1 1 1 1 5 1127 962841K01 3 Porcelain Bushing, PT Primary, 38 Module Only, Lower Stab, WYE & Delta PT Assm IS AF 11 2 1

1150 963313K01 8 EPOXY Breaker Primary Bushings, 1200A (up to 63kA) Advance/SafeGear, Order (2) Per Breaker.

ABB D52 11 2 2 2 2

1151 963294K01 8 EPOXY Breaker Primary Bushings, 2000A (up to 63kA) Advance/SafeGear, Order (2) Per Breaker.

ABB A52 11 2 2 2 2

1152 963242K01 6 EPOXY Breaker Primary Bushings, 3000A/4000A (up to 63kA) Advance/SafeGear, Order (2) Per Breaker.

ABB A52 11 2 2 2

TERMINAL BLOCKS

1555 926681T06 9 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number (1 - 8) & (1 - 10) Bottom to Top

PHOENIX CR 7 1 1 1 1 1 1 1 1 1

1556 926681T07 13 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 1 - 10 Bottom to Top PHOENIX CH 7 1 1 1 1 2 2 1 2 2

1564 926681T15 21 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 1 - 20 Bottom to Top PHOENIX CMX - CM - CL 7 3 2 3 4 1 1 3 1 1 2

1565 926681T16 21 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 21 - 40 Bottom to Top PHOENIX CMX - CM - CL 7 3 2 3 4 1 1 3 1 1 2

Sheet 2 of 4

1VAL314911B0000 FGC CONSTRUCTION LLC

Shop Order No.: Line Item No. 4916 E BROADWAY Serial No.:

CS03149 A01 MADISON, WI 53716 1VALCS03149A01

Engineer: Checked: For: Cust P.O.:

AAM ESV SLAC 1173 LVC LVC LVC LVC LVC

Date: Date: 2575 SAND HILL ROAD M/S 1 Rev:

2/8/24 8/14/25 MENLO PARK, CA 94025 9

PC. ABB ORDER NO. TOTAL FUNCTION / TYPE MFR. RATINGS DEV. PU. SAP SHIP

NO. QTY. CODE NO. CODE OPER LOOSE 1 2 3 4 5 6 7 8 9 10

20F PNLLPT 20F 20F 30T 20F

LVC

RELEASED

C U B I C L E

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2025 ABB. All rights reserved.

LVC

BPT

LVC

12F 12F

LVC

12F 12F

30M LPT 30M

1566 926681T17 7 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 41 - 60 Bottom to Top PHOENIX CMX - CM - CL - CLA 7 2 2 1 2

1572 926681T23 13 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 11 - 20 Bottom to Top PHOENIX CH 7 1 1 1 1 2 2 1 2 2

1573 926681T24 1 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 21 - 30 Bottom to Top PHOENIX CHA 7 1

1574 926681T25 8 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 1 - 12 Bottom to Top PHOENIX CL 7 2 2 2 2

1575 926681T26 8 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 13 - 24 Bottom to Top PHOENIX CL 7 2 2 2 2

1576 926681T27 8 Phoenix Terminal Block Assembly, Bolt Connection Type. TB Number 25 - 36 Bottom to Top PHOENIX CL 7 2 2 2 2

1581 926681T32 1 Phoenix Disconnect Terminal Block Assembly, Bolt Connection Type. TB Number 31 - 40 Bottom to Top

PHOENIX CHA 7 1

WIRE HARNESS

1843 965931T49 3 Wire Harness - Three Phase Wye-Wye, Potential Transformer (Phoenix TB). Up to 15kV, VIZ

11 and 27 kV, VIZ 12 or VIZ 12G

IS DP - AP 11 2 1

1958 966343T05 11 WIRE HARNESS - LAYOUT - BOM. MULTI RATIO CTs - 10 AWG - MODULE A & D -

POSITION A. (PHOENIX TB)

ABB DA - AA 11 1 1 2 2 1 2 2

1959 966343T06 6 WIRE HARNESS - LAYOUT - BOM. MULTI RATIO CTs - 10 AWG - MODULE A & D -

POSITION B. (PHOENIX TB)

ABB AB 11 1 1 1 1 1 1

1960 966343T07 7 WIRE HARNESS - LAYOUT - BOM. MULTI RATIO CTs - 10 AWG - MODULE A & D -

POSITION C. (PHOENIX TB)

ABB DC - AC 11 1 1 1 1 1 1 1

1961 966343T08 11 WIRE HARNESS - LAYOUT - BOM. MULTI RATIO CTs - 10 AWG - MODULE A & D -

POSITION D. (PHOENIX TB)

ABB DD - AD 11 1 1 2 2 1 2 2

1976 966126T07 4 Wire Harness - Breaker Secondary Harness Standard, 1200A Dual Plugs, Phoenix TB. Rating 1200A.

IS D52 11 1 1 1 1

1977 966126T08 7 Wire Harness - Breaker Secondary Harness Standard, 2000A/3000A/ROF and 27kV Breakers, Dual Plugs, Phoenix TB

IS A52 11 1 1 1 1 1 1 1

1979 965123T10 11 Wire Harness - TOC Switch Harness, Eight Contacts 4NO - 4NC. Position +RC Phoenix TB, Advance/SafeGear - Phoenix TB.

ABB D52 - A52 11 1 1 2 2 1 2 2

2001 SEL-3350#B05L 1 SEL-3350 Real-Time Automation Controller (RTAC); Sales Item Number: 3350#B05L;

Processor: Intel Atom x5-E3940 Quad Core, 1.6 GHz; Ram: 8 GB; Operating System: SEL Real-Time Automation Controller (RTAC); Conformal Coat: None; Chassis and Mounting:

Horizontal 3U Panel Mount; Power Supply A: 125-250 Vdc or 110-240 Vac; Power Supply B:

None; SSD Slot 1: SLC 32 GB Industrial Grade SSD; SSD Slot 2: None; Expansion Slot 1:

Serial Expansion Board: 32 x RJ45 Ports:

SL PL 1094 7 1

2002 7GIS1920314 1 (Mebane-NC_US03 SAP Torque Ordering Number: 7GIS1920314);

Catalog #: 2730M0ARAA1111CCCCX0; SIN: 2730#99K6;

Ethernet Switch SEL-2730M, Rack Mount (Front or Rear Cabled);

Power Supply A: 125/250 Vdc/Vac Euro-Style Connector;

Power Supply B: 125/250 Vdc or Vac;

Ports 1-4: 4 x 10/100/1000BASE-T SFP, 100 m, RJ45;

Ports 5-8: 4 x 10/100/1000Base-T;

Ports 9-24: (16) x 10/100Base -T;

Conformal Coat: None

SL CNG 865 7 1

4 2003 IE-3100-18T2C-E 1 Catalyst IE3100 w/18 Ports GE Copper and 2 GE Combo uplinks, NE; 12V to 48V nominal.. Cisco Systems Inc CNA 7 1

2005 24070A01B 1 Clock, Satellite-Synchronized , Type SEL-2407, Compatible with SEL-2812 Fiber Optic, with GPS Antenna & Connecting Cable, 19" Horizontal Rack Mtg. with Bracket (bracket on right side in front view)

SL PB 999 7 1

9 2006 915900043 1 Pipe Mounting Kit for use with an SEL-9524A GPS GNSS Antenna SL PB 7 1 9 2007 C965C-015 1 15' LMR-240-FR Cable, Indoor/Outdoor Rated SL PB 7 1

4 2010 PWR-IE50W-AC 1 IE 2000 Series Power Supply, 50W, Input Range AC 110-220VAC And DC 88-300VDC. Output Range 24VDC/2.1A

Cisco Systems Inc CNA 7 1

4 2015 2902#P7EK 1 SEL-2902 RJ45 to DB-9 Adapter Panel; Mounting: Surface Mount SL CNB 7 1 7 2060 C256-009 1 Cable, Coaxial, Type RG58, For IRIG-B Conn, DB9 - BNC Conn, 9' Length SL PL 7 1

2071 C273A-005 1 Communication Data Cable SEL-273A, 5 Feet Long SL PL 7 1 2072 C273A-012 1 Communication Data Cable SEL-273A, 12 Feet Long SL PL 7 1 2073 C273A-015 1 Communication Data Cable SEL-273A, 15 Feet Long SL PL 7 1 2074 C273A-021 2 Communication Data Cable SEL-273A, 21 Feet Long SL PL 7 2 2075 C273A-024 2 Communication Data Cable SEL-273A, 24 Feet Long SL PL PL 7 2 2076 C273A-028 1 Communication Data Cable SEL-273A, 28 Feet Long SL 7 1 2077 C273A-030 2 Communication Data Cable SEL-273A, 30 Feet Long SL PL 7 2 2078 C273A-033 2 Communication Data Cable SEL-273A, 33 Feet Long SL PL 7 2

MISCELLANEOUS DEVICES

Sheet 3 of 4

1VAL314911B0000 FGC CONSTRUCTION LLC

Shop Order No.: Line Item No. 4916 E BROADWAY Serial No.:

CS03149 A01 MADISON, WI 53716 1VALCS03149A01

Engineer: Checked: For: Cust P.O.:

AAM ESV SLAC 1173 LVC LVC LVC LVC LVC

Date: Date: 2575 SAND HILL ROAD M/S 1 Rev:

2/8/24 8/14/25 MENLO PARK, CA 94025 9

PC. ABB ORDER NO. TOTAL FUNCTION / TYPE MFR. RATINGS DEV. PU. SAP SHIP

NO. QTY. CODE NO. CODE OPER LOOSE 1 2 3 4 5 6 7 8 9 10

20F PNLLPT 20F 20F 30T 20F

LVC

RELEASED

C U B I C L E

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2025 ABB. All rights reserved.

LVC

BPT

LVC

12F 12F

LVC

12F 12F

30M LPT 30M

2100 C80405XXXXX 44 Fiber-Optic Arc Flash Sensor, Multimode, Type SEL-C804, Point Sensor, ST Connector, 05 Meters Long.

SL PF - PD 7 4 4 8 8 4 8 8

2200 CSD363610 1 Enclosure, Wall-Mount, 36"H x 36"W x 10"D, ANSI 61 Gray, Quater-turn latch style. Hoffman RP 7 1 2201 CP3636 1 Hoffman Panel. Hoffman RP 7 1 2301 72171341 3 4 in. x 2-1/8 in. Deep Square Box 42 cu. in. HomeDepot HW - HA 11 1 1 1 2302 72C1 3 4 in. Square Box Cover Blank HomeDepot HW - HA 11 1 1 1

2400 91610054 1 19" Touchscreen Monitor, DisplayPort/VGA, with 19" Rack-Mount Bracket and 120/240 Vac

125/250 Vdc power supply. Mounted by SEL mounting plate 900-0040.

SEL PC 7 1

2410 E001178 1 Elo 19-inch- Flush-mount Bracket ELO PC 7 1

Sheet 4 of 4

NAMEPLATE INFORMATION

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV

Date: Date: Rev:

Rev.

Sold To: FGC CONSTRUCTION LLC For: SLAC NATIONAL ACCELERATOR LAB

4916 E BROADWAY 2575 SAND HILL ROAD M/S 1

MADISON, WI 53716 MENLO PARK, CA 94025

Serial Number 1VALCS03149A01 Prod Year IEEE C37.20.2 Enclosure Category B Max Volts 15 kV Freq 60 Hz Main Bus 3000 A Peak Withstand Current kA Short-time, Sym RMS 50 kA Insulation Levels PF Withstand 36 kV Impulse kV Assembled in USA of foreign and domestic components

Serial Number 1VALCS03149A01 Prod Year 0 IEEE C37.20.7 Accessibility 2B Arcing Short-Circuit Current 50 KA Arcing Duration 10 Cycles

NOTES:

S.O. Tag(s) Located on Cub. No. ALL

1VAL314911K0000 RELEASED

CS03149 A01 1VALCS03149A01

02/08/2024 02/08/2024

S.O. TAG INFORMATION

Lower door, upper left corner.

Ref. General Arrangement Front View

Engraving will be provided as shown above and will be limited to the ratings listed. The S.O. Tag may NOT be altered in any way to satisfy customer specific requirements.

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV

Date: Date: Rev:

1VAL314911K0000 RELEASED

CS03149 A01 1VALCS03149A01

02/08/2024 02/08/2024

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

Rev.

White Nameplate Black Letters White Nameplate Black Letters Black Nameplate White Letters Black Nameplate White Letters White Nameplate Red Letters White Nameplate Red Letters NOTES:

Red Nameplate White Letters Red Nameplate White Letters Yellow Nameplate Black Letters

002112.47kV/120VPTLINE02N1A

08N1A VCB-94 SPARE BREAKER 1 002

CUIR-2 FEEDER BREAKER

1 002

1 00209N1D VCB-97

1 00207N1A VCB-27

08N1D VCB-95 CUIR-4 FEEDER BREAKER

TIE BREAKER

09N1A VCB-96 SPARE BREAKER

1 002

1 002 1 002

05N1A VCB-90

05N1D VCB-91 CUIR-8 FEEDER BREAKER

SPARE BREAKER

06N1D VCB-93 CUIR-6 FEEDER BREAKER

06N1A VCB-92 SPARE BREAKER 1 002

1 002

1 002 1 002

02N1D BUS

03N1A VCB-29 BUS 9 MAIN BREAKER

PT 12.47kV/120V

04N1A LINE PT 12.47kV/120V 1 002

1 002

NP # LINE 2 LINE 3

01N1A VCB-Q2 RPC-2 FEEDER BREAKER

LINE 1

008 1.5 x

009 1 x 3

007 1 x 3

002 1.5 x 6

1. Customer to fill in desired nameplate lettering and/or engraving will be provided as indicated.

2. Nameplates will NOT be provided if engraving information is not provided.

Qty.

6 3/8 15

3/16 15

Type

3/16

LINE 1

LINE 2

LINE 1

LINE 2

LINE 3

3/8 15

5/32 18

3/8 15

006 1.5 x 6 3/8 15 x

1 x

6004 1.5 x

003 1

3/163

W

Char Size Char / Line

LINE 1

Size (W x L) Material L

001 1 x 3

Type

5/32 18

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV

Date: Date: Rev:

1VAL314911K0000 RELEASED

CS03149 A01 1VALCS03149A01

02/08/2024 02/08/2024

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

Rev.

01N4 TEST SWITCH VCB-Q2 TS2 1 001

01N2 TEST SWITCH VCB-Q2 TS1

01N1 PROT. RELAY VCB-Q2

1 001 1 001

04N7 POWER METER VCB-93

1 001

04N8 TEST SWITCH VCB-93 TS4

01N10 HMI SWGR-9

1 001 1 001

1 001

04N4 TEST SWITCH VCB-91 TS2

04N3 POWER METER VCB-91 1 001

1 001

1 00104N5 POWER METER

04N6 TEST SWITCH VCB-92 TS3

VCB-92

03N7 LOCKOUT RELAY 86 1 001

1 001 1 001

04N1 POWER METER

04N2 TEST SWITCH VCB-90 TS1

VCB-90

03N4 TEST SWITCH VCB-29 TS2

03N3 POWER METER VCB-29 1 001

1 001 1 001 1 001

03N5 CONTROL SWITCH

03N6 OPEN/CLOSED VCB-29

VCB-29

02N3 TEST SWITCH 87B TS1 1 001

1 001 1 001

03N1 PROT. RELAY

03N2 TEST SWITCH VCB-29 TS1

VCB-29

01N9 SATELLITE SYNCHRONIZED CLOCK 1 001

1 001 1 001

02N1 DIFFERENTIAL

02N2 LOCKOUT RELAY 86-B9

PROT. RELAY 87B

01N7 LOCKOUT RELAY 86

01N6 OPEN/CLOSED VCB-Q2 1 001

1 001

1 00101N8 REAL-TIME AUTOMATION CONTROLLER

1 001

01N3 POWER METER

01N5 CONTROL SWITCH VCB-Q2

VCB-Q2

COMP'T / DEVICE NAMEPLATE ENGRAVING

NP # LINE 1 LINE 2 LINE 3 Qty.

1 001

Type

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV

Date: Date: Rev:

1VAL314911K0000 RELEASED

CS03149 A01 1VALCS03149A01

02/08/2024 02/08/2024

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

Rev.

1 001

07N9 TEST SWITCH VCB-94 TS3

1 001

07N10 POWER METER VCB-95

07N11 TEST SWITCH

VCB-96

VCB-95 TS4

1 001 1 001 1 001

07N12 POWER METER

07N6 OPEN/CLOSED VCB-27

07N5 CONTROL SWITCH VCB-27 1 001

1 001

1 00107N7 LOCKOUT

07N8 POWER METER VCB-94

RELAY 86

07N2 TEST SWITCH VCB-27 TS1

07N1 PROT. RELAY VCB-27 1 001

1 001 1 001 1 001

07N3 POWER METER

07N4 TEST SWITCH VCB-27 TS2

VCB-27

05N9 OPEN/CLOSED VCB-93

05N8 CONTROL SWITCH VCB-93 1 001

1 001

1 00105N10 LOCKOUT RELAY 86

05N5 LOCKOUT RELAY 86

05N4 OPEN/CLOSED VCB-92 1 001

1 001 1 001 1 001

05N6 PROT. RELAY

05N7 TEST SWITCH VCB-93 TS2

VCB-93

05N1 PROT. RELAY VCB-92 1 001

1 001 1 001

05N2 TEST SWITCH

05N3 CONTROL SWITCH VCB-92

VCB-92 TS1

05N8 CONTROL SWITCH VCB-91

05N7 TEST SWITCH VCB-91 TS2 1 001

1 001 1 001 1 001

05N9 OPEN/CLOSED

05N10 LOCKOUT RELAY 86

VCB-91

05N4 OPEN/CLOSED VCB-90

05N3 CONTROL SWITCH VCB-90 1 001

1 001 1 001 1 001

05N5 LOCKOUT

05N6 PROT. RELAY VCB-91

RELAY 86

1 001

COMP'T / DEVICE NAMEPLATE ENGRAVING

NP # LINE 1 LINE 2 LINE 3 Qty. Type

1 001TS1

05N1 PROT. RELAY VCB-90

05N2 TEST SWITCH VCB-90

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV

Date: Date: Rev:

1VAL314911K0000 RELEASED

CS03149 A01 1VALCS03149A01

02/08/2024 02/08/2024

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

Rev.

SWGR-9 1 00210N1A REMOTE PANEL

10N5 CONTROL SWITCH VCB-90

1 001

10N6 OPEN/CLOSED VCB-90

10N7 CONTROL SWITCH VCB-91

1 001 1 001 1 001

10N2 OPEN/CLOSED VCB-Q2

10N1 CONTROL SWITCH VCB-Q2 1 001

1 001

1 00110N3 CONTROL SWITCH

10N4 OPEN/CLOSED VCB-29

VCB-29

09N9 OPEN/CLOSED VCB-97

09N8 CONTROL SWITCH VCB-97 1 001

1 001

1 00109N10 LOCKOUT RELAY 86

09N5 LOCKOUT RELAY 86

09N4 OPEN/CLOSED VCB-96 1 001

1 001 1 001 1 001

09N6 PROT. RELAY

09N7 TEST SWITCH VCB-97 TS2

VCB-97

09N1 PROT. RELAY VCB-96 1 001

1 001 1 001

09N2 TEST SWITCH

09N3 CONTROL SWITCH VCB-96

VCB-96 TS1

08N8 CONTROL SWITCH VCB-95

08N7 TEST SWITCH VCB-95 TS2 1 001

1 001 1 001 1 001

08N9 OPEN/CLOSED

08N10 LOCKOUT RELAY 86

VCB-95

08N4 OPEN/CLOSED VCB-94

08N3 CONTROL SWITCH VCB-94 1 001

1 001 1 001 1 001

08N5 LOCKOUT

08N6 PROT. RELAY VCB-95

RELAY 86

07N15 TEST SWITCH VCB-97 TS6 1 001

1 001 1 001

08N1 PROT. RELAY

08N2 TEST SWITCH VCB-94 TS1

VCB-94

1 001

COMP'T / DEVICE NAMEPLATE ENGRAVING

NP # LINE 1 LINE 2 LINE 3 Qty. Type

1 001

TS507N13 TEST SWITCH VCB-96

07N14 POWER METER VCB-97

Shop Order No.: Line Item No.: Serial No.:

Engineer: Approved: Cust P.O.:

AAM ESV

Date: Date: Rev:

1VAL314911K0000 RELEASED

CS03149 A01 1VALCS03149A01

02/08/2024 02/08/2024

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2023 ABB.

All rights reserved.

Rev.

10N20 OPEN/CLOSED VCB-96

10N19 CONTROL SWITCH VCB-96 1 001

1 001 1 001 1 001

10N21 CONTROL SWITCH

10N22 OPEN/CLOSED VCB-97

VCB-97

10N16 OPEN/CLOSED VCB-94

10N15 CONTROL SWITCH VCB-94 1 001

1 001 1 001 1 001

10N17 CONTROL SWITCH

10N18 OPEN/CLOSED VCB-95

VCB-95

10N12 OPEN/CLOSED VCB-93

10N11 CONTROL SWITCH VCB-93 1 001

1 001 1 001 1 001

10N13 CONTROL SWITCH

10N14 OPEN/CLOSED VCB-27

VCB-27

1 001 1 001

COMP'T / DEVICE NAMEPLATE ENGRAVING

NP # LINE 1 LINE 2 LINE 3 Qty. Type

1 001

10N9 CONTROL SWITCH VCB-92

10N10 OPEN/CLOSED VCB-92

VCB-9110N8 OPEN/CLOSED

E F

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AM

08/14/24

AAM

08/14/24

No: REVISIONS CHD:BY: DATE:

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

INTERCONNECTION

Shop Order: Item:

A01CS03149

1VAL314911J0001

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

Back Mounting Sheet (Left Side)

(4) 10 POLE TERMINAL BLOCKS

LOW VOLTAGE COMPARTMENT (Back and Right Mounting Sheets) Right Mounting Sheet (Left Side)

(8) 50A 1 POLE TERMINAL BLOCKS

(10) 30A 1 POLE TERMINAL BLOCKS

Left Side

(4) 10 POLE TERMINAL BLOCKS

LOW VOLTAGE COMPARTMENT (Back and Right Mounting Sheets) Right Mounting Sheet

Right Side

(2) 10 POLE TERMINAL BLOCKS

Back Mounting Sheet Left Side

(8) 50A 1 POLE TERMINAL BLOCKS

(10) 30A 1 POLE TERMINAL BLOCKS

Definition of Shipping Section: Set of Cubicles or Switchgear Frames that are mechanically anchored to one same shipping base.

Shipping Sections will contain a maximum of three (3) cubicles or frames.

Shipping Sections will be counted from left to right seen from the front of the switchgear.

For shipping purposes all interconnection wires at a shipping split shall be re-coiled in to the left hand shipping split as viewed from the front.

Interconnection wiring within a shipping section must remain installed for shipping.

GENERAL NOTES AND PROCEDURE FOR COILING INTERCONNECTION WIRES

FROM ADJACENT SHIPPING SECTIONS:

1.

2.

3.

4.

5.

Lower Left Side

(4) 10 POLE TERMINAL BLOCKS

Lower Right Side

(2) 10 POLE TERMINAL BLOCKS

Back Mounting Sheet Upper Left Side

(4) 10 POLE TERMINAL BLOCKS

Right Mounting Sheet Upper Right Side

(4) 10 POLE TERMINAL BLOCKS

Back Mounting Sheet Left Side

LOW VOLTAGE COMPARTMENT (Back and Right Mounting Sheets) LOW VOLTAGE COMPARTMENT (Back and Right Mounting Sheets)

(8) 50A 1 POLE TERMINAL BLOCKS

(10) 30A 1 POLE TERMINAL BLOCKS

Back Mounting Sheet (Left Side)

(4) 10 POLE TERMINAL BLOCKS

LOW VOLTAGE COMPARTMENT (Back and Right Mounting Sheets) Right Mounting Sheet (Left Side)

(8) 50A 1 POLE TERMINAL BLOCKS

(10) 30A 1 POLE TERMINAL BLOCKS

SHIPPING SPLIT

No: REVISIONS ON APPROVED PRIOR TO FAT CHD:BY: DATE:

(STICK ON INTERNAL REVISION BLOCKS, REMOVING AFTER EACH DRAWING REVISION UPDATED. ) a REV'D PER CUSTOMER COMMENTS AM AAM 07/16/25 a a a a

2 02CM:2

CM

1 02CM:1

13 02CM:13

14 02CM:14

15 02CM:15

16 02CM:16

CM

LINE ITEM - A01 , CUBICLE - 01

202CRA:2(#8)

502CRA:5(#8)

702CRA:7(#8)

802CRA:8(#8)

CRB

02CRA:1(#8) 1

CRA

2 01CM:2

5 03CM:5

6 03CM:6

7 03CM:3

8 03CM:4

9 04CM:5

10 04CM:6

CM

1 01CM:1

11 04CM:7

12 04CM:8

13 01CM:13

14 01CM:14

15 01CM:15

16 01CM:16

17 03CM:17(#10)

18 03CM:18(#10)

19 03CM:19(#10)

20 03CM:20(#10)

2204CM:10

2304CM:21

2404CM:22

2504CM:23

2604CM:24

2704CM:41

2804CM:42

2904CM:43

3004CM:44

04CM:9 21

CM

3104CM:45

3204CM:46

3304CM:47

3404CM:48

3504CM:55

3604CM:56

3704CM:57

3804CM:58

3904CM:59

4004CM:60

LINE ITEM - A01 , CUBICLE - 02

42 04CMX:2

43 04CMX:3

44 04CMX:4

45 04CMX:5

46 04CMX:6

47 04CMX:7

48 04CMX:8

49 04CM:53

50 04CM:54

CM

41 04CMX:1

51 04CM:11

52 04CM:12

60 10

403CRB:4

303CRB:3

203CRB:2

03CRB:1 1

CRB

01CRA:1(#8), 03CRA:1(#8) 1

CRA

801CRA:8(#8), 03CRA:8(#8)

701CRA:7(#8), 03CRA:7(#8)

501CRA:5(#8), 03CRA:5(#8)

201CRA:2(#8), 03CRA:2(#8)

LINE ITEM - A01 , CUBICLE - 04

CM

10 05CM:6, 02CM:22

9 02CM:21, 05CM:5

8 05CM:4, 02CM:12

7 02CM:11, 05CM:3

6 05CM:2, 02CM:10

5 02CM:9, 05CM:1

20 03CM:20(#10), 05CM:20(#10)

19 03CM:19(#10), 05CM:19(#10)

18 03CM:18(#10), 05CM:18(#10)

17 03CM:17(#10), 05CM:17(#10)

16 03CM:16

15 03CM:15

14 03CM:14

13 03CM:13

12 05CM:8, 02CM:52

11 02CM:51, 05CM:7

02CM:23, 06CM:1 21

CM

3006CM:14(#10)

2906CM:13(#10)

2806CM:40(#10)

2706CM:39(#10)

2606CM:38(#10)

2506CM:37(#10)

2406CM:4, 02CM:26

2302CM:25, 06CM:3

2206CM:2, 02CM:24

4005CM:16(#10)

3905CM:15(#10)

3805CM:14(#10)

3705CM:13(#10)

3605CM:40(#10)

3505CM:39(#10)

3405CM:38(#10)

3305CM:37(#10)

3206CM:16(#10)

3106CM:15(#10)

CM

41 02CM:27, 06CM:5

50 07CM:10, 03CM:2

49 03CM:1, 07CM:9

48 07CM:8, 02CM:34

47 02CM:33, 07CM:7

46 07CM:6, 02CM:32

45 02CM:31, 07CM:5

44 06CM:8, 02CM:30

43 02CM:29, 06CM:7

42 06CM:6, 02CM:28

60 07CM:24, 02CM:40

59 02CM:39, 07CM:23

58 07CM:22, 02CM:38

57 02CM:37, 07CM:21

56 07CM:16, 02CM:36

55 02CM:35, 07CM:15

54 07CM:14, 02CM:50

53 02CM:49, 07CM:13

203CRA:2(#8), 05CRA:2(#8)

503CRA:5(#8), 05CRA:5(#8)

703CRA:7(#8), 05CRA:7(#8)

803CRA:8(#8), 05CRA:8(#8)

03CRA:1(#8), 05CRA:1(#8) 1

CRA

03CRB:1, 05CRB:1 1

CRB

203CRB:2, 05CRB:2

303CRB:3, 05CRB:3

403CRB:4, 05CRB:4

CMX

CMX

1 02CM:41, 07CM:25

8 07CM:44, 02CM:48

7 02CM:47, 07CM:43

6 07CM:42, 02CM:46

5 02CM:45, 07CM:41

4 07CM:28, 02CM:44

3 02CM:43, 07CM:27

2 07CM:26, 02CM:42 42

CMX

2 04CM:50

3 02CM:7

4 02CM:8

5 02CM:5

6 02CM:6

7 B01-07CM:25

8 B01-07CM:26

9 B01-03CM:9

10 B01-03CM:10

CM

1 04CM:49

11 B01-07CM:53

12 B01-07CM:54

13 04CM:13

14 04CM:14

15 04CM:15

16 04CM:16

17 02CM:17(#10), 04CM:17(#10)

18 02CM:18(#10), 04CM:18(#10)

19 02CM:19(#10), 04CM:19(#10)

20 02CM:20(#10), 04CM:20(#10)

22B01-03CM:8

B01-03CM:7 21

CM

LINE ITEM - A01 , CUBICLE - 03

202CRA:2(#8), 04CRA:2(#8)

502CRA:5(#8), 04CRA:5(#8)

702CRA:7(#8), 04CRA:7(#8)

802CRA:8(#8), 04CRA:8(#8)

02CRB:1, 04CRB:1 1

CRB

202CRB:2, 04CRB:2

02CRA:1(#8), 04CRA:1(#8) 1

CRA

302CRB:3, 04CRB:3

402CRB:4, 04CRB:4

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AM

08/19/24

AAM

08/18/24

No: REVISIONS CHD:BY: DATE:

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

WIRING DIAGRAM (MV "D")

Shop Order: Item:

A01CS03149

1VAL314911W0502

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

ØA ØB ØC

TO MAIN BUS

GD CBA

CABLE COMPARTMENT (R.V)

TO CIRCUIT BREAKER

ØC ØB ØA

ØC ØB ØA

HE

CBAGD

ØA ØB ØC

GE CBA CBA

C B

A

UPPER BREAKER COMPARTMENT (F.V)

UPPER CABLE COMPARTMENT (R.V)

+ COMPARTMENT

(A, B, D or E)

Harnesses uses "+" to indicate the "Mounting Location" in the device ID for use in multiple locations

12 POLE TERMINAL BLOCKS

BREAKER COMPARTMENT (Right Side Mounting Sheet) REFERENCE DRAWING No. 965122

STANDARD

REFERENCE DRAWING No. 965123

BREAKER COMPARTMENT

HORIZONTAL BREAKER WINDOW GUARD

TRUCK OPERATED CONTACTS

STANDARD

52H b a b a b a b a

BREAKER COMPARTMENT (Left Side Mounting Sheet)

6 AND 4 POLE SHORTING TERMINAL BLOCKS

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

BREAKER COMPARTMENT (Left Side Mounting Sheet)

6 AND 4 POLE SHORTING TERMINAL BLOCKS

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

X1 X2 X3 X4 X5

D52 15ADV50

1200A

VCB-91

DG

GROUND BUS

DZA:2 2 DZB:22

DZA:3 CDA:4, DRA:53 DZB:33

DZA:4 CLD:294 DZB:44

DZA:5 DRA:3, DRA:175 DZB:55

DZA:6 CM:76 DZB:66

DZA:7 CDB:4, DRA:97 DZB:77

DZA:8 CLD:258 DZB:88

DZA:9 DRA:79 DZB:99

DZA:10 CDB:2, DRC:310 DZB:1010

DZA:11 CHD:411 DZB:1111

DZA:12 12 DZB:1212

DZA:13 13 DZB:1313

DZA:14 14 DZB:1414

DZA:15 15 DZB:1515

DZA:16 CLD:2116 DZB:1616

DZA:17 DRA:517 DZB:1717

DZA:18 18 DZB:1818

DZA:19 19 DZB:1919

DZA:20 20 DZB:2020

DZA:21 21 DZB:2121

DZA:22 22 DZB:2222

DZA:23 23 DZB:2323

DZA:24 24 DZB:2424

DRB

1 DZB:1

DRA

1 CDA:2DZA:1

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DR

C:

DT

DRC

1DT:1

13DT:13

2DT:2

14DT:14

3 DRA:10DT:3

15DT:15

4 CHD:5DT:4

16DT:16

5DT:5

6DT:6

7DT:7

8DT:8

9DT:9

10DT:10

11DT:11

12DT:12

17 DDA:X2(#10)

18CM:20(#10) DDA:X1(#10)

7DLD:8(#10) DLD:13(#10), DLD:1(#10)

14DLD:13(#10) DDA:X5(#10)

11 DDB:X2(#10)

12CM:19(#10) DDB:X1(#10)

16 DDA:X3(#10)

15 DDA:X4(#10)

8DLD:7(#10) DDB:X5(#10)

9 DDB:X4(#10)

10 DDB:X3(#10)

13DLD:14(#10) DLD:7(#10)

DLD

1DLD:2(#10) DLD:7(#10)

2CM:17(#10), DLD:1(#10) DDC:X5(#10)

4 DDC:X3(#10)

3 DDC:X4(#10)

5 DDC:X2(#10)

6CM:18(#10) DDC:X1(#10)

X1 X2 X3 X4

X5 DLD:14(#10)

DLD:15(#10)

DLD:16(#10)

DLD:17(#10)

DLD:18(#10)

DDADDA

X1 X2 X3 X4

X5 DLD:2(#10)

DLD:3(#10)

DLD:4(#10)

DLD:5(#10)

DLD:6(#10)

DDCDDC

X1 X2 X3 X4

X5 DLD:8(#10)

DLD:9(#10)

DLD:10(#10)

DLD:11(#10)

DLD:12(#10)

DDBDDB

MRCT

3000-300:5A

C200

PC: 0168(3), 1961

17 DAA:X2(#10)

18PDA:4(#10) DAA:X1(#10)

7DLA:8(#10) DLA:13(#10), DLA:1(#10)

14DLA:13(#10) DAA:X5(#10)

11 DAB:X2(#10)

12PDA:8(#10) DAB:X1(#10)

16 DAA:X3(#10)

15 DAA:X4(#10)

8DLA:7(#10) DAB:X5(#10)

9 DAB:X4(#10)

10 DAB:X3(#10)

13DLA:14(#10) DLA:7(#10)

DLA

1DLA:2(#10) DLA:7(#10), DG:1(#10) GN

2DLA:1(#10), PDA:10(#10) DAC:X5(#10)

4 DAC:X3(#10)

3 DAC:X4(#10)

5 DAC:X2(#10)

6PDA:12(#10) DAC:X1(#10)

X1 X2 X3 X4

X5 DLA:14(#10)

DLA:15(#10)

DLA:16(#10)

DLA:17(#10)

DLA:18(#10)

DAADAA

X1 X2 X3 X4

X5 DLA:8(#10)

DLA:9(#10)

DLA:10(#10)

DLA:11(#10)

DLA:12(#10)

DABDAB

X1 X2 X3 X4

X5 DLA:2(#10)

DLA:3(#10)

DLA:4(#10)

DLA:5(#10)

DLA:6(#10)

DACDAC

1 DLA:1(#10) GN

MRCT

2000-300:5A

C200

PC: 0162(3), 1958

6 CM:38(#10)DCC:X1(#10)

5DCC:X2(#10)

3DCC:X4(#10)

4DCC:X3(#10)

2 DLC:1(#10), CM:37(#10)DCC:X5(#10)

DLC

DLC:7(#10), DG:3(#10) GN DLC:2(#10)1

13 DLC:14(#10)DLC:7(#10)

10DCB:X3(#10)

9DCB:X4(#10)

8 DLC:7(#10)DCB:X5(#10)

15DCA:X4(#10)

16DCA:X3(#10)

12 CM:39(#10)DCB:X1(#10)

11DCB:X2(#10)

14 DLC:13(#10)DCA:X5(#10)

7 DLC:8(#10)DLC:13(#10), DLC:1(#10)

18 CM:40(#10)DCA:X1(#10)

17DCA:X2(#10)

X1 X2 X3 X4

X5 DLC:14(#10)

DLC:15(#10)

DLC:16(#10)

DLC:17(#10)

DLC:18(#10)

DCADCA

X1 X2 X3 X4

X5 DLC:8(#10)

DLC:9(#10)

DLC:10(#10)

DLC:11(#10)

DLC:12(#10)

DCBDCB

X1 X2 X3 X4

X5 DLC:2(#10)

DLC:3(#10)

DLC:4(#10)

DLC:5(#10)

DLC:6(#10)

DCCDCC

3 DLC:1(#10) GN

2000-300:5A

PC: 0162(3), 1960

5 PD:GND(#12) GNDRAFT

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS

CUSTOMER COMMENTS

AAM

AAM

02/08/24

05/23/24

2 ESV

ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "C")

Shop Order: Item:

A01CS03149

1VAL314911L0202

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

M

OU

NT

IN

G

SH

EE

T

SEE NOTE 1

(0 1-

(0 1-

SW

GR

E

XT

ER

NA

L W

IR

IN

G

19" LOW VOLTAGE MODULE - RIGHT SHEET

NOTES:

1. FUSE BLOCKS AND CIRCUIT BREAKERS TO BE ROTATED CLOCKWISE.

NAME TAG SCHEDULE

19" LOW VOLTAGE MODULE - LEFT SHEET

M

OU

NT

IN

G

SH

EE

T

19" LOW VOLTAGE MODULE - BACK SHEET

M

OU

NT

IN

G

SH

EE

T

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

E

XT

ER

NA

L W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SWGR HORIZONTAL WIRING DUCT

SW

GR

E

XT

ER

NA

L W

IR

IN

G

(DWM REQUIRED, VARIANT C)

(01-20) (21-40) (41-60)

LOW VOLTAGE MODULE - CENTER FLOOR SHEET

LA

RG

E M

OU

NT

IN

G

SH

EE

T

SW

GR

D

OO

R W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SWGR HORIZONTAL WIRING DUCT

(01-10) (11-20)

CU

ST

OM

ER

C

ON

NE

CT

IO

N

(41-60)

SW

GR

IN

TE

RN

AL

W

IR

IN

G

CU

ST

OM

ER

C

ON

NE

CT

IO

N

SW

GR

IN

TE

RN

AL

W

IR

IN

G

(01-20) (21-40)

CRB CR

B

CRA

CR

A

PC: 15551

CRS

PC: 0782

PC: 0752(2)CAA 1

PC: 0762CR

S

2 1

CAA

PC: 0061

CRT

CAR

10A

FUSE

PT SECONDARY CKT

CAA

15A

FUSE

SEL-587

CDR

10A

FUSE

PT SECONDARY CKT

CRS

15A

MCB

HEATER CIRCUIT

PC: 1564

CM

CM

PC: 1565

CM

CM

PC: 1566

CM

CM

PC: 1556CHA

CH

A

PC: 1572CHA

CH

A

20PC: 0786(3), 0783

CAR

PC: 0786(3), 0783

CDR

CAR

CDR

PC: 1564

CLA

CL

A

PC: 1565

CLA

CL

A

PC: 1566

CLA

CL

A

50 DRAFT

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS AAM 02/08/241 ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "P")

Shop Order: Item:

A01CS03149

1VAL314911L0301

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

LVC DOOR PANEL 57"

PF

PC: 0503

SEL-751

03N1

PG

PC: 0311

CS

03N6

PH

PC: 0516

03N5 03N7

PGG

PC: 0344

G

PGR

PC: 0343

R

PMA

FT-1, 10P

PC: 0490

TS2

03N403N2

PFA

FT-14, 14P

PC: 0497

TS1

PM

PC: 0701

SEL-735

03N3 DRAFT

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS

CUSTOMER COMMENTS

AAM

AAM

02/08/24

05/23/24

2 ESV

ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "C")

Shop Order: Item:

A01CS03149

1VAL314911L0302

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

57" LOW VOLTAGE MODULE - LEFT SHEET

M

OU

NT

IN

G

SH

EE

T

SW

GR

IN

TE

RN

AL

W

IR

IN

G

CU

ST

OM

ER

C

ON

NE

CT

IO

N

SW

GR

IN

TE

RN

AL

W

IR

IN

G

CU

ST

OM

ER

C

ON

NE

CT

IO

N

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

(01-20) (21-40)

(01-20) (21-40)

57" LOW VOLTAGE MODULE - BACK SHEET

M

OU

NT

IN

G

SH

EE

T

SWGR HORIZONTAL WIRING DUCT

SW

GR

IN

TE

RN

AL

W

IR

IN

G

(01-20)

SW

GR

E

XT

ER

NA

L W

IR

IN

G

(21-40)

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

57" LOW VOLTAGE MODULE - RIGHT SHEET

NO

TE

S:

1.

F

US

E

BL

OC

KS

A

ND

C

IR

CU

IT

B

RE

AK

ER

S

TO

B E

RO

TA

TE

D

CL

OC

KW

IS

E.

NAME TAG SCHEDULE

M

OU

NT

IN

G

SH

EE

T

SEE NOTE 1

(0 1-

(0 1-

SW

GR

E

XT

ER

NA

L W

IR

IN

G

LOW VOLTAGE MODULE - CENTER FLOOR SHEET

LA

RG

E M

OU

NT

IN

G

SH

EE

T

SW

GR

D

OO

R W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SWGR HORIZONTAL WIRING DUCT

(01-10) (11-20)

PC: 1564

CLA

CL

A11

PC: 1565

CLA

CL

A31

PC: 1564

CLB

CL

B11

PC: 1565

CLB

CL

B31

PC: 1564

CM

CM

PC: 1565

CM

CM

PC: 0762CR

S

2 1

PC: 0782

PC: 0752(2)CAA 1

PC: 0782

PC: 0752(2)CAB 1

PC: 0782

PC: 0787(2)CAC 1

CRS

CAC

CAB

CAA

PC: 0061

CRT

CRB CR

B

CRA

CR

A

PC: 15551

CAE

1A

FUSE

VOLTAGE INPUTS

CAB

15A

FUSE

BKR TRIP CKT

CAA

15A

FUSE

BKR CLOSE CKT

CAC

1A

FUSE

VOLTAGE INPUTS

CAD

1A

FUSE

VOLTAGE INPUTS

CRS

15A

MCB

HEATER CIRCUIT

PC: 1556CHA

CH

A

PC: 1572CHA

CH

A

PC: 0787(3), 0783

CAD

PC: 0787(3), 0783

CAE

CAD

CAEDRAFT

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS AAM 02/08/241 ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "P")

Shop Order: Item:

A01CS03149

1VAL314911L0401

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

LVC DOOR PANEL 57"

PA

PC: 0701

SEL-735

04N1

04N2

PAA

FT-1, 10P

PC: 0490

TS1

PB

PC: 0701

SEL-735

04N3

04N4

PBA

FT-1, 10P

PC: 0490

TS2

PC

PC: 0701

SEL-735

04N5

PCA

FT-1, 10P

PC: 0490

TS3

PD

PC: 0701

SEL-735

04N7

PDA

FT-1, 10P

PC: 0490

TS4

04N6 04N8

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS

CUSTOMER COMMENTS

AAM

AAM

02/08/24

05/23/24

2 ESV

ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "C")

Shop Order: Item:

A01CS03149

1VAL314911L0402

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

57" LOW VOLTAGE MODULE - LEFT SHEET

M

OU

NT

IN

G

SH

EE

T

SW

GR

IN

TE

RN

AL

W

IR

IN

G

CU

ST

OM

ER

C

ON

NE

CT

IO

N

SW

GR

IN

TE

RN

AL

W

IR

IN

G

CU

ST

OM

ER

C

ON

NE

CT

IO

N

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

(01-20) (21-40)

(01-20) (21-40)

57" LOW VOLTAGE MODULE - RIGHT SHEET

NO

TE

S:

1.

F

US

E

BL

OC

KS

A

ND

C

IR

CU

IT

B

RE

AK

ER

S

TO

B E

RO

TA

TE

D

CL

OC

KW

IS

E.

NAME TAG SCHEDULE

M

OU

NT

IN

G

SH

EE

T

SEE NOTE 1

(0 1-

(0 1-

SW

GR

E

XT

ER

NA

L W

IR

IN

G

LOW VOLTAGE MODULE - CENTER FLOOR SHEET

LA

RG

E M

OU

NT

IN

G

SH

EE

T

SW

GR

D

OO

R W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SWGR HORIZONTAL WIRING DUCT

(01-10) (11-20)

57" LOW VOLTAGE MODULE - BACK SHEET

M

OU

NT

IN

G

SH

EE

T

SWGR HORIZONTAL WIRING DUCT

SW

GR

IN

TE

RN

AL

W

IR

IN

G

(01-20)

SW

GR

E

XT

ER

NA

L W

IR

IN

G

(21-40)

SW

GR

IN

TE

RN

AL

W

IR

IN

G

(41-60)

SW

GR

E

XT

ER

NA

L W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

E

XT

ER

NA

L W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

E

XT

ER

NA

L W

IR

IN

G (01-20) (21-40) (41-60)

SWGR HORIZONTAL WIRING DUCT

PC: 1564

CLA

CL

A11

PC: 1565

CLA

CL

A31

PC: 1564

CLB

CL

B11

PC: 1565

CLB

CL

B31

PC: 0762CR

S

2 1 CRS

PC: 0061

CRT

CRB CR

B

CRA

CR

A

PC: 15551

CAE

1A

FUSE

VOLTAGE INPUTS

CAA

15A

FUSE

SEL-735

CAC

1A

FUSE

VOLTAGE INPUTS

CAD

1A

FUSE

VOLTAGE INPUTS

CAF

1A

FUSE

VOLTAGE INPUTS

PC: 1556CHA

CH

A

PC: 1572CHA

CH

A

PC: 1564

CM

CM

PC: 1565

CM

CM

PC: 1566

CM

CM

PC: 1564

CMX

CM

X11

PC: 1565

CMX

CM

X31

PC: 1566

CMX

CM

X51

CAR

10A

FUSE

PT SECONDARY CKT

CRS

15A

MCB

HEATER CIRCUIT

PC: 0782

PC: 0752(2)CAA 1

CAC

CAA

PC: 0787(3), 0783

CAD

PC: 0787(3), 0783

CAE

CAD

CAE

PC: 0787(3), 0783

CAF

CAF

PC: 0786(3), 0783

CAR

CAR

PC: 0787(3), 0783

CAC

2DRAFT

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS AAM 02/08/241 ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "P")

Shop Order: Item:

A01CS03149

1VAL314911L0501

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

LVC DOOR PANEL 19"

PA

PC: 0311

CS

05N8

PL

PC: 0516

05N905N10

PAG

PC: 0344

G

PAR

PC: 0343

R

PD

PC: 0501

SEL-751

05N6

05N7

PDA

FT-1, 10P

PC: 0490

TS2

PG

PC: 0311

CS

05N3

05N4

PGG

PC: 0344

G

PGR

PC: 0343

R

PH

PC: 0516

05N5

PF

PC: 0501

SEL-751

05N1

05N2

PFA

FT-1, 10P

PC: 0490

TS1

F

G H I JEDCBA

G HDCBA I J

Approved By:

Date:

Drawn By:

Date:

Cust. P.O.:

For:

Sold To: 1173

SLAC

FGC CONSTRUCTION LLC

AAM

10/03/23

ESV

10/26/23

No: REVISIONS CHD:BY: DATE:

CUSTOMER COMMENTS

CUSTOMER COMMENTS

AAM

AAM

02/08/24

05/23/24

2 ESV

ESV

4916 E BROADWAY

MADISON, WI 53716

2575 SAND HILL ROAD M/S 1

MENLO PARK, CA 94025

Drawing Number: Rev:

PANEL LAYOUT (LV "C")

Shop Order: Item:

A01CS03149

1VAL314911L0502

Indoor Safegear, 15kV, 3000A, 50kA, 3PH-3W, 60Hz

Cubicle:

SAP #:

SWGR-9

152933518-10

The information contained in this document has to be kept strictly confidential.

Any unauthorized use, reproduction, distribution or disclosure to third parties is strictly forbidden. ABB reserves all rights regarding Intellectual Property Rights.

© Copyright 2019 ABB. All rights reserved. RELEASED

Status:

19" LOW VOLTAGE MODULE - BACK SHEET

M

OU

NT

IN

G

SH

EE

T

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

E

XT

ER

NA

L W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SWGR HORIZONTAL WIRING DUCT

(01-20) (21-40)

19" LOW VOLTAGE MODULE - LEFT SHEET

M

OU

NT

IN

G

SH

EE

T

SW

GR

IN

TE

RN

AL

W

IR

IN

G

CU

ST

OM

ER

C

ON

NE

CT

IO

N

CU

ST

OM

ER

C

ON

NE

CT

IO

N

(01-12) (13-24) (25-36)

SW

GR

I

NT

ER

NA

L W

IR

IN

G

NAME TAG SCHEDULE

19" LOW VOLTAGE MODULE - RIGHT SHEET

NOTES:

1. FUSE BLOCKS AND CIRCUIT BREAKERS TO BE ROTATED CLOCKWISE.

M

OU

NT

IN

G

SH

EE

T

SEE NOTE 1

(0 1-

(0 1-

SW

GR

E

XT

ER

NA

L W

IR

IN

G

LOW VOLTAGE MODULE - CENTER FLOOR SHEET

LA

RG

E M

OU

NT

IN

G

SH

EE

T

SW

GR

D

OO

R W

IR

IN

G

SW

GR

D

OO

R W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SW

GR

IN

TE

RN

AL

W

IR

IN

G

SWGR HORIZONTAL WIRING DUCT

SWGR HORIZONTAL WIRING DUCT

(01-…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .