B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part4.pdf
PDF 16 MB Posted
- Solicitation number
- 140P2026R0057
About this file
This document set comprises electrical, technology, fire protection, and fire alarm design drawings for the Rehabilitation of Kawuneeche Visitor Center at Rocky Mountain National Park. The project involves construction documents dated January 16, 2026, prepared by OTAK, Inc. (Redmond, WA) as the prime architect with AE Design (Denver, CO) and Interface Engineering (Portland, OR) as subcontractors.
The technology scope includes network infrastructure, audio-visual systems, security access control, intrusion detection, and video surveillance throughout the admin wing, auditorium, exhibit spaces, and comfort station. Key technology components include a dedicated server room (Room 116) with structured cabling, CAT6A copper and fiber connectivity, wireless access points, PTZ cameras, projection screens, touch panels, and digital signage. The fire protection system provides wet-pipe sprinklers with anti-freeze solution for the admin and VC/exhibit wings (140 total sprinkler heads across ordinary and light hazard occupancies at 0.10-0.15 GPM/SF design density), dry-pipe systems for the covered walkway and comfort station, and a single interlock preaction system for the server room. Fire alarm provisions include addressable smoke and heat detection, audiovisual notification appliances, and integration with sprinkler flow and tamper switches. All systems are designed in accordance with NFPA 13, 2024 IBC/IFC, and NPS requirements. Electrical infrastructure includes conduit pathways with sweeping bends, pull points not exceeding 100 feet apart, and surface-mounted wiremold in visible ceiling spaces. Equipment schedules identify manufacturers and part numbers for PDUs, fiber optic connectivity, copper patch panels, racks, wireless access points, cameras, and surge protection devices.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
L
K
2 3 4 5 76
M
8 9 10 11 12 13 14 15 16 17
SERVER ROOM
OFFICE
OFFICE
OFFICE
RR
RR
MECH. / ELEC.
BREAK ROOM
CONFERENCE
STOR
OFFICE
HALL
OFFICE
OFFICE
OFFICE
OFFICE
HALL
JC
CAM3
+7' 6" AFF
CAM3
+7' 0" AFF
CAM3
+7' 0" AFF
OUTLETS, DEVICES, EQUIPMENT,
ELEMENTS AND ANY OTHER ITEMS SHOWN
IN GREY SHALL BE CONSIDERED OUTSIDE
THIS SCOPE OF WORK. ITEMS SHALL BE
CONSIDERED AS EXISTING TO REMAIN
OUTLETS, DEVICES, EQUIPMENT,
ELEMENTS AND ANY OTHER ITEMS SHOWN
IN BLACK SHALL BE CONSIDERED WITHIN
THIS SCOPE OF WORK. ITEMS SHALL BE
CONSIDERED AS NEW, REFER TO
RESPONSIBILITY MATRIX FOR MORE
INFORMATION.
REHABILITATION LEGEND
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: B
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T301
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 151 177
TECHNOLOGY RCP -
ADMIN WING
T301
TECH FIRST FLOOR CEILING PLAN - ADMIN WING1
40 84
SCALE OF FEET
A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS,
AND SPECIFICATIONS FOR MORE INFORMATION.
B. DEVICE LOCATIONS SHOWN SHALL BE COORDINATED WITH
ARCHITECTURAL ELEMENTS, FURNITURE, AND OTHER TRADES FOR FINAL
INSTALLATION LOCATION.FINAL LOCATION TO BE APPROVED BY
CONTRACTING OFFICER.
C. ALL NETWORK, SECURITY, AND/OR AUDIO VIDEO CABLE SUPPORTING
SYSTEM DEVICES/OUTLETS SHALL BE ENCLOSED IN CONDUIT FROM THE
SERVER ROOM 116 TO THE DEVICE/OUTLET. NO CABLING SHALL BE
VISIBLE OR 'FREE RUN' IN CEILING SPACE. REFER TO DETAILS.
D. NO MORE THAN 100 FEET OF PATHWAY MAY BE INSTALLED BETWEEN
PULL POINTS.
E. ALL CONDUIT BENDS SHALL BE THE "SWEEPING" TYPE AND IN
ACCORDANCE WITH THE BEND RADIUS REQUIREMENTS SPECIFIED IN THE
PROJECT GENERAL NOTES. NO "BEND" OR "ELBOW" FITTINGS ARE
PERMITTED UNLESS SPECIFICALLY NOTED.
F. WHERE TECHNOLOGY OUTLET IS INDICATED ON AN EXISTING WALL, IT IS
ACCEPTABLE TO UTILIZE FLEXIBLE CONDUIT TO ROUTE THROUGH WALL
SPACE. WHERE TECHNOLOGY OUTLET IS INDICATED ON A NEW WALL,
ELECTRICAL METALLIC TUBING (EMT) SHALL BE UTILIZED. REFER TO
DETAILS FOR MORE INFORMATION.
TECHNOLOGY GENERAL NOTES
SCALE B
TRUE PLAN
01/08/2026
S1 S1
S1 S1
S1 S1
S3
S3
S2 S2S2
S2S2
H
G
F
EXHIBIT NO. 1
AUDITORIUM
MECH. RM
STORAGE
STORAGE
EXHIBIT NO. 2
VEST.
WILDERNESS DESK
P
PS1
PJ1
CAM3
CAM3
MA1
PB1
6' 6" AFF
CAM3
7' 6" AFF
8' 0" AFF
6' 6" AFF
(1) 1" C.
+13' 0" AFF
(1) 1" C.
+13' 0" AFF
24" x 36" x 8" ENCLOSURE
+6' 0" AFF
(1) 2" C.
+9' 0" AFF
(1) 3" C.
+9' 0" AFF
(1) 1" C.
+13' 0" AFF
(2) 3/4" C.
+13' 0" AFF
(1) 1" C.
+7' 0" AFF
(1) 4" C.
+13' 0" AFF
24" x 36" x 8" ENCLOSURE
ABOVE CEILING
OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER
ITEMS SHOWN IN GREY SHALL BE CONSIDERED OUTSIDE THIS
SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS EXISTING
TO REMAIN
OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER
ITEMS SHOWN IN BLACK SHALL BE CONSIDERED WITHIN THIS
SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS NEW,
REFER TO RESPONSIBILITY MATRIX FOR MORE INFORMATION.
REHABILITATION LEGEND
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: B
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T302
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 152 177
TECHNOLOGY RCP -
AUDITORIUM & EXHIBIT
T302
TECH FIRST FLOOR CEILING PLAN - AUDITORIUM & EXHIBIT1
40 84
SCALE OF FEET
A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS,
AND SPECIFICATIONS FOR MORE INFORMATION.
B. DEVICE LOCATIONS SHOWN SHALL BE COORDINATED WITH
ARCHITECTURAL ELEMENTS, FURNITURE, AND OTHER TRADES FOR FINAL
INSTALLATION LOCATION.FINAL LOCATION TO BE APPROVED BY
CONTRACTING OFFICER.
C. ALL NETWORK, SECURITY, AND/OR AUDIO VIDEO CABLE SUPPORTING
SYSTEM DEVICES/OUTLETS SHALL BE ENCLOSED IN CONDUIT FROM THE
SERVER ROOM 116 TO THE DEVICE/OUTLET. NO CABLING SHALL BE
VISIBLE OR 'FREE RUN' IN CEILING SPACE. REFER TO DETAILS.
D. NO MORE THAN 100 FEET OF PATHWAY MAY BE INSTALLED BETWEEN
PULL POINTS.
E. ALL CONDUIT BENDS SHALL BE THE "SWEEPING" TYPE AND IN
ACCORDANCE WITH THE BEND RADIUS REQUIREMENTS SPECIFIED IN THE
PROJECT GENERAL NOTES. NO "BEND" OR "ELBOW" FITTINGS ARE
PERMITTED UNLESS SPECIFICALLY NOTED.
F. WHERE TECHNOLOGY OUTLET IS INDICATED ON AN EXISTING WALL, IT IS
ACCEPTABLE TO UTILIZE FLEXIBLE CONDUIT TO ROUTE THROUGH WALL
SPACE. WHERE TECHNOLOGY OUTLET IS INDICATED ON A NEW WALL,
ELECTRICAL METALLIC TUBING (EMT) SHALL BE UTILIZED. REFER TO
DETAILS FOR MORE INFORMATION.
TECHNOLOGY GENERAL NOTES
SCALE B
TRUE PLAN
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 BOTTOM OF PROJECTOR SCREEN SHALL BE 4' 0" AFF WHEN SCREEN IS
DEPLOYED.
2 COORDINATE PRECISE INSTALLED LOCATION WITH CONTRACTING
OFFICER.
3 EXPOSED CONDUIT INDICATED SHALL BE SURFACE MOUNTED WIREMOLD.
ALL SURFACE MOUNTED WIREMOLD SHALL BE PAINTED TO MATCH WALLS
AT WHICH IS ATTACHED.
9 10 11 12 13 14 15 16
D
C
B
A
MEN'S RR
WOMEN'S RR
MECH. RM
JANITOR
CAM2
12" X 24" X 8" ENCLOSURE
+6' 0" AFF
(3) 1" C.
+8' 0" AFF
(RL)
(1) 1" C.
+8' 2" AFF
OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER
ITEMS SHOWN IN GREY SHALL BE CONSIDERED OUTSIDE THIS
SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS EXISTING
TO REMAIN
OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER
ITEMS SHOWN IN BLACK SHALL BE CONSIDERED WITHIN THIS
SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS NEW,
REFER TO RESPONSIBILITY MATRIX FOR MORE INFORMATION.
REHABILITATION LEGEND
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: B
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T303
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 153 177
TECHNOLOGY RCP -
COMFORT STATION
T303
TECH FIRST FLOOR CEILING PLAN - COMFORT STATION1
40 84
SCALE OF FEET
A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS,
AND SPECIFICATIONS FOR MORE INFORMATION.
B. DEVICE LOCATIONS SHOWN SHALL BE COORDINATED WITH
ARCHITECTURAL ELEMENTS, FURNITURE, AND OTHER TRADES FOR FINAL
INSTALLATION LOCATION.FINAL LOCATION TO BE APPROVED BY
CONTRACTING OFFICER.
C. ALL NETWORK, SECURITY, AND/OR AUDIO VIDEO CABLE SUPPORTING
SYSTEM DEVICES/OUTLETS SHALL BE ENCLOSED IN CONDUIT FROM THE
SERVER ROOM 116 TO THE DEVICE/OUTLET. NO CABLING SHALL BE
VISIBLE OR 'FREE RUN' IN CEILING SPACE. REFER TO DETAILS.
D. NO MORE THAN 100 FEET OF PATHWAY MAY BE INSTALLED BETWEEN
PULL POINTS.
E. ALL CONDUIT BENDS SHALL BE THE "SWEEPING" TYPE AND IN
ACCORDANCE WITH THE BEND RADIUS REQUIREMENTS SPECIFIED IN THE
PROJECT GENERAL NOTES. NO "BEND" OR "ELBOW" FITTINGS ARE
PERMITTED UNLESS SPECIFICALLY NOTED.
F. WHERE TECHNOLOGY OUTLET IS INDICATED ON AN EXISTING WALL, IT IS
ACCEPTABLE TO UTILIZE FLEXIBLE CONDUIT TO ROUTE THROUGH WALL
SPACE. WHERE TECHNOLOGY OUTLET IS INDICATED ON A NEW WALL,
ELECTRICAL METALLIC TUBING (EMT) SHALL BE UTILIZED. REFER TO
DETAILS FOR MORE INFORMATION.
TECHNOLOGY GENERAL NOTES
SCALE B
TRUE PLAN
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 CONDUIT SHALL BE ROUTED TIGHT ALONG ROOFLINE OF COVERED
WALKWAY. CONDUIT SHALL BE PAINTED TO MATCH THE SURROUNDING
SURFACE.
2 PENETRATION LOCATION FROM COVERED WALKWAY INTO ATTIC SPACE
SHALL BE APPROVED BY CONTRACTING OFFICER. THE PENETRATION
SHALL BE CONCEALED AS MUCH AS POSSIBLE.
3 EXTERIOR WIRELESS ACCESS POINT (WAP) SHALL BE RELOCATED TO
THIS LOCATION TO SUPPORT EXTERIOR WIFI ACCESS IN THE PUBLIC
PARKING LOT. THE WALL MOUNTED ENCLOSURE THE WIRELESS ACCESS
POINT SHALL BE MOUNTED IN SHALL BE OUTDOOR RATED, RADIO
FREQUENCY TRANSPARENT, AND PAINTABLE. ENCLOSURE SHALL BE
PAINTED WITH MANUFACTURER APPROVED PAINT TO COLOR MATCH
BUILDING WHERE MOUNTED. PAINT COLOR AND MOUNTING LOCATION
TO BE APPROVED BY CONTRACTING OFFICER. THE ENCLOSURE SHALL
BE MOUNTED ABOVE THE COVERED WALKWAY ROOF, SURFACE
MOUNTED TO THE COMFORT STATION WALL.
L
M
12 13 14
T4004
RR2
RV2
RV2
G B
C B
RL1
R L
RL1
R L
RL1
REFER TECHNOLOGY SITE PLAN
PLYWOOD BACKBOARD
PLYWOOD BACKBOARD
PLYWOOD BACKBOARD
INTRUSION PANEL ACCESS CONTROL
PANEL
R L
RL1
RL1
R L
SPACE DEDICATED
FOR ACCESS
CONTROL
EQUIPMENT
PLYWOOD BACKBOARD
RL1RL1
R L
CB1
GB1
RR2
RV2
PLYWOOD BACKBOARD
ACCESS CONTROL PANEL
PLYWOOD BACKBOARD
REFER TECHNOLOGY SITE PLAN
RL1
PLYWOOD BACKBOARD
RL1
SPACE
DEDICATED
FOR
INTRUSION
DETECTION
EQUIPMENT
RL1
R L
RL1
REFER TECHNOLOGY SITE PLAN
PLYWOOD BACKBOARD
PLYWOOD BACKBOARD
R L
RL1RL1
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: D
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T400
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 154 177
TECHNOLOGY
ENLARGED - RACK
LOCATION
T400
TECHNOLOGY ENLARGED PLAN - SERVER ROOM 1161
T400
SERVER ROOM 116 - EAST ELEVATION2
T400
SERVER ROOM 116 - SOUTH ELEVATION3
T400
SERVER ROOM 116 - WEST ELEVATION4
T400
SERVER ROOM 116 - NORTH ELEVATION5
A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS, AND SPECIFICATIONS FOR MORE
INFORMATION.
B. NO EQUIPMENT MAY ENTER OR PASS THROUGH THE TELECOMMUNICATION SPACE UNLESS SPECIFICALLY SUPPORTING THE SPACE. THIS INCLUDES, BUT IS NOT LIMITED TO, HVAC DUCTS, CONDUIT, PLUMBING, ETC.
C. ALL CABLING ROUTED VERTICALLY ON WALLS SHALL BE SUPPORTED WITH CABLE TIES MOUNTED TO WALL MOUNTED
VERTICAL LADDER RACK AND/OR D-RINGS.
D. A MINIMUM OF 3 FEET OF CLEARANCE SHALL BE MAINTAINED IN THE FRONT AND BACK OF EACH RACK, AFTER EQUIPMENT IS INSTALLED. CONTRACTOR SHALL ASSUME A MINIMUM OF 24 INCHES OF DEPTH FOR RACK MOUNTED
ACTIVE EQUIPMENT IN 2-POST RACKS.
E. ALL WALLS SHALL BE COVERED WITH PLYWOOD, REFER TO SPECIFICATIONS FOR MORE INFORMATION.
F. THE DEDICATED IN-ROOM HVAC THERMOSTAT SHALL BE MOUNTED ADJACENT THE LIGHT SWITCH NEAR ENTRY DOOR.
G. CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONTRACTORS/TRADES TO ENSURE WALL AND RACK SPACE
ALLOCATION NEEDS.
TECHNOLOGY GENERAL NOTES
20 42
SCALE OF FEET
SCALE D
SCALE DSCALE D
SCALE D SCALE D
W
ID
E V
E R
T
IC
A L
W
IR
E M
A N
A G
E R
KEY RACK 01
W
ID
E V
E R
T
IC
A L
W
IR
E M
A N
A G
R
45 RA6 UPPER TROUGH 45
44 FP1 FIBER PANEL 44
43 RA7 HORIZONTAL WIRE MANAGER 43
SPACE RESERVED FOR OWNER HEADEND
41 41
40 40
39 39
38 38
37 37
36 SP1 PDU 36
35 CP1 CAT6A PATCH PANEL 35
34 RA7 HORIZONTAL WIRE MANAGER 34
33 OWNER SWITCH 33
32 RA7 HORIZONTAL WIRE MANAGER 32
CP2 CAT6A PATCH PANEL
30 30
29 RA7 HORIZONTAL WIRE MANAGER 29
28 OWNER SWITCH 28
27 RA7 HORIZONTAL WIRE MANAGER 27
CP2 CAT6A PATCH PANEL
25 25
24 RA7 HORIZONTAL WIRE MANAGER 24
23 OWNER SWITCH 23
22 RA7 HORIZONTAL WIRE MANAGER 22
CP2 CAT6A PATCH PANEL
20 20
19 RA7 HORIZONTAL WIRE MANAGER 19
18 SV1 VIDEO SURVEILLANCE DEDICATED SWITCH 18
FUTURE
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
UPS (E)
7 7
UPS (E)
5 5
UPS (E)
3 3
EMPTY
1 1
RV2 RR2 RV2
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T401
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 155 177
TECHNOLOGY - RACK
ELEVATIONS
T401
SERVER ROOM 116 - RACK ELEVATION1
L G K 11/2 024
LAN
FROM FIRE ALARM
PANEL (PBO)
CC
CONTROL
SYSTEM CPU
VIDEO PROJECTOR
IP
AUDIO DSPIP
SURROUND SOUND PROCESSOR
IP
RS-232 PROJECTOR SCREEN UP / DOWN SWITCH
HDBT TO IP
ENCODER
IP
PAN TILT
ZOOM
CAMERA
PTZ1
HDBT
DANTE
WIRELESS
MICROPHONE
RECEIVER
2 CHANNEL
W/ DANTE)
RFWIRELESS MIC
ANTENNA
WM1
RFWIRELESS MIC
ANTENNA
WM1
HDMI
4K VIDEO
LASER
PROJECTOR
W/ MOUNT
PJ1
IP TO HDMI
DECODER RS-232
LAN
AV NETWORK
SWITCHES
W/POE+ &
PATCH-BAY
IP
LAN
PB1
IP
LAN
FROM AV NETWORK
HDBT TO IP
ENCODER
IP
USB-C VIDEO
TRANSMITTER
WALL PLATE
AV2
HDBT
AV-OVER-IP
SWITCHER W/
HDMI AND
USB-C
AV1
LAN
OFE LAPTOP
USB-C (VIDEO)
HDBT TO IP
ENCODER
IP
PAN TILT
ZOOM
CAMERA
PTZ1
HDBT
IP TO HDMI
DECODER
IP
LAN
DANTE
WIFI
ASSISTIVE
LISTENING
SYSTEM
HDMI
DIGITAL
SIGNAGE
MULTIMEDIA
PLAYER
IP IP
HDBT TO IP
ENCODER
IP
PAN TILT
ZOOM
CAMERA
PTZ1
HDBT
HDBT TO IP
ENCODER
IP
USB-C VIDEO
TRANSMITTER
WALL PLATE
AV2
HDBT
AV-OVER-IP
SWITCHER W/
HDMI AND
USB-C
AV1
LAN
HDBT TO IP
ENCODER
IP
USB-C VIDEO
TRANSMITTER
WALL PLATE
AV2
HDBT
AV-OVER-IP
SWITCHER W/
HDMI AND
USB-C
AV1
LAN
HDBT TO IP
ENCODER
IP
PROFESSIONAL
4K BLURAY
PLAYER
HDBT
BLURAY PLAYERIP
GENERAL NOTES:
A. ALL DATA PATCH CABLES REQUIRED TO CONNECT AN AV DEVICE TO A
DATA NETWORK OUTLET SHALL BE PROVIDED BY THE AVC AND SHALL
BE OF EXACTLY THE SAME CATEGORY CLASS ( OR BETTER) AS THE
INCOMING CABLES, I.E. A SHIELDED CAT6A INCOMING CABLES TO THE
PATCH BAY SHALL REQUIRE A SHIELDED CAT6A RATED PATCH CABLE
B. AVC SHALL PROVIDE ALL REQUIRED SPECIALIZED/CUSTOM CABLES
PROVIDING THE PARK WITH A TURN-KEY SOLUTION.
C. AVC SHALL SUPPLY AND UTILIZE RS-485/422/232 BALUNS FOR LOW
VOLTAGE CONTROL APPLICATIONS ETCETERA AS DISTANCE
LIMITATIONS REQUIRE.
D. AVC MUST UTILIZE THE 274100 SPECIFICATION SECTION IN
CONJUNCTION WITH THESE DRAWINGS TO FULLY UNDERSTAND THE
SCOPE OF WORK AND SYSTEM FUNCTIONALITY REQUIRED FOR THIS
PROJECT.
E. AVC SHALL VERIFY AND COORDINATE ALL INFRASTRUCTURE
REQUIREMENTS, I.E. CONDUIT, PULL, JOB AND BACK BOXES ETCETERA
WITH EC PRIOR TO THE COMPLETION OF ELECTRICAL ROUGH-IN PHASE.
IMMEDIATELY BRING DISCREPANCIES TO THE ATTENTION OF THE EC
AND THE AV CONSULTANT.
F. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS
CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR
COMPLETE AND FULLY OPERATIONAL SYSTEM.
G. ALL HIGH VOLTAGE CONNECTIONS SHALL BE PERFORMED BY THE BY
EC WITH THE LOW VOLTAGE WORK BY AVC.
H. ALL AUDIO CABLING AND TERMINATIONS SHALL UTILIZE THE THREE
WIRE "BALANCED" PROFESSIONAL AUDIO INDUSTRY STANDARD
WHEREVER POSSIBLE. STEREO AUDIO, THOUGH NOT ALWAYS
DETAILED IS REQUIRED.
I. ALL AV EQUIPMENT FURNISHED AND INSTALLED BY AVC UNLESS
SPECIFIED OTHERWISE.
J. AVC SHALL INSTALL EACH CEILING LOUDSPEAKER OR LOUDSPEAKER
CLUSTER WITH A SEISMIC RESTRAINING SYSTEM PER ALL LOCAL,
STATE AND FEDERAL CODES.
K. BASED ON SITE CONDITIONS, THE CONTRACTOR SHALL FIELD VERIFY
THE PROJECTION SCREEN IMAGE SIZE AS WELL AD THE PHYSICAL SITE
INSTALLATION LOCATIONS PRIOR TO SHOP DRAWING SUBMITTAL,
PURCHASE AND INSTALLATION. IN CASES WHEN THE SCREENS ARE
PBO THE CONTRACTOR SHALL VERIFY THE VALIDITY OF THE SCREEN
SIZE AND IMMEDIATELY CONTACT THE DESIGN TEAM IF VARIANCES OR
DEFICIENCIES HAVE BEEN FOUND WHERE THERE IS A MISMATCH IN THE
SCREEN ASPECT RATIO AND THE NATIVE PROJECTOR RESOLUTION
L. EQUIPMENT AND SIGNAL FLOW SHOWN IS OF A CONCEPTUAL NATURE.
AVC SHALL PROVIDE ALL NECESSARY INCIDENTAL ELECTRONICS AND
EQUIPMENT SUCH THAT A TURN-KEY SOLUTION IS INSTALLED AND
READY FOR THE IMMEDIATE USAGE. ITEMS SUCH AS BALUNS, POWER
SUPPLIES, CABLE MANAGEMENT ACCESSORIES, SMALL LOCAL
ETHERNET ROUTERS ETCETERA SHALL BE INCLUDED IN THE BASE
SCOPE. SUBMIT QUESTIONS FOR CLARIFICATION PRIOR TO YOUR
RETURN AS MONIES SHALL NOT BE AVAILABLE FOR ITEMS NOT
ACCOUNTED FOR IN YOUR DOCUMENTATION. NO EXCEPTIONS.
M. AVC SHALL CLOSELY COORDINATE WITH THE TELEDATA CONTRACTOR
ALL DATA DROP LOCATIONS AND MOUNTING HEIGHTS AS NECESSARY.
N. AVC SHALL CLOSELY COORDINATE WITH PARK IT STAFF TO PROCURE
THE NECESSARY NETWORK ACCESS, IP ADDRESSES ETCETERA
REQUIRED FOR THIS PROJECT.
O. AV CONTRACTOR SHALL PROVIDE A TURN-KEY THE DEDICATED
ETHERNET NETWORK FOR THIS PROJECT INCLUDING BUT NOT LIMITED
TO SWITCHES,PATCH-BAYS, PATCH CABLES ETCETERA.
10"
TOUCH
PANEL
TP10
LAN
CC
MOTORIZED
PR0JECTION
SCREEN W/
LVC MODULE
PS1
RS-232
FROM
CONTROL
CPU
WALL
MOUNTED UP
/ DOWN
SWITCH
SW1
CEILING
MICROPHONE
ARRAY
DANTE
MA1
RF BANDPASS
FILTER
RF
RF BANDPASS
FILTER
RF
HDMI
AV RACK ER1
BLUETOOTH
RECEIVER
DANTE
BT1
DOLBY
SURROUND
SOUND
PROCESSOR
FRONT LEFTHDMI
FRONT CENTER
FRONT RIGHT
SIDE LEFT
SIDE RIGHT
REAR LEFT
REAR RIGHT
FRONT SUB
REAT SUB
SPKR
SPKR
SPKR
SPKR
OUTINPUT
AUDIO DSP
NETWORK
DANTE
DANTE
LAN
OUTINPUT
300 W /
CHANNEL
AMPLIFIER
SPKR
SPKR
SPKR
SPKR
DIRECTIONAL
CEILING FRONT LEFT
8.00 OHM
FRONT + REAR SUB
8.00 OHM
(TYPICAL OF 2)
FROM AV
NETWORK LAN
S2
S2
S2
DIRECTIONAL
CEILING FRONT
CENTER
8.00 OHM
DIRECTIONAL
CEILING FRONT
RIGHT
8.00 OHM
LEFT SIDE CEILING
TAP @ 32W
(TYPICAL OF 3)
S1
S2
S2
S3
DIRECTIONAL
CEILING LEFT REAR
8.00 OHM
DIRECTIONAL
CEILING RIGHT REAR
8.00 OHM
DANTE
DANTE
RIGHT SIDE CEILING
TAP @ 32W
(TYPICAL OF 3)
S1
10"
TOUCH
PANEL
TP10
LAN
WIRELESS
MICROPHONE
ANTENNA
DANTE
WM1
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T500
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 156 177
AV ONE-LINES
T500
AV ONE-LINE AUDITORIUM1
L G K 2/2 025
IP
75" VIDEO
MONITOR
W/ MOUNT
USB-C (VIDEO)
OFE LAPTOP /
TABLET
LAN HDMI
USB-C VIDEO
TRANSMITTER
WALL PLATE
DESK MOUNT
AV2
VIDEO SOUND
BAR CAMERA
SYSTEM
W/ MOUNT
VSB
FP75
HDBT
FROM BUILDING
NETWORK
USB-C (DATA) USB IP
USB-C (DATA)
TRANSMITTER
WALL PLATE
USB
USB-C
RECEIVER
USB-C
HDMI
TRANSMITTER
WALL PLATE
DESK MOUNT
AV1
HDBTHDMI (VIDEO)
LAN
HDBT TO IP
ENCODER
HDMI
IP TO HDMI
DECODER RS-232
IP VIDEO
BB1
IP
HDBT TO IP
ENCODER
IP
USB/DATA
IP
USB-C VIDEO
TRANSMITTER
WALL PLATE
AV2
HDBT
HDMI
TRANSMITTER
WALL PLATE
AV1
HDBT HDBT TO IP
ENCODER
IP
HDBT TO IP
ENCODER
GENERAL NOTES:
ALL DATA PATCH CABLES REQUIRED TO CONNECT AN AV DEVICE TO A
DATA NETWORK OUTLET SHALL BE PROVIDED BY THE AVC AND SHALL BE
OF EXACTLY THE SAME CATEGORY CLASS ( OR BETTER) AS THE
INCOMING CABLES, I.E. A SHIELDED CAT6A INCOMING CABLES TO THE
PATCH BAY SHALL REQUIRE A SHIELDED CAT6A RATED PATCH CABLE
AVC SHALL PROVIDE ALL REQUIRED SPECIALIZED/CUSTOM CABLES
PROVIDING THE PARK WITH A TURN-KEY SOLUTION.
AVC SHALL SUPPLY AND UTILIZE RS-485/422/232 BALUNS FOR LOW
VOLTAGE CONTROL APPLICATIONS ETCETERA AS DISTANCE LIMITATIONS
REQUIRE.
AVC MUST UTILIZE THE 274100 SPECIFICATION SECTION IN CONJUNCTION
WITH THESE DRAWINGS TO FULLY UNDERSTAND THE SCOPE OF WORK
AND SYSTEM FUNCTIONALITY REQUIRED FOR THIS PROJECT.
AVC SHALL VERIFY AND COORDINATE ALL INFRASTRUCTURE
REQUIREMENTS, I.E. CONDUIT, PULL, JOB AND BACK BOXES ETCETERA
WITH EC PRIOR TO THE COMPLETION OF ELECTRICAL ROUGH-IN PHASE.
IMMEDIATELY BRING DISCREPANCIES TO THE ATTENTION OF THE EC AND
THE AV CONSULTANT.
PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS
CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR
COMPLETE AND FULLY OPERATIONAL SYSTEM.
ALL HIGH VOLTAGE CONNECTIONS SHALL BE PERFORMED BY THE BY EC
WITH THE LOW VOLTAGE WORK BY AVC.
ALL AUDIO CABLING AND TERMINATIONS SHALL UTILIZE THE THREE WIRE
"BALANCED" PROFESSIONAL AUDIO INDUSTRY STANDARD WHEREVER
POSSIBLE. STEREO AUDIO, THOUGH NOT ALWAYS DETAILED IS REQUIRED.
ALL AV EQUIPMENT FURNISHED AND INSTALLED BY AVC UNLESS
SPECIFIED OTHERWISE.
AVC SHALL INSTALL EACH CEILING LOUDSPEAKER OR LOUDSPEAKER
CLUSTER WITH A SEISMIC RESTRAINING SYSTEM PER ALL LOCAL, STATE
AND FEDERAL CODES.
BASED ON SITE CONDITIONS, THE CONTRACTOR SHALL FIELD VERIFY THE
PROJECTION SCREEN IMAGE SIZE AS WELL AD THE PHYSICAL SITE
INSTALLATION LOCATIONS PRIOR TO SHOP DRAWING SUBMITTAL,
PURCHASE AND INSTALLATION. IN CASES WHEN THE SCREENS ARE PBO
THE CONTRACTOR SHALL VERIFY THE VALIDITY OF THE SCREEN SIZE AND
IMMEDIATELY CONTACT THE DESIGN TEAM IF VARIANCES OR
DEFICIENCIES HAVE BEEN FOUND WHERE THERE IS A MISMATCH IN THE
SCREEN ASPECT RATIO AND THE NATIVE PROJECTOR RESOLUTION
EQUIPMENT AND SIGNAL FLOW SHOWN IS OF A CONCEPTUAL NATURE.
AVC SHALL PROVIDE ALL NECESSARY INCIDENTAL ELECTRONICS AND
EQUIPMENT SUCH THAT A TURN-KEY SOLUTION IS INSTALLED AND READY
FOR THE IMMEDIATE USAGE. ITEMS SUCH AS BALUNS, POWER SUPPLIES,
CABLE MANAGEMENT ACCESSORIES, SMALL LOCAL ETHERNET ROUTERS
ETCETERA SHALL BE INCLUDED IN THE BASE. SUBMIT QUESTIONS FOR
CLARIFICATION PRIOR TO YOUR RETURN AS MONIES SHALL NOT BE
AVAILABLE FOR ITEMS NOT ACCOUNTED FOR IN YOUR DOCUMENTATION.
NO EXCEPTIONS.
AVC SHALL CLOSELY COORDINATE WITH THE TELEDATA CONTRACTOR
ALL DATA DROP LOCATIONS AND MOUNTING HEIGHTS AS NECESSARY.
AVC SHALL CLOSELY COORDINATE WITH PARK IT STAFF TO PROCURE THE
NECESSARY NETWORK ACCESS, IP ADDRESSES ETCETERA REQUIRED
FOR THIS PROJECT.
AV CONTRACTOR SHALL PROVIDE A TURN-KEY THE DEDICATED ETHERNET
NETWORK FOR THIS PROJECT INCLUDING BUT NOT LIMITED TO
SWITCHES,PATCH-BAYS, PATCH CABLES ETCETERA.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
1 THIS DEVICE IS MOUNTED INSIDE THE
FLAT PANEL BACK BOX BB1.
AV NETWORK
SWITCH
W/POE+ &
PATCH BAY
LAN
AV RACK ER1
LAN
FROM BUILDING LAN
10"
TOUCH
PANEL
TP10
LANCONFERENCE
ROOM 120
KEYNOTE LEGEND
KEY
VALUE
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T501
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 157 177
AV ONE-LINES
T501
AV ONE-LINE CONFERENCE ROOM1
CW6
CJ2
CC2
SYMBOL:
CLG
CC2
CC2
CJ2
CW7
CJ2
SYMBOL:
CLG
#6 AWG BONDING
JUMPER TO BRIDGE
CABLE TRAY JUNCTIONS
TELEPHONE TYPE
CABLE TRAY TYPICAL
BUTT-SPLICE
TELEPHONE TYPE CABLE TRAY
TELEPHONE TYPE CABLE TRAY
#6 AWG BONDING JUMPER
TO BRIDGE CABLE TRAY
JUNCTIONS
TELEPHONE TYPE CABLE
TRAY TYPICAL JUNCTION
SPLICE KIT
#6 AWG BONDING JUMPER
FROM TELECOM CABLE TRAY
TELECOMMUNICATIONS ROOM
GROUNDING BUS BAR.
#6 AWG BONDING JUMPER
FROM EACH TELECOM EQUIPMENT
RACK TO TELECOMMUNICATIONS
ROOM GROUNDING BUS BAR.
1-T600
1-T600
1-T600
2700V
INSULATORS
STAND-OFFS
COPPER BUS BAR.
BOLT CONNECTION WITH
COMPRESSION SPADE LUG
FITTING (TYPICAL)
PROVIDE BONDING TO
CONNECTIONS TO
CABLE TRAY
SYSTEMS
AND EQUIPMENT
RACKS
(TYPICAL)
1" CONDUIT & CONNECTOR.
4-11/16" SQUARE, 2-1/8" DEEP
JUNCTION BOX WITH KNOCKOUTS.
4-11/16" SQUARE
1-DEVICE RAISED
MUD RING.
MODULAR JACK OR
BLANK AS NEEDED
FACEPLATE
CATEGORY CABLES
(QTY AS INDICATED ON PLANS)
1-1/4" CONDUIT &
CONNECTOR.
4-11/16" SQUARE, 2-1/8" DEEP
JUNCTION BOX WITH KNOCKOUTS.
4-11/16" SQUARE
1-DEVICE RAISED
MUD RING.
SYMBOL: CR IM KP XX-XXSYMBOL:
CABLES
(QTY AS INDICATED ON PLANS)
COUNTER
HALF WALL / CASEWORK WALL
DESK/WALL
NOTES:
1. A MAX OF (14) CAT6 CABLES / (7) CAT6A CABLES SHALL BE ROUTED THROUGH A 1-1/4-INCH CONDUIT.
2. A MAX OF (8) CAT6 CABLES / (4) CAT6A CABLES SHALL BE ROUTED THROUGH A 1-INCH CONDUIT.
3. CONFIGURATIONS AND QUANTITIES SHOWN ARE FOR REFERENCE ONLY. PRECISE
COUNTS,QUANTITIES, AND ROUTINGS SHALL BE BASED ON DRAWINGS AND IN-FIELD COORDINATION.
4. HEIGHT OF NETWORK TERMINATED OUTLETS SHALL BE AS INDICATED ON DRAWINGS. HEIGHT OF
JUNCTION OUTLET ('FF' OUTLET) SHALL BE FIELD COORDINATED.
TELECOMMUNICATION
OUTLET
UNDERCOUNTER /
TABLE MOUNTED
EQUIPMENT
FLOOR
FLOORBOX
REFER TO THE TELECOMMUNICATION
OUTLET ROUTING DETAIL(S) FOR CONDUIT
AND CABLE ROUTING INFORMATION.
3/4-INCH CONDUIT
3/4-INCH CONDUIT
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T600
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 158 177
TECHNOLOGY
DETAILS
T600
1 PORT SURFACE MOUNT BOX2
T600
2 PORT SURFACE MOUNT BOX3
T600
TYPICAL CABLE TRAY
GROUNDING DETAILS ER/TR ONLY7
T600
TYPICAL CABLE TRAY
JUNCTION GROUNDING DETAILS ER/TR ONLY5
T600
TELECOMMUNICATIONS
GROUNDING SYSTEM OVERVIEW ER/TR ONLY4
T600
TELECOMMUNICATIONS
GROUNDING BUS BAR (TYPICAL)6
T600
TECHNOLOGY SYSTEMS OUTLETS AND CONDUIT1
T600
FURNITURE FEEDTHROUGH OUTLETS AT
CASEWORK/HALFWALL8
A
D
L G
K
LGK
LG
K
STUD
STUD
AED
L G
K
GENERAL NOTES
KEYNOTE LEGEND
1. BACK-BOX: SHOWN FOR REFERENCE ONLY.
REFER TO AV DRAWINGS FOR
REQUIREMENTS. COORDINATE HEIGHT WITH
ARCHITECTURAL SO BOX WILL BE HIDDEN BY
DISPLAY.
2. CONDUIT: PROVIDE (1) 1" CONDUIT ROUTED
TO NEAREST COMMUNICATIONS ROOM OR IT
RACK.
3. FACE PLATE: PROVIDE MODULAR 2-PORT
PLATE.
4. DATA CABLE: PROVIDE (2) 4-PAIR CAT. 6A
(AUGMENTED) STP CABLE ORIGINATING
FROM THE NEAREST TELE-DATA ROOM. OR IT
RACK.
5. DATA TERMINATIONS: PROVIDE CAT. 6A RJ45
TYPE MODULAR JACK INTERCONNECTED TO
CAT. 6A UTP CABLE PER EIA/TIA-T568B.
6. COAXIAL CABLE: SHOWN FOR REFERENCE
ONLY. PROVIDED BY OTHERS. REFER TO AV
DRAWINGS FOR MORE INFORMATION.
7. COAXIAL TERMINATION: SHOWN FOR
REFERENCE ONLY. PROVIDED BY OTHERS.
REFER TO AV DRAWINGS FOR MORE
INFORMATION.
8. LABELS: PROVIDE WHITE LABELS WITH
BLACK TEXT TO NOTE STATION ID (YYY),
TERMINATION ID (ZZZ) AND CABLE ID (XXX).
REFER TO TYPICAL DEVICE LABELING DETAIL
FOR ADDITIONAL REQUIREMENTS.
9. AV: PROVIDE (1) 1.00" CONDUIT STUBBED UP
TO ACCESSIBLE CEILING SPACE (FUTURE).
10. POWER: POWER RECEPTACLES AND
CONDUIT SHOWN FOR REFERENCE ONLY. EC
TO FLUSH MOUNT AC DUPLEX IN BACK BOX
AND SIZE CONDUIT FOR POWER AS
REQUIRED.
KEY
VALUE
STUD
STUD
1. CONTRACTOR SHALL PROVIDE CONDUITS
THROUGH WALLS AND ACROSS
INACCESSIBLE CEILING SPACES TO ENSURE
UNOBSTRUCTED PATHWAY BACK TO
NEAREST COMM ROOM.
2. CONDUITS AS THEY ARE SHOWN ENTERING
THE FLAT PANEL BACK BOX ARE FOR
ILLUSTRATIVE PURPOSES ONLY. IT IS
POSSIBLE THAT CONDUITS MAY ENTER FROM
A DIFFERENT LOCATION BASED ON THE
PROJECT SPECIFICS, I.E. CONDUITS MAY
ENTER FROM THE SIDES, AND ADDITIONAL
CONDUITS MAY BE ROUTED TO EITHER THE
TOP OR BOTTOM OF THE BOX AS
DETERMINED BY THE EC / AVC.
3. DRAWING NOT TO SCALE.
FLAT PANEL BACK BOX
ROOF
SLAB
CONDUIT
STUB WITH 90-
DEGREE TURN
WALL
MUDRING FLUSH
WITH WALL
TELECOMMUNICATION
OUTLET
REFER TO "DEVICE
MOUNTING HEIGHT"
LEGEND FOR DEVICE
HEIGHT
CEILING
1" CONDUIT
CONDUIT SHALL ROUTE BACK
TO TELECOMMUNICATION
RACK.
SYMBOL:
CJ2
CJ2
CJ2
CJ2
LABEL
LABEL
CC2
CC2
CC2
CC2
SYMBOL:
CJ2CJ2
CJ2
LABEL
LABEL
CC2
CC2
CC2
BLANK
INSERT
SYMBOL:
CJ2CJ2
LABEL
LABEL
CC2
CC2
BLANK
INSERT
SYMBOL:
CJ2
LABEL
LABEL
CC2
BLANK
INSERT
BLANK
INSERT
BLANK
INSERT
BLANK
INSERT
CW4 CW4 CW4
CW4
ROOF
SLAB
EMT-TO-FLEX
INLINE
COUPLER
WALL
MUDRING FLUSH
WITH WALL
TELECOMMUNICATION
OUTLET
REFER TO "DEVICE
MOUNTING HEIGHT"
LEGEND FOR DEVICE
HEIGHT
CEILING
1" FLEXIBLE
CONDUIT
CONDUIT SHALL ROUTE BACK
TO TELECOMMUNICATION
RACK.
1" EMT CONDUIT
ROOF
SLAB
WALL
SLAB PENETRATION
REFER TO "DEVICE
MOUNTING HEIGHT"
LEGEND FOR DEVICE
HEIGHT OR DRAWING
700 SERIES
RACEWAY
CONDUIT SHALL ROUTE BACK TO
TELECOMMUNICATION RACK.
3/4" CONDUIT
END DEVICE
WIREMOLD 5782A
CONDUIT
CONNECTOR FITTING
CEILING
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T601
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 159 177
TECHNOLOGY
DETAILS
T601
TECHNOLOGY OUTLET ROUTING - NEW WALL4
T601
TELECOMMUNICATION OUTLET FACEPLATE DETAIL1
T601
AUDIO VIDEO DETAIL - FLAT PANEL BACKBOX - BB13
T601
TECHNOLOGY OUTLET ROUTING - EXISTING WALL2
T601
CONDUIT TO WIREMOLD TRANSITION5
FLOOR
3/4" CONDUIT 1" CONDUIT
RX
EXTERNAL REQUEST
TO EXIT DEVICE
(WHEN REQUIRED)
DOOR CONTACTDOOR CONTACT
CR
DOUBLE DOOR
MULLION ROUTED CABLING WITH WALL MOUNTED READER
3/4" CONDUIT
A SINGLE GANG BACKBOX TO
SUPPORT CARD READER/KEYPAD
ELECTRIFIED HINGE, LATCH,
OR POWER TRANSFER DEVICE
(WHEN REQUIRED)
ELECTRIFIED
STRIKE (WHEN
REQUIRED)
ELECTRIFIED HINGE,
LATCH, OR POWER
TRANSFER DEVICE
(WHEN REQUIRED)
DOOR HARDWARE
SPECIFIED BY DIVISION 08
DOOR HARDWARE
SPECIFIED BY DIVISION 08
3/4" CONDUIT
RX
EXTERNAL REQUEST
TO EXIT DEVICE
(WHEN REQUIRED)
DOOR CONTACTDOOR CONTACT
CR
DOUBLE DOOR
CONDUIT ROUTED CABLING WITH WALL MOUNTED READER
A SINGLE GANG BACKBOX TO
SUPPORT CARD READER/KEYPAD.
ELECTRIFIED HINGE, LATCH,
OR POWER TRANSFER DEVICE
(WHEN REQUIRED)
ELECTRIFIED HINGE,
LATCH, OR POWER
TRANSFER DEVICE
(WHEN REQUIRED)
DOOR HARDWARE
SPECIFIED BY DIVISION 08
DOOR HARDWARE
SPECIFIED BY DIVISION 08
3/4" CONDUIT3/4" CONDUIT
FLOOR
RX
DOOR CONTACT
CR
SINGLE DOOR
MULLION ROUTED CABLING WITH WALL MOUNTED READER
3/4" CONDUIT
A SINGLE GANG BACKBOX
TO SUPPORT CARD
READER/KEYPAD
ELECTRIFIED
STRIKE (WHEN
REQUIRED)
ELECTRIFIED HINGE,
LATCH, OR POWER
TRANSFER DEVICE
(WHEN REQUIRED)
DOOR HARDWARE
SPECIFIED BY DIVISION 08
1" CONDUIT DEDICATED
FOR DOOR HARDWARE
CABLING EXTERNAL
REQUEST TO EXIT
DEVICE (WHEN
REQUIRED)
NOTES
1. THE DETAILS HEREIN ARE DIAGRAMMATIC IN NATURE AND DO NOT
REPRESENT A SPECIFIC INSTANCE. THE DOOR TYPE, DOOR
CONFIGURATION, AND OTHER MISCELLANEOUS INFORMATION SHALL BE
COORDINATED WITH THE DIVISION 08 SPECIFICATIONS, ARCHITECTURAL
DRAWINGS, AND TECHNOLOGY DRAWINGS.
2. THE DETAILS HEREIN REPRESENT TYPICAL INFRASTRUCTURE
REQUIREMENTS. THE SPECIFIC ROUTING OF CONDUIT AND CABLING SHALL
BE COORDINATED FOR EACH ACCESS POINT LOCATION.
3. WHERE THE REQUEST TO EXIT DEVICE/FUNCTION IS INTEGRAL TO DOOR
HARDWARE COMPONENTS, CONDUIT, BACKBOX, AND EXTERNAL REQUEST
TO EXIT DEVICE SHOWN ARE NOT REQUIRED.
4. WHERE DOOR FRAME ALLOWS THE ROUTING OF CABLING, DOOR CONTACT
CABLING AND DOOR HARDWARE CABLING SHALL ROUTE THROUGH DOOR
FRAME AND CONSOLIDATED CONDUIT. WHERE DOOR FRAME DOES NOT
ALLOW CABLE ROUTING, INDIVIDUAL 3/4-INCH CONDUITS SHALL ROUTE
DIRECT TO EACH DEVICE FROM THE CONSOLIDATION BOX. COORDINATE
WITH DOOR HARDWARE SPECIFICATIONS TO DETERMINE ELECTRIFIED
COMPONENTS.
5. WHERE ACCESSIBLE CEILING IS WITHIN 50 FEET OF DOOR LOCATION, THE
CONSOLIDATION BACKBOX SHALL BE LOCATED ABOVE ACCESSIBLE CEILING
AT THE NEAREST POINT TO THE DOOR. WHERE AN ACCESSIBLE CEILING IS
GREATER THAN 50 FEET AWAY FROM THE DOOR LOCATION, THE
CONSOLIDATION BOX SHALL BE WALL OR CEILING MOUNTED BEHIND AN
ACCESS PANEL. CONTRACTOR SHALL FIELD COORDINATE ACCESS PANEL
LOCATION WITH ARCHITECT.
6. THE CONSOLIDATION BOX SHALL BE MOUNTED ON THE SECURE SIDE OF
THE DOOR; IT SHALL BE PLACED SO THAT IT IS ONLY ACCESSIBLE FROM THE
SECURE SIDE OF THE DOOR.
7. ALL CONDUITS AND CABLING SHALL BE RECESSED WITHIN THE WALL OR
FRAME, NO SURFACE MOUNT INFRASTRUCTURE IS ACCEPTABLE UNLESS
SPECIFICALLY NOTED.
SINGLE DOOR
CONDUIT ROUTED CABLING WITH WALL MOUNTED READER
RX
DOOR CONTACT
CR
A SINGLE GANG BACKBOX
TO SUPPORT CARD
READER/KEYPAD
ELECTRIFIED
STRIKE (WHEN
REQUIRED)
ELECTRIFIED HINGE,
LATCH, OR POWER
TRANSFER DEVICE
(WHEN REQUIRED)
DOOR HARDWARE
SPECIFIED BY DIVISION 08
EXTERNAL
REQUEST TO EXIT
DEVICE (WHEN
REQUIRED)
3/4" CONDUIT 3/4" CONDUIT
DOOR COORDINATION
CEILING COORDINATION
INACCESSIBLE CEILING
INACCESSIBLE CEILING
STRUCTURE
CONSOLIDATION BACKBOX - 4
GANG WITH COVER,
ORIENTED VERTICALLY
SUPPORT TO STRUCTURE
PATHWAY DEDICATED
FOR DOOR
HARDWARE CABLING
CABLE BACK TO
DOOR CONTROL
PANEL
A 1" CONDUIT SHALL ROUTE TO
NEAREST ACCESSIBLE CEILING.
INTERCOM CONDUIT SHALL ROUTE
BACK TO ACCESSIBLE CEILING OR TR.
ROOF
SLAB
EXTERIOR WALL
SLAB PENETRATION
CONDUIT
CONDUIT SHALL ROUTE BACK TO
TELECOMMUNICATION RACK.
INCOMING
CONDUIT
FROM MDF
PULL BOX
INACCESSIBLE CEILING
OUTSIDE OF
BUILDING
CONDUIT TO
END DEVICES
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T602
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 160 177
TECHNOLOGY
DETAILS
T602
DOOR ROUGH-IN: ACCESS CONTROLLED DOORS WITH CARD
READERS1
T602
CONDUIT TO WIREMOLD TRANSITION2
EQUIPMENT SCHEDULES INFORMATION
ALL COMPONENTS SHOWN HEREIN SHALL BE CONSIDERED AS 'BASIS OF DESIGN'. THEY ARE SHOWN TO INDICATE GENERAL FUNCTION AND APPLICATION, IT IS ACCEPTABLE TO SUBMIT/PROVIDE COMPONENTS DETERMINED TO BE 'APPROVED
EQUAL'.
POWER DISTRIBUTION DEVICES
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
SP1 PDU, HORIZTONAL, 120V INPUT, (16) 5-20 OUTLETS TRIPPLITE PDUMH20ATS
FIBER CONNECTIVITY
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
FC1 12 STRAND SM (OS2) FIBER, ISP/OSP, PLENUM, LOOSE TUBE, ARMORED PANDUIT FSGP912Y
FM2 FIBER CASSETTE, 12 STRAND SM, LC CONNECTOR PANDUIT FCS9N-12-10P
FP1 1 RU FIBER PANEL PANDUIT FRME-1U
COPPER CONNECTIVITY
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
CC2 CAT 6A CABLE, PLENUM, UTP COMMSCOPE CS44P
CC3 25-PAIR COPPER, CAT 5E, PLENUM, UTP SUPERIOR ESSEX 51-478-48
CJ2 CAT 6A JACK COMMSCOPE UKJ10G
CX3 CAT6A PATCH CABLE COMMSCOPE UC1AAA2
CX4 CAT6A PATCH CABLE - PLENUM RATED COMMSCOPE UC1AA22
CB1 110-BLOCK, WALL MOUNTED COMMSCOPE 569440-1
CW4 4-PORT FACEPLATE, LABELED COMMSCOPE 2111039-x FINISH SHALL MATCH COLOR OF POWER RECEPTACLE DEVICE FACEPLATES
CW5 FLOOR BOX TELECOM FACEPLATE SEE COMMENTS SEE COMMENTS
FLOORBOX SPECIFIED BY ELECTRICAL. FACEPLATE COORDINATED WITH
FLOORBOX MANUFACTURER.
CW6 SURFACE MOUNT BOX, (BISCUIT), PLENUM, 1 PORT COMMSCOPE SMB-1P-xxx PLENUM SECURITY CAMERA LOCATIONS
CW7 SURFACE MOUNT BOX, (BISCUIT), PLENUM, 2 PORT COMMSCOPE SMB-2P-xxx PLENUM WIRELESS ACCESSS POINT LOCATIONS
CP1 CAT 6A PATCH PANEL, 24 PORTS, 1RU, BLACK, FLAT COMMSCOPE UNP-6A-DM-1U-24
CP2 CAT 6A PATCH PANEL, 48 PORTS, 2RU, BLACK, FLAT COMMSCOPE UNP-6A-DM-2U-48
RACKS AND ACCESSORIES
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
RR2 4-POST RACK, 7-FOOT IN HEIGHT, EIA. 19-INCH IN WIDTH, BLACK CPI 50120-703
RV2
VERTICAL WIRE MANAGER, 7-FOOT IN HEIGHT, 6-INCH IN WIDTH, BLACK
DOUBLE-SIDED, FINGER STYLE FRONT, VERTICAL SECTION BACK
CPI 30162-703
RL1 LADDER RUNWAY, 12-INCH WIDE CPI 10250-712
RA1 BUTT-SPLICE KIT CPI 11301-701
RA2 JUNCTION-SPLICE KIT CPI 11302-701
RA3 LADDER RUNWAY ELEVATION KIT CPI 10506-706
RA4 LADDER RUNWAY RADIUS DROP CPI 12100-712
RA5 LADDER RUNWAY CORNER BRACKET CPI 11959-715
RA6 UPPER TROUGH CPI 13183-719
RA7 HORIZONTAL WIRE MANAGER, 1U, 5" DEEP CPI 30139-719
RA8 HORIZONTAL WIRE MANAGER, 2U, 5" DEEP CPI 30130-719
HORIZONTAL CABLE MATRIX
SYSTEM CABLE KEY CABLE COLOR JACK KEY JACK COLOR
PATCH CABLE COLOR:
IT ROOM
PATCH CABLE COLOR:
PREMISE
COMMENTS
NETWORK CC2 BLUE CJ2 BLUE BLUE BLUE
VOICE CC2 BLUE CJ2 BLUE BLUE BLUE
WIRELESS ACCESS POINT (WAP) CC2 GREEN CJ2 GREEN GREEN GREEN
SECURITY CC2 BLUE CJ2 BLUE BLUE BLUE
PAGING CC2 BLUE CJ2 BLUE BLUE BLUE
AUDIO VISUAL CC2 BLUE CJ2 BLUE BLUE BLUE
GROUNDING
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
GB1 PRIMARY BONDING BUSBAR (PBB) COMPLIANT WITH ANSI/TIA-607 CPI 40153-020
GS1 SURGE PROTECTION - 25 PAIR COPPER, CAT3/CAT5E CIRCA MAX 1880ENA/NSC-6E
GS2 SURGE PROTECTION - CAT6 / CAT6A CIRCA MAX 604-75RJ
BACKBONE CABLE MATRIX
ORIGINATION SPACE TERMINATION SPACE
CABLE 1 CABLE 2 CABLE 3
KEY COLOR QUANTITY KEY COLOR QUANTITY KEY COLOR QUANTITY COMMENTS
SERVER ROOM 116
GRAND LAKE ENTRANCE
STATION
CABLE IS EXISTING, COORDINATE WITH
CONTRACTING OFFICER. CABLE IS OWNER
FURNISHED, CONTRACTOR INSTALLED (OFCI).
SERVER ROOM 116
MAINTENANCE FACILITY
BUILDING
FC1 YELLOW 1 -- -- -- -- --
ESTIMATE LENGTH OF CABLE RUN SHALL BE 2,000
FEET.
SECURITY - ACCESS CONTROL SYSTEM (ACS)
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
KP1 KEYPAD DOOR HARDWARE - - REFER TO DIVISION 8 FOR DOOR HARDWARE
DC1 DOOR CONTACT (POSITION SWITCH), CONCEALED MOUNT GE INTERLOGIX 2767-L
RX1 REQUEST TO EXIT SENSOR BOSCH DS-160
SECURITY - INTRUSION DETECTION SYSTEM (IDS)
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
MD3 MOTION DETECTOR - WALL MOUNT, SHORT RANGE BOSCH DS860 DEVICE SHALL BE ALMOND COLOR.
KI1 SECURITY KEYPAD INTERFACE BOSCH B921C
CP1 SECURITY CONTROL PANEL BOSCH 9512G
DB1 DURESS BUTTON - HOLD UP SWITCH BOSCH ISC-PB1-100
SECURITY - VIDEO SURVEILLANCE SYSTEM (VSS)
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
CAM2
BLACK DOME AND COVER - EXTERIOR RATED - FIXED DOME CAMERA, 5MP - IP66/IK10
RATED
AXIS P3267-LVE
PROVIDE MOUNT AS INDICATED ON DETAILS AND AS REQUIRED PER LOCATION.
CAMERA DOME AND COVER SHALL BE BLACK.
CAM3 INTERIOR RATED - FIXED DOME CAMERA, 5MP - IP66/IK10 RATED AXIS P3267-LV PROVIDE MOUNT AS INDICATED ON DETAILS AND AS REQUIRED PER LOCATION
SV1 VIDEO SURVEILLANCE DEDICATED SWITCH AXIS T8524
EXISTING SERVER/WORKSTATION FOR VIDEO SURVEILLANCE SHALL BE
RELOCATED FROM GRAND LAKE ENTRANCE STATION TO SERVER 116.
PATHWAYS
KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS
HH1 SMALL HANDHOLE - NON-TRAFFIC RATED OLDCASTLE INFRASTRUCTURE 2436-36 TIER 15 RATED COVER
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
AE DESIGN
DENVER, CO
1/ 8/
:5
8:
P M
A ut od es k D oc s:
//2
4-
N
P S
R O
M O
K aw un ee ch e
V C
D D
-C A w O ta k/
N P
S R
O M
O K
A W
U E
E C
H E
V
IS
IT
O
R C
E N
T E
R
E
LE
C T
R
IC
A L.
rv t
T700
AE DESIGN
REHABILITATE KAWUNEECHE VISITOR CENTER
ROCKY MOUNTAIN NATIONAL PARK
165639
326235
TW/RS/BJLV
JM/JEB/MS
01/16/2026 161 177
TECHNOLOGY
SCHEDULES
Abbreviations
ABANDON IN PLACE(A)
EXISTING(E)
FUTURE(F)
NEW(N)
RELOCATE/RELOCATED LOCATION(R)
DEMOLITION(X)
ABOVE FINISHED FLOORAFF
AUTOMATIC SPRINKLERAS
BOTTOM OF BEAMBOB
BOTTOM OF DECKBOD
BOTTOM OF PIPEBOP
BOTTOM OF RISERBOR
BUTTERFLY VALVEBV
CENTER LINEC
CHECK VALVECV
DOUBLE DETECTOR CHECK VALVE ASSEMBLYDDCV
DROP NIPPLEDN
EXTENDED COVERAGEEC
ELEVATIONEL
FAHRENHEITF
FIRE DEPARTMENT CONNECTIONFDC
FINISHED FLOORFF
FLOOR FLANGEFFL
FIRE HOSE CABINETFHC
FIRE HOSE STATIONFHS
FLOW SWITCHFS
FEETFT
GRADEG
GALLONS PER MINUTEGPM
GATE VALVEGV
HANGERH
HORIZONTAL SIDE WALLHSW
HOSE VALVEHV
INSIDE DIAMETERID
INCHESIN
MAXIMUMMAX
MINIMUMMIN
NIPPLE AND CAPN&C
NOT IN CONTRACTNIC
NUMBERNO
NOT TO SCALENTS
OPEN BAR JOISTOBJ
OUTSIDE DIAMETEROD
OUTSIDE SCREW & YOKEOS & Y
POST INDICATOR VALVEPIV
PRESSURE REDUCING VALVEPRV
PRESSURE SWITCHPS
ROOF MANIFOLDRM
RISER NIPPLERN
SWAY BRACESB
SQUARE FEETSF
SHUT OFF VALVESOV
STANDPIPESP
STANDARD SPRAY PENDENTSSP
STANDARD SPRAY UPRIGHTSSU
TOP OF BEAMTOB
TOP OF PIPETOP
TOP OF RISERTOR
TOP OF STEELTOS
TAMPER SWITCHTS
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
Control
BELL/GONG
CONTROL PANEL
FLOW DETECTION SWITCH
MONITOR SWITCH
PRESSURE GAUGE
TAMPER DETECTOR
WATER MOTOR ALARM
Miscellaneous
2-WAY SWAY BRACE
4-WAY SWAY BRACE
AUXILIARY DRAIN
CONTINUATION OF PIPE
COUPLING
DEMOLITION PIPE
DEMOLITION PIPE
DRY HOSE STATION
ELEVATION ABOVE FINISHED FLOOR
EXISTING PIPE
FLANGED COUPLING
FLEXIBLE COUPLING
GROOVED CAP
GROOVED COUPLING
HANGER (TEXT INDICATES TYPE)
HYDRAULIC CALCULATION NODE
NEW PIPE
POINT OF CONNECTION
RISER
SCREWED CAP
SCREWED PLUG
UNION
WET HOSE STATION
Valves
ALARM CHECK VALVE, ELEVATION VIEW
ALARM CHECK VALVE, PLAN VIEW
ANGLE VALVE
CHECK VALVE
DELUGE VALVE
DRY PIPE VALVE, PLAN VIEW
INDICATING BUTTERFLY VALVE
NON-RISING STEM VALVE
PREACTION VALVE
VALVE WITH TAMPER SWITCH
Water Service
DOUBLE CHECK BACKFLOW PREVENTER (RP-TYPE)
FIRE DEPARTMENT CONNECTION
FREE STANDING F.D. CONNECTION
O.S.&Y. VALVE
POST INDICATOR VALVE
FIRE PROTECTION SYMBOL LIST
NOTE: This is a standard symbol list and not all items listed may be used.
F
M
T
14'-0"
FLEX
H1
T
NOMINAL PIPE SIZE (IN)
STEEL PIPE 1 1-1/4 1-1/2 2 2-1/2 3 4 6
12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0
FOR STEEL PIPE, THE MAXIMUM LENGTH FOR UNSUPPORTED ARMOVER
SHALL BE 2'-0". WHEN PRESSURE EXCEEDS 100 PSI, UNSUPPORTED LENGTH
SHALL BE 1'-0".
HANGER ROD SIZE
MAXIMUM DISTANCE BETWEEN HANGERS (FT-IN)
PIPE SIZE
UP TO AND
INCLUDING 4"
DIA. OF ROD
3/8"
6" AND 8" 1/2"
NOTE: TYPICAL TICK MARKS AS SHOWN ON
PIPING PLAN MAY NOT REFLECT ACTUAL FIELD
INSTALLATION. FINAL HANGER INSTALLATION
SHALL BE IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 13 CHAPTER 9.
GREATER THAN 36" FOR 1"
GREATER THAN 48" FOR 1-1/4"
GREATER THAN 60" FOR 1-1/2" OR LARGER
36" FOR 1"
48" FOR 1-1/4"
60" FOR 1-1/2" OR LARGER
DISTANCE FROM SPRINKLER TO HANGER
THEN EXTEND HERE
MAX
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF01/16/2026
326235
165639
REHABILITATE KAWUEECHE VISITOR CENTER
ROCKY MOUNTAIN NATION PARK
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
INTERFACE
ENGINEERING
PORTLAND, OR
1/ 7/
1:
:1
A
M A ut od es k
D oc s:
//2
4-
N P
S R
O M
O K aw un ee ch e V
C D
D -C
A w
O ta k/
N
P S
R O
M O
K A
W U
E E
C H
E V
IS
IT
O R
C E
N T
E R
_F
LS
_R
.r vt
FP001
CK
CK
KA
162 177
SYMBOL LIST AND
GENERAL NOTES -
FIRE PROTECTION
FP001 SYMBOL LIST AND GENERAL NOTES - FIRE PROTECTION
FP090 SITE PLAN - FIRE PROTECTION
FP101 OVERALL REFLECTED CEILING PLAN - FIRE PROTECTION
FP401 ENLARGED PLAN - ADMIN - FIRE PROTECTION
FP402 ENLARGED PLAN - AUDITORIUM & EXHIBIT - FIRE PROTECTION
FP403 ENLARGED PLAN - COMFORT STATION - FIRE PROTECTION
FP501 SECTIONS - FIRE PROTECTION
FP601 ADMIN SERVER ROOM - FIRE PROTECTION
FP701 DETAILS - FIRE PROTECTION
SHEET INDEX
SPRINKLER HEAD LEGEND
SYMBOL DESCRIPTION K-FACTOR
ORIFICE
SIZE
RESPONSE TEMP COVERAGE FINISH ESCHUTCHEON COUNT COMMENTS
CONCEALED PENDENT
SPRINKLER
5.6 1/2" Quick 165 Standard
WOOD
GRAIN
FLAT, ROUND 14
COORDINATE FINISH TYPE WITH CO
AT WOOD CEILINGS
DRY BARREL SIDEWALL
SPRINKLER
5.6 1/2" Quick 205 Standard CHROME CHROME 7
HORIZONTAL SIDEWALL
SPRINKLER
5.6 1/2" Quick 165 Standard
WHITE
POLY
NONE 2 INSTALL TIGHT TO BRANCH LINE PIPE
RECESSED PENDENT SPRINKLER 5.6 1/2" Quick 165 Standard
WHITE
POLY
RECESSED, WHITE 47
DRY BARREL CONCEALED
PENDENT SPRINKLER
5.6 1/2" Quick 205 Standard CHROME FLAT, ROUND 22
UPRIGHT SPRINKLER 5.6 1/2" Quick 165 Standard BRASS NONE 48
PROVIDE WITH METAL CAGE IN
MECHANICAL SPACES
TOTAL SPRINKLERS: 140
ORDINARY HAZARD GROUP 1 ELECTRICAL ROOMS, MECHANICAL ROOMS, JANITORS CLOSEST, MISC. STORAGE ROOMS 130 SQ FT 0.15 GPM/SQ FT 1500 SQ FT
LIGHT HAZARD
VESTIBULES, HALLS, RESTROOMS, OFFICES, TELECOMMUNICATION ROOMS, EVES AND
OVERHANGS WITH COMBUSTIBLE CONSTRUCTION AND NO COMBUSTIBLE BENEATH,
EXHIBIT AREA.
225 SQ FT 0.10 GPM/SQ FT 1500 SQ FT
OCCUPANCY DESCRIPTION MAX COVERAGE DESIGN DENSITY REMOTE AREA
HAZARD CLASSIFICATIONS
GENERAL FIRE PROTECTION NOTES
A. SCOPE OF WORK:
• PROVIDE A WET-PIPE FIRE SPRINKLERS SYSTEM FOR THE ADMIN, VC AND EXHIBIT
WINGS IN ACCORDANCE WITH NFPA 13, IBC/IFC AND NPS AHJ REQUIREMENTS.
SYSTEM(S) TO BE FILLED WITH A UL-APPROVED ANTI-FREEZE (TYCO LFP+ OR SIMILAR).
a. PROVIDE (1) SYSTEM WITH ASSOCIATED RP-BACKFLOW AND CONTROL VALVES
LOCATED WITHIN THE ADMIN WING TO PROTECT BOTH ADMIN AND VC WINGS.
• PROVIDE A DRY-PIPE SPRINKLER SYSTEM FOR THE COVERED WALKWAY AND
COMFORT STATION IN ACCORDANCE WITH NFPA 13, IBC/IFC AND NPS AHJ
REQUIREMENTS. DRY-PIPE SYSTEM TO BE FILLED WITH SUPERVISORY NITROGEN.
a. PROVIDE (1) SYSTEM WITH ASSOCIATED BACKFLOW AND CONTROL VALVE
LOCATED WITHIN THE COMFORT STATION.
• PROVIDE A SINGLE INTERLOCK PREACTION SPRINKLER SYSTEM TO PROTECT SERVER
ROOM INSTALLED IN ACCORDANCE WITH NFPA 13, IBC/IFC AND NPS AHJ
REQUIREMENTS. PROVIDE WITH A DEDICATED RELEASE PANEL AND DETECTION
DEVICES.
B. PROVIDE A FIRE DEPARTMENT CONNECTION (FDC). FDC LOCATED ON-SITE, REFER TO
CIVIL FOR ADDITIONAL INFORMATION.
C. SEISMIC DESIGN CATEGORY-B. NO SEISMIC BRACING REQUIRED. REFER TO STRUCTURAL
DRAWINGS FOR ADDITIONAL SITE/SEISMIC INFORMATION.
D. CONTRACTOR TO PROVIDE ALL REQUIRED HANGERS, AND THE LIKE IN ACCORDANCE WITH
NFPA 13 REQUIREMENTS.
E. ALL ABOVE GROUND FIRE SPRINKLER PIPING SHALL BE SCHEDULE 40 PER NPS
STANDARDS.
F. FIRE PROTECTION SYSTEM(S) SHALL BE DESIGNED BY SOMEONE MEETING THE
FOLLOWING:
a. NICET III OR HIGHER FOR WATER-BASED SYSTEMS.
b. FIRE PROTECTION ENGINEER.
c. AS APPROVED BY THE NPS AHJ.
G. FIRE PROTECTION SYSTEM(S) SHALL BE INSTALLED BY SOMEONE MEETING THE
FOLLOWING:
a. NICET II OR HIGHER FOR WATER-BASED SYSTEMS.
b. FIRE PROTECTION ENGINEER.
c. AS APPROVED BY THE AHJ.
WATER FLOW INFORMATION
LOCATION
MAIN SIZE
STATIC PRESSURE
RESIDUAL PRESSURE
COMMENTS:
FLOW AT RESIDUAL
DATE OF REPORT/TEST 9-2024
6 "
81 PSI
52 PSI
715 GPM
EXISTING HYDRANT FIELD FLOW TESTED
VC ENTRANCE (NORTH)
APPLICABLE CODES:
A. 2024 INTERNATIONAL BUILDING CODE (IBC)
B. 2024 INTERNATIONAL FIRE CODE (IFC)
C. ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
D. 2022 NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72)
E. NPS STRUCTURAL FIRE MANAGEMENT REFERENCE MANUAL 58 (RM #58)
(N) SITE FDC
FREE STANDING
6" FIRE SERVICE
4" FDC SERVICE
4" U.G FIRE MAIN
TO EXHIBIT SPACE
EXHIBIT SPACE
INDICATING
CONTROL VALVE
4" FIRE RISER
W/ RP-BFP (INSIDE)
4" FIRE RISER
W/ BFP (INSIDE)
RPB
BOR
(E) HYDRANT
(SEE CIVIL)
(E) SITE WATER MAIN
WITH (N) FIRE LINE TAP.
(SEE CIVIL)
FDC NOT REQUIRED FOR COMFORT STATION
PER NFPA 13 (16.12.2)
4" FIRE SERVICE
BFP
UG1
S
BORD
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: A
01/16/2026
326235
165639
REHABILITATE KAWUEECHE VISITOR CENTER
ROCKY MOUNTAIN NATION PARK
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
INTERFACE
ENGINEERING
PORTLAND, OR
1/ 7/
1:
:1
A
M A ut od es k
D oc s:
//2
4-
N P
S R
O M
O K aw un ee ch e V
C D
D -C
A w
O ta k/
N
P S
R O
M O
K A
W U
E E
C H
E V
IS
IT
O R
C E
N T
E R
_F
LS
_R
.r vt
FP090
CK
CK
KA
163 177
SITE PLAN - FIRE
PROTECTION
200 4020
SCALE OF FEETSCALEFP090
1 SITE PLAN - FIRE PROTECTION
A
TRUE PLAN
A. REFER TO CIVIL DRAWINGS FOR ADDITIONAL SITE
INFORMATION.
B. FIRE SPRINKLER SCOPE OF WORK TO START 5-FT OUT
FROM BUILDING FOOTPRINT. CONTRACTOR TO PROVIDE
ALL REQUIRED RESTRAINT JOINTS.
C. FREE-STANDING 2-PORT FDC TO SUPPLY ALL FIRE
SPRINKLER SYSTEM(S). CHECK VALVE PROVIDED INSIDE
AT EACH (2) FIRE RISER LOCATIONS.
GENERAL SHEET NOTES
L
K
2 3 4 5 76
M
8 9 10 11 12 13 14 15 16 17
H
G
F
E
D
C
B
A
FP401
FP403
FP402
TYP4
TYP4
TYP4
TYP4
TYP6
TYP6TYP6
TYP6 TYP6
TYP6
TYP6
TYP6
TYP6
TYP6
TYP6
EXHIBIT SPACE
INDICATING
CONTROL VALVE
4" FIRE RISER
W/ RP-BFP (INSIDE)
4" FIRE RISER
W/ BFP (INSIDE)
1-1/2" PREACTION
RISER ASSEMBLY
B F
P
BFP
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: A
01/16/2026
326235
165639
REHABILITATE KAWUEECHE VISITOR CENTER
ROCKY MOUNTAIN NATION PARK
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
INTERFACE
ENGINEERING
PORTLAND, OR
1/ 7/
1:
:2
A
M A ut od es k
D oc s:
//2
4-
N P
S R
O M
O K aw un ee ch e V
C D
D -C
A w
O ta k/
N
P S
R O
M O
K A
W U
E E
C H
E V
IS
IT
O R
C E
N T
E R
_F
LS
_R
.r vt
FP101
CK
CK
KA
164 177
OVERALL REFLECTED
CEILING PLAN - FIRE
PROTECTION
80 168
SCALE OF FEET
1. PROVIDE PREACTION SPRINKLER SYSTEM FOR SERVER,
REFER TO FP601 FOR RISER ASSEMBLY DETAIL.
2. REFER TO CIVIL WATER PLANS FOR SITE CONDITIONS
AND INFORMATION.
3. PROVIDE CONCEALED TYPE PENDENT SPRINKLERS WITH
COVER PLATES MATCHING THE CEILING TYPE.
4. PROVIDE DRY-TYPE SPRINKLERS PROTECTING EXTERIOR
OVERHANGS 4-FT OR GREATER.
5. ROUTE 4" FIRE MAIN, UNDERGROUND TO SERVE
VC/EXHIBIT WING. REFER TO CIVIL FOR SITE PIPING AND
CONTINUATION.
6. SPRINKLER PROTECTION OMITTED FROM EXTERIOR
EAVES OR OVERHANGS LESS THAN 4-FT IN WIDTH PER
NFPA 13 (9.2.1.20).
SHEET KEYNOTES
SCALEFP101
OVERALL REFLECTED CEILING PLAN -
FIRE PROTECTION
L
K
2 3 4 5 76
M
8 9 10 11 12 13 14 15 16 17
BREAK ROOM
SERVER ROOM
MECH. / ELEC.
115RR
RR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HALL
OFFICE
121 CONFERENCE
STOR
WILDERNESS DESK
JC
HALL
HALL
6" U.G FIRE
MAIN
4" FDC MAIN
4" TO VC WING
REFER TO CIVIL DRAWINGS
BEYOND 5-FT
FP701
TYP
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
7' - 10"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
2' - 0"
2' - 0"
1' - 10"
5' - 0"
2' - 0"
11' - 7"
FP501
PREACTION SYSTEM
PREACTION VALVE
102 103 104
108106 107
151412 13
TOR
FP701
FP701
FP701
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Flow at Base of Riser
Pressure at Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Comments:
Pressure at Source
Flow at Source
Remote Area Size
Head Coverage
NFPA 13 -
Light Hazard
0.10 GPM/SF
100.00 GPM
8 @ 17.60 + 4 @ 15.00
5.213316
242.15 GPM
42.44 PSI
+28.01 (37.67%)
ADMIN - UPRIGHTS
UPRIGHTS ABOVE CEILING.
DARCY-WEISBACH FOR
ANTI-FREEZE (TEMP = 0-F)
46.35 PSI
342.15 GPM
1521 SF
225 (MAX) SF
FP601
10' - 0"
3' - 9"
1 1/2"1 1/2"
1 1/2" 1 1/2"
1 1/2"
/4
1"
1 1/4"1"
1 1/2"
1 1/2"
1"
1"
INSTALL DIRECTLY TO BRANCH LINE ON TEE.
ADMIN UPRIGHT REMOTE AREA
5' - 5"
1 1/2"
7 1053 9
7' - 1"
4' - 10"
7' - 6"
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Flow at Base of Riser
Pressure at Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Comments:
Pressure at Source
Flow at Source
Remote Area Size
Head Coverage
NFPA 13 -
Light Hazard
0.10 GPM/SF
100.00 GPM
9 @ 13.79 + 1 @ 16.50
5.213316
179.81 GPM
37.72 PSI
+35.6 (46.5%)
ADMIN - PENDENTS
RA REDUCTION PER 19.2.3.2.3.1.
(40%). DARCY-WEISBACH FOR
ANTI-FREEZE (TEMP = 0-F)
40.96 PSI
279.81 GPM
917 SF
VARIES, AVG. 88 SF
ADMIN PENDENT REMOTE AREA
1 1/2" 1 1/2"
28 31
30 32
208 209
206 207
7' - 6"
7' - 6"
7' - 5" 7' - 6"
106105 108107
2 3
16335 85
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: A
01/16/2026
326235
165639
REHABILITATE KAWUEECHE VISITOR CENTER
ROCKY MOUNTAIN NATION PARK
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
INTERFACE
ENGINEERING
PORTLAND, OR
1/ 7/
1:
:2
A
M A ut od es k
D oc s:
//2
4-
N P
S R
O M
O K aw un ee ch e V
C D
D -C
A w
O ta k/
N
P S
R O
M O
K A
W U
E E
C H
E V
IS
IT
O R
C E
N T
E R
_F
LS
_R
.r vt
FP401
CK
CK
KA
165 177
ENLARGED PLAN -
ADMIN - FIRE
PROTECTION
40 84
SCALE OF FEET
SCALEFP401
1 ENLARGED PLAN - ADMIN - FIRE PROTECTION
A
TRUE PLAN
1. PROVIDE UPRIGHT SPRINKLER PROTECTION FOR
COMBUSTIBLE CONCEALED SPACE IN ACCORDANCE WITH
NFPA 13.
2. ROUTE PIPING IN WILDERNESS AREA EXPOSED, BELOW
CEILING.
3. PROVIDE DRY-TYPE FLEX PENDENT SPRINKLER TO SERVE
EXTERIOR AREA. RIGID PIPE TO BE WITHIN BUILDING
ENVELOPE.
SHEET KEYNOTES
H
G
F
WILDERNESS DESK
EXHIBIT NO. 1
EXHIBIT NO. 2
AUDITORIUM
STORAGE
STORAGE
MECH. RM
VEST.
4" U.G FIRE MAIN FROM RISER ROOM
(SEE CIVIL FOR SITE INFO)
10' - 9"
8' - 0"
8' - 0"
12' - 11"
8' - 0"
8' - 0"
11' - 5"
7' - 4"
7' - 10"
11' - 5"
8' - 0"
2' - 1"
2' - 1"
2' - 1"
2' - 7"
2' - 1"
FP501
FP501
48 49
305304
44 45
FP701
FP701
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Flow at Base of Riser
Pressure at Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Comments:
Pressure at Source
Flow at Source
Remote Area Size
Head Coverage
NFPA 13 -
Light Hazard
0.10 GPM/SF
100.00 GPM
8 @ 16.80
5.213316
153.56 GPM
50.21 PSI
+25.46 (31.49%)
EXHIBIT - LH
RA REDUCTION PER 19.2.3.2.3.1.
(32%) DARCY-WEISBACH FOR
ANTI-FREEZE (TEMP = 0-F)
55.40 PSI
253.56 GPM
1024 SF
168 (MAX) SF
/2
/2
/2
/2
/2
/2
/2
3"
1 1/2"
1 1/2"
1 1/2"
/4
1 1/2"
1 1/2"
1"
1 1/2"
1 1/2"
/4
/4
/2
/2
7' - 10"
11' - 5"
PROVIDE DRAIN DISCHARGE FOR SECTION
OF TRAPPED WATER IN ADMIN WING,
ROUTE TO EXTERIOR WITH 45-DEG TURN
DOWN ELBOW.
EXHIBIT LH REMOTE AREA
1"
/4
3"
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
SCALE: A
01/16/2026
326235
165639
REHABILITATE KAWUEECHE VISITOR CENTER
ROCKY MOUNTAIN NATION PARK
AE FIRM
PRIME:
OTAK, INC.
REDMOND, WA
SUBCONTRACTOR:
INTERFACE
ENGINEERING
PORTLAND, OR
1/ 7/
1:
:3
A
M A ut od es k
D oc s:
//2
4-
N P
S R
O M
O K aw un ee ch e V
C D
D -C
A w
O ta k/
N
P S
R O
M O
K A
W U
E E
C H
E V
IS
IT
O R
C E
N T
E R
_F
LS
_R
.r vt
FP402
CK
CK
KA
166 177
ENLARGED PLAN -
AUDITORIUM & EXHIBIT
- FIRE PROTECTION
40 84
SCALE OF FEET
SCALEFP402
1 ENLARGED PLAN - AUDITORIUM & EXHIBIT - FIRE PROTECTION
A
TRUE PLAN
1. CONCEALED COMBUSTIBLE SPACE LESS THAN
6" FROM TOP OF CEILING TO BOTTOM OF
STRUCTURE, NO SPRINKLERS PROVIDED
ABOVE FINISHED CEILING/DECK.
SHEET KEYNOTES
G
F
E
D
C
B
A
JANITOR
MECH. RM
WOMEN'S RR
MEN'S RR
4" U.G FIRE MAIN, SEE CIVIL FOR
SITE ROUTING AND CONNECTION
TO EXISTING MAIN
FP701
7' - 4"
7' - 0"
7' - 0"
FP501
2' - 6"
2 1/2"
/4
/4
/4
/4
/4
/4
/4
/4
/4
/2
1 1/4"
/4
/4
/4
INSTALL SPRINKLERS TIGHT
TO TEE ON BRANCH LINE, TYP.
DRY PENDENT SPRINKLERS
TYP.
FP403
REMOTE INSPECTOR'S TEST
PORT AND DRUM DRAIN.
1 1/4" 2' - 6"
B F
P
54405
404 4
DV
308 307
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Flow at Base of Riser
Pressure at Base of Riser
Safety Margin
Hydraulic Information
Remote…