B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part4.pdf

PDF 16 MB Posted

Attached to
ROMO 326235 Rehabilitate Kawuneeche Visitor Center
Solicitation number
140P2026R0057
Issued by

About this file

This document set comprises electrical, technology, fire protection, and fire alarm design drawings for the Rehabilitation of Kawuneeche Visitor Center at Rocky Mountain National Park. The project involves construction documents dated January 16, 2026, prepared by OTAK, Inc. (Redmond, WA) as the prime architect with AE Design (Denver, CO) and Interface Engineering (Portland, OR) as subcontractors.

The technology scope includes network infrastructure, audio-visual systems, security access control, intrusion detection, and video surveillance throughout the admin wing, auditorium, exhibit spaces, and comfort station. Key technology components include a dedicated server room (Room 116) with structured cabling, CAT6A copper and fiber connectivity, wireless access points, PTZ cameras, projection screens, touch panels, and digital signage. The fire protection system provides wet-pipe sprinklers with anti-freeze solution for the admin and VC/exhibit wings (140 total sprinkler heads across ordinary and light hazard occupancies at 0.10-0.15 GPM/SF design density), dry-pipe systems for the covered walkway and comfort station, and a single interlock preaction system for the server room. Fire alarm provisions include addressable smoke and heat detection, audiovisual notification appliances, and integration with sprinkler flow and tamper switches. All systems are designed in accordance with NFPA 13, 2024 IBC/IFC, and NPS requirements. Electrical infrastructure includes conduit pathways with sweeping bends, pull points not exceeding 100 feet apart, and surface-mounted wiremold in visible ceiling spaces. Equipment schedules identify manufacturers and part numbers for PDUs, fiber optic connectivity, copper patch panels, racks, wireless access points, cameras, and surge protection devices.

View the file

Other files

File Type Posted
B09_ROMO_KVC_326235_Final_CD_Specifications_Bid_Revisions_Part3_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part2_0005.pdf PDF
B09_QR_Tracker_ROMO_326235_9_4_26_0005.pdf PDF
Sol_140P2026R0057_Amd_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Specifications_Bid_Revisions_Part2_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part3_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part1_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Specifications_Bid_Revisions_Part1_0005.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_9_4_26_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part4_0005.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_8_26_0004.pdf PDF
Sol_140P2026R0057_Amd_0004.pdf PDF
BaselineScheduleReviewChecklist_Form_10-22-18_v508_0003.docx DOCX document
2nd_Site_Visit_Sign_in_Sheet_0003.pdf PDF
Sol_140P2026R0057_Amd_0003.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_8_21_0003.pdf PDF
B09_QR_Tracker_ROMO_326235_0003.pdf PDF
B08_Solit_PSP_Vol_II_Deliverables_LmtOnSubconRpt_REQD_0003.xlsx XLSX spreadsheet
Sol_140P2026R0057_Amd_0002.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_8_19_0002.pdf PDF
B09_Attachment_5_Solit_PSP_Vol_I_Exp_REQD_0002.docx DOCX document
Contact_Procedures_Reminder_0002.docx DOCX document
B09_Attachment_6_Solit_PSP_Vol_I_PastPerf_REQD_0002.docx DOCX document
B09_QR_Tracker_ROMO_326235_0002.pdf PDF
B11_PreProposal_Conf_Slides_ROMO_325250_0001.pptx PPTX presentation
B09_Amendment_1_ROMO_KVC_326235_ContractPriceSchedule_Rev_1_8-5-26_0001.xlsx XLSX spreadsheet
B09_P2026R0057_SF30_QA_and_Clauses_8_13_0001.pdf PDF
Sol_140P2026R0057_Amd_0001.pdf PDF
B09_QR_Tracker_ROMO_326235_0001.pdf PDF
ROMO_326235__-_Virtual_PreBid_Conference_Transcription_0001.docx DOCX document
Prebid_sign_in_sheet_0001.pdf PDF
B09_Amendment_1_What_Evaluators_Will_Ask_for_Each_Factor_0001.docx DOCX document
Virtual_sign_in_sheet_0001.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part1.pdf PDF
B01_Attatchment_1_ROMO_KVC_326235_Final_CD_Specifications_update_Part1.pdf PDF
B08_Attachment_10_ROMO_KVC_326235_CD_ContractPriceSchedule_BLANK.xlsx XLSX spreadsheet
Sol_140P2026R0057.pdf PDF
B08_Attachment_8_Solit_PSP_Vol_II_GenRefs.pdf PDF
B08_Attachment_6_Solit_PSP_Vol_I_PastPerf_REQD.pdf PDF
B08_Attachment_7_Solit_PSP_Vol_II_BidBond.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part2.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part3.pdf PDF
B01_Attatchment_1_ROMO_KVC_326235_Final_CD_Specifications_update_Part2.pdf PDF
B01_Attatchment_1_ROMO_KVC_326235_Final_CD_Specifications_update_Part3.pdf PDF
B08_Attachment_9_Solit_PSP_Vol_II_SubKPlan.pdf PDF
B08_Attachment_5_Solit_PSP_Vol_I_Exp_REQD.pdf PDF
B08_Attachment_3_Wage_Determination.pdf PDF
B08_Attachment_4_Construction_Contract_Administration.pdf PDF
B08_P2026R0057_SF1442_and_Clauses_7_30_26.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

L

K

2 3 4 5 76

M

8 9 10 11 12 13 14 15 16 17

SERVER ROOM

MAIL

OFFICE

OFFICE

OFFICE

RR

RR

MECH. / ELEC.

BREAK ROOM

CONFERENCE

STOR

OFFICE

HALL

OFFICE

OFFICE

OFFICE

OFFICE

HALL

JC

CAM3

+7' 6" AFF

CAM3

+7' 0" AFF

CAM3

+7' 0" AFF

OUTLETS, DEVICES, EQUIPMENT,

ELEMENTS AND ANY OTHER ITEMS SHOWN

IN GREY SHALL BE CONSIDERED OUTSIDE

THIS SCOPE OF WORK. ITEMS SHALL BE

CONSIDERED AS EXISTING TO REMAIN

OUTLETS, DEVICES, EQUIPMENT,

ELEMENTS AND ANY OTHER ITEMS SHOWN

IN BLACK SHALL BE CONSIDERED WITHIN

THIS SCOPE OF WORK. ITEMS SHALL BE

CONSIDERED AS NEW, REFER TO

RESPONSIBILITY MATRIX FOR MORE

INFORMATION.

REHABILITATION LEGEND

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: B

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T301

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 151 177

TECHNOLOGY RCP -

ADMIN WING

T301

TECH FIRST FLOOR CEILING PLAN - ADMIN WING1

40 84

SCALE OF FEET

A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS,

AND SPECIFICATIONS FOR MORE INFORMATION.

B. DEVICE LOCATIONS SHOWN SHALL BE COORDINATED WITH

ARCHITECTURAL ELEMENTS, FURNITURE, AND OTHER TRADES FOR FINAL

INSTALLATION LOCATION.FINAL LOCATION TO BE APPROVED BY

CONTRACTING OFFICER.

C. ALL NETWORK, SECURITY, AND/OR AUDIO VIDEO CABLE SUPPORTING

SYSTEM DEVICES/OUTLETS SHALL BE ENCLOSED IN CONDUIT FROM THE

SERVER ROOM 116 TO THE DEVICE/OUTLET. NO CABLING SHALL BE

VISIBLE OR 'FREE RUN' IN CEILING SPACE. REFER TO DETAILS.

D. NO MORE THAN 100 FEET OF PATHWAY MAY BE INSTALLED BETWEEN

PULL POINTS.

E. ALL CONDUIT BENDS SHALL BE THE "SWEEPING" TYPE AND IN

ACCORDANCE WITH THE BEND RADIUS REQUIREMENTS SPECIFIED IN THE

PROJECT GENERAL NOTES. NO "BEND" OR "ELBOW" FITTINGS ARE

PERMITTED UNLESS SPECIFICALLY NOTED.

F. WHERE TECHNOLOGY OUTLET IS INDICATED ON AN EXISTING WALL, IT IS

ACCEPTABLE TO UTILIZE FLEXIBLE CONDUIT TO ROUTE THROUGH WALL

SPACE. WHERE TECHNOLOGY OUTLET IS INDICATED ON A NEW WALL,

ELECTRICAL METALLIC TUBING (EMT) SHALL BE UTILIZED. REFER TO

DETAILS FOR MORE INFORMATION.

TECHNOLOGY GENERAL NOTES

SCALE B

TRUE PLAN

01/08/2026

S1 S1

S1 S1

S1 S1

S3

S3

S2 S2S2

S2S2

H

G

F

EXHIBIT NO. 1

AUDITORIUM

MECH. RM

STORAGE

STORAGE

EXHIBIT NO. 2

VEST.

WILDERNESS DESK

P

PS1

PJ1

CAM3

CAM3

MA1

PB1

6' 6" AFF

CAM3

7' 6" AFF

8' 0" AFF

6' 6" AFF

(1) 1" C.

+13' 0" AFF

(1) 1" C.

+13' 0" AFF

24" x 36" x 8" ENCLOSURE

+6' 0" AFF

(1) 2" C.

+9' 0" AFF

(1) 3" C.

+9' 0" AFF

(1) 1" C.

+13' 0" AFF

(2) 3/4" C.

+13' 0" AFF

(1) 1" C.

+7' 0" AFF

(1) 4" C.

+13' 0" AFF

24" x 36" x 8" ENCLOSURE

ABOVE CEILING

OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER

ITEMS SHOWN IN GREY SHALL BE CONSIDERED OUTSIDE THIS

SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS EXISTING

TO REMAIN

OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER

ITEMS SHOWN IN BLACK SHALL BE CONSIDERED WITHIN THIS

SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS NEW,

REFER TO RESPONSIBILITY MATRIX FOR MORE INFORMATION.

REHABILITATION LEGEND

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: B

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T302

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 152 177

TECHNOLOGY RCP -

AUDITORIUM & EXHIBIT

T302

TECH FIRST FLOOR CEILING PLAN - AUDITORIUM & EXHIBIT1

40 84

SCALE OF FEET

A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS,

AND SPECIFICATIONS FOR MORE INFORMATION.

B. DEVICE LOCATIONS SHOWN SHALL BE COORDINATED WITH

ARCHITECTURAL ELEMENTS, FURNITURE, AND OTHER TRADES FOR FINAL

INSTALLATION LOCATION.FINAL LOCATION TO BE APPROVED BY

CONTRACTING OFFICER.

C. ALL NETWORK, SECURITY, AND/OR AUDIO VIDEO CABLE SUPPORTING

SYSTEM DEVICES/OUTLETS SHALL BE ENCLOSED IN CONDUIT FROM THE

SERVER ROOM 116 TO THE DEVICE/OUTLET. NO CABLING SHALL BE

VISIBLE OR 'FREE RUN' IN CEILING SPACE. REFER TO DETAILS.

D. NO MORE THAN 100 FEET OF PATHWAY MAY BE INSTALLED BETWEEN

PULL POINTS.

E. ALL CONDUIT BENDS SHALL BE THE "SWEEPING" TYPE AND IN

ACCORDANCE WITH THE BEND RADIUS REQUIREMENTS SPECIFIED IN THE

PROJECT GENERAL NOTES. NO "BEND" OR "ELBOW" FITTINGS ARE

PERMITTED UNLESS SPECIFICALLY NOTED.

F. WHERE TECHNOLOGY OUTLET IS INDICATED ON AN EXISTING WALL, IT IS

ACCEPTABLE TO UTILIZE FLEXIBLE CONDUIT TO ROUTE THROUGH WALL

SPACE. WHERE TECHNOLOGY OUTLET IS INDICATED ON A NEW WALL,

ELECTRICAL METALLIC TUBING (EMT) SHALL BE UTILIZED. REFER TO

DETAILS FOR MORE INFORMATION.

TECHNOLOGY GENERAL NOTES

SCALE B

TRUE PLAN

KEYNOTE LEGEND

KEY

VALUE KEYNOTE TEXT

1 BOTTOM OF PROJECTOR SCREEN SHALL BE 4' 0" AFF WHEN SCREEN IS

DEPLOYED.

2 COORDINATE PRECISE INSTALLED LOCATION WITH CONTRACTING

OFFICER.

3 EXPOSED CONDUIT INDICATED SHALL BE SURFACE MOUNTED WIREMOLD.

ALL SURFACE MOUNTED WIREMOLD SHALL BE PAINTED TO MATCH WALLS

AT WHICH IS ATTACHED.

9 10 11 12 13 14 15 16

D

C

B

A

MEN'S RR

WOMEN'S RR

MECH. RM

JANITOR

CAM2

12" X 24" X 8" ENCLOSURE

+6' 0" AFF

(3) 1" C.

+8' 0" AFF

(RL)

(1) 1" C.

+8' 2" AFF

OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER

ITEMS SHOWN IN GREY SHALL BE CONSIDERED OUTSIDE THIS

SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS EXISTING

TO REMAIN

OUTLETS, DEVICES, EQUIPMENT, ELEMENTS AND ANY OTHER

ITEMS SHOWN IN BLACK SHALL BE CONSIDERED WITHIN THIS

SCOPE OF WORK. ITEMS SHALL BE CONSIDERED AS NEW,

REFER TO RESPONSIBILITY MATRIX FOR MORE INFORMATION.

REHABILITATION LEGEND

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: B

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T303

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 153 177

TECHNOLOGY RCP -

COMFORT STATION

T303

TECH FIRST FLOOR CEILING PLAN - COMFORT STATION1

40 84

SCALE OF FEET

A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS,

AND SPECIFICATIONS FOR MORE INFORMATION.

B. DEVICE LOCATIONS SHOWN SHALL BE COORDINATED WITH

ARCHITECTURAL ELEMENTS, FURNITURE, AND OTHER TRADES FOR FINAL

INSTALLATION LOCATION.FINAL LOCATION TO BE APPROVED BY

CONTRACTING OFFICER.

C. ALL NETWORK, SECURITY, AND/OR AUDIO VIDEO CABLE SUPPORTING

SYSTEM DEVICES/OUTLETS SHALL BE ENCLOSED IN CONDUIT FROM THE

SERVER ROOM 116 TO THE DEVICE/OUTLET. NO CABLING SHALL BE

VISIBLE OR 'FREE RUN' IN CEILING SPACE. REFER TO DETAILS.

D. NO MORE THAN 100 FEET OF PATHWAY MAY BE INSTALLED BETWEEN

PULL POINTS.

E. ALL CONDUIT BENDS SHALL BE THE "SWEEPING" TYPE AND IN

ACCORDANCE WITH THE BEND RADIUS REQUIREMENTS SPECIFIED IN THE

PROJECT GENERAL NOTES. NO "BEND" OR "ELBOW" FITTINGS ARE

PERMITTED UNLESS SPECIFICALLY NOTED.

F. WHERE TECHNOLOGY OUTLET IS INDICATED ON AN EXISTING WALL, IT IS

ACCEPTABLE TO UTILIZE FLEXIBLE CONDUIT TO ROUTE THROUGH WALL

SPACE. WHERE TECHNOLOGY OUTLET IS INDICATED ON A NEW WALL,

ELECTRICAL METALLIC TUBING (EMT) SHALL BE UTILIZED. REFER TO

DETAILS FOR MORE INFORMATION.

TECHNOLOGY GENERAL NOTES

SCALE B

TRUE PLAN

KEYNOTE LEGEND

KEY

VALUE KEYNOTE TEXT

1 CONDUIT SHALL BE ROUTED TIGHT ALONG ROOFLINE OF COVERED

WALKWAY. CONDUIT SHALL BE PAINTED TO MATCH THE SURROUNDING

SURFACE.

2 PENETRATION LOCATION FROM COVERED WALKWAY INTO ATTIC SPACE

SHALL BE APPROVED BY CONTRACTING OFFICER. THE PENETRATION

SHALL BE CONCEALED AS MUCH AS POSSIBLE.

3 EXTERIOR WIRELESS ACCESS POINT (WAP) SHALL BE RELOCATED TO

THIS LOCATION TO SUPPORT EXTERIOR WIFI ACCESS IN THE PUBLIC

PARKING LOT. THE WALL MOUNTED ENCLOSURE THE WIRELESS ACCESS

POINT SHALL BE MOUNTED IN SHALL BE OUTDOOR RATED, RADIO

FREQUENCY TRANSPARENT, AND PAINTABLE. ENCLOSURE SHALL BE

PAINTED WITH MANUFACTURER APPROVED PAINT TO COLOR MATCH

BUILDING WHERE MOUNTED. PAINT COLOR AND MOUNTING LOCATION

TO BE APPROVED BY CONTRACTING OFFICER. THE ENCLOSURE SHALL

BE MOUNTED ABOVE THE COVERED WALKWAY ROOF, SURFACE

MOUNTED TO THE COMFORT STATION WALL.

L

M

12 13 14

T4004

RR2

RV2

RV2

G B

C B

RL1

R L

RL1

R L

RL1

REFER TECHNOLOGY SITE PLAN

PLYWOOD BACKBOARD

PLYWOOD BACKBOARD

PLYWOOD BACKBOARD

INTRUSION PANEL ACCESS CONTROL

PANEL

R L

RL1

RL1

R L

SPACE DEDICATED

FOR ACCESS

CONTROL

EQUIPMENT

PLYWOOD BACKBOARD

RL1RL1

R L

CB1

GB1

RR2

RV2

PLYWOOD BACKBOARD

ACCESS CONTROL PANEL

PLYWOOD BACKBOARD

REFER TECHNOLOGY SITE PLAN

RL1

PLYWOOD BACKBOARD

RL1

SPACE

DEDICATED

FOR

INTRUSION

DETECTION

EQUIPMENT

RL1

R L

RL1

REFER TECHNOLOGY SITE PLAN

PLYWOOD BACKBOARD

PLYWOOD BACKBOARD

R L

RL1RL1

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: D

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T400

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 154 177

TECHNOLOGY

ENLARGED - RACK

LOCATION

T400

TECHNOLOGY ENLARGED PLAN - SERVER ROOM 1161

T400

SERVER ROOM 116 - EAST ELEVATION2

T400

SERVER ROOM 116 - SOUTH ELEVATION3

T400

SERVER ROOM 116 - WEST ELEVATION4

T400

SERVER ROOM 116 - NORTH ELEVATION5

A. CONTRACTOR SHALL REFER TO LEGEND, NOTES, SCHEDULES, DETAILS, AND SPECIFICATIONS FOR MORE

INFORMATION.

B. NO EQUIPMENT MAY ENTER OR PASS THROUGH THE TELECOMMUNICATION SPACE UNLESS SPECIFICALLY SUPPORTING THE SPACE. THIS INCLUDES, BUT IS NOT LIMITED TO, HVAC DUCTS, CONDUIT, PLUMBING, ETC.

C. ALL CABLING ROUTED VERTICALLY ON WALLS SHALL BE SUPPORTED WITH CABLE TIES MOUNTED TO WALL MOUNTED

VERTICAL LADDER RACK AND/OR D-RINGS.

D. A MINIMUM OF 3 FEET OF CLEARANCE SHALL BE MAINTAINED IN THE FRONT AND BACK OF EACH RACK, AFTER EQUIPMENT IS INSTALLED. CONTRACTOR SHALL ASSUME A MINIMUM OF 24 INCHES OF DEPTH FOR RACK MOUNTED

ACTIVE EQUIPMENT IN 2-POST RACKS.

E. ALL WALLS SHALL BE COVERED WITH PLYWOOD, REFER TO SPECIFICATIONS FOR MORE INFORMATION.

F. THE DEDICATED IN-ROOM HVAC THERMOSTAT SHALL BE MOUNTED ADJACENT THE LIGHT SWITCH NEAR ENTRY DOOR.

G. CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONTRACTORS/TRADES TO ENSURE WALL AND RACK SPACE

ALLOCATION NEEDS.

TECHNOLOGY GENERAL NOTES

20 42

SCALE OF FEET

SCALE D

SCALE DSCALE D

SCALE D SCALE D

W

ID

E V

E R

T

IC

A L

W

IR

E M

A N

A G

E R

KEY RACK 01

W

ID

E V

E R

T

IC

A L

W

IR

E M

A N

A G

R

45 RA6 UPPER TROUGH 45

44 FP1 FIBER PANEL 44

43 RA7 HORIZONTAL WIRE MANAGER 43

SPACE RESERVED FOR OWNER HEADEND

41 41

40 40

39 39

38 38

37 37

36 SP1 PDU 36

35 CP1 CAT6A PATCH PANEL 35

34 RA7 HORIZONTAL WIRE MANAGER 34

33 OWNER SWITCH 33

32 RA7 HORIZONTAL WIRE MANAGER 32

CP2 CAT6A PATCH PANEL

30 30

29 RA7 HORIZONTAL WIRE MANAGER 29

28 OWNER SWITCH 28

27 RA7 HORIZONTAL WIRE MANAGER 27

CP2 CAT6A PATCH PANEL

25 25

24 RA7 HORIZONTAL WIRE MANAGER 24

23 OWNER SWITCH 23

22 RA7 HORIZONTAL WIRE MANAGER 22

CP2 CAT6A PATCH PANEL

20 20

19 RA7 HORIZONTAL WIRE MANAGER 19

18 SV1 VIDEO SURVEILLANCE DEDICATED SWITCH 18

FUTURE

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

UPS (E)

7 7

UPS (E)

5 5

UPS (E)

3 3

EMPTY

1 1

RV2 RR2 RV2

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T401

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 155 177

TECHNOLOGY - RACK

ELEVATIONS

T401

SERVER ROOM 116 - RACK ELEVATION1

L G K 11/2 024

LAN

FROM FIRE ALARM

PANEL (PBO)

CC

CONTROL

SYSTEM CPU

VIDEO PROJECTOR

IP

AUDIO DSPIP

SURROUND SOUND PROCESSOR

IP

RS-232 PROJECTOR SCREEN UP / DOWN SWITCH

HDBT TO IP

ENCODER

IP

PAN TILT

ZOOM

CAMERA

PTZ1

HDBT

DANTE

WIRELESS

MICROPHONE

RECEIVER

2 CHANNEL

W/ DANTE)

RFWIRELESS MIC

ANTENNA

WM1

RFWIRELESS MIC

ANTENNA

WM1

HDMI

4K VIDEO

LASER

PROJECTOR

W/ MOUNT

PJ1

IP TO HDMI

DECODER RS-232

LAN

AV NETWORK

SWITCHES

W/POE+ &

PATCH-BAY

IP

LAN

PB1

IP

LAN

FROM AV NETWORK

HDBT TO IP

ENCODER

IP

USB-C VIDEO

TRANSMITTER

WALL PLATE

AV2

HDBT

AV-OVER-IP

SWITCHER W/

HDMI AND

USB-C

AV1

LAN

OFE LAPTOP

USB-C (VIDEO)

HDBT TO IP

ENCODER

IP

PAN TILT

ZOOM

CAMERA

PTZ1

HDBT

IP TO HDMI

DECODER

IP

LAN

DANTE

WIFI

ASSISTIVE

LISTENING

SYSTEM

HDMI

DIGITAL

SIGNAGE

MULTIMEDIA

PLAYER

IP IP

HDBT TO IP

ENCODER

IP

PAN TILT

ZOOM

CAMERA

PTZ1

HDBT

HDBT TO IP

ENCODER

IP

USB-C VIDEO

TRANSMITTER

WALL PLATE

AV2

HDBT

AV-OVER-IP

SWITCHER W/

HDMI AND

USB-C

AV1

LAN

HDBT TO IP

ENCODER

IP

USB-C VIDEO

TRANSMITTER

WALL PLATE

AV2

HDBT

AV-OVER-IP

SWITCHER W/

HDMI AND

USB-C

AV1

LAN

HDBT TO IP

ENCODER

IP

PROFESSIONAL

4K BLURAY

PLAYER

HDBT

BLURAY PLAYERIP

GENERAL NOTES:

A. ALL DATA PATCH CABLES REQUIRED TO CONNECT AN AV DEVICE TO A

DATA NETWORK OUTLET SHALL BE PROVIDED BY THE AVC AND SHALL

BE OF EXACTLY THE SAME CATEGORY CLASS ( OR BETTER) AS THE

INCOMING CABLES, I.E. A SHIELDED CAT6A INCOMING CABLES TO THE

PATCH BAY SHALL REQUIRE A SHIELDED CAT6A RATED PATCH CABLE

B. AVC SHALL PROVIDE ALL REQUIRED SPECIALIZED/CUSTOM CABLES

PROVIDING THE PARK WITH A TURN-KEY SOLUTION.

C. AVC SHALL SUPPLY AND UTILIZE RS-485/422/232 BALUNS FOR LOW

VOLTAGE CONTROL APPLICATIONS ETCETERA AS DISTANCE

LIMITATIONS REQUIRE.

D. AVC MUST UTILIZE THE 274100 SPECIFICATION SECTION IN

CONJUNCTION WITH THESE DRAWINGS TO FULLY UNDERSTAND THE

SCOPE OF WORK AND SYSTEM FUNCTIONALITY REQUIRED FOR THIS

PROJECT.

E. AVC SHALL VERIFY AND COORDINATE ALL INFRASTRUCTURE

REQUIREMENTS, I.E. CONDUIT, PULL, JOB AND BACK BOXES ETCETERA

WITH EC PRIOR TO THE COMPLETION OF ELECTRICAL ROUGH-IN PHASE.

IMMEDIATELY BRING DISCREPANCIES TO THE ATTENTION OF THE EC

AND THE AV CONSULTANT.

F. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS

CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR

COMPLETE AND FULLY OPERATIONAL SYSTEM.

G. ALL HIGH VOLTAGE CONNECTIONS SHALL BE PERFORMED BY THE BY

EC WITH THE LOW VOLTAGE WORK BY AVC.

H. ALL AUDIO CABLING AND TERMINATIONS SHALL UTILIZE THE THREE

WIRE "BALANCED" PROFESSIONAL AUDIO INDUSTRY STANDARD

WHEREVER POSSIBLE. STEREO AUDIO, THOUGH NOT ALWAYS

DETAILED IS REQUIRED.

I. ALL AV EQUIPMENT FURNISHED AND INSTALLED BY AVC UNLESS

SPECIFIED OTHERWISE.

J. AVC SHALL INSTALL EACH CEILING LOUDSPEAKER OR LOUDSPEAKER

CLUSTER WITH A SEISMIC RESTRAINING SYSTEM PER ALL LOCAL,

STATE AND FEDERAL CODES.

K. BASED ON SITE CONDITIONS, THE CONTRACTOR SHALL FIELD VERIFY

THE PROJECTION SCREEN IMAGE SIZE AS WELL AD THE PHYSICAL SITE

INSTALLATION LOCATIONS PRIOR TO SHOP DRAWING SUBMITTAL,

PURCHASE AND INSTALLATION. IN CASES WHEN THE SCREENS ARE

PBO THE CONTRACTOR SHALL VERIFY THE VALIDITY OF THE SCREEN

SIZE AND IMMEDIATELY CONTACT THE DESIGN TEAM IF VARIANCES OR

DEFICIENCIES HAVE BEEN FOUND WHERE THERE IS A MISMATCH IN THE

SCREEN ASPECT RATIO AND THE NATIVE PROJECTOR RESOLUTION

L. EQUIPMENT AND SIGNAL FLOW SHOWN IS OF A CONCEPTUAL NATURE.

AVC SHALL PROVIDE ALL NECESSARY INCIDENTAL ELECTRONICS AND

EQUIPMENT SUCH THAT A TURN-KEY SOLUTION IS INSTALLED AND

READY FOR THE IMMEDIATE USAGE. ITEMS SUCH AS BALUNS, POWER

SUPPLIES, CABLE MANAGEMENT ACCESSORIES, SMALL LOCAL

ETHERNET ROUTERS ETCETERA SHALL BE INCLUDED IN THE BASE

SCOPE. SUBMIT QUESTIONS FOR CLARIFICATION PRIOR TO YOUR

RETURN AS MONIES SHALL NOT BE AVAILABLE FOR ITEMS NOT

ACCOUNTED FOR IN YOUR DOCUMENTATION. NO EXCEPTIONS.

M. AVC SHALL CLOSELY COORDINATE WITH THE TELEDATA CONTRACTOR

ALL DATA DROP LOCATIONS AND MOUNTING HEIGHTS AS NECESSARY.

N. AVC SHALL CLOSELY COORDINATE WITH PARK IT STAFF TO PROCURE

THE NECESSARY NETWORK ACCESS, IP ADDRESSES ETCETERA

REQUIRED FOR THIS PROJECT.

O. AV CONTRACTOR SHALL PROVIDE A TURN-KEY THE DEDICATED

ETHERNET NETWORK FOR THIS PROJECT INCLUDING BUT NOT LIMITED

TO SWITCHES,PATCH-BAYS, PATCH CABLES ETCETERA.

10"

TOUCH

PANEL

TP10

LAN

CC

MOTORIZED

PR0JECTION

SCREEN W/

LVC MODULE

PS1

RS-232

FROM

CONTROL

CPU

WALL

MOUNTED UP

/ DOWN

SWITCH

SW1

CEILING

MICROPHONE

ARRAY

DANTE

MA1

RF BANDPASS

FILTER

RF

RF BANDPASS

FILTER

RF

HDMI

AV RACK ER1

BLUETOOTH

RECEIVER

DANTE

BT1

DOLBY

SURROUND

SOUND

PROCESSOR

FRONT LEFTHDMI

FRONT CENTER

FRONT RIGHT

SIDE LEFT

SIDE RIGHT

REAR LEFT

REAR RIGHT

FRONT SUB

REAT SUB

SPKR

SPKR

SPKR

SPKR

OUTINPUT

AUDIO DSP

NETWORK

DANTE

DANTE

LAN

OUTINPUT

300 W /

CHANNEL

AMPLIFIER

SPKR

SPKR

SPKR

SPKR

DIRECTIONAL

CEILING FRONT LEFT

8.00 OHM

FRONT + REAR SUB

8.00 OHM

(TYPICAL OF 2)

FROM AV

NETWORK LAN

S2

S2

S2

DIRECTIONAL

CEILING FRONT

CENTER

8.00 OHM

DIRECTIONAL

CEILING FRONT

RIGHT

8.00 OHM

LEFT SIDE CEILING

TAP @ 32W

(TYPICAL OF 3)

S1

S2

S2

S3

DIRECTIONAL

CEILING LEFT REAR

8.00 OHM

DIRECTIONAL

CEILING RIGHT REAR

8.00 OHM

DANTE

DANTE

RIGHT SIDE CEILING

TAP @ 32W

(TYPICAL OF 3)

S1

10"

TOUCH

PANEL

TP10

LAN

WIRELESS

MICROPHONE

ANTENNA

DANTE

WM1

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T500

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 156 177

AV ONE-LINES

T500

AV ONE-LINE AUDITORIUM1

L G K 2/2 025

IP

75" VIDEO

MONITOR

W/ MOUNT

USB-C (VIDEO)

OFE LAPTOP /

TABLET

LAN HDMI

USB-C VIDEO

TRANSMITTER

WALL PLATE

DESK MOUNT

AV2

VIDEO SOUND

BAR CAMERA

SYSTEM

W/ MOUNT

VSB

FP75

HDBT

FROM BUILDING

NETWORK

USB-C (DATA) USB IP

USB-C (DATA)

TRANSMITTER

WALL PLATE

USB

USB-C

RECEIVER

USB-C

HDMI

TRANSMITTER

WALL PLATE

DESK MOUNT

AV1

HDBTHDMI (VIDEO)

LAN

HDBT TO IP

ENCODER

HDMI

IP TO HDMI

DECODER RS-232

IP VIDEO

BB1

IP

HDBT TO IP

ENCODER

IP

USB/DATA

IP

USB-C VIDEO

TRANSMITTER

WALL PLATE

AV2

HDBT

HDMI

TRANSMITTER

WALL PLATE

AV1

HDBT HDBT TO IP

ENCODER

IP

HDBT TO IP

ENCODER

GENERAL NOTES:

ALL DATA PATCH CABLES REQUIRED TO CONNECT AN AV DEVICE TO A

DATA NETWORK OUTLET SHALL BE PROVIDED BY THE AVC AND SHALL BE

OF EXACTLY THE SAME CATEGORY CLASS ( OR BETTER) AS THE

INCOMING CABLES, I.E. A SHIELDED CAT6A INCOMING CABLES TO THE

PATCH BAY SHALL REQUIRE A SHIELDED CAT6A RATED PATCH CABLE

AVC SHALL PROVIDE ALL REQUIRED SPECIALIZED/CUSTOM CABLES

PROVIDING THE PARK WITH A TURN-KEY SOLUTION.

AVC SHALL SUPPLY AND UTILIZE RS-485/422/232 BALUNS FOR LOW

VOLTAGE CONTROL APPLICATIONS ETCETERA AS DISTANCE LIMITATIONS

REQUIRE.

AVC MUST UTILIZE THE 274100 SPECIFICATION SECTION IN CONJUNCTION

WITH THESE DRAWINGS TO FULLY UNDERSTAND THE SCOPE OF WORK

AND SYSTEM FUNCTIONALITY REQUIRED FOR THIS PROJECT.

AVC SHALL VERIFY AND COORDINATE ALL INFRASTRUCTURE

REQUIREMENTS, I.E. CONDUIT, PULL, JOB AND BACK BOXES ETCETERA

WITH EC PRIOR TO THE COMPLETION OF ELECTRICAL ROUGH-IN PHASE.

IMMEDIATELY BRING DISCREPANCIES TO THE ATTENTION OF THE EC AND

THE AV CONSULTANT.

PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS

CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR

COMPLETE AND FULLY OPERATIONAL SYSTEM.

ALL HIGH VOLTAGE CONNECTIONS SHALL BE PERFORMED BY THE BY EC

WITH THE LOW VOLTAGE WORK BY AVC.

ALL AUDIO CABLING AND TERMINATIONS SHALL UTILIZE THE THREE WIRE

"BALANCED" PROFESSIONAL AUDIO INDUSTRY STANDARD WHEREVER

POSSIBLE. STEREO AUDIO, THOUGH NOT ALWAYS DETAILED IS REQUIRED.

ALL AV EQUIPMENT FURNISHED AND INSTALLED BY AVC UNLESS

SPECIFIED OTHERWISE.

AVC SHALL INSTALL EACH CEILING LOUDSPEAKER OR LOUDSPEAKER

CLUSTER WITH A SEISMIC RESTRAINING SYSTEM PER ALL LOCAL, STATE

AND FEDERAL CODES.

BASED ON SITE CONDITIONS, THE CONTRACTOR SHALL FIELD VERIFY THE

PROJECTION SCREEN IMAGE SIZE AS WELL AD THE PHYSICAL SITE

INSTALLATION LOCATIONS PRIOR TO SHOP DRAWING SUBMITTAL,

PURCHASE AND INSTALLATION. IN CASES WHEN THE SCREENS ARE PBO

THE CONTRACTOR SHALL VERIFY THE VALIDITY OF THE SCREEN SIZE AND

IMMEDIATELY CONTACT THE DESIGN TEAM IF VARIANCES OR

DEFICIENCIES HAVE BEEN FOUND WHERE THERE IS A MISMATCH IN THE

SCREEN ASPECT RATIO AND THE NATIVE PROJECTOR RESOLUTION

EQUIPMENT AND SIGNAL FLOW SHOWN IS OF A CONCEPTUAL NATURE.

AVC SHALL PROVIDE ALL NECESSARY INCIDENTAL ELECTRONICS AND

EQUIPMENT SUCH THAT A TURN-KEY SOLUTION IS INSTALLED AND READY

FOR THE IMMEDIATE USAGE. ITEMS SUCH AS BALUNS, POWER SUPPLIES,

CABLE MANAGEMENT ACCESSORIES, SMALL LOCAL ETHERNET ROUTERS

ETCETERA SHALL BE INCLUDED IN THE BASE. SUBMIT QUESTIONS FOR

CLARIFICATION PRIOR TO YOUR RETURN AS MONIES SHALL NOT BE

AVAILABLE FOR ITEMS NOT ACCOUNTED FOR IN YOUR DOCUMENTATION.

NO EXCEPTIONS.

AVC SHALL CLOSELY COORDINATE WITH THE TELEDATA CONTRACTOR

ALL DATA DROP LOCATIONS AND MOUNTING HEIGHTS AS NECESSARY.

AVC SHALL CLOSELY COORDINATE WITH PARK IT STAFF TO PROCURE THE

NECESSARY NETWORK ACCESS, IP ADDRESSES ETCETERA REQUIRED

FOR THIS PROJECT.

AV CONTRACTOR SHALL PROVIDE A TURN-KEY THE DEDICATED ETHERNET

NETWORK FOR THIS PROJECT INCLUDING BUT NOT LIMITED TO

SWITCHES,PATCH-BAYS, PATCH CABLES ETCETERA.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

1 THIS DEVICE IS MOUNTED INSIDE THE

FLAT PANEL BACK BOX BB1.

AV NETWORK

SWITCH

W/POE+ &

PATCH BAY

LAN

AV RACK ER1

LAN

FROM BUILDING LAN

10"

TOUCH

PANEL

TP10

LANCONFERENCE

ROOM 120

KEYNOTE LEGEND

KEY

VALUE

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T501

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 157 177

AV ONE-LINES

T501

AV ONE-LINE CONFERENCE ROOM1

CW6

CJ2

CC2

SYMBOL:

CLG

CC2

CC2

CJ2

CW7

CJ2

SYMBOL:

CLG

#6 AWG BONDING

JUMPER TO BRIDGE

CABLE TRAY JUNCTIONS

TELEPHONE TYPE

CABLE TRAY TYPICAL

BUTT-SPLICE

TELEPHONE TYPE CABLE TRAY

TELEPHONE TYPE CABLE TRAY

#6 AWG BONDING JUMPER

TO BRIDGE CABLE TRAY

JUNCTIONS

TELEPHONE TYPE CABLE

TRAY TYPICAL JUNCTION

SPLICE KIT

#6 AWG BONDING JUMPER

FROM TELECOM CABLE TRAY

TELECOMMUNICATIONS ROOM

GROUNDING BUS BAR.

#6 AWG BONDING JUMPER

FROM EACH TELECOM EQUIPMENT

RACK TO TELECOMMUNICATIONS

ROOM GROUNDING BUS BAR.

1-T600

1-T600

1-T600

2700V

INSULATORS

STAND-OFFS

COPPER BUS BAR.

BOLT CONNECTION WITH

COMPRESSION SPADE LUG

FITTING (TYPICAL)

PROVIDE BONDING TO

CONNECTIONS TO

CABLE TRAY

SYSTEMS

AND EQUIPMENT

RACKS

(TYPICAL)

1" CONDUIT & CONNECTOR.

4-11/16" SQUARE, 2-1/8" DEEP

JUNCTION BOX WITH KNOCKOUTS.

4-11/16" SQUARE

1-DEVICE RAISED

MUD RING.

MODULAR JACK OR

BLANK AS NEEDED

FACEPLATE

CATEGORY CABLES

(QTY AS INDICATED ON PLANS)

1-1/4" CONDUIT &

CONNECTOR.

4-11/16" SQUARE, 2-1/8" DEEP

JUNCTION BOX WITH KNOCKOUTS.

4-11/16" SQUARE

1-DEVICE RAISED

MUD RING.

SYMBOL: CR IM KP XX-XXSYMBOL:

CABLES

(QTY AS INDICATED ON PLANS)

COUNTER

HALF WALL / CASEWORK WALL

DESK/WALL

NOTES:

1. A MAX OF (14) CAT6 CABLES / (7) CAT6A CABLES SHALL BE ROUTED THROUGH A 1-1/4-INCH CONDUIT.

2. A MAX OF (8) CAT6 CABLES / (4) CAT6A CABLES SHALL BE ROUTED THROUGH A 1-INCH CONDUIT.

3. CONFIGURATIONS AND QUANTITIES SHOWN ARE FOR REFERENCE ONLY. PRECISE

COUNTS,QUANTITIES, AND ROUTINGS SHALL BE BASED ON DRAWINGS AND IN-FIELD COORDINATION.

4. HEIGHT OF NETWORK TERMINATED OUTLETS SHALL BE AS INDICATED ON DRAWINGS. HEIGHT OF

JUNCTION OUTLET ('FF' OUTLET) SHALL BE FIELD COORDINATED.

TELECOMMUNICATION

OUTLET

UNDERCOUNTER /

TABLE MOUNTED

EQUIPMENT

FLOOR

FLOORBOX

REFER TO THE TELECOMMUNICATION

OUTLET ROUTING DETAIL(S) FOR CONDUIT

AND CABLE ROUTING INFORMATION.

3/4-INCH CONDUIT

3/4-INCH CONDUIT

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T600

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 158 177

TECHNOLOGY

DETAILS

T600

1 PORT SURFACE MOUNT BOX2

T600

2 PORT SURFACE MOUNT BOX3

T600

TYPICAL CABLE TRAY

GROUNDING DETAILS ER/TR ONLY7

T600

TYPICAL CABLE TRAY

JUNCTION GROUNDING DETAILS ER/TR ONLY5

T600

TELECOMMUNICATIONS

GROUNDING SYSTEM OVERVIEW ER/TR ONLY4

T600

TELECOMMUNICATIONS

GROUNDING BUS BAR (TYPICAL)6

T600

TECHNOLOGY SYSTEMS OUTLETS AND CONDUIT1

T600

FURNITURE FEEDTHROUGH OUTLETS AT

CASEWORK/HALFWALL8

A

D

L G

K

LGK

LG

K

STUD

STUD

AED

L G

K

GENERAL NOTES

KEYNOTE LEGEND

1. BACK-BOX: SHOWN FOR REFERENCE ONLY.

REFER TO AV DRAWINGS FOR

REQUIREMENTS. COORDINATE HEIGHT WITH

ARCHITECTURAL SO BOX WILL BE HIDDEN BY

DISPLAY.

2. CONDUIT: PROVIDE (1) 1" CONDUIT ROUTED

TO NEAREST COMMUNICATIONS ROOM OR IT

RACK.

3. FACE PLATE: PROVIDE MODULAR 2-PORT

PLATE.

4. DATA CABLE: PROVIDE (2) 4-PAIR CAT. 6A

(AUGMENTED) STP CABLE ORIGINATING

FROM THE NEAREST TELE-DATA ROOM. OR IT

RACK.

5. DATA TERMINATIONS: PROVIDE CAT. 6A RJ45

TYPE MODULAR JACK INTERCONNECTED TO

CAT. 6A UTP CABLE PER EIA/TIA-T568B.

6. COAXIAL CABLE: SHOWN FOR REFERENCE

ONLY. PROVIDED BY OTHERS. REFER TO AV

DRAWINGS FOR MORE INFORMATION.

7. COAXIAL TERMINATION: SHOWN FOR

REFERENCE ONLY. PROVIDED BY OTHERS.

REFER TO AV DRAWINGS FOR MORE

INFORMATION.

8. LABELS: PROVIDE WHITE LABELS WITH

BLACK TEXT TO NOTE STATION ID (YYY),

TERMINATION ID (ZZZ) AND CABLE ID (XXX).

REFER TO TYPICAL DEVICE LABELING DETAIL

FOR ADDITIONAL REQUIREMENTS.

9. AV: PROVIDE (1) 1.00" CONDUIT STUBBED UP

TO ACCESSIBLE CEILING SPACE (FUTURE).

10. POWER: POWER RECEPTACLES AND

CONDUIT SHOWN FOR REFERENCE ONLY. EC

TO FLUSH MOUNT AC DUPLEX IN BACK BOX

AND SIZE CONDUIT FOR POWER AS

REQUIRED.

KEY

VALUE

STUD

STUD

1. CONTRACTOR SHALL PROVIDE CONDUITS

THROUGH WALLS AND ACROSS

INACCESSIBLE CEILING SPACES TO ENSURE

UNOBSTRUCTED PATHWAY BACK TO

NEAREST COMM ROOM.

2. CONDUITS AS THEY ARE SHOWN ENTERING

THE FLAT PANEL BACK BOX ARE FOR

ILLUSTRATIVE PURPOSES ONLY. IT IS

POSSIBLE THAT CONDUITS MAY ENTER FROM

A DIFFERENT LOCATION BASED ON THE

PROJECT SPECIFICS, I.E. CONDUITS MAY

ENTER FROM THE SIDES, AND ADDITIONAL

CONDUITS MAY BE ROUTED TO EITHER THE

TOP OR BOTTOM OF THE BOX AS

DETERMINED BY THE EC / AVC.

3. DRAWING NOT TO SCALE.

FLAT PANEL BACK BOX

ROOF

SLAB

CONDUIT

STUB WITH 90-

DEGREE TURN

WALL

MUDRING FLUSH

WITH WALL

TELECOMMUNICATION

OUTLET

REFER TO "DEVICE

MOUNTING HEIGHT"

LEGEND FOR DEVICE

HEIGHT

CEILING

1" CONDUIT

CONDUIT SHALL ROUTE BACK

TO TELECOMMUNICATION

RACK.

SYMBOL:

CJ2

CJ2

CJ2

CJ2

LABEL

LABEL

CC2

CC2

CC2

CC2

SYMBOL:

CJ2CJ2

CJ2

LABEL

LABEL

CC2

CC2

CC2

BLANK

INSERT

SYMBOL:

CJ2CJ2

LABEL

LABEL

CC2

CC2

BLANK

INSERT

SYMBOL:

CJ2

LABEL

LABEL

CC2

BLANK

INSERT

BLANK

INSERT

BLANK

INSERT

BLANK

INSERT

CW4 CW4 CW4

CW4

ROOF

SLAB

EMT-TO-FLEX

INLINE

COUPLER

WALL

MUDRING FLUSH

WITH WALL

TELECOMMUNICATION

OUTLET

REFER TO "DEVICE

MOUNTING HEIGHT"

LEGEND FOR DEVICE

HEIGHT

CEILING

1" FLEXIBLE

CONDUIT

CONDUIT SHALL ROUTE BACK

TO TELECOMMUNICATION

RACK.

1" EMT CONDUIT

ROOF

SLAB

WALL

SLAB PENETRATION

REFER TO "DEVICE

MOUNTING HEIGHT"

LEGEND FOR DEVICE

HEIGHT OR DRAWING

700 SERIES

RACEWAY

CONDUIT SHALL ROUTE BACK TO

TELECOMMUNICATION RACK.

3/4" CONDUIT

END DEVICE

WIREMOLD 5782A

CONDUIT

CONNECTOR FITTING

CEILING

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T601

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 159 177

TECHNOLOGY

DETAILS

T601

TECHNOLOGY OUTLET ROUTING - NEW WALL4

T601

TELECOMMUNICATION OUTLET FACEPLATE DETAIL1

T601

AUDIO VIDEO DETAIL - FLAT PANEL BACKBOX - BB13

T601

TECHNOLOGY OUTLET ROUTING - EXISTING WALL2

T601

CONDUIT TO WIREMOLD TRANSITION5

FLOOR

3/4" CONDUIT 1" CONDUIT

RX

EXTERNAL REQUEST

TO EXIT DEVICE

(WHEN REQUIRED)

DOOR CONTACTDOOR CONTACT

CR

DOUBLE DOOR

MULLION ROUTED CABLING WITH WALL MOUNTED READER

3/4" CONDUIT

A SINGLE GANG BACKBOX TO

SUPPORT CARD READER/KEYPAD

ELECTRIFIED HINGE, LATCH,

OR POWER TRANSFER DEVICE

(WHEN REQUIRED)

ELECTRIFIED

STRIKE (WHEN

REQUIRED)

ELECTRIFIED HINGE,

LATCH, OR POWER

TRANSFER DEVICE

(WHEN REQUIRED)

DOOR HARDWARE

SPECIFIED BY DIVISION 08

DOOR HARDWARE

SPECIFIED BY DIVISION 08

3/4" CONDUIT

RX

EXTERNAL REQUEST

TO EXIT DEVICE

(WHEN REQUIRED)

DOOR CONTACTDOOR CONTACT

CR

DOUBLE DOOR

CONDUIT ROUTED CABLING WITH WALL MOUNTED READER

A SINGLE GANG BACKBOX TO

SUPPORT CARD READER/KEYPAD.

ELECTRIFIED HINGE, LATCH,

OR POWER TRANSFER DEVICE

(WHEN REQUIRED)

ELECTRIFIED HINGE,

LATCH, OR POWER

TRANSFER DEVICE

(WHEN REQUIRED)

DOOR HARDWARE

SPECIFIED BY DIVISION 08

DOOR HARDWARE

SPECIFIED BY DIVISION 08

3/4" CONDUIT3/4" CONDUIT

FLOOR

RX

DOOR CONTACT

CR

SINGLE DOOR

MULLION ROUTED CABLING WITH WALL MOUNTED READER

3/4" CONDUIT

A SINGLE GANG BACKBOX

TO SUPPORT CARD

READER/KEYPAD

ELECTRIFIED

STRIKE (WHEN

REQUIRED)

ELECTRIFIED HINGE,

LATCH, OR POWER

TRANSFER DEVICE

(WHEN REQUIRED)

DOOR HARDWARE

SPECIFIED BY DIVISION 08

1" CONDUIT DEDICATED

FOR DOOR HARDWARE

CABLING EXTERNAL

REQUEST TO EXIT

DEVICE (WHEN

REQUIRED)

NOTES

1. THE DETAILS HEREIN ARE DIAGRAMMATIC IN NATURE AND DO NOT

REPRESENT A SPECIFIC INSTANCE. THE DOOR TYPE, DOOR

CONFIGURATION, AND OTHER MISCELLANEOUS INFORMATION SHALL BE

COORDINATED WITH THE DIVISION 08 SPECIFICATIONS, ARCHITECTURAL

DRAWINGS, AND TECHNOLOGY DRAWINGS.

2. THE DETAILS HEREIN REPRESENT TYPICAL INFRASTRUCTURE

REQUIREMENTS. THE SPECIFIC ROUTING OF CONDUIT AND CABLING SHALL

BE COORDINATED FOR EACH ACCESS POINT LOCATION.

3. WHERE THE REQUEST TO EXIT DEVICE/FUNCTION IS INTEGRAL TO DOOR

HARDWARE COMPONENTS, CONDUIT, BACKBOX, AND EXTERNAL REQUEST

TO EXIT DEVICE SHOWN ARE NOT REQUIRED.

4. WHERE DOOR FRAME ALLOWS THE ROUTING OF CABLING, DOOR CONTACT

CABLING AND DOOR HARDWARE CABLING SHALL ROUTE THROUGH DOOR

FRAME AND CONSOLIDATED CONDUIT. WHERE DOOR FRAME DOES NOT

ALLOW CABLE ROUTING, INDIVIDUAL 3/4-INCH CONDUITS SHALL ROUTE

DIRECT TO EACH DEVICE FROM THE CONSOLIDATION BOX. COORDINATE

WITH DOOR HARDWARE SPECIFICATIONS TO DETERMINE ELECTRIFIED

COMPONENTS.

5. WHERE ACCESSIBLE CEILING IS WITHIN 50 FEET OF DOOR LOCATION, THE

CONSOLIDATION BACKBOX SHALL BE LOCATED ABOVE ACCESSIBLE CEILING

AT THE NEAREST POINT TO THE DOOR. WHERE AN ACCESSIBLE CEILING IS

GREATER THAN 50 FEET AWAY FROM THE DOOR LOCATION, THE

CONSOLIDATION BOX SHALL BE WALL OR CEILING MOUNTED BEHIND AN

ACCESS PANEL. CONTRACTOR SHALL FIELD COORDINATE ACCESS PANEL

LOCATION WITH ARCHITECT.

6. THE CONSOLIDATION BOX SHALL BE MOUNTED ON THE SECURE SIDE OF

THE DOOR; IT SHALL BE PLACED SO THAT IT IS ONLY ACCESSIBLE FROM THE

SECURE SIDE OF THE DOOR.

7. ALL CONDUITS AND CABLING SHALL BE RECESSED WITHIN THE WALL OR

FRAME, NO SURFACE MOUNT INFRASTRUCTURE IS ACCEPTABLE UNLESS

SPECIFICALLY NOTED.

SINGLE DOOR

CONDUIT ROUTED CABLING WITH WALL MOUNTED READER

RX

DOOR CONTACT

CR

A SINGLE GANG BACKBOX

TO SUPPORT CARD

READER/KEYPAD

ELECTRIFIED

STRIKE (WHEN

REQUIRED)

ELECTRIFIED HINGE,

LATCH, OR POWER

TRANSFER DEVICE

(WHEN REQUIRED)

DOOR HARDWARE

SPECIFIED BY DIVISION 08

EXTERNAL

REQUEST TO EXIT

DEVICE (WHEN

REQUIRED)

3/4" CONDUIT 3/4" CONDUIT

DOOR COORDINATION

CEILING COORDINATION

INACCESSIBLE CEILING

INACCESSIBLE CEILING

STRUCTURE

CONSOLIDATION BACKBOX - 4

GANG WITH COVER,

ORIENTED VERTICALLY

SUPPORT TO STRUCTURE

PATHWAY DEDICATED

FOR DOOR

HARDWARE CABLING

CABLE BACK TO

DOOR CONTROL

PANEL

A 1" CONDUIT SHALL ROUTE TO

NEAREST ACCESSIBLE CEILING.

INTERCOM CONDUIT SHALL ROUTE

BACK TO ACCESSIBLE CEILING OR TR.

ROOF

SLAB

EXTERIOR WALL

SLAB PENETRATION

CONDUIT

CONDUIT SHALL ROUTE BACK TO

TELECOMMUNICATION RACK.

INCOMING

CONDUIT

FROM MDF

PULL BOX

INACCESSIBLE CEILING

OUTSIDE OF

BUILDING

CONDUIT TO

END DEVICES

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T602

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 160 177

TECHNOLOGY

DETAILS

T602

DOOR ROUGH-IN: ACCESS CONTROLLED DOORS WITH CARD

READERS1

T602

CONDUIT TO WIREMOLD TRANSITION2

EQUIPMENT SCHEDULES INFORMATION

ALL COMPONENTS SHOWN HEREIN SHALL BE CONSIDERED AS 'BASIS OF DESIGN'. THEY ARE SHOWN TO INDICATE GENERAL FUNCTION AND APPLICATION, IT IS ACCEPTABLE TO SUBMIT/PROVIDE COMPONENTS DETERMINED TO BE 'APPROVED

EQUAL'.

POWER DISTRIBUTION DEVICES

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

SP1 PDU, HORIZTONAL, 120V INPUT, (16) 5-20 OUTLETS TRIPPLITE PDUMH20ATS

FIBER CONNECTIVITY

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

FC1 12 STRAND SM (OS2) FIBER, ISP/OSP, PLENUM, LOOSE TUBE, ARMORED PANDUIT FSGP912Y

FM2 FIBER CASSETTE, 12 STRAND SM, LC CONNECTOR PANDUIT FCS9N-12-10P

FP1 1 RU FIBER PANEL PANDUIT FRME-1U

COPPER CONNECTIVITY

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

CC2 CAT 6A CABLE, PLENUM, UTP COMMSCOPE CS44P

CC3 25-PAIR COPPER, CAT 5E, PLENUM, UTP SUPERIOR ESSEX 51-478-48

CJ2 CAT 6A JACK COMMSCOPE UKJ10G

CX3 CAT6A PATCH CABLE COMMSCOPE UC1AAA2

CX4 CAT6A PATCH CABLE - PLENUM RATED COMMSCOPE UC1AA22

CB1 110-BLOCK, WALL MOUNTED COMMSCOPE 569440-1

CW4 4-PORT FACEPLATE, LABELED COMMSCOPE 2111039-x FINISH SHALL MATCH COLOR OF POWER RECEPTACLE DEVICE FACEPLATES

CW5 FLOOR BOX TELECOM FACEPLATE SEE COMMENTS SEE COMMENTS

FLOORBOX SPECIFIED BY ELECTRICAL. FACEPLATE COORDINATED WITH

FLOORBOX MANUFACTURER.

CW6 SURFACE MOUNT BOX, (BISCUIT), PLENUM, 1 PORT COMMSCOPE SMB-1P-xxx PLENUM SECURITY CAMERA LOCATIONS

CW7 SURFACE MOUNT BOX, (BISCUIT), PLENUM, 2 PORT COMMSCOPE SMB-2P-xxx PLENUM WIRELESS ACCESSS POINT LOCATIONS

CP1 CAT 6A PATCH PANEL, 24 PORTS, 1RU, BLACK, FLAT COMMSCOPE UNP-6A-DM-1U-24

CP2 CAT 6A PATCH PANEL, 48 PORTS, 2RU, BLACK, FLAT COMMSCOPE UNP-6A-DM-2U-48

RACKS AND ACCESSORIES

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

RR2 4-POST RACK, 7-FOOT IN HEIGHT, EIA. 19-INCH IN WIDTH, BLACK CPI 50120-703

RV2

VERTICAL WIRE MANAGER, 7-FOOT IN HEIGHT, 6-INCH IN WIDTH, BLACK

DOUBLE-SIDED, FINGER STYLE FRONT, VERTICAL SECTION BACK

CPI 30162-703

RL1 LADDER RUNWAY, 12-INCH WIDE CPI 10250-712

RA1 BUTT-SPLICE KIT CPI 11301-701

RA2 JUNCTION-SPLICE KIT CPI 11302-701

RA3 LADDER RUNWAY ELEVATION KIT CPI 10506-706

RA4 LADDER RUNWAY RADIUS DROP CPI 12100-712

RA5 LADDER RUNWAY CORNER BRACKET CPI 11959-715

RA6 UPPER TROUGH CPI 13183-719

RA7 HORIZONTAL WIRE MANAGER, 1U, 5" DEEP CPI 30139-719

RA8 HORIZONTAL WIRE MANAGER, 2U, 5" DEEP CPI 30130-719

HORIZONTAL CABLE MATRIX

SYSTEM CABLE KEY CABLE COLOR JACK KEY JACK COLOR

PATCH CABLE COLOR:

IT ROOM

PATCH CABLE COLOR:

PREMISE

COMMENTS

NETWORK CC2 BLUE CJ2 BLUE BLUE BLUE

VOICE CC2 BLUE CJ2 BLUE BLUE BLUE

WIRELESS ACCESS POINT (WAP) CC2 GREEN CJ2 GREEN GREEN GREEN

SECURITY CC2 BLUE CJ2 BLUE BLUE BLUE

PAGING CC2 BLUE CJ2 BLUE BLUE BLUE

AUDIO VISUAL CC2 BLUE CJ2 BLUE BLUE BLUE

GROUNDING

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

GB1 PRIMARY BONDING BUSBAR (PBB) COMPLIANT WITH ANSI/TIA-607 CPI 40153-020

GS1 SURGE PROTECTION - 25 PAIR COPPER, CAT3/CAT5E CIRCA MAX 1880ENA/NSC-6E

GS2 SURGE PROTECTION - CAT6 / CAT6A CIRCA MAX 604-75RJ

BACKBONE CABLE MATRIX

ORIGINATION SPACE TERMINATION SPACE

CABLE 1 CABLE 2 CABLE 3

KEY COLOR QUANTITY KEY COLOR QUANTITY KEY COLOR QUANTITY COMMENTS

SERVER ROOM 116

GRAND LAKE ENTRANCE

STATION

CABLE IS EXISTING, COORDINATE WITH

CONTRACTING OFFICER. CABLE IS OWNER

FURNISHED, CONTRACTOR INSTALLED (OFCI).

SERVER ROOM 116

MAINTENANCE FACILITY

BUILDING

FC1 YELLOW 1 -- -- -- -- --

ESTIMATE LENGTH OF CABLE RUN SHALL BE 2,000

FEET.

SECURITY - ACCESS CONTROL SYSTEM (ACS)

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

KP1 KEYPAD DOOR HARDWARE - - REFER TO DIVISION 8 FOR DOOR HARDWARE

DC1 DOOR CONTACT (POSITION SWITCH), CONCEALED MOUNT GE INTERLOGIX 2767-L

RX1 REQUEST TO EXIT SENSOR BOSCH DS-160

SECURITY - INTRUSION DETECTION SYSTEM (IDS)

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

MD3 MOTION DETECTOR - WALL MOUNT, SHORT RANGE BOSCH DS860 DEVICE SHALL BE ALMOND COLOR.

KI1 SECURITY KEYPAD INTERFACE BOSCH B921C

CP1 SECURITY CONTROL PANEL BOSCH 9512G

DB1 DURESS BUTTON - HOLD UP SWITCH BOSCH ISC-PB1-100

SECURITY - VIDEO SURVEILLANCE SYSTEM (VSS)

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

CAM2

BLACK DOME AND COVER - EXTERIOR RATED - FIXED DOME CAMERA, 5MP - IP66/IK10

RATED

AXIS P3267-LVE

PROVIDE MOUNT AS INDICATED ON DETAILS AND AS REQUIRED PER LOCATION.

CAMERA DOME AND COVER SHALL BE BLACK.

CAM3 INTERIOR RATED - FIXED DOME CAMERA, 5MP - IP66/IK10 RATED AXIS P3267-LV PROVIDE MOUNT AS INDICATED ON DETAILS AND AS REQUIRED PER LOCATION

SV1 VIDEO SURVEILLANCE DEDICATED SWITCH AXIS T8524

EXISTING SERVER/WORKSTATION FOR VIDEO SURVEILLANCE SHALL BE

RELOCATED FROM GRAND LAKE ENTRANCE STATION TO SERVER 116.

PATHWAYS

KEY DESCRIPTION MANUFACTURER PART NUMBER COMMENTS

HH1 SMALL HANDHOLE - NON-TRAFFIC RATED OLDCASTLE INFRASTRUCTURE 2436-36 TIER 15 RATED COVER

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

T700

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 161 177

TECHNOLOGY

SCHEDULES

Abbreviations

ABANDON IN PLACE(A)

EXISTING(E)

FUTURE(F)

NEW(N)

RELOCATE/RELOCATED LOCATION(R)

DEMOLITION(X)

ABOVE FINISHED FLOORAFF

AUTOMATIC SPRINKLERAS

BOTTOM OF BEAMBOB

BOTTOM OF DECKBOD

BOTTOM OF PIPEBOP

BOTTOM OF RISERBOR

BUTTERFLY VALVEBV

CENTER LINEC

CHECK VALVECV

DOUBLE DETECTOR CHECK VALVE ASSEMBLYDDCV

DROP NIPPLEDN

EXTENDED COVERAGEEC

ELEVATIONEL

FAHRENHEITF

FIRE DEPARTMENT CONNECTIONFDC

FINISHED FLOORFF

FLOOR FLANGEFFL

FIRE HOSE CABINETFHC

FIRE HOSE STATIONFHS

FLOW SWITCHFS

FEETFT

GRADEG

GALLONS PER MINUTEGPM

GATE VALVEGV

HANGERH

HORIZONTAL SIDE WALLHSW

HOSE VALVEHV

INSIDE DIAMETERID

INCHESIN

MAXIMUMMAX

MINIMUMMIN

NIPPLE AND CAPN&C

NOT IN CONTRACTNIC

NUMBERNO

NOT TO SCALENTS

OPEN BAR JOISTOBJ

OUTSIDE DIAMETEROD

OUTSIDE SCREW & YOKEOS & Y

POST INDICATOR VALVEPIV

PRESSURE REDUCING VALVEPRV

PRESSURE SWITCHPS

ROOF MANIFOLDRM

RISER NIPPLERN

SWAY BRACESB

SQUARE FEETSF

SHUT OFF VALVESOV

STANDPIPESP

STANDARD SPRAY PENDENTSSP

STANDARD SPRAY UPRIGHTSSU

TOP OF BEAMTOB

TOP OF PIPETOP

TOP OF RISERTOR

TOP OF STEELTOS

TAMPER SWITCHTS

TYPICALTYP

UNLESS NOTED OTHERWISEUNO

Control

BELL/GONG

CONTROL PANEL

FLOW DETECTION SWITCH

MONITOR SWITCH

PRESSURE GAUGE

TAMPER DETECTOR

WATER MOTOR ALARM

Miscellaneous

2-WAY SWAY BRACE

4-WAY SWAY BRACE

AUXILIARY DRAIN

CONTINUATION OF PIPE

COUPLING

DEMOLITION PIPE

DEMOLITION PIPE

DRY HOSE STATION

ELEVATION ABOVE FINISHED FLOOR

EXISTING PIPE

FLANGED COUPLING

FLEXIBLE COUPLING

GROOVED CAP

GROOVED COUPLING

HANGER (TEXT INDICATES TYPE)

HYDRAULIC CALCULATION NODE

NEW PIPE

POINT OF CONNECTION

RISER

SCREWED CAP

SCREWED PLUG

UNION

WET HOSE STATION

Valves

ALARM CHECK VALVE, ELEVATION VIEW

ALARM CHECK VALVE, PLAN VIEW

ANGLE VALVE

CHECK VALVE

DELUGE VALVE

DRY PIPE VALVE, PLAN VIEW

INDICATING BUTTERFLY VALVE

NON-RISING STEM VALVE

PREACTION VALVE

VALVE WITH TAMPER SWITCH

Water Service

DOUBLE CHECK BACKFLOW PREVENTER (RP-TYPE)

FIRE DEPARTMENT CONNECTION

FREE STANDING F.D. CONNECTION

O.S.&Y. VALVE

POST INDICATOR VALVE

FIRE PROTECTION SYMBOL LIST

NOTE: This is a standard symbol list and not all items listed may be used.

F

M

T

14'-0"

FLEX

H1

T

NOMINAL PIPE SIZE (IN)

STEEL PIPE 1 1-1/4 1-1/2 2 2-1/2 3 4 6

12-0 12-0 15-0 15-0 15-0 15-0 15-0 15-0

FOR STEEL PIPE, THE MAXIMUM LENGTH FOR UNSUPPORTED ARMOVER

SHALL BE 2'-0". WHEN PRESSURE EXCEEDS 100 PSI, UNSUPPORTED LENGTH

SHALL BE 1'-0".

HANGER ROD SIZE

MAXIMUM DISTANCE BETWEEN HANGERS (FT-IN)

PIPE SIZE

UP TO AND

INCLUDING 4"

DIA. OF ROD

3/8"

6" AND 8" 1/2"

NOTE: TYPICAL TICK MARKS AS SHOWN ON

PIPING PLAN MAY NOT REFLECT ACTUAL FIELD

INSTALLATION. FINAL HANGER INSTALLATION

SHALL BE IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 13 CHAPTER 9.

GREATER THAN 36" FOR 1"

GREATER THAN 48" FOR 1-1/4"

GREATER THAN 60" FOR 1-1/2" OR LARGER

36" FOR 1"

48" FOR 1-1/4"

60" FOR 1-1/2" OR LARGER

DISTANCE FROM SPRINKLER TO HANGER

THEN EXTEND HERE

MAX

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF01/16/2026

326235

165639

REHABILITATE KAWUEECHE VISITOR CENTER

ROCKY MOUNTAIN NATION PARK

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

INTERFACE

ENGINEERING

PORTLAND, OR

1/ 7/

1:

:1

A

M A ut od es k

D oc s:

//2

4-

N P

S R

O M

O K aw un ee ch e V

C D

D -C

A w

O ta k/

N

P S

R O

M O

K A

W U

E E

C H

E V

IS

IT

O R

C E

N T

E R

_F

LS

_R

.r vt

FP001

CK

CK

KA

162 177

SYMBOL LIST AND

GENERAL NOTES -

FIRE PROTECTION

FP001 SYMBOL LIST AND GENERAL NOTES - FIRE PROTECTION

FP090 SITE PLAN - FIRE PROTECTION

FP101 OVERALL REFLECTED CEILING PLAN - FIRE PROTECTION

FP401 ENLARGED PLAN - ADMIN - FIRE PROTECTION

FP402 ENLARGED PLAN - AUDITORIUM & EXHIBIT - FIRE PROTECTION

FP403 ENLARGED PLAN - COMFORT STATION - FIRE PROTECTION

FP501 SECTIONS - FIRE PROTECTION

FP601 ADMIN SERVER ROOM - FIRE PROTECTION

FP701 DETAILS - FIRE PROTECTION

SHEET INDEX

SPRINKLER HEAD LEGEND

SYMBOL DESCRIPTION K-FACTOR

ORIFICE

SIZE

RESPONSE TEMP COVERAGE FINISH ESCHUTCHEON COUNT COMMENTS

CONCEALED PENDENT

SPRINKLER

5.6 1/2" Quick 165 Standard

WOOD

GRAIN

FLAT, ROUND 14

COORDINATE FINISH TYPE WITH CO

AT WOOD CEILINGS

DRY BARREL SIDEWALL

SPRINKLER

5.6 1/2" Quick 205 Standard CHROME CHROME 7

HORIZONTAL SIDEWALL

SPRINKLER

5.6 1/2" Quick 165 Standard

WHITE

POLY

NONE 2 INSTALL TIGHT TO BRANCH LINE PIPE

RECESSED PENDENT SPRINKLER 5.6 1/2" Quick 165 Standard

WHITE

POLY

RECESSED, WHITE 47

DRY BARREL CONCEALED

PENDENT SPRINKLER

5.6 1/2" Quick 205 Standard CHROME FLAT, ROUND 22

UPRIGHT SPRINKLER 5.6 1/2" Quick 165 Standard BRASS NONE 48

PROVIDE WITH METAL CAGE IN

MECHANICAL SPACES

TOTAL SPRINKLERS: 140

ORDINARY HAZARD GROUP 1 ELECTRICAL ROOMS, MECHANICAL ROOMS, JANITORS CLOSEST, MISC. STORAGE ROOMS 130 SQ FT 0.15 GPM/SQ FT 1500 SQ FT

LIGHT HAZARD

VESTIBULES, HALLS, RESTROOMS, OFFICES, TELECOMMUNICATION ROOMS, EVES AND

OVERHANGS WITH COMBUSTIBLE CONSTRUCTION AND NO COMBUSTIBLE BENEATH,

EXHIBIT AREA.

225 SQ FT 0.10 GPM/SQ FT 1500 SQ FT

OCCUPANCY DESCRIPTION MAX COVERAGE DESIGN DENSITY REMOTE AREA

HAZARD CLASSIFICATIONS

GENERAL FIRE PROTECTION NOTES

A. SCOPE OF WORK:

• PROVIDE A WET-PIPE FIRE SPRINKLERS SYSTEM FOR THE ADMIN, VC AND EXHIBIT

WINGS IN ACCORDANCE WITH NFPA 13, IBC/IFC AND NPS AHJ REQUIREMENTS.

SYSTEM(S) TO BE FILLED WITH A UL-APPROVED ANTI-FREEZE (TYCO LFP+ OR SIMILAR).

a. PROVIDE (1) SYSTEM WITH ASSOCIATED RP-BACKFLOW AND CONTROL VALVES

LOCATED WITHIN THE ADMIN WING TO PROTECT BOTH ADMIN AND VC WINGS.

• PROVIDE A DRY-PIPE SPRINKLER SYSTEM FOR THE COVERED WALKWAY AND

COMFORT STATION IN ACCORDANCE WITH NFPA 13, IBC/IFC AND NPS AHJ

REQUIREMENTS. DRY-PIPE SYSTEM TO BE FILLED WITH SUPERVISORY NITROGEN.

a. PROVIDE (1) SYSTEM WITH ASSOCIATED BACKFLOW AND CONTROL VALVE

LOCATED WITHIN THE COMFORT STATION.

• PROVIDE A SINGLE INTERLOCK PREACTION SPRINKLER SYSTEM TO PROTECT SERVER

ROOM INSTALLED IN ACCORDANCE WITH NFPA 13, IBC/IFC AND NPS AHJ

REQUIREMENTS. PROVIDE WITH A DEDICATED RELEASE PANEL AND DETECTION

DEVICES.

B. PROVIDE A FIRE DEPARTMENT CONNECTION (FDC). FDC LOCATED ON-SITE, REFER TO

CIVIL FOR ADDITIONAL INFORMATION.

C. SEISMIC DESIGN CATEGORY-B. NO SEISMIC BRACING REQUIRED. REFER TO STRUCTURAL

DRAWINGS FOR ADDITIONAL SITE/SEISMIC INFORMATION.

D. CONTRACTOR TO PROVIDE ALL REQUIRED HANGERS, AND THE LIKE IN ACCORDANCE WITH

NFPA 13 REQUIREMENTS.

E. ALL ABOVE GROUND FIRE SPRINKLER PIPING SHALL BE SCHEDULE 40 PER NPS

STANDARDS.

F. FIRE PROTECTION SYSTEM(S) SHALL BE DESIGNED BY SOMEONE MEETING THE

FOLLOWING:

a. NICET III OR HIGHER FOR WATER-BASED SYSTEMS.

b. FIRE PROTECTION ENGINEER.

c. AS APPROVED BY THE NPS AHJ.

G. FIRE PROTECTION SYSTEM(S) SHALL BE INSTALLED BY SOMEONE MEETING THE

FOLLOWING:

a. NICET II OR HIGHER FOR WATER-BASED SYSTEMS.

b. FIRE PROTECTION ENGINEER.

c. AS APPROVED BY THE AHJ.

WATER FLOW INFORMATION

LOCATION

MAIN SIZE

STATIC PRESSURE

RESIDUAL PRESSURE

COMMENTS:

FLOW AT RESIDUAL

DATE OF REPORT/TEST 9-2024

6 "

81 PSI

52 PSI

715 GPM

EXISTING HYDRANT FIELD FLOW TESTED

VC ENTRANCE (NORTH)

APPLICABLE CODES:

A. 2024 INTERNATIONAL BUILDING CODE (IBC)

B. 2024 INTERNATIONAL FIRE CODE (IFC)

C. ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

D. 2022 NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72)

E. NPS STRUCTURAL FIRE MANAGEMENT REFERENCE MANUAL 58 (RM #58)

(N) SITE FDC

FREE STANDING

6" FIRE SERVICE

4" FDC SERVICE

4" U.G FIRE MAIN

TO EXHIBIT SPACE

EXHIBIT SPACE

INDICATING

CONTROL VALVE

4" FIRE RISER

W/ RP-BFP (INSIDE)

4" FIRE RISER

W/ BFP (INSIDE)

RPB

BOR

(E) HYDRANT

(SEE CIVIL)

(E) SITE WATER MAIN

WITH (N) FIRE LINE TAP.

(SEE CIVIL)

FDC NOT REQUIRED FOR COMFORT STATION

PER NFPA 13 (16.12.2)

4" FIRE SERVICE

BFP

UG1

S

BORD

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

01/16/2026

326235

165639

REHABILITATE KAWUEECHE VISITOR CENTER

ROCKY MOUNTAIN NATION PARK

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

INTERFACE

ENGINEERING

PORTLAND, OR

1/ 7/

1:

:1

A

M A ut od es k

D oc s:

//2

4-

N P

S R

O M

O K aw un ee ch e V

C D

D -C

A w

O ta k/

N

P S

R O

M O

K A

W U

E E

C H

E V

IS

IT

O R

C E

N T

E R

_F

LS

_R

.r vt

FP090

CK

CK

KA

163 177

SITE PLAN - FIRE

PROTECTION

200 4020

SCALE OF FEETSCALEFP090

1 SITE PLAN - FIRE PROTECTION

A

TRUE PLAN

A. REFER TO CIVIL DRAWINGS FOR ADDITIONAL SITE

INFORMATION.

B. FIRE SPRINKLER SCOPE OF WORK TO START 5-FT OUT

FROM BUILDING FOOTPRINT. CONTRACTOR TO PROVIDE

ALL REQUIRED RESTRAINT JOINTS.

C. FREE-STANDING 2-PORT FDC TO SUPPLY ALL FIRE

SPRINKLER SYSTEM(S). CHECK VALVE PROVIDED INSIDE

AT EACH (2) FIRE RISER LOCATIONS.

GENERAL SHEET NOTES

L

K

2 3 4 5 76

M

8 9 10 11 12 13 14 15 16 17

H

G

F

E

D

C

B

A

FP401

FP403

FP402

TYP4

TYP4

TYP4

TYP4

TYP6

TYP6TYP6

TYP6 TYP6

TYP6

TYP6

TYP6

TYP6

TYP6

TYP6

EXHIBIT SPACE

INDICATING

CONTROL VALVE

4" FIRE RISER

W/ RP-BFP (INSIDE)

4" FIRE RISER

W/ BFP (INSIDE)

1-1/2" PREACTION

RISER ASSEMBLY

B F

P

BFP

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

01/16/2026

326235

165639

REHABILITATE KAWUEECHE VISITOR CENTER

ROCKY MOUNTAIN NATION PARK

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

INTERFACE

ENGINEERING

PORTLAND, OR

1/ 7/

1:

:2

A

M A ut od es k

D oc s:

//2

4-

N P

S R

O M

O K aw un ee ch e V

C D

D -C

A w

O ta k/

N

P S

R O

M O

K A

W U

E E

C H

E V

IS

IT

O R

C E

N T

E R

_F

LS

_R

.r vt

FP101

CK

CK

KA

164 177

OVERALL REFLECTED

CEILING PLAN - FIRE

PROTECTION

80 168

SCALE OF FEET

1. PROVIDE PREACTION SPRINKLER SYSTEM FOR SERVER,

REFER TO FP601 FOR RISER ASSEMBLY DETAIL.

2. REFER TO CIVIL WATER PLANS FOR SITE CONDITIONS

AND INFORMATION.

3. PROVIDE CONCEALED TYPE PENDENT SPRINKLERS WITH

COVER PLATES MATCHING THE CEILING TYPE.

4. PROVIDE DRY-TYPE SPRINKLERS PROTECTING EXTERIOR

OVERHANGS 4-FT OR GREATER.

5. ROUTE 4" FIRE MAIN, UNDERGROUND TO SERVE

VC/EXHIBIT WING. REFER TO CIVIL FOR SITE PIPING AND

CONTINUATION.

6. SPRINKLER PROTECTION OMITTED FROM EXTERIOR

EAVES OR OVERHANGS LESS THAN 4-FT IN WIDTH PER

NFPA 13 (9.2.1.20).

SHEET KEYNOTES

SCALEFP101

OVERALL REFLECTED CEILING PLAN -

FIRE PROTECTION

L

K

2 3 4 5 76

M

8 9 10 11 12 13 14 15 16 17

BREAK ROOM

SERVER ROOM

MECH. / ELEC.

115RR

RR

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HALL

OFFICE

121 CONFERENCE

STOR

WILDERNESS DESK

JC

MAIL

HALL

HALL

6" U.G FIRE

MAIN

4" FDC MAIN

4" TO VC WING

REFER TO CIVIL DRAWINGS

BEYOND 5-FT

FP701

TYP

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

7' - 10"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

2' - 0"

2' - 0"

1' - 10"

5' - 0"

2' - 0"

11' - 7"

FP501

PREACTION SYSTEM

PREACTION VALVE

102 103 104

108106 107

151412 13

TOR

FP701

FP701

FP701

Occupancy Classification

Density

Total Hose Streams

Flowing Heads

K-Factor

Flow at Base of Riser

Pressure at Base of Riser

Safety Margin

Hydraulic Information

Remote Area Name

Comments:

Pressure at Source

Flow at Source

Remote Area Size

Head Coverage

NFPA 13 -

Light Hazard

0.10 GPM/SF

100.00 GPM

8 @ 17.60 + 4 @ 15.00

5.213316

242.15 GPM

42.44 PSI

+28.01 (37.67%)

ADMIN - UPRIGHTS

UPRIGHTS ABOVE CEILING.

DARCY-WEISBACH FOR

ANTI-FREEZE (TEMP = 0-F)

46.35 PSI

342.15 GPM

1521 SF

225 (MAX) SF

FP601

10' - 0"

3' - 9"

1 1/2"1 1/2"

1 1/2" 1 1/2"

1 1/2"

/4

1"

1 1/4"1"

1 1/2"

1 1/2"

1"

1"

INSTALL DIRECTLY TO BRANCH LINE ON TEE.

ADMIN UPRIGHT REMOTE AREA

5' - 5"

1 1/2"

7 1053 9

7' - 1"

4' - 10"

7' - 6"

Occupancy Classification

Density

Total Hose Streams

Flowing Heads

K-Factor

Flow at Base of Riser

Pressure at Base of Riser

Safety Margin

Hydraulic Information

Remote Area Name

Comments:

Pressure at Source

Flow at Source

Remote Area Size

Head Coverage

NFPA 13 -

Light Hazard

0.10 GPM/SF

100.00 GPM

9 @ 13.79 + 1 @ 16.50

5.213316

179.81 GPM

37.72 PSI

+35.6 (46.5%)

ADMIN - PENDENTS

RA REDUCTION PER 19.2.3.2.3.1.

(40%). DARCY-WEISBACH FOR

ANTI-FREEZE (TEMP = 0-F)

40.96 PSI

279.81 GPM

917 SF

VARIES, AVG. 88 SF

ADMIN PENDENT REMOTE AREA

1 1/2" 1 1/2"

28 31

30 32

208 209

206 207

7' - 6"

7' - 6"

7' - 5" 7' - 6"

106105 108107

2 3

16335 85

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

01/16/2026

326235

165639

REHABILITATE KAWUEECHE VISITOR CENTER

ROCKY MOUNTAIN NATION PARK

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

INTERFACE

ENGINEERING

PORTLAND, OR

1/ 7/

1:

:2

A

M A ut od es k

D oc s:

//2

4-

N P

S R

O M

O K aw un ee ch e V

C D

D -C

A w

O ta k/

N

P S

R O

M O

K A

W U

E E

C H

E V

IS

IT

O R

C E

N T

E R

_F

LS

_R

.r vt

FP401

CK

CK

KA

165 177

ENLARGED PLAN -

ADMIN - FIRE

PROTECTION

40 84

SCALE OF FEET

SCALEFP401

1 ENLARGED PLAN - ADMIN - FIRE PROTECTION

A

TRUE PLAN

1. PROVIDE UPRIGHT SPRINKLER PROTECTION FOR

COMBUSTIBLE CONCEALED SPACE IN ACCORDANCE WITH

NFPA 13.

2. ROUTE PIPING IN WILDERNESS AREA EXPOSED, BELOW

CEILING.

3. PROVIDE DRY-TYPE FLEX PENDENT SPRINKLER TO SERVE

EXTERIOR AREA. RIGID PIPE TO BE WITHIN BUILDING

ENVELOPE.

SHEET KEYNOTES

H

G

F

WILDERNESS DESK

EXHIBIT NO. 1

EXHIBIT NO. 2

AUDITORIUM

STORAGE

STORAGE

MECH. RM

VEST.

4" U.G FIRE MAIN FROM RISER ROOM

(SEE CIVIL FOR SITE INFO)

10' - 9"

8' - 0"

8' - 0"

12' - 11"

8' - 0"

8' - 0"

11' - 5"

7' - 4"

7' - 10"

11' - 5"

8' - 0"

2' - 1"

2' - 1"

2' - 1"

2' - 7"

2' - 1"

FP501

FP501

48 49

305304

44 45

FP701

FP701

Occupancy Classification

Density

Total Hose Streams

Flowing Heads

K-Factor

Flow at Base of Riser

Pressure at Base of Riser

Safety Margin

Hydraulic Information

Remote Area Name

Comments:

Pressure at Source

Flow at Source

Remote Area Size

Head Coverage

NFPA 13 -

Light Hazard

0.10 GPM/SF

100.00 GPM

8 @ 16.80

5.213316

153.56 GPM

50.21 PSI

+25.46 (31.49%)

EXHIBIT - LH

RA REDUCTION PER 19.2.3.2.3.1.

(32%) DARCY-WEISBACH FOR

ANTI-FREEZE (TEMP = 0-F)

55.40 PSI

253.56 GPM

1024 SF

168 (MAX) SF

/2

/2

/2

/2

/2

/2

/2

3"

1 1/2"

1 1/2"

1 1/2"

/4

1 1/2"

1 1/2"

1"

1 1/2"

1 1/2"

/4

/4

/2

/2

7' - 10"

11' - 5"

PROVIDE DRAIN DISCHARGE FOR SECTION

OF TRAPPED WATER IN ADMIN WING,

ROUTE TO EXTERIOR WITH 45-DEG TURN

DOWN ELBOW.

EXHIBIT LH REMOTE AREA

1"

/4

3"

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

01/16/2026

326235

165639

REHABILITATE KAWUEECHE VISITOR CENTER

ROCKY MOUNTAIN NATION PARK

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

INTERFACE

ENGINEERING

PORTLAND, OR

1/ 7/

1:

:3

A

M A ut od es k

D oc s:

//2

4-

N P

S R

O M

O K aw un ee ch e V

C D

D -C

A w

O ta k/

N

P S

R O

M O

K A

W U

E E

C H

E V

IS

IT

O R

C E

N T

E R

_F

LS

_R

.r vt

FP402

CK

CK

KA

166 177

ENLARGED PLAN -

AUDITORIUM & EXHIBIT

- FIRE PROTECTION

40 84

SCALE OF FEET

SCALEFP402

1 ENLARGED PLAN - AUDITORIUM & EXHIBIT - FIRE PROTECTION

A

TRUE PLAN

1. CONCEALED COMBUSTIBLE SPACE LESS THAN

6" FROM TOP OF CEILING TO BOTTOM OF

STRUCTURE, NO SPRINKLERS PROVIDED

ABOVE FINISHED CEILING/DECK.

SHEET KEYNOTES

G

F

E

D

C

B

A

JANITOR

MECH. RM

WOMEN'S RR

MEN'S RR

4" U.G FIRE MAIN, SEE CIVIL FOR

SITE ROUTING AND CONNECTION

TO EXISTING MAIN

FP701

7' - 4"

7' - 0"

7' - 0"

FP501

2' - 6"

2 1/2"

/4

/4

/4

/4

/4

/4

/4

/4

/4

/2

1 1/4"

/4

/4

/4

INSTALL SPRINKLERS TIGHT

TO TEE ON BRANCH LINE, TYP.

DRY PENDENT SPRINKLERS

TYP.

FP403

REMOTE INSPECTOR'S TEST

PORT AND DRUM DRAIN.

1 1/4" 2' - 6"

B F

P

54405

404 4

DV

308 307

Occupancy Classification

Density

Total Hose Streams

Flowing Heads

K-Factor

Flow at Base of Riser

Pressure at Base of Riser

Safety Margin

Hydraulic Information