B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part3_0005.pdf

PDF 22 MB Posted

Attached to
ROMO 326235 Rehabilitate Kawuneeche Visitor Center
Solicitation number
140P2026R0057
Issued by

About this file

This document comprises architectural and engineering design drawings and schedules for the mechanical, plumbing, and electrical rehabilitation of the Kawuneeche Visitor Center at Rocky Mountain National Park, dated January 16, 2026.

The mechanical systems scope includes installation of gas furnaces (six units ranging from 39-120 MBH capacity), an air-handling unit with economizer mixing box, split-system air conditioning, exhaust fans, electric water heaters, and associated ductwork, piping, and controls. The plumbing scope encompasses new domestic water supply distribution, sanitary waste and vent lines, gas service extensions, and fixtures including water coolers, lavatories, sinks, floor drains, and water heaters across multiple building zones (Comfort Station, Admin Wing, Visitor Center, and Mechanical Rooms). The electrical scope requires three new 200-amp panelboards (L1A, L2A, L3A) with subfeeds from existing service; new branch circuitry for lighting, receptacles, and equipment; LED lighting fixtures with integral or remote emergency battery backup and dimming controls; wireless distributed lighting control system with networked head-end; lightning protection system with air terminals, downleads, and ground rods; and dedicated circuits for mechanical equipment. All work must comply with 2024 IBC/IEBC, 2023 NEC, 2024 IFC, and 2016 ASHRAE 90.1. Schedules detail equipment specifications including manufacturers, models, electrical ratings, and performance characteristics for all HVAC units, plumbing fixtures, and electrical devices. Detailed specifications reference Division 22-26 of the Construction Specifications Institute standards.

View the file

Other files

File Type Posted
B09_ROMO_KVC_326235_Final_CD_Specifications_Bid_Revisions_Part3_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part2_0005.pdf PDF
B09_QR_Tracker_ROMO_326235_9_4_26_0005.pdf PDF
Sol_140P2026R0057_Amd_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Specifications_Bid_Revisions_Part2_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part1_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Specifications_Bid_Revisions_Part1_0005.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_9_4_26_0005.pdf PDF
B09_ROMO_KVC_326235_Final_CD_Drawing_Set_Bid_Revisions_Part4_0005.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_8_26_0004.pdf PDF
Sol_140P2026R0057_Amd_0004.pdf PDF
BaselineScheduleReviewChecklist_Form_10-22-18_v508_0003.docx DOCX document
2nd_Site_Visit_Sign_in_Sheet_0003.pdf PDF
Sol_140P2026R0057_Amd_0003.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_8_21_0003.pdf PDF
B09_QR_Tracker_ROMO_326235_0003.pdf PDF
B08_Solit_PSP_Vol_II_Deliverables_LmtOnSubconRpt_REQD_0003.xlsx XLSX spreadsheet
Sol_140P2026R0057_Amd_0002.pdf PDF
B09_P2026R0057_SF30_QA_and_Clauses_8_19_0002.pdf PDF
B09_Attachment_5_Solit_PSP_Vol_I_Exp_REQD_0002.docx DOCX document
Contact_Procedures_Reminder_0002.docx DOCX document
B09_Attachment_6_Solit_PSP_Vol_I_PastPerf_REQD_0002.docx DOCX document
B09_QR_Tracker_ROMO_326235_0002.pdf PDF
B11_PreProposal_Conf_Slides_ROMO_325250_0001.pptx PPTX presentation
B09_Amendment_1_ROMO_KVC_326235_ContractPriceSchedule_Rev_1_8-5-26_0001.xlsx XLSX spreadsheet
B09_P2026R0057_SF30_QA_and_Clauses_8_13_0001.pdf PDF
Sol_140P2026R0057_Amd_0001.pdf PDF
B09_QR_Tracker_ROMO_326235_0001.pdf PDF
ROMO_326235__-_Virtual_PreBid_Conference_Transcription_0001.docx DOCX document
Prebid_sign_in_sheet_0001.pdf PDF
B09_Amendment_1_What_Evaluators_Will_Ask_for_Each_Factor_0001.docx DOCX document
Virtual_sign_in_sheet_0001.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part4.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part1.pdf PDF
B01_Attatchment_1_ROMO_KVC_326235_Final_CD_Specifications_update_Part1.pdf PDF
B08_Attachment_10_ROMO_KVC_326235_CD_ContractPriceSchedule_BLANK.xlsx XLSX spreadsheet
Sol_140P2026R0057.pdf PDF
B08_Attachment_8_Solit_PSP_Vol_II_GenRefs.pdf PDF
B08_Attachment_6_Solit_PSP_Vol_I_PastPerf_REQD.pdf PDF
B08_Attachment_7_Solit_PSP_Vol_II_BidBond.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part2.pdf PDF
B02_Attatchment_2_26_0330_-_ROMO_KVC_326235_Final_CD_Drawing_Set_Part3.pdf PDF
B01_Attatchment_1_ROMO_KVC_326235_Final_CD_Specifications_update_Part2.pdf PDF
B01_Attatchment_1_ROMO_KVC_326235_Final_CD_Specifications_update_Part3.pdf PDF
B08_Attachment_9_Solit_PSP_Vol_II_SubKPlan.pdf PDF
B08_Attachment_5_Solit_PSP_Vol_I_Exp_REQD.pdf PDF
B08_Attachment_3_Wage_Determination.pdf PDF
B08_Attachment_4_Construction_Contract_Administration.pdf PDF
B08_P2026R0057_SF1442_and_Clauses_7_30_26.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

L

M

10 11 12

(D) F-1

24"x96"

MECH. / ELEC.

(D) F-2 (D) F-3

(D) 24"x96" RETURN

AIR PLENUM

(D) COMBUSITION

AIR LOUVER

(D) 58"X12" RA UP

(D) 36"X12"

RA DN6

M300

L

M

10 11 12

MECH. / ELEC.

(D) 24"x96" RETURN

AIR PLENUM

(D) 58"X12" RA DN

136"x12"

58"x12"58"x12"

(D) 136"x12" FRESH

AIR INTAKE PLENUM

(D) 12"X20" RA

DROPS TO

FURNACES

(D) 12"x36" GRILLE

IN CEILING

(D) 24"x12" RA

M300

(D) 58"X12" RA DNEXTERIOR LOUVER TO

REMAIN AND RECEIVE

NEW DUCTWORK

CONNECTION

EXTERIOR LOUVER TO

REMAIN AND RECEIVE

NEW DUCTWORK

CONNECTION

H

MECH. RM

"x

"x

16"x14" 14"x16"

(D) EXISTING

SUPPLY AIR

DIFFUSER

(D) EXISTING

RETURN AIR

GRILLE

(D) EXISTING

SUPPLY AIR

DIFFUSER

(D) COMBUSTION

AIR PIPING

(D) F-4

(D) F-5

EXTERIOR LOUVER TO

REMAIN AND RECEIVE NEW

DUCTWORK CONNECTION

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: D

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

6:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

M400

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 99 177

MECHANICAL DEMO

ENLARGED PLANS

SCALE DM400

1 115 - MECH ROOM DEMO PLAN AT FLOOR

SCALE DM400

2 115 - MECH ROOM DEMO PLAN AT CEILING

TRUE PLAN

SCALE DM400

3 106 - MECH ROOM DEMOLITION PLAN

EXTERIOR LOUVER TO

REMAIN AND RECEIVE NEW

DUCTWORK CONNECTION

20 42

SCALE OF FEET

01/16/26

F

F F

F

F

L

M

10 11 12

MECH. / ELEC.

115 GF-1

GF-2

GF-3

M300

22.20

M300

135"x20" B/C

"x

B /C

"x

B /C

18"x18" B/C

"x

B /C

130"x12" B/C

"x

B /C

"x

B /C

"x

B /C

"x

B /C

"x

B /C

EWH-1

3/4"ø CD

1/2"ø CD

1/2"ø CD

23.35

AC-1

H

MECH. RM

GF-4

GF-5

6"x6" B

125 CFM

M300

14"x14" D

M300

12"x6" C

250 CFM

T

"x

"x

A /C

"x

A /C

"x

B /C

18"x18" B/C

8"x24" B/C

4" CONCENTRIC

VENT TERMINATION

UP THRU ROOF

12"x6" A/C

GF-5

23.37

CO₂

23.36

1"ø CD

D

MECH. RM

GF-6

23.28

12"x6"

200 CFM

23.41

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: D

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

M401

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 100 177

MECHANICAL

ENLARGED PLANS

SCALE DM401

1 115 - MECH/ELEC - MECHANICAL ENLARGED PLAN

SCALE DM401

2 106 - MECH. RM - MECHANICAL ENLARGED PLAN

# KEYNOTES:

22.20 ROUTE 3/4"CONDENSATE TO FLOOR DRAIN. TERMINATE

VIA AIRGAP AT (E) FLOOR DRAIN.

23.28 NEW FURNACE SHALL BE INSTALLED PER

MANUFACTURER INSTRUCTIONS. CONNECT TO EXISTING

SUPPLY AND RETURN AIR DUCTWORK.

23.35 INSTALL ACID NEUTRALIZATION KIT IN CONDENSATE

DRAIN LINE IN ACCESSIBLE LOCATION.

23.36 DISCHARGE CONDENSATE DRAIN TO GRADE. PIPING ON

BUILDING EXTERIOR SHALL BE HEAT TRACED. SEAL

PENETRATION ON BUILDING EXTERIOR TO MATCH

EXISTING CONDITIONS.

23.37 INSTALL 1/2" CONDENSATE DRAIN WITH ACID

NEUTRALIZATION KIT IN ACCESSIBLE LOCATION.

DISCHARGE TO GRADE AS SHOWN ON M401.

23.41 PROVIDE NEW 8" EXHAUST WALL CAP TO MATCH NEW

FASCIA.

TRUE PLAN

SCALE DM401

3 153 - MECH. RM ENLARGED PLAN

20 42

SEAL AIRTIGHT AROUND ENTIRE TAKE-OFF

AIR FLOW

W

PROVIDE MANUAL BALANCING DAMPER

1/4 OF DIMENSION

"W" OR 6 INCHES,

WHICHEVER IS

GREATER

SUPPLY GRILLE

EXPOSED PIPING

TO BE PAINTED

UNION

FURNACE

6" DIRT LEG

GAS COCK

PROVIDE WITH

BACKDRAFT DAMPER

MOUNT FAN IN CEILING

MOUNT FAN FROM

STRUCTURE ABOVE WITH

METAL STRAPS AND

VIBRATION ISOLATION

FLEXIBLE

CONNECTION

A

C

MINIMUM CONDENSATE PIPE SIZE

MIN. DRAIN SIZE

1"

AC TONS

6 TO 20

0 TO 5 3/4"

B

CLEAN-OUT

(LEFT OPEN)

CASING SLEEVE

UNION IF REQUIRED

FOR DISASSEMBLY

DRAIN PAN

CAPA = (SEE TABLE)

B = (1" FOR EACH 1" OF

MAXIMUM NEGATIVE

STATIC PRESSURE + 1"

C = HALF OF B

3/4" CONDENSATE

DRAIN LINE

FURNACE

ECONOMIZER

MIXING BOX

MOUNT EACH CORNER OF

AHU ON STILTS/UNISTRUT

WITH WAFFLE PADS.

ECONOMIZER MIXING BOX

SHALL BE INSIDE SUPPORTS

SUPPLY AIR DUCT

36" FOR FUTURE

INSTALLATION OF

EVAPORATOR COIL

FLEXIBLE CONNECTION

WITH COPPER JUMPER

VIBRATION ISOLATION WAFFLE PAD (TYP.)

2" DEEP AUXILIARY DRAIN PAN

RETURN

AIR DUCT

OUTDOOR

AIR DUCT

MANUAL

BALANCING

DAMPER

NOTE:

1. THIS DETAIL IS SHOWN AS A SCHEMATIC LAYOUT. SEE FLOOR

PLANS FOR DUCTWORK SIZES AND ROUTING.

3/4" CONDENSATE

DRAIN LINE

FURNACE

ECONOMIZER

MIXING BOX

MOUNT EACH CORNER OF

AHU ON STILTS/UNISTRUT

WITH WAFFLE PADS.

SUPPLY AIR DUCT

36" FOR FUTURE

INSTALLATION OF

EVAPORATOR COIL

FLEXIBLE CONNECTION

WITH COPPER JUMPER

VIBRATION ISOLATION WAFFLE PAD (TYP.)

RETURN

AIR DUCTOUTDOOR

AIR DUCT

MANUAL

BALANCING

DAMPER

NOTE:

1. THIS DETAIL IS SHOWN AS A SCHEMATIC LAYOUT. SEE FLOOR

PLANS FOR DUCTWORK SIZES AND ROUTING.

FINISHED FLOOR

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

M500

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 101 177

MECHANICAL DETAILS

NOT TO SCALEM500

1 45° DUCT TAKE-OFF DETAIL

NOT TO SCALEM500

2 GAS EQUIPMENT CONNECTION DETAIL

NOT TO SCALEM500

3 CEILING MOUNTED EXHAUST FAN DETAIL

NOT TO SCALEM500

4 AC UNIT DRAIN TRAP DETAIL

NOT TO SCALEM500

5 VERTICAL UPFLOW FURNACE DETAIL

SCALE AM500

6 VERTICAL DOWNFLOW FURNACE DETAIL

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

M600

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 102 177

MECHANICAL

SCHEDULES

GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE / SALIENT CHARACTERISTICS

GENERAL

NOTES

TAG

BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL SERVICE MATERIAL FACE SIZE FINISH

- - - SUPPLY - SEE DRAWINGS - 1,6

A TITUS 300FL SUPPLY ALUMINUM 14x6 PRIME FINISH TO BE FIELD PAINTED 2,3,5

B TITUS 300FL SUPPLY ALUMINUM 6x6 PRIME FINISH TO BE FIELD PAINTED 2,3,5

C TITUS 300FL SUPPLY ALUMINUM 12x6 PRIME FINISH TO BE FIELD PAINTED 2,3,5

D TITUS 350FL RETURN ALUMINUM SEE DRAWINGS PRIME FINISH TO BE FIELD PAINTED 3,5

E RECTORSEAL 375 SUPPLY STEEL SEE DRAWINGS STORM GRAY 4,5,6

F HART & COOLEY 420 SUPPLY STEEL SEE DRAWINGS GOLDEN SAND 4

G HART & COOLEY 406 SUPPLY STEEL SEE DRAWINGS WHITE 4,6

FAN SCHEDULE / SALIENT CHARACTERISTICS

GENERAL PERFORMANCE (@ 8,841FT) ELECTRICAL PHYSICAL

NOTESTAG BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

LOCATION TYPE AIRFLOW

[CFM]

ESP

[IN. W.C.]

SPEED

[RPM]

POWER

[W]

SOUND

[SONES]

VOLTAGE

[V]

PHASE MCA

[A]

MOCP

[A]

FLA

[A]

LENGTH

[IN.]

WIDTH

[IN.]

HEIGHT

[IN.]

WEIGHT

[LB]

CF-1 BIG ASS FANS HAIKU 101 - EXHIBIT CEILING 403 / 6062 - 174 2.4 / 15.9 - 115 1 - - - 60 60 12 18.5 4

EF-1 GREENHECK SP-A125 112 - RR CEILING 70 0.25 1100 15 1.2 115 1 0.2 15 0.18 11 13 9 17 1-3

EF-2 GREENHECK SP-A125 113 - RR CEILING 70 0.25 1100 15 1.2 115 1 0.2 15 0.18 11 13 9 17 1-3

SPLIT SYSTEMS SCHEDULE - OUTDOOR UNIT / SALIENT CHARACTERISTICS

GENERAL DX COOLING ELECTRICAL PHYSICAL

NOTESTAG BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

LOCATION REFRIGERANT TOTAL COOLING

[BTU/H]

SENSIBLE CAPACITY

[BTU/H]

OPERATING RANGE

[°F]

VOLTAGE

[V]

PHASE FREQ.

[Hz]

MCA

[A]

MOCP

[A]

LENGTH

[IN]

WIDTH

[IN]

HEIGHT

[IN]

WEIGHT

[LB]

CU-1 MITSUBISHI PUY-AH30 GRADE R454B 30,400 21,000 -40 - 115 208/230 1 60 22.0 37 37-13/32 14 37-1/8 155 1-8

SPLIT SYSTEMS SCHEDULE - INDOOR UNIT / SALIENT CHARACTERISTICS

GENERAL SUPPLY FAN DX COOLING EFFICIENCY PHYSICAL

NOTESTAG BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

LOCATION REFRIGERANT OUTDOOR

UNIT

AIRFLOW

[CFM]

OUTSIDE AIR

[CFM]

TOTAL COOLING

[BTU/H]

SENSIBLE CAPACITY

[BTU/H]

OPERATING RANGE

[°F]

SEER2 LENGTH

[IN]

WIDTH

[IN]

HEIGHT

[IN]

WEIGHT

[LB]

AC-1 MITSUBISHI PKA-AK30 019 - SERVER ROOM R454B CU-1 705 0 30,400 21,000 66 - 90 19.7 51-3/16 11-5/8 14-3/8 46 1-5

FURNACE SCHEDULE / SALIENT CHARACTERISTICS

GENERAL SUPPLY FAN GAS HEATING ELECTRICAL PHYSICAL

NOTES

TAG BASIS OF

DESIGN

MANUFACTURER

BASIS OF

DESIGN

MODEL

LOCATION SERVICE TYPE TOTAL

[CFM]

OA

[CFM]

ESP

[IN.

W.C.]

SPEED

[RPM]

POWER

[HP]

SIZE

[HP]

OAT DB

[°F]

EAT DB

[°F]

LAT DB

[°F]

INPUT @

SEA LEVEL

[MBH]

INPUT @

8841'

[MBH]

OUTPUT @

SEA LEVEL

[MBH]

OUTPUT

@ 8841'

[MBH]

TOTAL

CAPACITY

[MBH]

AFUE

VOLTAGE

[V]

PHASE FREQ.

[Hz]

MCA

[A]

MOCP

[A]

LENGTH

[IN]

WIDTH

[IN]

HEIGHT

[IN]

WEIGHT

[LB]

GF-1 TRANE S9X2C100D 115 - MECH/ELEC NORTH OFFICES DOWNFLOW 2150 115 0.5 1075 1 1 -17.7 63.4 93.4 65/100 46.8/72 63.1/96.8 45.4/69.7 69.7 95 120 1 60 14.1 15 28.75 21 34 145 1-8

GF-2 TRANE S9X2D120D 115 - MECH/ELEC EXHIBIT NO. 1 DOWNFLOW 2250 325 0.5 1075 1 1 -17.7 55.6 89.2 78/120 56.2/86.4 75.7/113.4 54.5/81.6 81.6 96 120 1 60 14.1 15 28.75 24.5 34 156 1-9

GF-3 TRANE S9X2C100D 115 - MECH/ELEC SOUTH OFFICES & CORRIDOR DOWNFLOW 1800 225 0.5 1075 1 1 -17.7 57.3 93.1 65/100 46.8/72 63.1/96.8 45.4/69.7 69.7 95 120 1 60 14.1 15 28.75 21 34 145 1-8

GF-4 TRANE S9X2C100U 106 - MECH RM. AUDITORIUM UPFLOW 1700 405 0.5 1075 1 1 -17.7 47.6 85.5 65/100 46.8/72 63.1/96.8 45.4/69.7 69.7 95 120 1 60 14.1 15 28.75 21 34 139 1-9

GF-5 TRANE S9X2B060U 106 - MECH RM. EXHIBIT NO. 2 UPFLOW 1000 180 0.5 1075 3/4 3/4 -17.7 52.6 91.5 39/60 28.1/43.2 37.8/58.3 27.2/42.0 42.0 96 120 1 60 10.3 15 28.75 17.5 34 122 1-9

GF-6 TRANE S9X2C100U 153 - MECH RM. COMFORT STATION UPFLOW 1200 300 0.5 1075 1 1 -17.7 46.6 100.4 65/100 46.8/72 63.1/96.8 45.4/69.7 69.7 96 120 1 60 13.3 15 28.75 21 34 145 1-8

NOTES

1. EXISTING TO REMAIN SUPPLY GRILLE. BALANCE TO CFM VALUE NOTED ON DRAWINGS.

2. OPPOSED BLADE DAMPER IN FACE OF GRILLE.

3. PROVIDE WITH GYPSUM BOARD MOUNTING FRAME FOR GYPSUM BOARD HARD LID CEILING/WALL - SEE PLAN.

4. PROVIDE WITH INTEGRAL BALANCING DAMPER.

5. BLADES PARALLEL WITH LONG DIMENSION.

6. PROVIDE WITH 1/4" WIRE MESH AT DUCT OPENING.

NOTES

1. PROVIDE WITH CONDENSATE PUMP.

• BASIS OF DESIGN MANUFACTURER: BLUE DIAMOND

2. POWERED BY OUTDOOR UNIT.

3. DISCONNECT BY DIVISION 26.

4. PROVIDE WITH WIRED THERMOSTAT.

5. ALL REFRIGERANT PIPING, INCLUDING VALVES, FITTINGS, AND CONNECTIONS, TO BE PROVIDED, SIZED, AND ROUTED PER MANUFACTURER'S RECOMMENDATIONS.

NOTES

1. PROVIDE WITH MANUFACTURER HAIL GUARDS.

2. PROVIDE 48" TALL FIELD FABRICATED OUTDOOR UNIT STAND.

3. PROVIDE WITH SINGLE POWER POINT CONNECTION

4. PROVIDE WITH FIELD-MOUNTED DISCONNECT BY E.C.

5. PROVIDE WITH LOW AMBIENT COOLING KIT OPERATION.

6. PROVIDE ALUMINUM JACKETING FOR ALL EXTERIOR REFRIGERANT PIPING.

7. PROVIDE WITH WIRED THERMOSTAT.

8. ALL REFRIGERANT PIPING, INCLUDING VALVES, FITTINGS, AND CONNECTIONS, TO BE PROVIDED, SIZED, AND ROUTED PER MANUFACTURER'S RECOMMENDATIONS.

NOTES

1. FAN SHALL BE INTERLOCKED WITH LIGHTS.

2. PROVIDE WITH BACKDRAFT DAMPER.

3. UNIT WEIGHT DOES NOT INCLUDE ACCESSORIES.

4. OIL RUBBED BRONZE AIRFOIL AND HARDWARE FINISH.

NOTES

1. TWO-STAGE HEATING. CAPACITY RATINGS ARE SHOWN AS "1ST STAGE/2ND STAGE".

2. PROVIDE WITH MERV 13 FILTER.

3. PROVIDE WITH 7-DAY PROGRAMMABLE THERMOSTAT. THERMOSTAT SHALL BE CAPABLE OF CONTROLLING GAS FURNACE HEATING AND FUTURE DIRECT EXPANSION COOLING.

4. PROVIDE WITH ECONOMIZER MIXING BOX WITH BOTTOM AND SIDE INLETS FOR RETURN AIR AND OUTSIDE AIR (OUTSIDE AIR DAMPER SHALL HAVE A LEAKAGE RATE 4 CFM/SQFT OR LESS @ 1 INCH PRESSURE).

• BASIS OF DESIGN MANUFACTURER: MICROMETL

5. PROVIDE WITH CONCENTRIC VENT KIT AND ROUTE UP THROUGH ROOF.

6. PROVIDE WITH ECONOMIZER FAULT DETECTION AND DIAGNOSTICS.

7. FILTER FRAME FOR 1" THROWAWAY FILTER IN RETURN AIR DUCT.

8. PROVIDE WITH CONDENSATE PUMP AND ACID NEUTRALIZATION KIT.

9. PROVIDE WITH CO2 SENSOR IN SPACE FOR DEMAND CONTROLLED VENTILATION. SEE FLOOR PLANS FOR SENSOR LOCATION. SEE SHEET M700 FOR DEMAND CONTROLLED VENTILATION SEQUENCE.

ELECTRIC HEATER SCHEDULE / SALIENT CHARACTERISTICS

GENERAL PERFORMANCE ELECTRICAL PHYSICAL

NOTESTAG BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

LOCATION TYPE/MOUNTING AIRFLOW

[CFM]

OUTPUT

[BTU/H]

POWER

[kW]

VOLTAGE

[V]

PHASE FREQ.

[Hz]

LENGTH

[IN]

WIDTH

[IN]

HEIGHT

[IN]

WEIGHT

[LB]

EWH-1 QMARK CWH3504F 115 - MECH/ELEC RECESSED WALL 100 16,378 4.8 240 1 60 5" 15 3/4" 19 5/16" 22 1,2,3,4

NOTES

1. PROVIDE WITH INTEGRAL THERMOSTAT.

2. PROVIDE WITH INTEGRAL ELECTRICAL DISCONNECT .

3. PROVIDE WITH MANUFACTURER'S MOUNTING BRACKET AND HARDWARE.

4. WHITE FINISH.

RELIEF HOOD SCHEDULE / SALIENT CHARACTERISTICS

GENERAL PERFORMANCE PHYSICAL

NOTESTAG MANUFACTURER MODEL LOCATION SERVICE AIRFLOW

[CFM]

FREE AREA

[SF]

FACE VELOCITY

[FPM]

PRESSURE DROP

[IN. W.C.]

LENGTH

[IN]

WIDTH

[IN]

HEIGHT

[IN]

WEIGHT

[LB]

RH-1 GREENHECK FGR-32x44 ROOF RELIEF 6,200 10 634 0.097 63 51 31 164 1,2

NOTES

1. PROVIDE WITH MANUFACTURER STANDARD ROOF CURB.

2. 46.5"x34.5" ROOF OPENING.

GENERAL NOTE:

BASIS OF DESIGN PRODUCTS LISTED IN THE

SCHEDULES ESTABLISH THE QUALITIES AND

CHARACTERISTICS FOR THE EVALUATION OF

PRODUCT SUBSTITUTIONS BY THE CONTRACTING

OFFICER. QUALITIES AND CHARACTERISTICS ARE

LISTED FOR THE BASIS OF DESIGN PRODUCT IN THE

SCHEDULES AND/OR THE PROJECT SPECIFICATIONS.

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

M700

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 103 177

MECHANICAL

CONTROLS

SEQUENCES

FURNACE CONTROL SEQUENCE:

OCCUPIED MODE:

THE GAS FURNACE SHALL BE CONTROLLED BY A 7-DAY PROGRAMMABLE THERMOSTAT. THE SUPPLY FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS. THE PROGRAMMABLE THERMOSTAT SHALL CYCLE ON THE GAS

HEAT EXCHANGER AS REQUIRED TO MAINTAIN HEATING SETPOINT (70°F - ADJUSTABLE).

WHEN THE SUPPLY FAN RUNS, THE OUTSIDE AIR DAMPER SHALL OPEN TO PROVIDE THE SCHEDULE OUTSIDE AIR

TO THE SPACE.

WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 70°F (ADJUSTABLE), THE ECONOMIZER MIXING BOX CONTROLLER SHALL MODULATE THE OA AUTOMATIC DAMPER OPEN AND THE RA AUTOMATIC DAMPER

OPEN/CLOSED AS REQUIRED TO MAINTAIN HEATING SETPOINT (70°F - ADJUSTABLE).

UNOCCUPIED MODE:

THE PROGRAMMABLE THERMOSTAT SHALL CYCLE ON THE SUPPLY FAN AND GAS HEAT EXCHANGER TO MAINTAIN THE UNOCCUPIED HEATING SETPOINT (55°F - ADJUSTABLE). THE OUTSIDE AIR DAMPERS SHALL REMAIN

CLOSED DURING UNOCCUPIED HOURS.

DEMAND CONTROLLED VENTILATION:

THE OUTSIDE AIR DAMPER SHALL BE CONTROLLED VIA THE ECONOMIZER/DCV CONTROL MODULE (BASIS OF

DESIGN - HONEYWELL JADE W7220).

WHEN SPACE CO2 SENSOR DETECTS CO2 LEVELS BELOW SETPOINT OF 1,100PPM (ADJUSTABLE), OUTSIDE AIR TO THE SPACE WILL BE AT THE VENTILATION MINIMUM SETPOINT (VENTMIN VALUE IN VENTILATION SETTINGS

TABLE BELOW).

WHEN SPACE CO2 SENSOR DETECTS CO2 LEVELS ABOVE SETPOINT OF 1,100PPM (ADJUSTABLE), OUTSIDE AIR TO THE SPACE WILL MODULATE UP TO THE VENTILATION MAXIMUM SETPOINT (VENTMAX VALUE IN VENTILATION

SETTINGS TABLE BELOW).

VENTILATION SETTINGS TABLE

EQUIP. TAG

GF-1

GF-2

GF-3

GF-4

GF-5

VENTMIN

[CFM]

VENTMAX

[CFM]

ECONOMIZER AND DEMAND CONTROL VENTILATION SEQUENCE OF OPERATION MATRIX

DCV

BELOW SETPOINT

ABOVE SETPOINT

OA GOOD TO

ECONOMIZE?

NO

YES

NO

YES

CALL FOR STAGE

1 HEATING

OFF

ON

ON

OFF

ON

ON

OFF

ON

ON

OFF

ON

ON

CALL FOR STAGE

2 HEATING

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

ON

HEATING STAGE

1 OUTPUT

OFF

ON

ON

OFF

ON

ON

OFF

ON

ON

OFF

ON

ON

HEATING STAGE

2 OUTPUT

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

ON

OCCUPIED

VENTMIN

VENTMIN

VENTMIN

VENTMIN

VENTMIN

TO FULL-OPEN

VENTMIN

TO FULL-OPEN

VENTMIN

TO VENTMAX

VENTMIN

TO VENTMAX

VENTMIN

TO VENTMAX

VENTMIN

TO VENTMAX

VENTMIN

TO FULL-OPEN

VENTMIN

TO FULL-OPEN

UNOCCUPIED

CLOSED

CLOSED

CLOSED

CLOSED

CLOSED TO

FULL-OPEN

CLOSED TO

FULL-OPEN

CLOSED

CLOSED

CLOSED

CLOSED

CLOSED TO

FULL-OPEN

CLOSED TO

FULL-OPEN

GF-1

GF-2

GF-3

GF-4

GF-5

GENERAL NOTES

A.

SYSTEM NOTES

Multi-Zone

Multi-Zone

Multi-Zone

Single Zone

Single Zone

As

(SQ. FT)

Ps

(People)

Ez

1.0

1.0

1.0

0.8

0.8

Vot

(CFM)

111.4

322.7

222.6

400.7

176.3

(CFM)

YES

YES

YES

YES

YES

NotesSystem Name and Number

ASHRAE 62.1 - 2019: Outside Air Calculations Summary

System

Type

System Floor Area

System Population

Average Air Distribution

Effectiveness

Outdoor Air Intake Flow (required by

62.1)

Outdoor Air Intake Flow

Provided (measured or design)

Outdoor air intake flow provided meets or exceeds

Vot?

MULTI-ZONE SYSTEM OUTSIDE AIR QUANTITY WAS CALCULATED USING THE SIMPLIFIED METHOD IN SECTION 6.4.2.3

THIS TABLE IS PROVIDED AS A CONDENSED SUMMARY OF THE CALCULATIONS FOR EACH SYSTEM. EACH SYSTEM'S OUTSIDE AIR QUANTITIES ARE CALCULATED USING THE VENTILATION RATE PROCEDURE OUTLINED IN SECTION 6.2 AND BASED ON THE SYSTEM TYPE

CLASSIFIED USING SECTIONS 6.2.2, 6.2.3, AND 6.2.4.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

/7

/2

:3 :0

P

M A u to d e sk

D o cs

-2

N

P S

R O

M O

K a w u n e e ch e V

C D

D -C

A w

O ta k/ R

O M

O K

V C

M e ch

-P lu m b .r vt

M800

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 104 177

MECHANICAL CALCS

AND COMCHECK

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

/7

/2

:3 :0

P

M A u to d e sk

D o cs

-2

N

P S

R O

M O

K a w u n e e ch e V

C D

D -C

A w

O ta k/ R

O M

O K

V C

M e ch

-P lu m b .r vt

M801

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 105 177

MECHANICAL CALCS

AND COMCHECK

PLUMBING ABBREVIATIONS

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

BLDG BUILDING

CA COMPRESSED AIR

CD CONDENSATE DRAIN

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CW COLD WATER

CWV COMBINATION WASTE AND VENT

Cx COMMISSIONING

(D) DEMOLISH

DIA DIAMETER

DFU DRAINAGE FIXTURE UNIT

(E) EXISTING

FD FLOOR DRAIN

FFA FROM FLOOR ABOVE

FFB FROM FLOOR BELOW

FPM FEET PER MINUTE

GPM GALLONS PER MINUTE

GW GREASE WASTE

GPM GALLON PER MINUTE

HW HOT WATER

HWC HOT WATER CIRCULATION

HT HEAT TRACE

ID INDIRECT DRAIN

I.D. INSIDE DIAMETER

LPG LIQUEFIED PETROLEUM GAS (PROPANE)

MAX MAXIMUM

MIN MINIMUM

(N) NEW

NG NATURAL GAS

NIC NOT IN CONTRACT

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

PSIA POUNDS PER SQUARE INCH (ABSOLUTE)

PSIG POUNDS PER SQUARE INCH (GAUGE)

(R) RELOCATED

RE:__ REFERENCE ____

REQ REQUIRED/REQUIREMENT

SF SQUARE FEET

STD STANDARD

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

V VENT

VTR VENT THRU ROOF

W WASTE

W.C. WATER COLUMN

WSFU WATER SUPPLY FIXTURE UNIT

PIPING SERVICES

NATURAL GAS

COLD WATER (CW)

HOT WATER (HW)

HOT WATER RECIRCULATION (HWC)

VENT (V)

WASTE ABOVE (W)

WASTE BELOW (W)

CONDENSATE ABOVE (CD)

GAS (G)

PLUMBING LEGEND

G

DRAWING NOTATION

NEW TO EXISTING

NEW WORK

EXISTING ITEMS

EXISTING ITEMS TO BE DEMOLISHED

PIPING SYSTEM COMPONENTS

ELBOW DOWN

ELBOW UP

TEE DOWN

TEE UP

CAP

UNION

FLEXIBLE CONNECTION

FLOOR DRAIN

FLOOR SINK

DRAIN VALVE

VENTURI TYPE

BALANCING VALVE

STRAINER

FLOW SENSOR

TEMPERATURE SENSOR

GRADE CLEAN OUT

FLOOR CLEAN OUT

WALL CLEAN OUT

AUTOMATIC AIR CENT

GAUGE

THERMOMETER

MANUAL AIR VENT

P&T TAP

IN LINE PUMP

METER

THERMOSTAT

PRESSURE SENSOR

T

P

S

FS

FCO

GCO

M

VALVES

GATE VALVE

BALL VALVE

PLUG VALVE

CHECK VALVE

2WAY ATC VALVE

3WAY ATC VALVE

PRESSURE REDUCING VALVE

SAFETY RELIEF VALVE

BACK FLOW PREVENTER

BALANCING VALVE

BUTTERFLY VALVE

THREE WAY CONTROL VALVE

PLUMBING NOTES

1. GENERAL

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS

SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION.

2. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY THE CONTRACTING OFFICER IF

ANY CONFLICTS OCCUR.

3. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT THE CONTRACTING OFFICER FOR RESOLUTION OF ANY DISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE SOLICITATION DATE. IN THE EVENT THAT AN INTERPRETATION OF SOLICITATION DOCUMENTS IS NECESSARY AFTER THE SOLICITATION DATE, THE DECISION OF THE CONTRACTING OFFICER SHALL BE FINAL AND BINDING.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COSTS OF ALL CHANGE ORDERS, WHICH THE CONTRACTING OFFICER HAS NOT APPROVED IN WRITING PRIOR TO THE EXECUTION OF THE ASSOCIATED

WORK.

5. IN THE CASE OF A CONFLICT, UNLESS OTHERWISE NOTED, KEYNOTES ON PLUMBING PLANS SHALL

SUPERCEDE ANY GENERAL NOTES ON THE PLANS.

6. ALL REMOVED EQUIPMENT SHALL REMAIN THE PROPERTY OF THE FEDERAL GOVERNMENT AND SHALL BE

STORED OR DISPOSED OF PER THE DIRECTION OF THE CONTRACTING OFFICER.

2. EXECUTION

1. ALL PLUMBING WORK SHALL COMPLY WITH LOCAL CODES AND ORDINANCES.

2. PITCH WASTE LINES NOT LESS THAN 1/4" PER FOOT. (UNLESS NOTED OTHERWISE).

3. RUN ALL PIPING ON WARM SIDE OF BUILDING INSULATION. PIPE INSULATION IS NOT CONSIDERED FREEZE

PROTECTION.

4. PROVIDE DIELECTRIC UNIONS AT CONNECTIONS BETWEEN DISSIMILAR METALS, I.E., IRON VALVES AND

COPPER TUBING.

5. PROVIDE PIPE HANGERS OF THE SAME MATERIAL AS THE PIPING SYSTEM OR USE COATED HANGERS.

6. SET FLOOR DRAINS SO THAT TOP WILL BE SLIGHTLY LOWER THAN SURROUNDING FLOOR.

7. PROVIDE BALL VALVES AND UNIONS ON ALL LINES TO EQUIPMENT FOR ISOLATION AND REMOVAL.

8. PLUMBING CONTRACTOR SHALL CHECK OPERATION AND CONDITION OF ALL EXISTING PLUMBING EQUIPMENT WITHIN THE CONFINES OF THIS SPACE, AND PREPARE A WRITTEN LIST OF DEFICIENCIES IN EQUIPMENT OPERATION OR CONDITION. LIST SHALL BE SUBMITTED TO THE CONTRACTING OFFICER WITHIN 2 WEEKS OF

CONTRACT AWARD DATE.

9. THE CONTRACTOR SHALL X-RAY THE FLOOR AND OBTAIN CONTRACTING OFFICER APPROVAL BEFORE

CUTTING ANY FLOOR PENETRATIONS.

10. WHERE REMOVAL OR RELOCATION OF EXISTING FIXTURES OCCURS, CONTRACTOR SHALL REMOVE ALL WASTE

AND VENT BRANCH LINES NOT REQUIRED FOR NEW, OR REMAINING FIXTURE LOCATIONS.

11. PROVIDE ADHESIVE, MULTICOLOR PIPE LABELS FOR ALL SYSTEMS. PROVIDE EVERY 50 FEET, AND EVERY 25

FEET IN CONGESTED AREAS.

12. CONTRACTOR SHALL FLUSH ALL FLOOR DRAINS PRIOR TO TURNING OVER BUILDING OCCUPANCY TO THE

PARK.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P000

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 106 177

PLUMBING LEGENDS

AND NOTES

PLUMBING SHEET LIST

NUMBER SHEET NAME

P000 PLUMBING LEGENDS AND NOTES

P101 OVERALL DEMO PLUMBING FLOOR PLAN

P111 OVERALL PLUMBING FLOOR PLAN - DOMESTIC & GAS

P121 OVERALL PLUMBING FLOOR PLAN - WASTE & VENT

P300 PLUMBING SECTIONS

P400 PLUMBING DEMO ENLARGED PLANS

P401 PLUMBING ENLARGED PLANS

P500 PLUMBING DETAILS

P600 PLUMBING SCHEDULES

P800 PLUMBING CALCS AND COMCHECK

P900 PLUMBING WASTE AND VENT ISOMETRICS

APPLICABLE CODES:

2024 INTERNATIONAL MECHANICAL CODE (IMC)

2024 INTERNATIONAL BUILDING CODE (IBC)

2024 INTERNATIONAL PLUMBING CODE (IPC)

2024 INTERNATIONAL FUEL GAS CODE (IFGC)

2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

2024 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

ASHRAE 90.1-2022

ASHRAE 90.1-2022

NPS SUSTAINABILITY GUIDELINES

J

L

K

2 3 4 5 76

M

8 9 10 11 12 13 14 15 16 17

H

G

F

E

D

C

B

A

BREAK ROOM

SERVER ROOM

MECH. / ELEC.

RR

RR

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HALL

OFFICE

CONFERENCE

STOR

WILDERNESS

DESK

EXHIBIT NO. 1

EXHIBIT NO. 2

AUDITORIUM

STORAGE

STORAGE

MECH. RM

VEST.

JANITOR

MECH. RM

WOMEN'S RR

MEN'S RR

JC

P400

P400

P400

P400

22.30

3/4"ø CW (E)

(E) HOSE BIBB

22.40

2"ø W (E)

1 1/2"ø CW (E)3/4"ø CW (E) 3/4"ø CW (E)

2"ø W (E)

4"ø W (E)

3/4"ø CW (E)

WASTE & VENTDOMESTIC & GAS

DOMESTIC & GAS WASTE & VENT

(E) HOSE BIBB

(E) WATER SERVICE

ENTRY TO ADMIN AREA

(E) GAS SERVICE UP

FROM BELOW GRADE

(E) GAS SERVICE DOWN

TO BELOW GRADE

(E) GAS SERVICE DOWN

TO BELOW GRADE

22.41

22.49

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P101

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 107 177

OVERALL DEMO

PLUMBING FLOOR

PLAN

GENERAL NOTES:

# KEYNOTES:

22.30 EXISTING WATER HEATER TO BE REMOVED. DISCONNECT

ELECTRICAL CONNECTIONS PRIOR TO REMOVAL.

DISCONNECT EXISTING HW AND CW CONNECTIONS AND

MAKE READY FOR CONNECTION TO NEW WATER HEATER.

SEE NEW WORK PLANS.

22.40 EXISTING GAS PIPING SHALL REMAIN. EXTEND EXISTING

GAS BRANCH PIPING AS NECESSARY TO CONNECT TO

NEW FURNACES.

22.41 EXISTING GAS METER SHALL REMAIN.

22.49 EXISTING GAS PIPING TO BE REMOVED IN MECHANICAL

ROOM. EXISTING BRANCH SHALL BE MADE READY FOR

RECONNECTION TO NEW PIPING.

SCALE AP101

1 OVERALL DEMO PLUMBING FLOOR PLAN

TRUE PLAN

1. SEE REFERENCED ENLARGED PLANS FOR

ADDITIONAL NOTES AND DETAILS IN VARIOUS

AREAS AS INDICATED.

80 168

ADO

A D

O A

D O

ADOADO

ADO ADO

J

L

K

2 3 4 5 76

M

8 9 10 11 12 13 14 15 16 17

H

G

F

E

D

C

B

A

BREAK ROOM

SERVER ROOM

MECH. / ELEC.

RR

RR

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HALL

OFFICE

CONFERENCE

STOR

WILDERNESS

DESK

EXHIBIT NO. 1

EXHIBIT NO. 2

AUDITORIUM

STORAGE

STORAGE

MECH. RM

VEST.

JANITOR

MECH. RM

WOMEN'S RR

MEN'S RR

JC

MAIL

3/4"ø CW (E)

3/4"ø CW (E)

3/4"ø CW (E)

3/4"ø CW (E) 3/4"ø CW

P401

P401

(E) HOSE BIBB (E) HOSE BIBB

EWH-2

KS-1A

22.10

22.41

22.42

22.42

EWC-1

3/4"ø CW

(E) WATER SERVICE

ENTRY BELOW GRADE

TO ADMIN AREA

(E) GAS SERVICE UP

FROM BELOW GRADE

(E) GAS SERVICE DOWN

TO BELOW GRADE

(E) GAS SERVICE DOWN

TO BELOW GRADE

3/4"ø CW

22.38

P401

P401

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P111

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 108 177

OVERALL PLUMBING

FLOOR PLAN -

DOMESTIC & GAS

# KEYNOTES:

22.10 ROUTE CW AND HW, AND EXTEND TO SERVE FIXTURES

SHOWN.

22.38 INSTALL PLUMBING EXPANSION TANK (PET-1) AS SHOWN

IN DETAIL 1/P500.

22.41 EXISTING GAS METER SHALL REMAIN.

22.42 EXTEND 3/4"G TO EACH FURNACE.

SCALE AP111

1 OVERALL PLUMBING FLOOR PLAN - DOMESTIC & GAS

TRUE PLAN

80 168

A D

O A

D O

ADOADO

ADO ADO

J

L

K

2 3 4 5 76

M

8 9 10 11 12 13 14 15 16 17

H

G

F

E

D

C

B

A

BREAK ROOM

SERVER ROOM

MECH. / ELEC.

115RR

113RR

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HALL

OFFICE

CONFERENCE

STOR

WILDERNESS

DESK

EXHIBIT NO. 1

EXHIBIT NO. 2

AUDITORIUM

STORAGE

STORAGE

MECH. RM

VEST.

JANITOR

MECH. RM

153WOMEN'S RR

MEN'S RR

JC

MAIL

4"ø W (E)

2"ø W (E)

2"ø W (E)

2"ø W (E)

P401

P401

KS-1A

22.44

EWC-1

1 1/2"ø V

2"ø W

RE: CIVIL FOR CONTINUATION

RE: CIVIL FOR CONTINUATION

22.50

22.51

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: A

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P121

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 109 177

OVERALL PLUMBING

FLOOR PLAN - WASTE

& VENT

# KEYNOTES:

22.44 ROUTE WASTE TO CONNECT TO EXISTING. ROUTE ABOVE

SLAB IN CABINETRY IF POSSIBLE. VENT PIPING SHALL

CONNECT TO EXISTING.

22.50 PROVIDE HUB DRAIN FOR WATER HEATER T&P RELIEF.

22.51 VENT THRU WALL AT THIS LOCATION WITH DOWNTURNED

90 DEG ELBOW. PAINTED TO MATCH BUILDING EXTERIOR.

TERMINATION SHALL BE COVERED WITH 1/2" WIRE MESH.

SCALE AP121

1 OVERALL PLUMBING FLOOR PLAN - WASTE & VENT

TRUE PLAN

80 168

FIRST FLOOR

100' - 0"

JC

1 1/2"ø CW (E)

1 1/2"ø CW

EWH-1

RP-1

MS-1

3"ø W

2"ø V

3/4"ø HW

1/2"ø CW

3/4"ø HW

3/4"ø CW (E)

FIRST FLOOR

100' - 0"

L

JC

1 1/2"ø CW (E)

1 1/2"ø CW

EWH-1

PRV-1

FIRST FLOOR

100' - 0"

C B

2"ø CW

2"CW TO COMFORT

STATION FIXTURES

2"ø CW

2"ø CW

1 1/2"ø CW

(E)1-1/2"CW TO ADMIN WING

RPBP-1

RPBP-22"ø CW

PRV-2

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: D

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P300

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 110 177

PLUMBING SECTIONS

SCALE DP300

1 JANITOR'S CLOSET WATER ENTRY - SECTION AA

SCALE DP300

2 JANITOR'S CLOSET WATER ENTRY - SECTION BB

SCALE DP300

3 COMFORT STATION WATER ENTRY - SECTION AA

20 42

D

C

B

JANITOR

MECH. RM

WOMEN'S RR

MEN'S RR

22.45

22.45

4"ø W (E)

2"ø W (E)

22.35

D

C

B

JANITOR

MECH. RM

WOMEN'S RR

MEN'S RR

22.29

22.29

22.31

22.31

22.3222.32

22.32

22.33

22.34

22.36

22.35

L

M

8 9

RR

RR

JC

22.30

22.29

22.32 22.32

22.33

22.29

L

M

8 9

RR

RR

JC

GCO

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: B

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P400

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 111 177

PLUMBING DEMO

ENLARGED PLANS

# KEYNOTES:

22.29 EXISTING LAVATORY TO BE REMOVED. DISCONNECT

EXISTING DOMESTIC WATER PIPING AND MAKE READY

FOR CONNECTION TO NEW FIXTURE. SEE NEW WORK

PLANS FOR DETAILS.

22.30 EXISTING WATER HEATER TO BE REMOVED. DISCONNECT

ELECTRICAL CONNECTIONS PRIOR TO REMOVAL.

DISCONNECT EXISTING HW AND CW CONNECTIONS AND

MAKE READY FOR CONNECTION TO NEW WATER HEATER.

SEE NEW WORK PLANS.

22.31 EXISTING DRINKING FOUNTAIN TO BE REMOVED. REMOVE

EXISTING DOMESTIC WATER, SANITARY, AND VENT PIPING

BACK TO THE MAIN.

22.32 EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT

EXISTING DOMESTIC WATER CONNECTIONS AND MAKE

READY FOR CONNECTION TO NEW FIXTURE. SEE NEW

WORK PLANS FOR DETAILS.

22.33 EXISTING URINAL TO BE REMOVED. DISCONNECT

EXISTING DOMESTIC WATER PIPING AND MAKE READY

FOR CONNECTION TO NEW FIXTURE. SEE NEW WORK

PLANS FOR DETAILS.

22.34 EXISTING WATER HEATER TO BE REMOVED. DISCONNECT

EXISTING DOMESTIC WATER AND GAS CONNECTIONS AND

MAKE READY FOR CONNECTION TO NEW WATER HEATER.

SEE NEW WORK PLANS FOR DETAILS.

22.35 EXISTING DRINKING FOUNTAIN TO BE REMOVED.

DOMESTIC WATER, SANITARY, AND VENT CONNECTIONS

SHALL BE MADE READY FOR RECONNECTION TO NEW

FIXTURE.

22.36 EXISTING WATER SERVICE ENTRY PIPING, VALVES, ETC.

TO BE REMOVED. SEE NEW WORK PLANS FOR NEW

CONFIGURATION OF WATER SERVICE ENTRY.

22.45 WASTE AND VENT PIPING TO LAVATORIES AND DRINKING

FOUNTAINS ARE SHOWN AS ASSUMPTIONS. CONTRACTOR

SHALL VERIFY ROUTING PRIOR TO BEGINNING WORK AND

NOTIFY CONTRACTING OFFICER OF ANY DISCREPANCIES.

NEW WORK PIPING SHALL FOLLOW A SIMILAR ROUTING TO

EXISTING

SCALE BP400

2 ENLARGED DEMO PLUMBING FLOOR PLAN - WASTE & VENT - COMFORT STATION

SCALE BP400

1 ENLARGED DEMO PLUMBING FLOOR PLAN - DOMESTIC & GAS - COMFORT STATION

SCALE BP400

3 ENLARGED DEMO PLUMBING FLOOR PLAN - DOMESTIC & GAS - ADMIN RESTROOMS

SCALE BP400

4 ENLARGED DEMO PLUMBING FLOOR PLAN - WASTE & VENT - ADMIN RESTROOMS

TRUE PLAN

40 84

ADOADO

ADO ADO

ADOADO

ADO ADO

D

C

B

GWH-1

MEN'S RR

JANITOR

1"ø CW (E)

3/4"ø HW (E)

3/4"ø HW

22.12

RP-2

P300

UR-1UR-1UR-1

L-1AL-1A

L-1A

L-1A L-1A L-1A

MS-1

WC-1AWC-1 WC-1 WC-1WC-1

WC-1

WC-1A

2"ø CW

RPBP-1

RPBP-2

22.42

22.38

3/4"ø G (E)

EWC-2

PRV-2

D

B

JANITOR

152MEN'S RR

WOMEN'S RR

MECH. RM

4"ø W (E)

2"ø W (E)

4"ø W (E)

22.24

L-1A L-1A

L-1A

L-1A

L-1AL-1A

P300

UR-1UR-1UR-1

1 1/2"ø V (E)

FS-1

4"ø W

MS-1

4"ø W

WC-1 WC-1WC-1WC-1 WC-1A

WC-1A WC-1

FD-1 FD-1

FD-1

FD-1

FCO

VENT THRU

WALL WITH

ELBOW IN

SOFFIT

22.48

22.48

L

M

8 9

P300

RR

RR

JC

L-1AL-1A

WC-1A WC-1A

3/4"ø CW (E)

3/4"ø CW (E)

1 1/2"ø CW (E)

P300

EWH-1

1"ø CW (E)

RP-1

MS-1

MS-1

22.38

PRV-1

L

M

8 9

WC-1A

L-1A L-1A

WC-1A

RR

RR

JC

FD-1FD-1

MS-1

4"ø W (E)

3"ø W

22.39

EXISTING GRADE CLEANOUT

22.46

L

M

10 11 12

MECH. / ELEC.

GF-1 GF-2 GF-3

2"ø G (E)

3/4"ø G 3/4"ø G

3/4"ø G

H

GF-5

GF-4

MECH. RM

1"ø G (E)

1"ø G

3/4"ø G

3/4"ø G

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

SCALE: B

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P401

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 112 177

PLUMBING ENLARGED

PLANS

SCALE BP401

1 ENLARGED PLUMBING FLOOR PLAN - DOMESTIC & GAS - COMFORT STATION

# KEYNOTES:

22.12 WATER PIPING CONTINUES TO SUPPLY. RE: CIVIL FOR

CONTINUATION.

22.24 WASTE PIPING TO DOWNSTREAM CONNECTION. RE: CIVIL

FOR CONTINUATION.

22.38 INSTALL PLUMBING EXPANSION TANK (PET-1) AS SHOWN

IN DETAIL 1/P500.

22.39 WATER HEATER P&T RELIEF AND DRAIN PAN DISCHARGE

SHALL BE ROUTED TO MOP SINK. SEE DETAIL 1/P500.

22.42 EXTEND 3/4"G TO EACH FURNACE.

22.46 3" VTR. UTILIZE EXISTING ROOF PENETRATION.

22.48 PROVIDE WALL CLEANOUT UNDER LAVATORY.

SCALE BP401

2 ENLARGED PLUMBING FLOOR PLAN - WASTE & VENT - COMFORT STATION

SCALE BP401

3 ENLARGED PLUMBING FLOOR PLAN - DOMESTIC & GAS - ADMIN RESTROOMS

SCALE BP401

4 ENLARGED PLUMBING FLOOR PLAN - WASTE & VENT - ADMIN RESTROOMS

TRUE PLANSCALE BP401

5 ENLARGED PLUMBING FLOOR PLAN - DOMESTIC & GAS - 115 MECH

SCALE BP401

6 ENLARGED PLUMBING FLOOR PLAN - DOMESTIC & GAS - 106 MECH

40 84

18 G A. G

ALVAN

IZED

D R

AIN

PAN

TO

BE A

M

IN

IM

U

M O

F 4" D

EEP

1-1/4" PAN

D

R

AIN

SEE PLAN

FO

R

ISC

H

AR

G

E LO

C

ATIO

N

HO

T W

ATER O

UT

SUSPEND P

AN F

RO

M

S

TRUCTURE

W

IT

H 1 /2

" T

HREADED R

O D

PRO

VID

E 3 /8

" N O

N-F

ERRO

US S

PACERS

BETW

EEN T

ANK A

ND P

AN

BALL V

ALVE (T

YP)

CO

LD W

ATER IN

1" A

IR

G

AP S

EPARATIO

N B

ETW

EEN T

/P O

UTLET A

ND P

AN

DIE

LECTRIC

U

NIO

NS

P&T R

ELIE

F V

ALVE S

PIL

L IN

TO

P

AN

W

ATER H

EATER

SEE P

LAN F

O R S

IZ

ES

SUPPO

RT T

HE W

ATER H

EATER A

IN

UM

UM

O F 1

" A

BO

VE T

HE B

O

TTO

O F T

HE P

AN U

SIN

G

A N

O N-

CO

M

BUSTIB

LE M

ATERIA

L

EXPANSIO

N T

ANK

CHECK V

ALVE (T

YP)

ANTI-S

IP

HO

N V

ACUUM

R

ELIE

F V

ALVE

HW

C R

ETURN

PRESSURE G

AUG

E

UNIO

N (T

YP)

THERM

O M

ETER

CIR

CUIT

S

ETTERY-S

TRAIN

ER

RECIR

CULATIO

N P

UM

P

1/2" TEMPERED WATER TO

FAUCET

1/2" CW SUPPLY W/

STOP VALVE1/2" HW SUPPLY W/

STOP VALVE

WASTE

FINISHED FLOOR

1/2" CW TO FAUCET

1/2" THERMOSTATIC

TEMPERING VALVE SET

AT 110° F

COUNTER

TAILPIECE

COUNTERTOP

FLOOR

SUPPLY STOP

HW HWC CW

CEILING

CIRCUIT SETTER

(0.5 GPM)

THERMOSTATIC

MIXING VALVE

(ASSE 1070)

TOTAL PIPE LENGTH BETWEEN HWC

CROSSOVER AND LAVATORY TO BE A

MAXIMUM OF 2 FEET PER IECC

BRASS CLEANOUT PLUG WITH

COUNTER SUNK HEAD & TRACTOR

GRATE COVER

FINISHED GRADE

16" SQUARE CONCRETE PAD, TROWEL

SMOOTH AND EDGE

1/8 CAST IRON BEND

CAST IRON WASTE LINE

1/8 BEND IF CLEANOUT OCCURS AT END OF LINE

WASTE LINE

STRAINER

BALL VALVE (TYP)

BALANCING VALVE

CHECK VALVE

PRESSURE GAUGE (TYP)

P & T PORT (TYP)

PIPE HANGERS - PROVIDE DOUBLE

DEFLECTION NEOPRENE FOR FIRST TWO ON EACH

SIDE OF PUMP (SEE NOTE NO. 1)

FLEXIBLE

CONNECTION

NOTES:

1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

FLOOR

HW TO FIXTURES

G

1" CW

PUMP

1"

THERMOMETER (TYP)

SEE PLAN FOR SIZE

CIRCUIT SETTER (TYP)

NEW 6" HOUSEKEEPING PAD

EXPANSION TANK

BALL VALVE (TYP)

DIELECTRIC FITTING

CHECK VALVE (TYP)

1/2"

HWC

1-1/4" PAN DRAIN. SEE PLAN FOR

DISCHARGE LOCATION

18 GAUGE GALVANIZED DRAIN PAN. TO BE

A MINIMUM OF 4" DEEP

ROUTE T&P RELIEF TO

DRAIN AND AIRGAP

GAS PIPE, SEE PLAN

FOR SIZE

GAS COCK

6" DIRT LEG

UNION (TYP)

18 G A. G

ALVANIZ

ED D

RAIN

P

AN T

O

B E A

IN

IM

UM

O F 4

" D

EEP

HO

T W

ATER O

UT

PRO

VID

E 3 /8

" N O

N-F

ERRO

US S

PACERS

BETW

EEN T

ANK A

ND P

AN

BALL V

ALVE (T

YP)

CO

LD W

ATER IN

DIE

LECTRIC

U

NIO

NS

P&T R

ELIE

F V

ALVE R

O

UTED T

O H

UB D

RAIN

W

ATER H

EATER

SEE P

LAN F

O R S

IZ

ES

EXPANSIO

N T

ANK

CHECK V

ALVE (T

YP)

ANTI-S

IP

HO

N V

ACUUM

R

ELIE

F V

ALVE

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P500

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 113 177

PLUMBING DETAILS

NOT TO SCALEP500

1 JANITOR CLOSET - ELECTRIC WATER HEATER DETAIL

NOT TO SCALEP500

5 LOCAL MIXING VALVE DETAIL

NOT TO SCALEP500

7 LAVATORY HOT WATER RECIRCULATION

NOT TO SCALEP500

4 GRADE CLEANOUT DETAIL

NOT TO SCALEP500

6 HORIZONTAL IN-LINE PUMP DETAIL

NOT TO SCALEP500

3 GAS WATER HEATER DETAIL

NOT TO SCALEP500

2 BREAK ROOM - ELECTRIC WATER HEATER DETAIL

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P600

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 114 177

PLUMBING

SCHEDULES

PLUMBING FIXTURE SCHEDULE / SALIENT CHARACTERISTICS

FIXTURE ACCESSORIES INFO

NOTES

TAG DESCRIPTION

BASIS OF DESIGN

MANUFACTURER

BASIS OF DESIGN

MODEL FINISH

BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL FINISH GPM/GPF ELECTRICAL

EWC-1 ABA - ELECTRIC WATER COOLER HI/LO BOTTLE FILLER HAWS 1119.14P STAINLESS STEEL - - - - 120V/1PH 1,2,3,4

EWC-2 ABA - FREEZE RESISTANT HI/LO DRINKING FOUNTAIN

AND BOTTLE FILLER

HAWS 1117P STAINLESS STEEL - - - - 120V/1PH 1,2,3,4

FD-1 FLOOR DRAIN JAY R SMITH 2005Y NICKEL BRONZE - - - - - 5,6,8

FS-1 FLOOR SINK JAY R SMITH 3410-Y WHITE - ACID RESISTANT - - - - - 5,6,7,8

L-1A ABA - WALL MOUNTED LAVATORY AMERICAN STANDARD 0355.012 VITREOUS CHINA - WHITE AMERICAN

STANDARD

1340.227 CHROME 0.5 GPM - 9,10,11,12,13

MS-1 MOP SINK BASIN FIAT MSB2424 WHITE CHICAGO 445-897SRXKCCP CHROME 2.2 GPM - 14

RPBP-1 REDUCED PRESSURE BACKFLOW PREVENTER WATTS 009 BRONZE - - - - - 15

RPBP-2 REDUCED PRESSURE BACKFLOW PREVENTER WATTS 009 BRONZE - - - - - 15

S-1A ABA - SINGLE COMPARTMENT KITCHEN SINK AMERICAN STANDARD 20SB STAINLESS STEEL DELTA 9959-LS-DST CHROME 1.8 GPM - 16,17,18,19

UR-1 FLUSH VALVE URINAL AMERICAN STANDARD 6590.001 VITREOUS CHINA - WHITE AMERICAN

STANDARD

6063.013.002 CHROME 0.125 GPF - 20,21

WC-1 FLOOR MOUNTED FLUSH VALVE WATER CLOSET AMERICAN STANDARD 2234.001 VITREOUS CHINA - WHITE AMERICAN

STANDARD

6065.121.002 CHROME 1.28 GPF - 22,23,24

WC-1A ABA - FLOOR MOUNTED FLUSH VALVE WATER CLOSET AMERICAN STANDARD 3043.001 VITREOUS CHINA - WHITE AMERICAN

STANDARD

6065.121.002 CHROME 1.28 GPF - 22,23,24,25

PLUMBING FIXTURE CONNECTION SCHEDULE

GENERAL

NOTESTAG CW

[IN.]

HW

[IN.]

HWC

[IN.]

WASTE

[IN.]

VENT

[IN.]

EWC-1 1/2" - - 2" 1-1/2" -

EWC-2 1/2" - - 2" 1-1/2" -

FD-1 - - - SEE DWGS SEE DWGS -

FS-1 - - - SEE DWGS SEE DWGS -

L-1A 1/2" 1/2" 1/2" 1-1/2" 1-1/4" 1

MS-1 3/4" 3/4" 1/2" 3" 2" -

RPBP-1 2" - - - - -

RPBP-2 1-1/2" - - - - -

S-1A 1/2" 1/2" 1/2" 1-1/2" 1-1/4" -

UR-1 3/4" - - 2" 2" -

WC-1 1" - - 4" 2" -

WC-1A 1" - - 4" 2" -

GAS/ELECTRIC WATER HEATER SCHEDULE / SALIENT CHARACTERISTICS

GENERAL HEATING PHYSICAL ELECTRICAL

NOTESTAG BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

INPUT @ SEA LEVEL

[BTU/H]

POWER

[kW]

RECOVERY

AT 90°F RISE

CAPACITY

[GAL]

HEIGHT

[IN]

DIAMETER

[IN.]

WEIGHT

[LB]

VOLTAGE

[V]

PHASE

EWH-1 AO SMITH DEL-20 - 2.5 11 20 22.25 21.75 73 240 1 1-2

EWH-2 AO SMITH DEL-10 - 2.5 11 10 18.25 18 54 240 1 1-2

GWH-1 AO SMITH BTX-80 76,000 - 95 50 71 27 225 120 1 3-6

PUMP SCHEDULE / SALIENT CHARACTERISTICS

GENERAL PERFORMANCE ELECTRICAL

NOTESTAG BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

SYSTEM FLOW

[GPM]

HEAD

[FT]

POWER

[W]

RP-1 BELL & GOSSETT ECOCIRC+ 20-18 HOT WATER

CIRCULATION

1.5 15 70 1-2

RP-2 BELL & GOSSETT ECOCIRC+ 20-18 HOT WATER

CIRCULATION

3.5 15 70 1-2

NOTES

LAVATORIES

1. CONNECT HOT WATER RECIRCULATION TO HOT WATER LINE PER

2024 IECC TABLE C404.5.1.

NOTES

ELECTRIC WATER HEATER

1. PROVIDE WITH MAGNESIUM ANODE ROD

2. PROVIDE WITH EXPANSION TANK (PET-1)

GAS WATER HEATER

3. 3.5-14" W.C. GAS

4. PROVIDE WITH ACID NEUTRALIZATION KIT

5. 4" PVC INTAKE AND 4" VENT PER MANUFACTURER' RECOMMENDATIONS

6. PROVIDE WITH EXPANSION TANK (PET-1)

NOTES

DRINKING FOUNTAINS AND ELECTRIC WATER COOLERS

1. PROVIDE WITH CONCEALED FLOOR MOUNTED CARRIER (COORDINATE WITH WALL THICKNESS).

2. 17 GA. P-TRAP, LOOSE KEY ANGLE STOPS, STAINLESS STEEL BRAIDED SUPPLIES.

3. VANDAL PROOF.

4. PROVIDE WITH CANE DETECTION APRON TO BOTTOM OF HIGH FOUNTAIN.

FLOOR DRAINS AND SINKS

5. PROVIDE WITH TRAP GUARD.

6. MOUNT FLUSH WITH FLOOR.

7. 1/2 GRATE, DOME STRAINER.

8. BODY/CONNECTION MATERIAL TO MATCH WASTE PIPING.

LAVATORIES

9. 17 GA. P-TRAP, LOOSE KEY ANGLE STOPS, STAINLESS STEEL BRAIDED SUPPLIES.

10. PROVIDE MIXING VALVE UNDER FIXTURE. ASSE 1070 RATED.

• MANUFACTURER/MODEL BASIS OF DESIGN: LEONARD #270-LF

11. PROVIDE WITH P-TRAP AND SUPPLIES INSULATION KIT.

• MANUFACTURER/MODEL BASIS OF DESIGN: TRUEBRO #103 E-Z

12. PROVIDE WITH CONCEALED FLOOR MOUNTED CARRIER (COORDINATE WITH WALL THICKNESS).

13. SEE ARCHITECTURAL PLANS FOR MOUNTING HEIGHT.

MOP SERVICE BASIN

14. PROVIDE WITH HOSE AND HOSE BRACKET, MOP HANGER, SS WALL GUARD.

REDUCED PRESSURE BACKFLOW PREVENTER

15. PROVIDE WITH STRAINER.

NOTES

SINKS

16. 17 GA. P-TRAP, LOOSE KEY ANGLE STOPS, STAINLESS STEEL BRAIDED SUPPLIES.

17. PROVIDE MIXING VALVE UNDER FIXTURE. ASSE 1070 RATED.

• MANUFACTURER/MODEL BASIS OF DESIGN: LEONARD #270-LF

18. PROVIDE WITH P-TRAP AND SUPPLIES INSULATION KIT.

• MANUFACTURER/MODEL BASIS OF DESIGN: TRUEBRO #103 E-Z

19. 6" DEEP BOWL, REAR DRAIN LOCATION.

URINALS

20. PROVIDE WITH CONCEALED FLOOR MOUNTED CARRIER (COORDINATE WITH WALL THICKNESS).

21. SEE ARCHITECTURAL PLANS FOR MOUNTING HEIGHT.

WATER CLOSETS

22. LOOSE KEY ANGLE STOP, STAINLESS STEEL BRAIDED SUPPLIES.

23. FLUSHOMETER WATER CLOSET.

24. FLOOR MOUNTED WATER CLOSET WITH BOTTOM OUTLET.

25. PROVIDE FLUSH VALVE HANDLE ON OPEN SIDE OF FIXTURE AWAY FROM WALL FOR ABAAS

ACCESS.

NOTES

RECIRCULATION PUMP

1. LEAD FREE BRONZE

2. PROVIDE WITH AQUASTAT AND TIMECLOCK TO RUN DURING OCCUPIED HOURS

PLUMBING MISCELLANEOUS SCHEDULE / SALIENT CHARACTERISTICS

GENERAL

NOTES

TAG DESCRIPTION MANUFACTURER MODEL

PET-1 PLUMBING EXPANSION TANK ARMSTRONG AST-12 1

PRV-1 PRESSURE REDUCING VALVE WATTS LF25AUB-Z3 2

PRV-2 PRESSURE REDUCING VALVE WATTS LF25AUB-Z3 3

NOTES

PLUMBING EXPANSION TANKS

1. 3.3 GALLONS ACCEPTANCE VOLUME

PRESSURE REDUCING VALVES

2. 1-1/2" CONNECTION SIZE

3. 2" CONNECTION SIZE

GENERAL NOTE:

BASIS OF DESIGN PRODUCTS LISTED IN THE

SCHEDULES ESTABLISH THE QUALITIES AND

CHARACTERISTICS FOR THE EVALUATION OF

PRODUCT SUBSTITUTIONS BY THE CONTRACTING

OFFICER. QUALITIES AND CHARACTERISTICS ARE

LISTED FOR THE BASIS OF DESIGN PRODUCT IN THE

SCHEDULES AND/OR THE PROJECT SPECIFICATIONS.

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P800

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 115 177

PLUMBING CALCS AND

COMCHECK

COMFORT STATION

SANITARY DRAINAGE FIXTURE UNIT CALCULATION

(CALCULATIONS BASED ON IPC TABLE 709.1)

FIXTURE

WATER CLOSET, FLUSH VALVE

URINAL, FLUSH VALVE

LAVATORY

MOP SERVICE BASIN

DRINKING FOUNTAIN

FLOOR DRAIN

TOTAL

EXISTING 4" WASTE MAIN CAN ACCEPT A 180 DFU CAPACITY AT 1/8" PER FOOT SLOPE

NUMBER OF

INSTANCES

DFU UNITS

TOTAL LOAD

1.5

61.5

VISITOR CENTER + ADMIN WING

SANITARY DRAINAGE FIXTURE UNIT CALCULATION

(CALCULATIONS BASED ON IPC TABLE 709.1)

FIXTURE

WATER CLOSET, FLUSH VALVE

LAVATORY

SINK

MOP SERVICE BASIN

FLOOR DRAIN

TOTAL

EXISTING 4" WASTE MAIN CAN ACCEPT A 180 DFU CAPACITY AT 1/8" PER FOOT SLOPE

NUMBER OF

INSTANCES

DFU UNITS

TOTAL LOAD

COMFORT STATION

WATER SUPPLY FIXTURE UNIT CALCULATION (CALCULATIONS BASED ON IPC TABLE E103.3(2))

FIXTURE

WATER CLOSET (VALVE)

URINAL

LAVATORY

MOP SINK BASIN

DRINKING FOUNTAIN

HOSE BIB

TOTAL

117 WSFU TOTAL -> 72 GPM. THE NEW SERVICE IS 2" AND CAN HANDLE A MAXIMUM FLOW RATE OF 85 GPM.

NUMBER OF

INSTANCES

COLD (WSFU)

1.5

0.25

HOT (WSFU)

1.5

TOTAL LOAD (WSFU)

0.25

TOTAL LOAD (WSFU)

0.75

VISITOR CENTER + ADMIN WING

WATER SUPPLY FIXTURE UNIT CALCULATION (CALCULATIONS BASED ON IPC TABLE E103.3(2))

FIXTURE

WATER CLOSET (VALVE)

LAVATORY

KITCHEN SINK

MOP SINK BASIN

HOSE BIB

TOTAL

47 WSFU TOTAL -> 49 GPM. THE EXISTING SERVICE IS 1-1/2" AND CAN HANDLE A MAXIMUM FLOW RATE OF 50 GPM.

NUMBER OF

INSTANCES

COLD (WSFU)

1.5

HOT (WSFU)

1.5

TOTAL LOAD (WSFU)

TOTAL LOAD (WSFU)

GAS CALCULATIONS (LINE SIZING PER IFGC TABLE 402.4(2))

NEW GAS LINE CONNECTED LOAD

EQUIPMENT

(N) GWH-1

(N) GF-1

(N) GF-2

(N) GF-3

(N) GF-4

(N) GF-5

(N) GF-6

TOTAL LOAD (MBH)

TOTAL LOAD (CFH)

TOTAL EQUIVALENT LENGTH (FT)

SYSTEM DESIGN PRESSURE (PSI)

SYSTEM DESIGN PRESSURE DROP (IN. W.C.)

820 CFH WITH THE ABOVE DESIGN VARIABLES EQUALS A 2" GAS MAIN.

INPUT EACH AT SEA LEVEL (MBH)

INPUT EACH AT ALT (CFH)

LESS THAN 2

0.5

L-1A

L-1A L-1A

L-1A

L-1A

L-1A

1 1/4"ø W

2"ø W

1 1/4"ø W

1 1/4"ø W

2"ø W

1 1/2"ø V (E)

4"ø W (E)

2"ø W (E)

4"ø W

4"ø W

FS-1

MS-1

4"ø W

UR-1

UR-1

UR-1

WC-1

WC-1A

WC-1A

WC-1

WC-1

WC-1

WC-1

2"ø V

2"ø V

2"ø V

2"ø V

2"ø V

2"ø V

2"ø V

1 1/4"ø W 1 1/4"ø W

1 1/4"ø W

2"ø W

4"ø W

RE: P121 FOR CONTINUATION OF EXISTING.

3" VENT THRU WALL

WITH ELBOW IN

SOFFIT

EWC-2

FD-1

FD-1

FD-1

FD-1

FCO

(E)GCO

COMBO WASTE/VENT

2"ø V

2"ø W

1 1/4"ø V

2"ø V

WC-1A

WC-1A

L-1A

L-1AFD-1

FD-1

4"ø W (E)

2"ø W

3"ø V (E)

2"ø V (E)

3"ø W (E)

4"ø W (E)

3" VTR. TRANSITION FROM 2"V TO

3"V 18" BELOW ROOF PENETRATION.

MS-1

2"ø V

2"ø V

2"ø V

2"ø V

SEE P121 FOR

CONTINUATION

(E) FCO

EWC-1

2"ø W

1 1/2"ø V

RE: P121 FOR CONTINUATION

RE: P121 FOR CONTINUATION

KS-1A

2"ø W

1 1/2"ø V

EWH-2

2"ø W (E)

1 1/2"ø V (E)

RE: P121 FOR

CONTINUATION

RE: P121 FOR

CONTINUATION

HUB DRAIN FOR

WATER HEATER

T&P RELIEF

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

360 ENGINEERING,

INC.

GOLDEN, CO

1/ 7/

:3

7:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

R O

M O

K V

C M ec h-

P lu m b.

rv t

P900

JEG/MM

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

JEG/MM

SJR/DMD

01/16/2026 116 177

PLUMBING WASTE

AND VENT

ISOMETRICS

NOT TO SCALEP900

1 WASTE & VENT ISO - COMFORT STATION

NOT TO SCALEP900

2 WASTE & VENT ISO - ADMIN RESTROOMS

NOT TO SCALEP900

3 WASTE & VENT ISO - EXHIBIT ELECTRIC WATER COOLER

NOT TO SCALEP900

4 WASTE & VENT ISO - BREAK ROOM SINK

ELECTRICAL DEMOLITION REQUIREMENTS

THE BASIS OF THESE DRAWINGS WERE SITE OBSERVATIONS, ORIGINAL BUILDING DRAWINGS AND

VARIOUS OTHER SOURCES. EVERY ATTEMPT HAS BEEN MADE TO DOCUMENT THE ACTUAL

CONDITIONS. HOWEVER, THE CONTRACTOR SHALL CAREFULLY EXAMINE THE CONTRACT

DOCUMENTS AND THOROUGHLY BECOME FAMILIAR WITH THE BUILDING/NPS STANDARDS RELATING TO THE WORK. FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR OF THE OBLIGATIONS OF

THE CONTRACT.

THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF ANY MATERIALS OR APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES, RULES

OR REGULATIONS OF AUTHORITIES HAVING JURISDICTION.

THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN THEIR COST THE REMOVAL OF ALL EXISTING

ELECTRICAL DEVICES, CONDUITS, FIXTURES AND EQUIPMENT. DISCARD ALL EQUIPMENT AS

REQUIRED, UNLESS NOTED OTHERWISE.

EXISTING DEVICES NOT NOTED AS EXISTING (E) OR INDICATED ON PLANS SHALL REMAIN, AS THEY PRESENTLY EXIST. FOR DEMOLISHED DEVICES IN WALLS WHICH ARE TO REMAIN, THE ELECTRICAL CONTRACTOR SHALL INSTALL A BLANK FACE PLATE ON THE BACKBOX. FOR DEMOLISHED DEVICES INSTALLED IN THE FLOOR, THE ELECTRICAL CONTRACTOR SHALL CUT THE FLOOR BOX FLUSH WITH

THE FLOOR AND FILL WITH CONCRETE; COORDINATE WITH THE CONTRACTING OFFICER.

THE DEMOLITION OF SOME DEVICES MAY INTERRUPT POWER TO DEVICES DOWN STREAM. THE

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REWORKING THESE CIRCUITS TO MAINTAIN POWER

TO THE DOWN STREAM DEVICES WHICH WILL REMAIN.

ALL UNENERGIZED/DEMOLISHED CIRCUITRY SHALL HAVE THE CONDUCTORS REMOVED FROM THE

CONDUIT AND THE CONDUIT SHALL BE MARKED "EMPTY" WITH INDELIBLE MARKER.

HISTORIC MATERICAL CONSIDERATIONS

WOOD SLAT CEILING IN EXHIBIT HALL AREA IS A HISTORIC FABRIC AND SHALL NOT BE

CUT/DRILLED/PENETRATED UNDER ANY CIRCUMSTANCES WITHOUT SPECIFIC APPROVAL AND COORDINATION WITH THE CONTRACTING OFFICER. EVERY EFFORT HAS BEEN MADE TO ENSURE THAT SPECIFIC LOCATIONS REQUIRING NEW OPENINGS ARE IDENTIFIED SPECIFICALLY. PHASING OF INSTALLATION OF EQUIPMENT SHALL BE COORDINATED WITH RE-INSTALLATION OF THE HISTORIC MATERIALS TO AVOID UNNECESSARY OPENINGS

OR DAMAGE ASSOCIATED WITH THE CONSTRUCTABILITY OF THE SCOPE OF WORK.

ELECTRICAL GENERAL NOTES

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OF

AE FIRM

PRIME:

OTAK, INC.

REDMOND, WA

SUBCONTRACTOR:

AE DESIGN

DENVER, CO

1/ 8/

:5

8:

P M

A ut od es k D oc s:

//2

4-

N

P S

R O

M O

K aw un ee ch e

V C

D D

-C A w O ta k/

N P

S R

O M

O K

A W

U E

E C

H E

V

IS

IT

O

R C

E N

T E

R

E

LE

C T

R

IC

A L.

rv t

E000

AE DESIGN

REHABILITATE KAWUNEECHE VISITOR CENTER

ROCKY MOUNTAIN NATIONAL PARK

165639

326235

TW/RS/BJLV

JM/JEB/MS

01/16/2026 117 177

ELECTRICAL COVER

SHEET

1. THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL NECESSARY FOR A

COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM.

2. MATERIALS AND INSTALLATION SHALL COMPLY WITH CODES, LAWS AND ORDINANCES OF

FEDERAL, STATE AND LOCAL GOVERNING BODIES HAVING JURISDICTION. CODES FOR THIS

SCOPE OF WORK INCLUDE THE 2024 IBC AND IEBC, 2024 IECC, 2023 NEC, 2024 IFC, AND 2016

ASHRAE 90.1.

3. MATERIALS AND EQUIPMENT SHALL BE LISTED AND/OR LABELED BY U.L., ETL, CSA OR

ANOTHER RECOGNIZED TESTING LAB.

4. ALL WORK REQUIRED FOR THE INSTALLATION AS SHOWN ON DRAWINGS INCLUDING

LABOR, EQUIPMENT AND MATERIALS SHALL BE IN STRICT COMPLIANCE WITH THE BUILDING

STANDARDS, EXCEPT AS NOTED OTHERWISE.

5. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES,

TAXES AND LICENSES NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF

THE ELECTRICAL WORK.

6. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO GOVERNMENTAL AGENCIES AND

UTILITY COMPANIES SHOP DRAWINGS, WHICH ARE REQUIRED BY THESE AGENCIES, FOR

THEIR APPROVAL.

7. FOR ALL JOBS THAT INCLUDE DEMOLITION WORK BY THE ELECTRICAL CONTRACTOR,

DURING AND AFTER DEMOLITION, EC SHALL MAINTAIN CIRCUIT CONTINUITY TO ALL

EXISTING DEVICES THAT ARE TO REMAIN. EC SHALL REMOVE, RELOCATE, AND/OR

REWORK ANY CONDUIT AND WIRING TO FACILITATE THE NEW CONSTRUCTION SCOPE OF

WORK. FOR ALL LUMINAIRES THAT ARE EXISTING TO REMAIN OR EXISTING TO BE

RELOCATED, EC SHALL CLEAN LENSES AND REPLACE ALL EXTINGUISHED LAMPS, UON.

8. ALL MATERIALS, AND EQUIPMENT SHALL BE ERECTED, INSTALLED, CONNECTED, CLEANED,

ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE

MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS.

9. ALL CUTTING, DRILLING AND PATCHING OF MASONRY, STEEL OR IRON WORK BELONGING

TO THE BUILDING MUST BE DONE BY THIS CONTRACTOR IN ORDER THAT HIS WORK MAY BE

PROPERLY INSTALLED, BUT UNDER NO CONDITIONS MAY STRUCTURAL MEMBERS BE CUT,

EXCEPT AT THE DIRECTION OF THE CONTRACTING OFFICER.

10. ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW, UNLESS SPECIFICALLY

INDICATED AS EXISTING TO BE REUSED.

11. THE CONTRACTOR SHALL PROVIDE NEW TYPE WRITTEN PANEL DIRECTORIES FOR ALL NEW

PANELS. PANELBOARD SHALL BE MARKED WHERE THE SOURCE OF POWER SUPPLY

ORIGINATES.

12. DO NOT SHARE NEUTRAL CONDUCTORS FOR MULTIWIRE BRANCH CIRCUITS. WHERE THE

E.C. PROPOSES THE USE OF SHARED NEUTRAL CONDUCTORS OR SHARED NEUTRAL

CONDUCTORS ARE REQUIRED (SUCH AS POWERED FURNITURE SYSTEMS), HANDLE TIES

SHALL BE PROVIDED ON THE CIRCUIT BREAKERS, WITH SHARED NEUTRALS, SUCH THAT IT

WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS. ALL HANDLE TIES

ARE REQUIRED TO BE INDICATED ON THE PANELBOARD SHOP DRAWINGS.

13. SHOULD ACTUAL FIELD CONDITIONS REQUIRE INDICATED CIRCUIT DESIGNATIONS TO VARY, INDICATE THE CIRCUIT NUMBER USED ON THE "AS-BUILT" DRAWINGS.

14. ALL SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD BY THE ELECTRICAL

CONTRACTOR WITH THE MAXIMUM AVAILABLE FAULT CURRENT AS INDICATED WITHIN

THESE DOCUMENTS. THE FIELD MARKING(S) SHALL COMPLY WITH…