B-34 Electrical.pdf

PDF 10 MB Posted

Attached to
Renovate Building #34 to Correct FCA Deficiencies
Solicitation number
36C24921R0010
Issued by

About this file

This document outlines a federal contract opportunity from the Department of Veterans Affairs to renovate Building 34. The solicitation number is 36C24921R0010 and seeks to correct deficiencies identified in the Federal Capital Assets report. The opportunity type is a solicitation to renovate Building 34 and address outstanding issues noted in the assessment of federal capital assets for the building. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9. The document provides relevant details about the federal agency involved, purpose and location of the renovations, and solicitation number for interested parties to respond to the contract opportunity.

View the file

Other files

File Type Posted
36C24921R0010 0005.pdf PDF
Bldg 34 Spec Section 281300.pdf PDF
423-926.1171.Arch-Mtn_Home updated 2-10.pdf PDF
RFI 005 - 210205_Responded.pdf PDF
RFI 004 - 210129_Responded_02092021.pdf PDF
RFI 002 - 210120 (GLMV Comments) (002).pdf PDF
RFIs response clarifications.pdf PDF
RFI 001 - 210118_Responded.pdf PDF
Site visit 2 28 Jan 2020.pdf PDF
36C24921R0010 0004.pdf PDF
Site Visit 13 Jan 2021.PDF PDF
brick vault at slab infill4.jpg JPG image
B34 new ACM Survey.pdf PDF
brick vault at slab infill1.jpg JPG image
Protect in place equipment.pdf PDF
01-29-21 Reno Bldg. 34 - RFI 88-91_Responded.pdf PDF
LBP DOC-Word.pdf PDF
brick vault at slab infill2.jpg JPG image
01-20-21 Reno Bldg. 34 - RFI 44-51 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 1-16 Valiant_Responsed.pdf PDF
RFI 003 - 210129_Responded.pdf PDF
Advon RFIs response.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 26-34 Valiant_Responsed.pdf PDF
Building 34 ACM Report.pdf PDF
36C24921R0010 0003.pdf PDF
brick vault at slab infill3.jpg JPG image
brick vault at slab infill5.jpg JPG image
01-29-21 Reno Bldg. 34 - RFI 79-87_Responded.pdf PDF
423-926.1171.Arch-Mtn_Home 2.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 52-60 Valiant_Responsed.pdf PDF
brick vault at slab infill.jpg JPG image
TN20200111 01012021RFI BIC 4 1-20-21_Responded.pdf PDF
TN20200111 01012021RFI BIC 6 Responded.pdf PDF
TN20200111 01012021RFI BIC 2 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 17-25 Valiant_Responsed.pdf PDF
REQUEST FOR INFORMATION (RFI) 1 1-13-21 BIC_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 71-75 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 61-70 Valiant_Responsed.pdf PDF
TN20200111 01012021RFI BIC 3 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 35-43 Valiant_Responsed.pdf PDF
36C24921R0010 0002.pdf PDF
36C24921R0010 0001.pdf PDF
36C24921R0010 0001.docx DOCX document
Calculation of Self Performed Work.pdf PDF
Past Performance Questionnaire.pdf PDF
Copy of General Conditions Breakout.xlsx XLSX spreadsheet
36C24921R0010_1.docx DOCX document
Contractor EMR Certification Form.pdf PDF
B-34 Architectural.pdf PDF
B-34 Plumbing.pdf PDF
Show 40 more

Latest 50 of 58 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

DESCRIPTIONTYPE

A

AC

AF

AFC

AFF

AFG

BFC

C

EF

EC

ETBD

ETR

ETBR

EWC

FA

FAAP

FACP

AMPERE

ALTERNATING CURRENT

AMPERE FRAME

ABOVE FINISHED COUNTER

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

BELOW FINISHED CEILING

CONDUIT

EXHAUST FAN

ELECTRICAL CONTRACTOR

G OR GND

GF OR GFI

KVA

KW

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

EXISTING TO BE RELOCATED

ELECTRIC WATER COOLER

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

GROUND

GROUND FAULT INTERRUPTER

KILOVOLT AMPERES

KILOWATTS

AIC AMPERE INTERRUPTING CURRENT

AMP AMPERE

ARA AREA OF RESCUE ASSISTANCE

AT AMPERE TRIP

AWG AMERICAN WIRE GAUGE

CCT CIRCUIT

CCT BRKR CIRCUIT BREAKER

CR CARD READER

CT CURRENT TRANSFORMER

FPN FUSE/TRIP PER NAMEPLATE

FVNR FULL VOLTAGE NON-REVERSING

HID HIGH INTENSITY DISCHARGE

HOA HAND OFF AUTO

IG ISOLATED GROUND

INTERCOM INTERCOMMUNICATION

J-BOX JUNCTION BOX

GC GENERAL CONTRACTOR

CLG CEILING

GEN GENERATOR

ATS AUTOMATIC TRANSFER SWITCH

BET BUILDING ENTRANCE TERMINAL

MCB

MLO

NEC

Ø OR PH

R

REF

RTU

UON

V

W

WP

MAIN CIRCUIT BREAKER

MAIN LUG ONLY

PHASE

RELOCATED DEVICE

REFRIGERATOR

ROOFTOP UNIT

UNLESS OTHERWISE NOTED

VOLT(S)

WATTS OR WIRE

WEATHERPROOF

P POLE

MCC MOTOR CONTROL CENTER

MD MOTION DETECTOR

MIC MICROPHONE

MOCP MAXIMUM OVERCURRENT PROTECTION

NATIONAL ELECTRICAL CODE

N OR NEUT NEUTRAL

NTS NOT TO SCALE

OC ON CENTER

OL OVERLOAD

PA PUBLIC ADDRESS

PB PUSHBUTTON SWITCH

PNL PANELBOARD

RVNR REDUCED VOLTAGE NON-REVERSING

SPD SURGE PROTECTION DEVICE

SWBD SWITCHBOARD

TTB TELEPHONE TERMINAL BOARD

TC TIME CLOCK

TS TIME SWITCH

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VFD VARIABLE FREQUENCY DRIVE

VSD VARIABLE SPEED DRIVE

XFMR TRANSFORMER

Z IMPEDANCE

WG WIRE GUARD

PC PLUMBING CONTRACTOR

SPKR SPEAKER

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPACITY

SOG SLAB ON GRADE

LV LOW VOLTAGE

MSB MAIN SWITCH BOARD

NIC NOT IN CONTRACT

ABBREVIATIONS

DESCRIPTIONTYPEA. ALL WORK SHALL CONFORM TO THE LATEST NATIONAL ELECTRICAL CODE, STATE

CODE, & LOCAL AUTHORITY REQUIREMENTS.

B. THE CONTRACTOR SHALL VISIT THE PREMISES AND THOROUGHLY FAMILIARIZE

THEMSELVES WITH ALL DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL

FIELD CONDITIONS INCLUDING LOCATION OF UTILITY LINES, STRUCTURES, AND ADVISE

THE ENGINEER OF ANY DISCREPANCY THAT MAY PREVENT OR HINDER THE SPECIFIED

WORK FROM BEING COMPLETED.

C. THE CONTRACTOR SHALL STUDY THE STRUCTURE AND FINISH CONDITIONS AFFECTING

THEIR WORK AND SHALL COORDINATE THEIR WORK ACCORDINGLY. THE CONTRACTOR

SHALL PROVIDE ALL ACCESSORIES, HANGERS, AND ANCHORS AS NECESSARY TO MEET

SUCH CONDITIONS WITHOUT ANY ADDITIONAL COST TO THE COR.

D. PRIOR TO ACCOMPLISHING ANY WORK IN ANY AREA, ALL WORK SHALL BE PLANNED AND

COORDINATED WITH OTHER TRADES AND THE COR. ALL CONDUITS SHALL BE

INSTALLED CONCEALED, UON. THE CONDUIT ROUTING SHALL BE COORDINATED WITH

DUCT WORK, AND OTHER OBSTACLES SO AS TO PROVIDE THE MOST EFFICIENT AND

AESTHETICALLY PLEASING INSTALLATION.

E. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT.

STUDY ALL DRAWINGS, MANUFACTURER'S INSTRUCTIONS, UL LISTINGS, AND CATALOG

DATA TO DETERMINE HOW EQUIPMENT ACCESSORIES AND RELATED ITEMS ARE TO BE

SUPPORTED, MOUNTED, OR SUSPENDED. PROVIDE ALL BOLTS, INSERTS, BRACKETS,

SPACERS, STRUCTURAL SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF

EQUIPMENT FURNISHED UNDER THIS CONTRACT.

F. PROVIDE GREEN EQUIPMENT GROUNDING CONDUCTOR WITH ALL FEEDER AND BRANCH

CIRCUITS.

G. MOUNTING HEIGHTS INDICATED ARE TO THE CENTER OF THE DEVICE, OR EQUIPMENT

UNLESS NOTED OTHERWISE. RECEPTACLE AND DATA/TELEPHONE OUTLET SHOWN

ADJACENT ON DRAWING SHALL BE MOUNTED 6" APART ON CENTER HORIZONTALLY.

CONTRACTOR SHALL NOT INSTALL J-BOXES, OUTLETS, DEVICES, ETC. BACK TO BACK

FOR NEW OR RENOVATION WORK.

H. COORDINATE ALL DEVICES AND OUTLETS ABOVE, OR BELOW WITH CASEWORK

INSTALLATION AND THE ARCHITECT IN ORDER TO POSITION AT THE PROPER LOCATION

AND THE HEIGHT.

I. THE CONTRACTOR SHALL USE THE ARCHITECTURAL PLANS FOR EXACT DIMENSIONS.

DO NOT SCALE THESE PLANS.

J. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL WALL MOUNTED EQUIPMENT

WITH ARCHITECTURAL ELEVATIONS.

K. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. THE ELECTRICAL INSTALLATION

SHALL BE FULLY COORDINATED WITH ALL OTHER TRADES PRIOR TO ROUGH-IN

BETWEEN THE ELECTRICAL WIRING AND DEVICES AND ARCHITECTURAL, STRUCTURAL,

PLUMBING, MECHANICAL AND FIRE PROTECTION WORK.

L. RECEPTACLES LOCATED WITHIN 6'-0" OF A WATER SOURCE SHALL BE GFI TYPE.

GENERAL NOTES

ELECTRICAL ENERGY CODE SUMMARY

(STATE ENERGY CODE, LATEST EDITION ADOPTED)

ELECTRICAL SYSTEM AND EQUIPMENT:

METHOD OF COMPLIANCE:

STATE ENERGY CODE: (X) PRESCRIPTIVE ( ) PERFORMANCE

LUMINAIRE SCHEDULE:

LAMP TYPE REQUIRED IN LUMINAIRE

NUMBER OF LAMPS IN LUMINAIRE

BALLAST TYPE USED IN THE LUMINAIRE

NUMBER OF BALLASTS IN LUMINAIRE

TOTAL WATTAGE PER LUMINAIRE

TOTAL INTERIOR WATTAGE ALLOWED VS. SPECIFIED

EXTERIOR LIGHTING ZONE

TOTAL EXTERIOR WATTAGE ALLOWED VS. SPECIFIED

EXTERIOR LUMINAIRES >100 WATTS MUST HAVE A

MINIMUM EFFICACY OF 60 LUMENS/WATT

PROJECT TOTAL SQUARE FOOTAGE:

STATE ENERGY CODE ADDITIONAL PRESCRIPTIVE COMPLIANCE SUMMARY:

MUST COMPLY WITH ONE OF THE FOLLOWING SECTIONS:

( ) 506.2.1 MORE EFFICIENT MECHANICAL EQUIPMENT

(X) 506.2.2 REDUCED LIGHTING POWER DENSITY

( ) 506.2.3 ENERGY RECOVERY VENTILATION SYSTEMS

( ) 506.2.4 HIGHER EFFICIENCY SERVICE WATER HEATING

( ) 506.2.5 ON-SITE SUPPLY OF RENEWABLE ENERGY

( ) 506.2.6 AUTOMATIC DAYLIGHTING CONTROL SYSTEM

CALCULATION ABOVE INCLUDES REDUCED LIGHTING POWER DENSITY

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

40,000 VS 6,000

N/A N/A

53,819 SQFT

TYPE DESCRIPTION

SURFACE OR PENDANT MOUNTED LIGHT FIXTURE. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.

EXIT LIGHT FIXTURE WITH BATTERY BACK-UP. ARROW, WHEN INDICATED, INDICATES DIRECTION. PROVIDE FACES AS INDICATED ON DRAWINGS. CONNECT TO A CONSTANT HOT CONDUCTOR AHEAD OF LOCAL SWITCH OR RELAY. REFER

TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.

DUPLEX CONVENIENCE RECEPTACLE 20A, 120V, MOUNT 18" AFF, UON. SUBSCRIPT 'GFI' INDICATES GROUND FAULT

INTERRUPTING TYPE.

DUPLEX CONVENIENCE RECEPTACLE, GROUND FAULT INTERRUPTING TYPE WITH WEATHERPROOF WHILE IN USE

ENCLOSURE, 20A, 120V, MOUNT 18" AFF, UON.

SURFACE OR PENDANT MOUNTED EMERGENCY LIGHT FIXTURE WITH BATTERY BACK-UP, BATTERY CONNECTED TO A CONSTANT HOT CONDUCTOR AHEAD OF SWITCHING. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL

INFORMATION.

WP

WALL MOUNTED EMERGENCY LIGHT FIXTURE WITH BATTERY BACK-UP, BATTERY CONNECTED TO A CONSTANT HOT CONDUCTOR AHEAD OF SWITCHING. COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.

REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.

SWITCH, 20A, 120/277V, MOUNT 46" AFF, UON.

NO SUBSCRIPT DENOTES SINGLE POLE SWITCH.

SUBSCRIPT '3' DENOTES THREE-WAY SWITCH.

SUBSCRIPT '4' DENOTES FOUR-WAY SWITCH.

SUBSCRIPT 'D' DENOTES DIMMER SWITCH. COMPATIBLE WITH ASSOCIATED LIGHT FIXTURE.

EQUIPMENT CONNECTION, AS NOTED. REFER TO EQUIPMENT CONNECTION SCHEDULE.

XXX

208/120 VOLT, SURFACE MOUNTED PANELBOARD

DESIGNATION AS NOTED. REFER TO PANEL

SCHEDULES FOR ADDITIONAL INFORMATION.

208/120 VOLT, RECESSED MOUNTED PANELBOARD

XXX

1LA-3

(FOR

EXAMPLE)

BRANCH CIRCUIT, OR FEEDER WIRING, RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD INDICATED. SINGLE PHASE CIRCUIT SHALL CONTAIN 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR AND 1 #12 GROUNDING CONDUCTOR IN 3/4" CONDUIT, MINIMUM. CONDUCTORS LARGER THAN #12, AND CONDUIT LARGER THAN 3/4", SHALL BE AS INDICATED. WHERE "MULTIPLE PHASED" ELECTRICAL LOADS ARE REQUIRED, PROVIDE ADDITIONAL PHASE AND NEUTRAL CONDUCTORS AS INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS MAY BE GROUPED TOGETHER IN A COMMON CONDUIT AS ALLOWED AND IN ACCORDANCE WITH THE NEC. CONTRACTOR SHALL PROVIDE ADDITIONAL "SWITCH LEG" CONDUCTORS, AS REQUIRED TO ACHIEVE FIXTURE CONTROL INDICATED ON PLANS. PROVIDE DEDICATED NEUTRAL CONDUCTOR FOR EACH SINGLE POLE CIRCUIT BREAKER. GROUNDING CONDUCTORS SHALL BE SHARED IN ACCORDANCE WITH AND AS ALLOWED BY THE NEC.

WHEN SHOWN DASHED, IT SHALL DENOTE WIRING UNDERGROUND OR ABOVE TILE CEILING OF FLOOR BELOW. CONDUITS SHOWN ARE DIAGRAMMATIC ONLY AND DO NOT REPRESENT ACTUAL CONDUIT ROUTING UNLESS SPECIFICALLY NOTED.

CONTRACTOR TO DETERMINE CONDUIT ROUTING IN THE FIELD.

SYMBOL LEGEND

GFI

CCTV CAMERA. SUBSCRIPT DENOTES CAMERA TYPE. PROVIDE 4-11/16" SQUARE BY 2-1/18" DEEP J-BOX WITH 1" EMPTY CONDUIT WITH PULL STRING STUBBED ABOVE ACCESSIBLE CEILING. CAMERAS PROVIDED AND INSTALLED BY OWNER.

'C1' = PTZ CAMERA W/CORNER MOUNT - OC#H4iRPTZ-DP45-WP

'C2' = PTZ CAMERA W/CORNER MOUNT - OC#H4PTZ-DP30

'C3' = H4SL CAMERA W/PENDANT MOUNT - OC#H4SL-D01-IR

AP WIRELESS ACCESS POINT

DATA OUTLET MOUNTED 18" AFF, UON. DATA CABLES AND DEVICES BY OTHERS, 4-11/16" SQUARE BY 2-1/18" DEEP J-BOX WITH SINGLE GANG PLASTER RING. PROVIDE WITH 1" CONDUIT STUB-OUT ABOVE ACCESSIBLE CEILING, UON.

DATA OUTLET MOUNTED 46" AFF, UON. DATA CABLES AND DEVICES BY OTHERS, 4-11/16" SQUARE BY 2-1/18" DEEP J-BOX WITH SINGLE GANG PLASTER RING. PROVIDE WITH 1" CONDUIT STUB-OUT ABOVE ACCESSIBLE CEILING, UON.

JUNCTION BOX, PROVIDE STANDARD 4-11/16" SQUARE BY 2-1/18" DEEP J-BOX, UON.

COORDINATE MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.

J

SPECIAL PURPOSE RECEPTACLE. CONFIRM EXACT NEMA CONFIGURATION AND REQUIREMENTS WITH EQUIPMENT BEING INSTALLED. COORDINATE BREAKER SIZE, WIRE SIZE AND NUMBER WITH CORD AND PLUG OF EQUIPMENT. MOUNT 18" AFF, UON.

DISCONNECT SWITCH/FUSED DISCONNECT.

J

QUADRUPLEX CONVENIENCE RECEPTACLE, 20A, 120V, MOUNT 18" AFF, UON.

OUTDOOR PHOTOCELL, MOUNT ON ROOF FACING NORTH.

PE

WALL MOUNTED LIGHT FIXTURE. COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECT PRIOR TO

ROUGH-IN. REFER TO LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.

CARD READER, PROVIDE APPROPRIATE SIZED BOX, MOUNT 46" AFF WITH 3/4" EMPTY CONDUIT WITH PULLSTRING TO JUNCTION BOX ABOVE CEILING. PROVIDE CONDUIT FROM JUNCTION BOX ABOVE CEILING TO DOOR JAMB FOR ELECTRIC LOCKS/STRIKE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH OWNER/SECURITY CONTRACTOR PRIOR TO

ROUGH-IN. EQUIPMENT AND WIRING BY OTHERS.

CR

TELECOMMUNICATIONS TERMINATION BACKBOARD - 3/4" THICK X 8' HIGH X LENGTH PER PLANS, A/C GRADE MOUNTED WITH THE A SIDE FACING OUT, UON. BACKBOARD SHALL BE FIRE RATED AND PAINTED WITH WHITE FIRE RETARDANT PAINT ON BOTH SIDES & ALL EDGES. CONTRACTOR SHALL NOT PAINT OVER ANY FIRE RETARDANT STAMPING ON THE PLYWOOD.

TTB

TELECOMMUNICATIONS STYLE COPPER GROUND BAR WITH STAND-OFF INSULATORS. PROVIDE #3/0G, 1-1/4"C., BACK TO SERVICE GROUND.TMGB

CONDUIT SLEEVE

SEISMIC AND WIND REQUIREMENTS

FOR ELECTRICAL SYSTEMS

INFORMATION FOR IBC-2015/ASCE 7-10

A. ALL ROOF CURBS/ROOF RAILS INCLUDING THEIR ATTACHMENT TO THE EQUIPMENT AND

STRUCTURE MUST BE EVALUATED FOR WIND LOADING. WHERE SEISMIC RESTRAINT IS REQUIRED, THE MORE DEMANDING FORCE OF WIND AND SEISMIC MUST BE USED. SEE SEISMIC INFORMATION CONTAINED IN THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN

CATEGORY.

B. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR

DESIGNATIONS.

C. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH

MECHANICAL COMPONENT.

D. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND

ATTACHMENTS SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.

E. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT

POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF THE SEISMIC SUBMITTAL.

F. SEISMIC RESTRAINTS FOR CONDUIT, CABLE TRAY AND BUS DUCT MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND

CALCULATIONS.

COMPONENT

CERTIFICATION

NOT REQUIRED

13.1.4.3NOT REQUIRED

NOT REQUIRED

NOT REQUIRED

NOT REQUIREDCOMPONENT SUPPORTS

WALL MOUNTED

FLOOR MOUNTED

ROOF MOUNTED

COMPONENT

IDENTIFICATION

SEISMIC

RESTRAINT

REQUIREMENT

ASCE 7-05

REFERENCE

1.0

COMPONENT IMPORTANCE FACTOR (Ip)

SEISMIC DESIGN CATEGORIES C

NOT REQUIREDSUSPENDED EQUIPMENT

CABLE TRAY/ BUS DUCT

TRAPEZED CONDUIT

NOT REQUIRED

SINGLE CONDUIT NOT REQUIRED

PENDANT, LAY-IN & CAN

LIGHTS REQUIRED

REQUIRED

RESTRAIN ALL

SEISMIC

RESTRAINT

REQUIREMENT

ASCE 7-05

REFERENCE

>2"

(SEE NOTES 1 & 2)

REQUIRED

1.5

13.1.4.3

13.1.4.3

13.1.4.3

13.1.4.3

13.1.4.3

13.1.4.3

13.2.2

SEE NOTE 4

13.1.4.3

13.1.4.3

13.6.5

13.1.4.3

13.1.4.3

13.6.8.2b

13.2.2

SEE NOTE 4

GENERAL NOTES:

1. ALL NON-STEEL CONDUIT (I.E. - PVC) MUST BE RESTRAINED.

2. RESTRAINT IS NOT REQUIRED IF SUSPENDED 12 IN. OR LESS FROM THE STRUCTURE AND THE

HANGERS ARE DETAILED TO AVOID SIGNIFICANT BENDING OF THE HANGERS AND THEIR

ATTACHMENTS AND PROVISIONS ARE MADE FOR CONDUIT TO ACCOMMODATE EXPECTED

DEFLECTIONS.

3. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURERS AT TIME OF

SUBMITTAL FOR REVIEW BY ENGINEER OF RECORD.

4. THE RESTRAINT OF PENDANT, LAY-IN & RECESSED DOWN LIGHTS IS GOVERNED BY "CISCA-04 FOR

SEISMIC ZONES" (CEILINGS AND INTERIOR SYSTEMS CONSTRUCTION ASSOCIATION).

TC-8-CH13-48-R8

13.6.8.3.1

RESTRAIN IF ANY

CONDUIT ON TRAPEZE

>2" RESTRAIN IF

TOTAL WEIGHT OF

CONDUIT ON TRAPEZE

> 10 LBS/FT

(SEE NOTE 2)

RESTRAIN ALL

RESTRAIN ALL

RESTRAIN ALL

RESTRAIN ALL

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

/2

/2

:2

:3

A M

C

U se rs \m th ra ilk ill

\D o c u m e n ts \M

E P

R a m e e n g in e e rs

.r v t

34-E-001

ELECTRICAL - GENERAL NOTES AND

LEGENDS

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 SBT GMT 117 149

Revisions: Date:

07/24/2020

ATS

O S

O S

O S

AP

AP

AP

AP

AP

AP

AP

AP

AP

AP

J

J

ATS

D-34B-0-11-EEP-1

D-34B-09-EEP

D-34B-0-1-EEP-C

D-34B-0-1-EEP-B

D-34B-0-1-EEP-A

D-34B-0-1-EEP

D-34B-0-EEP

D-34B-0-EEP-1

D-34B-0-11-EEP

D-34A-0-6

D-34-0-EEP-3

D-34A-0-11

D-34B-0-13-EEP

SWBD 34-SB-A DEMOLITION AREA 1

D-34B-0-SB2

PULL BOX

D-34B-ATS

FAN

HTR

AHU

AHU

C1

C2

C1

C4

C5

C6 C3

ETR ETR

C7

EF EF

EF

EF

CKT

LOCATION

CIRCUIT NAME

STREET LIGHTS

LIFT

STREET LIGHTS

OLD PANEL NEW PANEL

D-34B-0-13-EEP-1

D-34B-0-13-EEP-21,23,25

D-34B-0-B-1 D-34B-0-B-2,4,6

D-34B-0-11-EEP-21,23 D-34B-0-B-3,5

C1

C2

GEN HTR.

TANK MON

TANK ALARM

OUTSIDE LTS

OUTSIDE LTS

C3

D34-0-EEP-1-7,9

D34-0-EEP-1-13

D34-0-EEP-1-15

D34-0-EEP-1-2

D34-0-EEP-1-12

D-34B-0-B-14,16 D-34B-0-B-13 D-34B-0-B-15 D-34B-0-B-18 D-34B-0-B-20

ELEV. CKT

FREIGHT ELEV

D-34B-0-1-EEP-A-3

D-34B-0-1-EEP-A-7,9,11

D-34B-0-B-8 D-34B-0-B-7,9,11

C4

REAR GATE

OUT BLOG

D-34A-0-11-1,3,5 D-34A-0-11-17

D-34A-0-A-1,3,5 D-34A-0-A-2

C5

SUMP PUMP

STREET LIGHTS

D-34B-0-11-EEP-8

D-34B-0-11-EEP-9

D-34B-0-B-10 D-34B-0-B-22,24,26

C6

GAZEBO SWBD-34-SB-A SWBD-34B-A-9C7

NOTE: INTERCEPT EXISTING CIRCUITS SHOWN IN THIS LOCATION AND EXTEND OVER TO NEW PANEL AS SHOWN, MATCH CONDUIT AND WIRE. FIELD VERIFY EXACT

CIRCUIT NUMBER AND NUMBER OF CIRCUITS TO BE RE-FED.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:2

:0

A M

C

U se rs \m th ra ilk ill

\D o c u m e n ts \M

E P

R a m e e n g in e e rs

.r v t

34-ED101

ELECTRICAL - LOWER LEVEL

DEMOLITION PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 SBT GMT 118 149

ELECTRICAL GENERAL NOTES - DEMO

L THE CONTRACTOR SHALL PROPERLY HANDLE AND DISPOSE OF ALL PCB CONTAINING EQUIPMENT SUCH AS

BALLASTS, TRANSFORMERS, AND POTTING COMPOUNDS THROUGH PROPER AUTHORITIES.

M THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES, FIXTURES, WIRING, AND ROUGH-IN IN WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED. THE CONTRACTOR SHALL REMOVE EXISTING ELECTRICAL

DEVICES, LIGHTING FIXTURES, SYSTEMS DEVICE, ASSOCIATED WIRING, AND CONDUIT BACK TO SOURCE OR NEAREST DEVICE TO REMAIN, UNLESS OTHERWISE NOTED. IF EXISTING CIRCUIT HAS DOWNSTREAM DEVICES

TO REMAIN, CONTRACTOR SHALL REFEED THESE ITEMS ACCORDINGLY THROUGH ALTERNATE PATH.

N THE ELECTRICAL CONTRACTOR SHALL DETERMINE THE EXTENT TO WHICH EXISTING CONDUIT AND THE WIRING WILL HAVE TO BE RE-ROUTED, RELOCATED, OR RECONNECTED, AND THE AMOUNT OF ADDITIONAL

WORK WHICH MAY BE REQUIRED DUE TO THE PHYSICAL LOCATION OF THE CONDUIT AND WIRING SHALL BE

PERFORMED UNDER THIS CONTRACT WITHOUT ADDITIONAL CHARGES TO THE OWNER.

O PRIOR TO ANY DEACTIVATION AND RELOCATION OF DEMOLITION WORK, ARRANGE A CONFERENCE WITH ARCHITECT AND THE OWNER'S REPRESENTATIVE IN THE FIELD TO INSPECT EACH OF THE ITEMS TO BE

DEACTIVATED, REMOVED OR RELOCATED. CARE SHALL BE TAKEN TO PROTECT ALL EQUIPMENT DESIGNATED TO BE RELOCATED AND REUSED OR TO REMAIN OPERATION AND BE INTEGRATED WITH THE NEW SYSTEMS.

P CONTRACTOR SHALL INSPECT AND IDENTIFY ANY CONDUIT AND/OR CONDUCTORS THAT MAY BE EMBEDDED IN WALLS TO BE DEMOLISHED OR LOCATED IN THE DEMOLITION AREA AND RELOCATE THESE TO NEW LOCATION

PRIOR TO THE START OF DEMOLITION. BID PRICE SHALL INCLUDE CONDUIT AND CONDUCTORS AND LABOR

FOR ANY THAT MUST BE REMOVED OR RELOCATED.

Q NO WORK IN HATCHED AREAS. E.C. TO MAINTAIN ALL CIRCUITS IN THIS AREA DURING CONSTRUCTION.

R ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOW BOLD AND/OR DASHED IS

EXISTING TO BE DEMOLISHED.

S DEVICES/EQUIPMENT NOTED AS ETBR ON THE DEMOLITION PLAN(S) SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION AS INDICATED ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S). DEVICES/EQUIPMENT NOTED AS ETBR ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S) INDICATES THE NEW LOCATION FOR THE

RELOCATED EXISTING DEVICE/EQUIPMENT.

ELECTRICAL GENERAL NOTES - DEMO

A IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS REQUIRED TO

ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED. THE CONTRACTOR SHALL REFER TO THE NEW ARCHITECTURAL, PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL, ETC. PLANS FOR WORK

SHOWN TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED.

B WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL BE TAKEN TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ANY

STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANENT.

C THE CONTRACTOR SHALL EXERCISE CARE SO THAT ONLY THAT CONSTRUCTION INDICATED OR REASONABLY IMPLIED TO BE REMOVED SHALL BE DEMOLISHED. THE EXISTING CONSTRUCTION TO REMAIN SHALL BE LEFT INTACT AND UNDAMAGED. THE CONTRACTOR SHALL PROTECT ALL ADJACENT SURFACES AND MATERIALS AS

REQUIRED TO PREVENT DAMAGE.

D THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND CONSTRUCTION

DEBRIS GENERATED. TAKE CARE TO PREVENT EXCESSIVE LOADING OF FLOOR ASSEMBLIES.

E THE CONTRACTOR SHALL COORDINATE/SCHEDULE ALL POWER INTERRUPTIONS WITH THE OWNER AND

POWER COMPANY IN WRITING.

F WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED, ALL REMAINING OPENINGS IN THE SLAB/WALL SHALL BE FILLED IN BY THE CONTRACTOR TO MATCH ADJACENT.

G REMOVE ALL MISCELLANEOUS ELECTRICAL, FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDENTIFIED

FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER.

H THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO MAINTAIN THE INTEGRITY AND OPERATION OF EXISTING LIFE SAFETY AND EMERGENCY EGRESS EQUIPMENT.

I THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS, DOORWAYS, AND STAIRS.

J THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GREATEST EXTENT POSSIBLE.

K THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND PROPER DISPOSAL OF ALL FLUORESCENT AND HID LAMPS. THE CONTRACTOR SHALL PROVIDE VERIFICATION OF PROPER LAMP DISPOSAL UPON OWNER

REQUEST.

KEYNOTES:

1 REMOVE ALL ELECTRICAL WITHIN THE DEMOLITION BOUNDARY UON. DISCONNECT

AND REMOVE ALL CONDUIT, PANELS, FEEDERS, DISCONNECTS, DEVICES, WIRE,

ETC. IN IT'S ENTIRETY UNO.

2 REMOVE ALL EXISTING TELECOMMUNICATIONS WITHIN THE DEMOLITION

BOUNDARY COMPLETELY BACK TO THE EXISTING TELECOM ROOM ON THE FIRST

FLOOR, UON. DISCONNECT AND REMOVE ALL CONDUIT, JUNCTION BOXES, JACKS,

OUTLET PLATES, CABLES, ETC. IN IT'S ENTIRETY, UNO.

3 DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, CONDUIT

AND WIRE BACK TO SOURCE FOR HVAC EQUIPMENT.

4 PULLBOX. FIELD VERIFY IF REQUIRED TO REMAIN. IF NOT, REMOVE IT AND

ASSOCIATED CONDUIT CONDUIT AND WIRES BACK TO SOURCE.

5 EXISTING METERING EQUIPMENT SHALL REMAIN.

6 EXISTING PULLBOX FOR SERVICE FEEDERS SHALL REMAIN.

7 EXISTING SERVICE FEEDERS SHALL REMAIN.

8 EXISTING PANEL TO REMAIN AND RE-FED FROM NEW SWITCHBOARD. RE-USE

EXISTING FEEDER, EXTEND AND RECONNECT AS REQUIRED. MATCH CONDUIT AND

WIRE. PANEL SHALL BE RENAMED TO 'D-34B-0-A'.

1/8" = 1'-0"1

ELECTRICAL - LOWER LEVEL DEMOLITION PLAN - AREA A

AP

AP

AP

AP

AP AP

AP

JJ

D-34A-0-2

D-34-0-EEP-2

D-34A-0-4-A

D-34A-0-4-B

D-34-A-0-5-B

D-34A-0-5-C

DEMOLITION AREA 1

HIGH TEMP ALARM SIGN

PUMPS

PUMPS

CONTROLS

PUMPS

FAN

FAN

TO

SERVICE

X/F

C9

C8

C7

CKT

LOCATION

CIRCUIT NAME

LIFT

JOCKEY PUMP

PAINT BOOTH

OLD PANEL NEW PANEL

D-34-0-EEP-2-19,21,23

D-34-0-EEP-2-26,28,30

D-34A-0-B-1,3,5 D-34A-0-B-2,4,6

D-34A-0-2-2,4,6 D-34A-0-D-1,3,5

C8

C9

NOTE: INTERCEPT EXISTING CIRCUITS SHOWN IN THIS LOCATION AND EXTEND OVER TO NEW PANEL AS SHOWN, MATCH CONDUIT AND WIRE. FIELD VERIFY EXACT

CIRCUIT NUMBER AND NUMBER OF CIRCUITS TO BE RE-FED.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:2

:1

A M

C

U se rs \m th ra ilk ill

\D o c u m e n ts \M

E P

R a m e e n g in e e rs

.r v t

34-ED102

ELECTRICAL - LOWER LEVEL

DEMOLITION PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 SBT GMT 119 149

KEYNOTES:

1 REMOVE ALL ELECTRICAL WITHIN THE DEMOLITION BOUNDARY UON. DISCONNECT

AND REMOVE ALL CONDUIT, PANELS, FEEDERS, DISCONNECTS, DEVICES, WIRE,

ETC. IN IT'S ENTIRETY UNO.

2 REMOVE ALL EXISTING TELECOMMUNICATIONS WITHIN THE DEMOLITION

BOUNDARY COMPLETELY BACK TO THE EXISTING TELECOM ROOM ON THE FIRST

FLOOR, UON. DISCONNECT AND REMOVE ALL CONDUIT, JUNCTION BOXES, JACKS,

OUTLET PLATES, CABLES, ETC. IN IT'S ENTIRETY, UNO.

3 DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, CONDUIT

AND WIRE BACK TO SOURCE FOR HVAC EQUIPMENT.

4 DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, CONDUIT

AND WIRE BACK TO SOURCE FOR WALK-IN COOLER.

5 PULLBOX. FIELD VERIFY IF REQUIRED TO REMAIN. IF NOT, REMOVE IT AND

ASSOCIATED CONDUIT CONDUIT AND WIRES BACK TO SOURCE.

6 EXISTING PULLBOX FOR SERVICE FEEDERS SHALL REMAIN.

7 EXISTING SERVICE FEEDERS SHALL REMAIN.

8 FIELD VERIFY IF EXISTING CONDUITS ARE TO REMAIN. IF NOT, REMOVE CONDUITS

AND FEEDERS BACK TO SOURCE.

1/8" = 1'-0"1

ELECTRICAL - LOWER LEVEL DEMOLITION PLAN - AREA B

ELECTRICAL GENERAL NOTES - DEMO

L THE CONTRACTOR SHALL PROPERLY HANDLE AND DISPOSE OF ALL PCB CONTAINING EQUIPMENT SUCH AS

BALLASTS, TRANSFORMERS, AND POTTING COMPOUNDS THROUGH PROPER AUTHORITIES.

M THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES, FIXTURES, WIRING, AND ROUGH-IN IN WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED. THE CONTRACTOR SHALL REMOVE EXISTING ELECTRICAL

DEVICES, LIGHTING FIXTURES, SYSTEMS DEVICE, ASSOCIATED WIRING, AND CONDUIT BACK TO SOURCE OR NEAREST DEVICE TO REMAIN, UNLESS OTHERWISE NOTED. IF EXISTING CIRCUIT HAS DOWNSTREAM DEVICES

TO REMAIN, CONTRACTOR SHALL REFEED THESE ITEMS ACCORDINGLY THROUGH ALTERNATE PATH.

N THE ELECTRICAL CONTRACTOR SHALL DETERMINE THE EXTENT TO WHICH EXISTING CONDUIT AND THE WIRING WILL HAVE TO BE RE-ROUTED, RELOCATED, OR RECONNECTED, AND THE AMOUNT OF ADDITIONAL

WORK WHICH MAY BE REQUIRED DUE TO THE PHYSICAL LOCATION OF THE CONDUIT AND WIRING SHALL BE

PERFORMED UNDER THIS CONTRACT WITHOUT ADDITIONAL CHARGES TO THE OWNER.

O PRIOR TO ANY DEACTIVATION AND RELOCATION OF DEMOLITION WORK, ARRANGE A CONFERENCE WITH ARCHITECT AND THE OWNER'S REPRESENTATIVE IN THE FIELD TO INSPECT EACH OF THE ITEMS TO BE

DEACTIVATED, REMOVED OR RELOCATED. CARE SHALL BE TAKEN TO PROTECT ALL EQUIPMENT DESIGNATED TO BE RELOCATED AND REUSED OR TO REMAIN OPERATION AND BE INTEGRATED WITH THE NEW SYSTEMS.

P CONTRACTOR SHALL INSPECT AND IDENTIFY ANY CONDUIT AND/OR CONDUCTORS THAT MAY BE EMBEDDED IN WALLS TO BE DEMOLISHED OR LOCATED IN THE DEMOLITION AREA AND RELOCATE THESE TO NEW LOCATION

PRIOR TO THE START OF DEMOLITION. BID PRICE SHALL INCLUDE CONDUIT AND CONDUCTORS AND LABOR

FOR ANY THAT MUST BE REMOVED OR RELOCATED.

Q NO WORK IN HATCHED AREAS. E.C. TO MAINTAIN ALL CIRCUITS IN THIS AREA DURING CONSTRUCTION.

R ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOW BOLD AND/OR DASHED IS

EXISTING TO BE DEMOLISHED.

S DEVICES/EQUIPMENT NOTED AS ETBR ON THE DEMOLITION PLAN(S) SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION AS INDICATED ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S). DEVICES/EQUIPMENT NOTED AS ETBR ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S) INDICATES THE NEW LOCATION FOR THE

RELOCATED EXISTING DEVICE/EQUIPMENT.

ELECTRICAL GENERAL NOTES - DEMO

A IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS REQUIRED TO

ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED. THE CONTRACTOR SHALL REFER TO THE NEW ARCHITECTURAL, PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL, ETC. PLANS FOR WORK

SHOWN TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED.

B WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL BE TAKEN TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ANY

STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANENT.

C THE CONTRACTOR SHALL EXERCISE CARE SO THAT ONLY THAT CONSTRUCTION INDICATED OR REASONABLY IMPLIED TO BE REMOVED SHALL BE DEMOLISHED. THE EXISTING CONSTRUCTION TO REMAIN SHALL BE LEFT INTACT AND UNDAMAGED. THE CONTRACTOR SHALL PROTECT ALL ADJACENT SURFACES AND MATERIALS AS

REQUIRED TO PREVENT DAMAGE.

D THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND CONSTRUCTION

DEBRIS GENERATED. TAKE CARE TO PREVENT EXCESSIVE LOADING OF FLOOR ASSEMBLIES.

E THE CONTRACTOR SHALL COORDINATE/SCHEDULE ALL POWER INTERRUPTIONS WITH THE OWNER AND

POWER COMPANY IN WRITING.

F WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED, ALL REMAINING OPENINGS IN THE SLAB/WALL SHALL BE FILLED IN BY THE CONTRACTOR TO MATCH ADJACENT.

G REMOVE ALL MISCELLANEOUS ELECTRICAL, FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDENTIFIED

FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER.

H THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO MAINTAIN THE INTEGRITY AND OPERATION OF EXISTING LIFE SAFETY AND EMERGENCY EGRESS EQUIPMENT.

I THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS, DOORWAYS, AND STAIRS.

J THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GREATEST EXTENT POSSIBLE.

K THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND PROPER DISPOSAL OF ALL FLUORESCENT AND HID LAMPS. THE CONTRACTOR SHALL PROVIDE VERIFICATION OF PROPER LAMP DISPOSAL UPON OWNER

REQUEST.

J

J

J

AP

AP

AP

AP

AP

AP

AP

AP

OS

OS

OS

AP

APAP

AP

AP

AP

AP

AP

J

J

J

J

J

I D-34B-0-5-EEP

34-101-C

34-101-A

D-34B-0-4-EEP

DEMOLITION AREA 1

34B-1-11-EEP

34B-2-11-EEP

34-101-B

IRM

LIFT

TO GAZEBO

TO PUMP HOUSE

PE

IC

EF EF

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:2

:2

A M

C

U se rs \m th ra ilk ill

\D o c u m e n ts \M

E P

R a m e e n g in e e rs

.r v t

34-ED111

ELECTRICAL - FIRST FLOOR

DEMOLITION PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 SBT GMT 120 149

KEYNOTES:

1 REMOVE ALL ELECTRICAL WITHIN THE DEMOLITION BOUNDARY UON. DISCONNECT AND REMOVE

ALL CONDUIT, PANELS, FEEDERS, DISCONNECTS, DEVICES, WIRE, ETC. IN IT'S ENTIRETY UNO.

2 EXISTING TELECOMMUNICATIONS RACKS, EQUIPMENT AND CABLING IN THE EXISTING TELECOM

ROOM TO REMAIN, UON. CONTRACTOR SHALL PROTECT ALL EQUIPMENT DURING

CONSTRUCTION, AND ALL EQUIPMENT SHALL REMAIN ACTIVE AT ALL TIMES.

3 REMOVE ALL EXISTING TELECOMMUNICATIONS WITHIN THE DEMOLITION BOUNDARY

COMPLETELY BACK TO THE EXISTING TELECOM ROOM ON THE FIRST FLOOR, UON. DISCONNECT

AND REMOVE ALL CONDUIT, JUNCTION BOXES, JACKS, OUTLET PLATES, CABLES, ETC. IN IT'S

ENTIRETY, UNO.

4 DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, CONDUIT AND WIRE BACK

TO SOURCE FOR HVAC EQUIPMENT.

5 FIELD VERIFY IF EXISTING FEEDER SERVES GAZEBO. THIS FEEDER SHALL REMAIN AND SHALL BE

RE-FED FROM NEW PANEL.

6 EXISTING FEEDER TO PUMP HOUSE TO REMAIN.

7 EXISTING DECORATIVE PENDANT LIGHT FIXTURE SHALL BE REMOVED AND TURNED OVER TO

OWNER.

1/8" = 1'-0"1

ELECTRICAL - FIRST FLOOR DEMOLITION PLAN - AREA A

ELECTRICAL GENERAL NOTES - DEMO

L THE CONTRACTOR SHALL PROPERLY HANDLE AND DISPOSE OF ALL PCB CONTAINING EQUIPMENT SUCH AS

BALLASTS, TRANSFORMERS, AND POTTING COMPOUNDS THROUGH PROPER AUTHORITIES.

M THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES, FIXTURES, WIRING, AND ROUGH-IN IN WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED. THE CONTRACTOR SHALL REMOVE EXISTING ELECTRICAL

DEVICES, LIGHTING FIXTURES, SYSTEMS DEVICE, ASSOCIATED WIRING, AND CONDUIT BACK TO SOURCE OR NEAREST DEVICE TO REMAIN, UNLESS OTHERWISE NOTED. IF EXISTING CIRCUIT HAS DOWNSTREAM DEVICES

TO REMAIN, CONTRACTOR SHALL REFEED THESE ITEMS ACCORDINGLY THROUGH ALTERNATE PATH.

N THE ELECTRICAL CONTRACTOR SHALL DETERMINE THE EXTENT TO WHICH EXISTING CONDUIT AND THE WIRING WILL HAVE TO BE RE-ROUTED, RELOCATED, OR RECONNECTED, AND THE AMOUNT OF ADDITIONAL

WORK WHICH MAY BE REQUIRED DUE TO THE PHYSICAL LOCATION OF THE CONDUIT AND WIRING SHALL BE

PERFORMED UNDER THIS CONTRACT WITHOUT ADDITIONAL CHARGES TO THE OWNER.

O PRIOR TO ANY DEACTIVATION AND RELOCATION OF DEMOLITION WORK, ARRANGE A CONFERENCE WITH ARCHITECT AND THE OWNER'S REPRESENTATIVE IN THE FIELD TO INSPECT EACH OF THE ITEMS TO BE

DEACTIVATED, REMOVED OR RELOCATED. CARE SHALL BE TAKEN TO PROTECT ALL EQUIPMENT DESIGNATED TO BE RELOCATED AND REUSED OR TO REMAIN OPERATION AND BE INTEGRATED WITH THE NEW SYSTEMS.

P CONTRACTOR SHALL INSPECT AND IDENTIFY ANY CONDUIT AND/OR CONDUCTORS THAT MAY BE EMBEDDED IN WALLS TO BE DEMOLISHED OR LOCATED IN THE DEMOLITION AREA AND RELOCATE THESE TO NEW LOCATION

PRIOR TO THE START OF DEMOLITION. BID PRICE SHALL INCLUDE CONDUIT AND CONDUCTORS AND LABOR

FOR ANY THAT MUST BE REMOVED OR RELOCATED.

Q NO WORK IN HATCHED AREAS. E.C. TO MAINTAIN ALL CIRCUITS IN THIS AREA DURING CONSTRUCTION.

R ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOW BOLD AND/OR DASHED IS

EXISTING TO BE DEMOLISHED.

S DEVICES/EQUIPMENT NOTED AS ETBR ON THE DEMOLITION PLAN(S) SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION AS INDICATED ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S). DEVICES/EQUIPMENT NOTED AS ETBR ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S) INDICATES THE NEW LOCATION FOR THE

RELOCATED EXISTING DEVICE/EQUIPMENT.

ELECTRICAL GENERAL NOTES - DEMO

A IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS REQUIRED TO

ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED. THE CONTRACTOR SHALL REFER TO THE NEW ARCHITECTURAL, PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL, ETC. PLANS FOR WORK

SHOWN TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED.

B WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL BE TAKEN TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ANY

STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANENT.

C THE CONTRACTOR SHALL EXERCISE CARE SO THAT ONLY THAT CONSTRUCTION INDICATED OR REASONABLY IMPLIED TO BE REMOVED SHALL BE DEMOLISHED. THE EXISTING CONSTRUCTION TO REMAIN SHALL BE LEFT INTACT AND UNDAMAGED. THE CONTRACTOR SHALL PROTECT ALL ADJACENT SURFACES AND MATERIALS AS

REQUIRED TO PREVENT DAMAGE.

D THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND CONSTRUCTION

DEBRIS GENERATED. TAKE CARE TO PREVENT EXCESSIVE LOADING OF FLOOR ASSEMBLIES.

E THE CONTRACTOR SHALL COORDINATE/SCHEDULE ALL POWER INTERRUPTIONS WITH THE OWNER AND

POWER COMPANY IN WRITING.

F WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED, ALL REMAINING OPENINGS IN THE SLAB/WALL SHALL BE FILLED IN BY THE CONTRACTOR TO MATCH ADJACENT.

G REMOVE ALL MISCELLANEOUS ELECTRICAL, FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDENTIFIED

FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER.

H THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO MAINTAIN THE INTEGRITY AND OPERATION OF EXISTING LIFE SAFETY AND EMERGENCY EGRESS EQUIPMENT.

I THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS, DOORWAYS, AND STAIRS.

J THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GREATEST EXTENT POSSIBLE.

K THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND PROPER DISPOSAL OF ALL FLUORESCENT AND HID LAMPS. THE CONTRACTOR SHALL PROVIDE VERIFICATION OF PROPER LAMP DISPOSAL UPON OWNER

REQUEST.

FD

AP

CR

AP

CR

AP

AP

AP

J

J

J

J CR

CR

AP

AP

CR

CR

OS

OS

AP

AP

AP

OS

AP

AP

CR

J

AP

CR

D-34A-1-3

D-34-1-2

D34-A-1-7

D34-A-1-8 D34-A-1-4

D34A-1-8-EEP

D-34B-1-8-EEP

DEMOLITION AREA 1

FAN

GFI

HOOD

D34-A-0-5

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:2

:2

A M

C

U se rs \m th ra ilk ill

\D o c u m e n ts \M

E P

R a m e e n g in e e rs

.r v t

34-ED112

ELECTRICAL - FIRST FLOOR

DEMOLITION PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 SBT GMT 121 149

KEYNOTES:

1 REMOVE ALL ELECTRICAL WITHIN THE DEMOLITION BOUNDARY UON. DISCONNECT

AND REMOVE ALL CONDUIT, PANELS, FEEDERS, DISCONNECTS, DEVICES, WIRE,

ETC. IN IT'S ENTIRETY UNO.

2 REMOVE ALL EXISTING TELECOMMUNICATIONS WITHIN THE DEMOLITION

BOUNDARY COMPLETELY BACK TO THE EXISTING TELECOM ROOM ON THE FIRST

FLOOR, UON. DISCONNECT AND REMOVE ALL CONDUIT, JUNCTION BOXES, JACKS,

OUTLET PLATES, CABLES, ETC. IN IT'S ENTIRETY, UNO.

3 DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, CONDUIT

AND WIRE BACK TO SOURCE FOR HVAC EQUIPMENT.

4 DISCONNECT AND REMOVE ALL ASSOCIATED ELECTRICAL EQUIPMENT, CONDUIT

AND WIRE BACK TO SOURCE FOR WALK-IN COOLER.

5 EXISTING LIFT SHALL REMAIN AND REFED FROM NEW PANEL.

6 EXISTING GENERATOR SHALL REMAIN.

7 EXISTING LAB UNITS SHALL BE REMOVED AND ALL ASSOCIATED EQUIPMENT, WIRE

AND CONDUIT BACK TO SOURCE.

1/8" = 1'-0"1

ELECTRICAL - FIRST FLOOR DEMOLITION PLAN - AREA B

ELECTRICAL GENERAL NOTES - DEMO

L THE CONTRACTOR SHALL PROPERLY HANDLE AND DISPOSE OF ALL PCB CONTAINING EQUIPMENT SUCH AS

BALLASTS, TRANSFORMERS, AND POTTING COMPOUNDS THROUGH PROPER AUTHORITIES.

M THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES, FIXTURES, WIRING, AND ROUGH-IN IN WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED. THE CONTRACTOR SHALL REMOVE EXISTING ELECTRICAL

DEVICES, LIGHTING FIXTURES, SYSTEMS DEVICE, ASSOCIATED WIRING, AND CONDUIT BACK TO SOURCE OR NEAREST DEVICE TO REMAIN, UNLESS OTHERWISE NOTED. IF EXISTING CIRCUIT HAS DOWNSTREAM DEVICES

TO REMAIN, CONTRACTOR SHALL REFEED THESE ITEMS ACCORDINGLY THROUGH ALTERNATE PATH.

N THE ELECTRICAL CONTRACTOR SHALL DETERMINE THE EXTENT TO WHICH EXISTING CONDUIT AND THE WIRING WILL HAVE TO BE RE-ROUTED, RELOCATED, OR RECONNECTED, AND THE AMOUNT OF ADDITIONAL

WORK WHICH MAY BE REQUIRED DUE TO THE PHYSICAL LOCATION OF THE CONDUIT AND WIRING SHALL BE

PERFORMED UNDER THIS CONTRACT WITHOUT ADDITIONAL CHARGES TO THE OWNER.

O PRIOR TO ANY DEACTIVATION AND RELOCATION OF DEMOLITION WORK, ARRANGE A CONFERENCE WITH ARCHITECT AND THE OWNER'S REPRESENTATIVE IN THE FIELD TO INSPECT EACH OF THE ITEMS TO BE

DEACTIVATED, REMOVED OR RELOCATED. CARE SHALL BE TAKEN TO PROTECT ALL EQUIPMENT DESIGNATED TO BE RELOCATED AND REUSED OR TO REMAIN OPERATION AND BE INTEGRATED WITH THE NEW SYSTEMS.

P CONTRACTOR SHALL INSPECT AND IDENTIFY ANY CONDUIT AND/OR CONDUCTORS THAT MAY BE EMBEDDED IN WALLS TO BE DEMOLISHED OR LOCATED IN THE DEMOLITION AREA AND RELOCATE THESE TO NEW LOCATION

PRIOR TO THE START OF DEMOLITION. BID PRICE SHALL INCLUDE CONDUIT AND CONDUCTORS AND LABOR

FOR ANY THAT MUST BE REMOVED OR RELOCATED.

Q NO WORK IN HATCHED AREAS. E.C. TO MAINTAIN ALL CIRCUITS IN THIS AREA DURING CONSTRUCTION.

R ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOW BOLD AND/OR DASHED IS

EXISTING TO BE DEMOLISHED.

S DEVICES/EQUIPMENT NOTED AS ETBR ON THE DEMOLITION PLAN(S) SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION AS INDICATED ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S). DEVICES/EQUIPMENT NOTED AS ETBR ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S) INDICATES THE NEW LOCATION FOR THE

RELOCATED EXISTING DEVICE/EQUIPMENT.

ELECTRICAL GENERAL NOTES - DEMO

A IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS REQUIRED TO

ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED. THE CONTRACTOR SHALL REFER TO THE NEW ARCHITECTURAL, PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL, ETC. PLANS FOR WORK

SHOWN TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED.

B WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL BE TAKEN TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ANY

STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANENT.

C THE CONTRACTOR SHALL EXERCISE CARE SO THAT ONLY THAT CONSTRUCTION INDICATED OR REASONABLY IMPLIED TO BE REMOVED SHALL BE DEMOLISHED. THE EXISTING CONSTRUCTION TO REMAIN SHALL BE LEFT INTACT AND UNDAMAGED. THE CONTRACTOR SHALL PROTECT ALL ADJACENT SURFACES AND MATERIALS AS

REQUIRED TO PREVENT DAMAGE.

D THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND CONSTRUCTION

DEBRIS GENERATED. TAKE CARE TO PREVENT EXCESSIVE LOADING OF FLOOR ASSEMBLIES.

E THE CONTRACTOR SHALL COORDINATE/SCHEDULE ALL POWER INTERRUPTIONS WITH THE OWNER AND

POWER COMPANY IN WRITING.

F WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED, ALL REMAINING OPENINGS IN THE SLAB/WALL SHALL BE FILLED IN BY THE CONTRACTOR TO MATCH ADJACENT.

G REMOVE ALL MISCELLANEOUS ELECTRICAL, FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDENTIFIED

FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER.

H THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO MAINTAIN THE INTEGRITY AND OPERATION OF EXISTING LIFE SAFETY AND EMERGENCY EGRESS EQUIPMENT.

I THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS, DOORWAYS, AND STAIRS.

J THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION AND CONSTRUCTION TO

PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GREATEST EXTENT POSSIBLE.

K THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND PROPER DISPOSAL OF ALL FLUORESCENT AND HID LAMPS. THE CONTRACTOR SHALL PROVIDE VERIFICATION OF PROPER LAMP DISPOSAL UPON OWNER

REQUEST.

D-34B-2-6-EEP-16,18

D-34-B-2-6-EEP

DEMOLITION AREA 1 2

C10

CKT

LOCATION

CIRCUIT NAME

EXIST. CKT

EXIST. CKT

EXIST. CKT

EXIST. CKT

EXIST. CKT

EXIST. CKT

EXIST. CKT

EXIST. CKT

OLD PANEL NEW PANEL

C10

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-6-EEP

D-34B-2-A-1 D-34B-2-A-3 D-34B-2-A-5 D-34B-2-A-2 D-34B-2-A-4 D-34B-2-A-6 D-34B-2-A-8

D-34B-2-A-10

NOTE: INTERCEPT EXISTING CIRCUITS SHOWN IN THIS LOCATION AND EXTEND OVER TO NEW PANEL AS SHOWN, MATCH CONDUIT AND WIRE. FIELD VERIFY EXACT

CIRCUIT NUMBER AND NUMBER OF CIRCUITS TO BE RE-FED.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:2

:3

A M

C

U se rs \m th ra ilk ill

\D o c u m e n ts \M

E P

R a m e e n g in e e rs

.r v t

34-ED121

ELECTRICAL - SECOND FLOOR / ATTIC

DEMOLITION PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 SBT GMT 122 149

KEYNOTES:

1 REMOVE ALL ELECTRICAL WITHIN THE DEMOLITION BOUNDARY UON. DISCONNECT AND REMOVE

ALL CONDUIT, PANELS, FEEDERS, DISCONNECTS, DEVICES, WIRE, ETC. IN IT'S ENTIRETY UNO.

2 REMOVE ALL EXISTING TELECOMMUNICATIONS WITHIN THE DEMOLITION BOUNDARY COMPLETELY

BACK TO THE EXISTING TELECOM ROOM ON THE FIRST FLOOR, UON. DISCONNECT AND REMOVE

ALL CONDUIT, JUNCTION BOXES, JACKS, OUTLET PLATES, CABLES, ETC. IN IT'S ENTIRETY, UNO.

1/8" = 1'-0"1

ELECTRICAL - SECOND FLOOR / ATTIC DEMOLITION PLAN - AREA A

ELECTRICAL GENERAL NOTES - DEMO

L THE CONTRACTOR SHALL PROPERLY HANDLE AND DISPOSE OF ALL PCB CONTAINING EQUIPMENT SUCH AS

BALLASTS, TRANSFORMERS, AND POTTING COMPOUNDS THROUGH PROPER AUTHORITIES.

M THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES, FIXTURES, WIRING, AND ROUGH-IN IN WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED. THE CONTRACTOR SHALL REMOVE EXISTING ELECTRICAL

DEVICES, LIGHTING FIXTURES, SYSTEMS DEVICE, ASSOCIATED WIRING, AND CONDUIT BACK TO SOURCE OR NEAREST DEVICE TO REMAIN, UNLESS OTHERWISE NOTED. IF EXISTING CIRCUIT HAS DOWNSTREAM DEVICES

TO REMAIN, CONTRACTOR SHALL REFEED THESE ITEMS ACCORDINGLY THROUGH ALTERNATE PATH.

N THE ELECTRICAL CONTRACTOR SHALL DETERMINE THE EXTENT TO WHICH EXISTING CONDUIT AND THE WIRING WILL HAVE TO BE RE-ROUTED, RELOCATED, OR RECONNECTED, AND THE AMOUNT OF ADDITIONAL

WORK WHICH MAY BE REQUIRED DUE TO THE PHYSICAL LOCATION OF THE CONDUIT AND WIRING SHALL BE

PERFORMED UNDER THIS CONTRACT WITHOUT ADDITIONAL CHARGES TO THE OWNER.

O PRIOR TO ANY DEACTIVATION AND RELOCATION OF DEMOLITION WORK, ARRANGE A CONFERENCE WITH ARCHITECT AND THE OWNER'S REPRESENTATIVE IN THE FIELD TO INSPECT EACH OF THE ITEMS TO BE

DEACTIVATED, REMOVED OR RELOCATED. CARE SHALL BE TAKEN TO PROTECT ALL EQUIPMENT DESIGNATED TO BE RELOCATED AND REUSED OR TO REMAIN OPERATION AND BE INTEGRATED WITH THE NEW SYSTEMS.

P CONTRACTOR SHALL INSPECT AND IDENTIFY ANY CONDUIT AND/OR CONDUCTORS THAT MAY BE EMBEDDED IN WALLS TO BE DEMOLISHED OR LOCATED IN THE DEMOLITION AREA AND RELOCATE THESE TO NEW LOCATION

PRIOR TO THE START OF DEMOLITION. BID PRICE SHALL INCLUDE CONDUIT AND CONDUCTORS AND LABOR

FOR ANY THAT MUST BE REMOVED OR RELOCATED.

Q NO WORK IN HATCHED AREAS. E.C. TO MAINTAIN ALL CIRCUITS IN THIS AREA DURING CONSTRUCTION.

R ALL WORK SHOWN LIGHT AND SOLID IS EXISTING TO REMAIN. ALL WORK SHOW BOLD AND/OR DASHED IS

EXISTING TO BE DEMOLISHED.

S DEVICES/EQUIPMENT NOTED AS ETBR ON THE DEMOLITION PLAN(S) SHALL BE REMOVED AND RELOCATED TO THE NEW LOCATION AS INDICATED ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S). DEVICES/EQUIPMENT NOTED AS ETBR ON THE NEW LIGHTING/POWER/SYSTEMS PLAN(S) INDICATES THE NEW LOCATION FOR THE

RELOCATED EXISTING DEVICE/EQUIPMENT.

ELECTRICAL GENERAL NOTES - DEMO

A IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING EQUIPMENT AS REQUIRED TO

ACCOMPLISH THE NEW WORK AS SHOWN OR REASONABLY IMPLIED. THE CONTRACTOR SHALL REFER TO THE NEW ARCHITECTURAL, PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL, ETC. PLANS FOR WORK

SHOWN TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED.

B WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL BE TAKEN TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ANY

STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANENT.

C THE CONTRACTOR SHALL EXERCISE CARE SO THAT ONLY THAT CONSTRUCTION INDICATED OR REASONABLY IMPLIED TO BE REMOVED SHALL BE DEMOLISHED. THE EXISTING CONSTRUCTION TO REMAIN SHALL BE LEFT INTACT AND UNDAMAGED. THE CONTRACTOR SHALL PROTECT ALL ADJACENT SURFACES AND MATERIALS AS

REQUIRED TO PREVENT DAMAGE.

D THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION AND CONSTRUCTION

DEBRIS GENERATED. TAKE CARE TO PREVENT EXCESSIVE LOADING OF FLOOR ASSEMBLIES.

E THE CONTRACTOR SHALL COORDINATE/SCHEDULE ALL POWER INTERRUPTIONS WITH THE OWNER AND

POWER COMPANY IN…