01-20-21 Reno Bldg. 34 - RFI 44-51 Valiant_Responsed.pdf

PDF 103 KB Posted

Attached to
Renovate Building #34 to Correct FCA Deficiencies
Solicitation number
36C24921R0010
Issued by

About this file

This document contains responses to questions from contractors regarding a solicitation for renovations to Building 34 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The solicitation seeks to correct facility condition assessment deficiencies and involves demolishing interior walls, removing and replacing an existing skylight and air intake, and repairing or replacing plaster ceilings, gutters, and downspouts as needed. Contractors were asked to specify the relevant specification or drawing references in their questions. Responses clarified issues such as the scope of flooring demolition and replacement, provided a site image in place of a referenced civil utility plan, and advised reporting extensive roof damage rather than repairing it. The lead content of existing paint and the contractor's responsibilities regarding water damage were also addressed. The response compilation date was January 27, 2021 and the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is the contracting agency.

View the file

Other files

File Type Posted
36C24921R0010 0005.pdf PDF
Bldg 34 Spec Section 281300.pdf PDF
423-926.1171.Arch-Mtn_Home updated 2-10.pdf PDF
RFI 005 - 210205_Responded.pdf PDF
RFI 004 - 210129_Responded_02092021.pdf PDF
RFI 002 - 210120 (GLMV Comments) (002).pdf PDF
RFIs response clarifications.pdf PDF
RFI 001 - 210118_Responded.pdf PDF
Site visit 2 28 Jan 2020.pdf PDF
36C24921R0010 0004.pdf PDF
Site Visit 13 Jan 2021.PDF PDF
brick vault at slab infill4.jpg JPG image
B34 new ACM Survey.pdf PDF
brick vault at slab infill1.jpg JPG image
Protect in place equipment.pdf PDF
01-29-21 Reno Bldg. 34 - RFI 88-91_Responded.pdf PDF
LBP DOC-Word.pdf PDF
brick vault at slab infill2.jpg JPG image
01-20-21 Reno Bldg. 34 - RFI 1-16 Valiant_Responsed.pdf PDF
RFI 003 - 210129_Responded.pdf PDF
Advon RFIs response.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 26-34 Valiant_Responsed.pdf PDF
Building 34 ACM Report.pdf PDF
36C24921R0010 0003.pdf PDF
brick vault at slab infill3.jpg JPG image
brick vault at slab infill5.jpg JPG image
01-29-21 Reno Bldg. 34 - RFI 79-87_Responded.pdf PDF
423-926.1171.Arch-Mtn_Home 2.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 52-60 Valiant_Responsed.pdf PDF
brick vault at slab infill.jpg JPG image
TN20200111 01012021RFI BIC 4 1-20-21_Responded.pdf PDF
TN20200111 01012021RFI BIC 6 Responded.pdf PDF
TN20200111 01012021RFI BIC 2 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 17-25 Valiant_Responsed.pdf PDF
REQUEST FOR INFORMATION (RFI) 1 1-13-21 BIC_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 71-75 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 61-70 Valiant_Responsed.pdf PDF
TN20200111 01012021RFI BIC 3 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 35-43 Valiant_Responsed.pdf PDF
36C24921R0010 0002.pdf PDF
36C24921R0010 0001.pdf PDF
36C24921R0010 0001.docx DOCX document
Calculation of Self Performed Work.pdf PDF
Past Performance Questionnaire.pdf PDF
Copy of General Conditions Breakout.xlsx XLSX spreadsheet
36C24921R0010_1.docx DOCX document
Contractor EMR Certification Form.pdf PDF
B-34 Architectural.pdf PDF
B-34 Plumbing.pdf PDF
WD - TN20200111 01012021.pdf PDF
Show 40 more

Latest 50 of 58 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

36C24921R0010

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

SUBMITTED BY: City/State:

PHONE NO.:

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: 44-51 DATE:01-20-21 SPEC/DWG. REFERENCE:

REPLY NEEDED BY:

INFORMATION NEEDED:

44. There is a lot of existing flooring that is not noted as being demo'd or abated, therefore would remain. However, when the demo of the interior walls occurs, there will be different floor types left in new areas. Is this correct? Is the flooring meant to be removed in a future contract?

45. 34-PL-111 Note says "Extend 4" S to 5'-0" outside building. See Civil Utility Plan for continuation." Please provide civil utility plan.

46. Sheet 34-A-201 the drawings indicate, " Repair and replace gutters and downspout as required." During the Site visit existing conditions show that an existing corner Roof Rafter to the Clock Tower is rotted out due to water damage.

Does the VA want the General Contractor to include a repair to this rafter in the base bid, or report it on the required roofing survey?

47. Sheet 34-AD-105 in Room E101 "Foyer" Note 9 states, "Existing Plaster ceiling to remain. Patch/repair as required." The existing conditions show that the paint is currently flakey. Can the VA confirm this is not LEAD Based

Paint?

48. Sheet 34-FX-001 shows the existing Water Site Plan around Building 34, the Symbol list on the drawing shows existing to remain line type as a lighter colored line type and new work line type as a darker line. Is the underground dark lines on the Water Site Plan part of this contract? If so, could the VA provide a scale and Civil Drawings to accommodate the work?

49. The existing skylight in the attic may have to be removed and replaced to allow access for new equipment.

During the Site Visit existing conditions show extensive water damage to the existing wood structure supporting the skylight. Does the VA intend for the General Contractor to have this repaired?

50, The Existing skylight has caused severe water damage to the existing conditions within the Plenum Return

Grille Room. Does the VA intend for the General Contractor to have this repaired?

51. Sheet 34-AD-105 shows note 9 in Room E104 Museum. To replace and repair plaster ceiling as required. There is several locations in this room with Flakey Paint and possible Plaster repairs. Should the GC account for the entire room in their repair, as it wasn't possible to quantify the locations during the site visit. Can the VA confirm if the paint is LEAD based?

mailto:Dewayne.Knowles@va.gov mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov mailto:diana.grube@va.gov

REPLY:

44. Demolition floor plan to be updated to show where floor is to be removed. (GLMV)

45. Remove reference to civil utility plan. See attached site image. (GLMV)

46. Report extensive roof damage on required roofing survey. Roof rafters are not to be repaired in this scope of work. (GLMV)

47. Reference specification section 028333.13. (GLMV)

48. Image was pulled from previous work not part of this contract. All dark linework shown as new has been completed and is now existing. See notes referencing water and sprinkler tie-ins. (GLMV) The contractor’s scope of work starts at the incoming fire protection water supply flange inside of the basement. The drawing on 34-FX-001 is for information only, to allow the contractor to perform hydraulic calculations. This drawing was provided to the design team as a PDF, therefore it was not possible to edit the line types.

During phase 1, condition of the underground piping will be evaluated to determine whether it will require replacement during a subsequent phase. (GHD)

49. Existing skylight and air intake to be removed and replaced. Extensive roof damage to be recorded on the roofing survey. (GLMV)

50. Existing skylight and air intake to be removed and replaced. Extensive roof damage to be recorded on the roofing survey. (GLMV)

51. Yes GC should account for repair and replacement as required. Reference specification section 028333.13.

(GLMV)

REPLY COMPILED BY: DATE: 1/27/2021

ATTACHMENTS: COPY TO: