B-34 Plumbing.pdf
PDF 8 MB Posted
- Solicitation number
- 36C24921R0010
About this file
This package includes construction documents and specifications for the renovation of Building 34 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee to correct facility condition assessment deficiencies. The project involves demolishing existing plumbing fixtures and piping in multiple areas of the lower, first, second, and attic levels and installing new domestic cold and hot water, sanitary waste and vent, and medical gas systems. Drawings provide demolition plans, waste and vent routing, and water supply layouts. Specifications include general notes, material schedules, riser diagrams, and construction details. The solicitation is for contract number 36C24921R0010 to complete the work outlined in the construction documents issued by the Department of Veterans Affairs.
View the file
Other files
Show 40 more
Latest 50 of 58 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING ABBREVIATIONS
DESCRIPTIONTYPE
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
BFF BELOW FINISH FLOOR
BTU BRITISH THERMAL UNIT
F FAHRENHEIT
FF FINISH FLOOR
FT FEET
GAL GALLON
HW HOT WATER
I.E. INVERT ELEVATION
LAV LAVATORY
MAX MAXIMUM
MIN MINIMUM
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
WC WATER COLUMN/WATER CLOSET
°F DEGREE FAHRENHEIT
NSF NATIONAL SANITATION FOUNDATION
GC GENERAL CONTRACTOR
PC PLUMBING CONTRACTOR
DFU DRAINAGE FIXTURE UNIT
DWV DRAIN, WASTE & VENT
WSB WATER SUPPLY BOX
WH WATER HEATER
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
DEG DEGREE
DIAM DIAMETER
EWC ELECTRIC WATER COOLER
IN INCH
OC ON CENTER
SF SQUARE FEET
VTR VENT THROUGH ROOF
TMV THERMOSTATIC MIXING VALVE
RCP RECIRCULATION PUMP
1. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0" AT
ROOF BEFORE ROOF PENETRATION.
2. ALL PLUMBING VENTS SHALL BE LOCATED NO CLOSER THAN 15'-0" FROM ANY
MECHANICAL UNIT OR OUTDOOR AIR INTAKE. COORDINATE WITH MECHANICAL
CONTRACTOR.
3. ALL PLUMBING AND PLUMBING MATERIALS SHALL MEET THE REQUIREMENTS OF THE
STATE AND LOCAL PLUMBING CODES.
4. THE USE OF HORIZONTAL CLEANOUTS ON SANITARY SEWERS IS PROHIBITED. USE
FLOOR OR WALL CLEANOUT.
5. ALL WALL HYDRANTS SHALL BE MOUNTED 24" ABOVE FINISHED GRADE UNLESS
OTHERWISE SPECIFIED.
6. ALL PIPING SHALL BE ROUTED TO AVOID CONFLICTS WITH OTHER TRADES.
7. COORDINATE WITH ARCHITECTURAL WORKING DRAWINGS BEFORE ROUGHING-IN
PLUMBING FIXTURES.
8. MAKE PROPER HOT AND COLD WATER, WASTE, AND VENT ETC., PIPING CONNECTIONS
TO ALL FIXTURES AND EQUIPMENT EVEN THOUGH ALL BRANCHES, FITTINGS AND
CONNECTIONS MAY NOT BE SHOWN.
9. COORDINATE LOCATION OF ALL EQUIPMENT, FIXTURES AND PIPING WITH STRUCTURAL
AND ALL OTHER TRADES. PIPING ROUTED ABOVE CEILING SHALL BE ROUTED AS HIGH
AS POSSIBLE.
10. ALL OPENINGS IN CEILINGS AND PLENUM WALLS FOR PLUMBING PIPES SHALL BE
SEALED AIR TIGHT.
11. THE USE OF DOUBLE SANITARY "WYE" FITTINGS IS PROHIBITED. USE SINGLE "WYE"
FITTINGS ONLY.
12. ALL HOT AND COLD WATER PIPING INDICATED TO ROUTED ABOVE FINISHED CEILINGS
OR IN EXTERIOR WALLS SHALL BE INSTALLED ON THE CONDITIONED SPACE SIDE OF
THE BUILDING INSULATION.
13. SLOPES AND INVERT ELEVATIONS OF EXISTING SEWERS, ETC., SHALL BE ESTABLISHED
AND VERIFIED BY PLUMBING CONTRACTOR BEFORE ANY PIPING IS INSTALLED IN
ORDER THAT PROPER SLOPES WILL BE MAINTAINED AND NECESSARY INVERT
ELEVATIONS OBTAINED.
14. IT IS THE INTENTION OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL FOR A
COMPLETE FIRST CLASS INSTALLATION. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM
HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH
NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, BUT WHICH MAY BE
NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY
THE ARCHITECT) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART
OF HIS TOTAL WORK.
15. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK OR ORDERING
EQUIPMENT, PIPING, FIXTURES, ETC.
16. SEAL AROUND ALL WALL PENETRATIONS AIR TIGHT AT FIRE RATED WALLS AND FILL
ANY VOIDS APPROVED FIRESTOPPING.
17. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS AND ALL APPLICABLE LISTING REQUIREMENTS. COORDINATE
BLOCKING AND NECESSARY SUPPORTS WITH THE GENERAL CONTRACTOR. PROVIDE
AND INSTALL UNLESS SPECIFICALLY ASSIGNED BY THE G.C. TO ANOTHER
CONTRACTOR.
18. ANY PIPES PENETRATING RATED WALLS, SMOKE WALLS, SMOKE BARRIERS, ETC.,
SHALL BE SEALED WITH A CODE COMPLIANT U.L. RATED ASSEMBLY THAT MAINTAINS
THE INTEGRITY AND FUNCTION OF THE WALL WHILE ACCOUNTING FOR THE PIPE
MATERIAL, SIZE AND INSULATION.
19. ALL PIPING, FITTINGS, VALVES, ETC. USED IN DOMESTIC WATER SYSTEMS SHALL BE
NSF 61 CERTIFIED.
20. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO DETERMINE FIELD
CONDITIONS AND EXTENT OF THE WORK UNDER THIS CONTRACT. LACK OF
KNOWLEDGE OF EXISTING FIELD CONDITIONS WILL NOT BE CONSIDERED A BASIS FOR
CHANGE ORDERS.
PLUMBING GENERAL NOTES
SUSPENDED PIPE ON
TRAPEZE
NOT REQUIRED
COMPONENT CERTIFICATION NOT REQUIRED 13.2.2
NOT REQUIRED
SUSPENDED NON DUCTILE
PIPING (CAST IRON, PLASTIC,
CERAMIC)
13.1.4.5NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
NOT REQUIREDCOMPONENT SUPPORTS
WALL MOUNTED
FLOOR MOUNTED
ROOF MOUNTED
COMPONENT
IDENTIFICATION
SEISMIC
RESTRAINT
REQUIREMENT
ASCE 7-16
REFERENCE
1.0
COMPONENT IMPORTANCE FACTOR (Ip)
SEISMIC DESIGN CATEGORY C, OCCUPANCY GROUP II
SEISMIC AND WIND REQUIREMENTS
FOR PLUMBING SYSTEMS
INFORMATION FOR IBC-2018/ASCE 7-16
NOT REQUIRED
SUSPENDED DUCTILE PIPING
(STEEL,AL,CU.ETC.)
PIPE TURN UP
PIPE TURN DOWN
PIPE DROP OFF BOTTOM OF MAIN PIPE
DOMESTIC COLD WATER PIPE (CW)
DOMESTIC HOT WATER PIPE (HW)
SANITARY WASTE PIPE (S)
SANITARY VENT PIPE (V)
DESIGNATION DESCRIPTION
PLUMBING LEGEND
TABLE NOTES:
1. ALL PIPING, REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES MUST BE
RESTRAINED.
A. PER 2018 INTERNATIONAL BUILDING CODE, MECHANICAL EQUIPMENT AND COMPONENTS, INCLUDING THEIR SUPPORTS AND ATTACHMENTS, SHALL BE DESIGNED FOR SEISMIC FORCES IN ACCORDANCE WITH
CHAPTER 13 OF ASCE 7-16.
B. EXTERIOR EQUIPMENT (INCLUDING ROOF CURBS AND ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH CHAPTERS 26
THROUGH 29 OF ASCE 7-16.
C. WHERE DESIGN FOR SEISMIC AND WIND LOADS IS REQUIRED, THE MORE DEMANDING FORCE MUST BE USED.
D. REFERENCE THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN
CATEGORY, WIND SPEED, ETC.
E. USE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH COMPONENT.
F. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS
SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.
G. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF
EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY
HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF APPROVED SEISMIC SUBMITTAL.
H. SEISMIC RESTRAINTS FOR DUCTWORK, PIPING AND CONDUIT MUST BE SHOWN ON SEISMIC SUBMITTAL LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS
AND CALCULATIONS.
DOMESTIC HOT WATER RETURN PIPE (HWR)
FLOOR CLEAN OUT (FCO)/GRADE CLEANOUT (GCO)
WALL CLEAN OUT (WCO)/CLEANOUT FITTING
FLOOR DRAIN (FD)
NEW WORK
DESIGNATION DESCRIPTION
PLUMBING NEW/EXISTING LEGEND
EXISTING TO REMAIN (ETR)
EXISTING TO BE DEMOLISHED (ETBD)
BEGINNING OR END OR NEW WORK OR
CONNECTION TO EXISTING (CTE)
CW COLD WATER
HR HOUR
S SANITARY
V VENT
ETBD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
CTE CONNECT TO EXISTING
13.1.4.5
13.1.4.5
13.1.4.5
13.1.4.5
13.1.4.5
13.1.4.5
SUSPENDED
EQUIPMENT
INLINE W/
PIPE
NOT INLINE
W/PIPE
NOT REQUIRED
NOT REQUIRED
13.1.4.5
13.1.4.5
PROPOSED WORK FOR PHASE II OF PROJECT
NOTE
PIPING MATERIAL SCHEDULE
MATERIALAPPLICATION
POLYPROPYLENE (SDR 7.4)DOMESTIC WATER (MAIN PIPING)
NOTES:
1. ALL POLYPROPYLENE AND PEX-A PIPING USED FOR HEATING HOT WATER
PIPING SHALL MEET THE FOLLOWING MINIMUM REQUIREMENTS:
A. MAXIMUM OPERATING TEMPERATURE: 180°F
B. MAXIMUM OPERATING PRESSURE: 100 PSI AT 180°F
2. ALL POLYPROPYLENE AND PEX-A FITTINGS SHALL BE SUPPLIED BY THE SAME
MANUFACTURER AS THE PIPING AND SHALL BE INSTALLED TO MATCH THE
APPLICATION LISTED ABOVE.
3. THE CONTRACTOR SHALL PROVIDE THE VA WITH A NEW POLYPROPYLENE
PIPE JOINING TOOL AT THE COMPLETION OF THE PROJECT. THE
POLYPROPYLENE PIPING TOOL SHALL BE PROVIDED WITH ALL
APPURTENANCES REQUIRED TO WORK ON THE RANGE OF PIPE SIZES USED
ON THIS PROJECT.
4. THE CONTRACTOR SHALL PROVIDE THE VA WITH A NEW PEX-A PIPE JOINING
TOOL AT THE COMPLETION OF THE PROJECT. THE PEX-A PIPING TOOL SHALL
BE PROVIDED WITH ALL APPURTENANCES REQUIRED TO WORK ON THE
RANGE OF PIPE SIZES USED ON THIS PROJECT.
5. REFER TO SPECIFICATION 22 11 00 FOR MORE INFORMATION REGARDING
ACCEPTABLE PIPING MATERIALS.
CROSS-LINKED POLYETHYLENE (PEX-A)DOMESTIC WATER (FIXTURE RUNOUTS)
PVC (SCHEDULE 40)SANITARY AND VENT
PEX-A CROSS-LINKED POLYETHYLENE (TYPE A)
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
/2
/2
:3
:0
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-P-001
PLUMBING - GENERAL NOTES,
SCHEDULES AND LEGENDS
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 70 149
Revisions: Date:
07/24/2020
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
URNIAL COMPLETE
DEMOLISH EXISTING CW, HW, AND
HWR PIPING TIGHT TO STRUCTURE
COMPLETE ALL AREAS.
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
SHOWER COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
URNIAL COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
SHOWERS COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
ROOM
TRANS VAULT
ROOM
ELECTRICAL
ROOM
026 CORRIDOR
HVAC
ROOM
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.
THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,
ETC.
2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS
INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.
3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN
REMOVED. FINISH SHALL MATCH EXISTING.
4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF
BUILDING. FINISH SHALL MATCH EXISTING.
5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER
COMPLIANT WITH ALL LOCAL AND STATE CODES.
DEMOLITION NOTES
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:1
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PD101
PLUMBING - LOWER LEVEL
DEMOLITION PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 71 149
1/8" = 1'-0"1
PLUMBING - LOWER LEVEL DEMOLITION WATER PLAN - AREA A
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH CW PIPING, BACKFLOW
DEVICES, PRV STATIONS COMPLETE.
DEMOLISH HW AND CW PIPING
AND HEAT EXCHANGER COMPLETE
(ETR)
DEMOLISH EXISTING
FLOOR DRAIN COMPLETE
DEMOLISH EXISTING CW, HW, AND
HWR PIPING TIGHT TO STRUCTURE
COMPLETE ALL AREAS.
ROOM
UNEXCAVATED
ROOM
CORRIDOR
ROOM
ROOM
MECHANICAL
ROOM
ELEV
ELEV EQUIP
UNEXCAVATED
TRANS VAULT
1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.
THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,
ETC.
2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS
INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.
3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN
REMOVED. FINISH SHALL MATCH EXISTING.
4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF
BUILDING. FINISH SHALL MATCH EXISTING.
5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER
COMPLIANT WITH ALL LOCAL AND STATE CODES.
DEMOLITION NOTES
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:2
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PD102
PLUMBING - LOWER LEVEL
DEMOLITION PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 72 149
1/8" = 1'-0"1
PLUMBING - LOWER LEVEL DEMOLITION WATER PLAN - AREA B
ETBD CW AND HW
RISER
ETBD CW AND HW
RISER
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
URINAL COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
WATER COOLER COMPLETE
DEMOLISH EXISTING
WATER COOLER COMPLETEDEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
FLOOR DRAIN COMPLETE
DEMOLISH EXISTING
MOP SINK COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
COMM CLOSET
CORRIDOR
ROOM
ROOM
CORRIDOR
ROOM
PORCH 2
STAIRS
ROOM
102b
FOYER
ROOM
PORCH 1
1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.
2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE.
3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN
REMOVED. FINISH SHALL MATCH EXISTING.
4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF
BUILDING. FINISH SHALL MATCH EXISTING.
5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER
COMPLIANT WITH ALL LOCAL AND STATE CODES.
DEMOLITION NOTES
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:2
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PD111
PLUMBING - FIRST FLOOR
DEMOLITION PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 73 149
1/8" = 1'-0"1
PLUMBING - FIRST FLOOR DEMOLITION WATER PLAN - AREA A
ETBD CW AND HW
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
ETBD CW AND HW
RISER
DEMOLISH COMPLETE EXISTING
MED GAS (OXYGEN AND VACUUM)
PIPING, PVDF WASTE AND VENT
SYSTEM, AND FIXTURES COMPLETE.
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
EMERGENCY SHOWER
COMPLETE
DEMOLISH EXISTING
FLOOR DRAIN COMPLETE
DEMOLISH EXISTING
EMERGENCY SHOWER
COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
EMERGENCY SHOWER
COMPLETE
DEMOLISH EXISTING
SINK COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
URINAL COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
ROOM
STAIR 3
CLOSET
ROOM
ROOM
CORRIDOR
ROOM
ELEV
WELDING
ENTRY
CORRIDOR
REF
ROOM
COMM CLOSET
CORRIDOR
1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.
THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,
ETC.
2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS
INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.
3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN
REMOVED. FINISH SHALL MATCH EXISTING.
4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF
BUILDING. FINISH SHALL MATCH EXISTING.
5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER
COMPLIANT WITH ALL LOCAL AND STATE CODES.
DEMOLITION NOTES
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:3
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PD112
PLUMBING - FIRST FLOOR
DEMOLITION PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 74 149
1/8" = 1'-0"1
PLUMBING - FIRST FLOOR DEMOLITION WATER PLAN - AREA B
MECHANICAL
MEZZANINE
BELL TOWER
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:3
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PD121
PLUMBING - SECOND FLOOR / ATTIC
DEMOLITION PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 75 149
1/8" = 1'-0"1
PLUMBING - SECOND FLOOR / ATTIC DEMOLITION WATER PLAN - AREA A
ROOM
STAIRS
ROOM
208?
ROOM
ROOM
ROOM
ROOM
CORRIDOR
DEMOLISH EXISTING LAB
EQUIPMENT COMPLETE
DEMOLISH EXISTING LAB
EQUIPMENT COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
DEMOLISH EXISTING
TOILET COMPLETE
DEMOLISH EXISTING
SHOWER COMPLETE
DEMOLISH EXISTING
LAVATORY COMPLETE
ROOM
1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.
THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,
ETC.
2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS
INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.
3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN
REMOVED. FINISH SHALL MATCH EXISTING.
4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF
BUILDING. FINISH SHALL MATCH EXISTING.
5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER
COMPLIANT WITH ALL LOCAL AND STATE CODES.
DEMOLITION NOTES
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:4
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PD122
PLUMBING - SECOND FLOOR / ATTIC
DEMOLITIONPLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 76 149
1/8" = 1'-0"1
PLUMBING - SECOND FLOOR / ATTIC DEMOLITION WATER PLAN - AREA B
TRANS VAULT
CORRIDOR
ROOM
ELEV
ELEV EQUIP
ROOM
ELECTRICAL
ROOM
HVAC
CORRIDOR
ROOM
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
FCO
4"S UP TO 2'-0"
AND CAP FOR
FUTURE.
4"S UP TO 2'-0"
AND CAP FOR
FUTURE.
FCO
4" S
4" S
4" S 4" S
FCO
EXTEND 4"S TO 5'-0"
OUTSIDE BUIDLING. SEE
CIVIL UTILITY PLAN FOR
CONTINUATION.
4" S
4" S
4" S
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:4
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL101
PLUMBING - LOWER LEVEL WASTE &
VENT PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 77 149
1/8" = 1'-0"1
PLUMBING - LOWER LEVEL IMPROVEMENT WASTE & VENT PLAN - AREA A
CORRIDOR
ROOM
CORRIDOR
070MECHANICAL
ROOM
ROOM
UNEXCAVATED
ROOM
ELEV EQUIP
ELEV
UNEXCAVATED
TRANS VAULT
CORRIDOR
ROOM
4"S UP TO 2'-0"
AND CAP FOR
FUTURE.
4"S UP TO 2'-0"
AND CAP FOR
FUTURE.
4"S UP TO 2'-0"
AND CAP FOR
FUTURE.
FCO
4" S
4" S
4" S
4" S
4" S
4" S
4" S
3"V STACK.
PROVIDE VENT CAPPED ABOVE
CEILING FOR FUTURE.
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:5
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL102
PLUMBING - LOWER LEVEL WASTE &
VENT PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 78 149
1/8" = 1'-0"1
PLUMBING - LOWER LEVEL IMPROVEMENT WASTE & VENT PLAN - AREA B
PORCH 2
STAIRS
ROOM
102b
FOYER
ROOM
PORCH 1
ROOM
CORRIDOR
ROOM
ROOM
COMM CLOSET
EXTEND 4"S TO 5'-0"
OUTSIDE BUILDING. SEE
CIVIL UTILITY PLAN FOR
CONTINUATION.
4" S 4" S
FCO
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:0
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL111
PLUMBING - FIRST FLOOR WASTE &
VENT PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 79 149
1/8" = 1'-0"1
PLUMBING - FIRST FLOOR IMPROVEMENT WASTE & VENT PLAN - AREA A
COMM CLOSET
WELDING
REF
CORRIDOR
ENTRY
ELEV
ROOM
ROOM
CORRIDOR
ROOM
STAIR 3
CLOSET
ROOM
ROOM
3"V STACK.
PROVIDE VENT CAPPED ABOVE
CEILING FOR FUTURE.
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:0
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL112
PLUMBING - FIRST FLOOR WASTE &
VENT PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 80 149
1/8" = 1'-0"1
PLUMBING - FIRST FLOOR IMPROVEMENT WASTE & VENT PLAN - AREA B
BELL TOWER
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:1
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL121
PLUMBING - SECOND FLOOR / ATTIC
WASTE & VENT PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 81 149
1/8" = 1'-0"1
PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WASTE & VENT PLAN - AREA A
CORRIDOR
STAIRS
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
3"V STACK.
PROVIDE VENT CAPPED ABOVE
CEILING FOR FUTURE.
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:1
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL122
PLUMBING - SECOND FLOOR / ATTIC
WASTE & VENT PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 82 149
1/8" = 1'-0"1
PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WASTE & VENT PLAN - AREA B
1 1/2" CW
1 1/2"CW AND 1/2"HW
RISER
3"CW AND 1"HW
RISER
1 1/4" HW
1 1/4" HW
1 1/4" HW
1 1/4" HW
1 1/2" CW
1 1/4" HW
1 1/2" CW
2" CW1 1/4" HW
1 1/2" CW
1 1/4" HW
1 1/4" HW
1 1/2" CW
1 1/4" HW
1 1/4" HW
1/2" CW
2" CW1 1/4" HW
1 1/4" HW
2" CW
1 1/4" HW
1 1/4" HW
3" CW
1" HW
TRANS VAULT
CORRIDOR
ROOM
ELEV
ELEV EQUIP
ROOM
ELECTRICAL
ROOM
HVAC
CORRIDOR
ROOM
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:2
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL131
PLUMBING - LOWER LEVEL WATER
PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 83 149
1/8" = 1'-0"1
PLUMBING - LOWER LEVEL IMPROVEMENT WATER PLAN - AREA A
CONNECT NEW 4"CW TO
EXISTING CW SERVICE. PC
SHALL VERIFY CONDITION
OF EXISTING MAIN INTO
BUILDING PRIOR TO
CONNECTION.
REDUCED PRESSURE
BACKFLOW DEVICE. PROVIDE
FUNNEL DRAIN AND INDIRECT
WASTE PIPING TO SPILL OVER
ADJACENT SUMP BASIN.
2"CW AND 3/4"HW
RISER
1 1/4" HW
3" CW
1" HW
1" HW
3" CW
1 1/4" HW
1" HW
2" CW
3/4" HW
1" HW
2" CW
3/4" HW
ROOM
CORRIDOR
ROOM
CORRIDOR
070MECHANICAL
ROOM
ROOM
UNEXCAVATED
ROOM
ELEV EQUIP
ELEV
UNEXCAVATED
TRANS VAULT
CORRIDOR
ROOM
TERMINATE WITH VALVE
AND CAP FOR PHASE II
DEDUCT ALTERNATE: REFER TO
SPECIFICATION 01 00 00 GENERAL
REQUIREMENTS FOR MORE INFORMATION.
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:2
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL132
PLUMBING - LOWER LEVEL WATER
PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 84 149
1/8" = 1'-0"1
PLUMBING - LOWER LEVEL IMPROVEMENT WATER PLAN - AREA B
1 1/2"CW AND 1/2"HW
3"CW AND 1"HW
RISER
PORCH 2
STAIRS
ROOM
102b
FOYER
ROOM
PORCH 1
ROOM
CORRIDOR
ROOM
ROOM
COMM CLOSET
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:3
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL141
PLUMBING - FIRST FLOOR WATER
PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 85 149
1/8" = 1'-0"1
PLUMBING - FIRST FLOOR IMPROVEMENT WATER PLAN - AREA A
2"CW AND 3/4"HW
ROOM
COMM CLOSET
WELDING
REF
CORRIDOR
ENTRY
ELEV
ROOM
ROOM
CORRIDOR
ROOM
STAIR 3
CLOSET
ROOM
ROOM
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:3
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL142
PLUMBING - FIRST FLOOR WATER
PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 86 149
1/8" = 1'-0"1
PLUMBING - FIRST FLOOR IMPROVEMENT WATER PLAN - AREA B
BELL TOWER
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
A
KEYPLAN
TRUE NORTH
/2
/2
:3
:4
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL151
PLUMBING - SECOND FLOOR / ATTIC
WATER PLAN - AREA A
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 87 149
1/8" = 1'-0"1
PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WATER PLAN - AREA A
CORRIDOR
STAIRS
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
ROOM
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
B
KEYPLAN
TRUE NORTH
/2
/2
:3
:5
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-PL152
PLUMBING - SECOND FLOOR / ATTIC
WATER PLAN - AREA B
Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 88 149
1/8" = 1'-0"1
PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WATER PLAN - AREA B
4" S
FCO
4" S
FCO
FCO
4" S
FCO
4" S
FCO
4" S
4" S
4" S
FCO
4" S
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture, Inc.
Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108
Phone: 816-474-0900 www.strata-arch.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
/2
/2
:3
:0
P
M C
U s e rs \J
F o rd \D o c u m e n ts \M
E P
R
J F o rd a m e -p c .c o m
.r v t
34-P-501
PLUMBING - RISERS Renovate Building 34 to Correct FCA Deficiencies
James H. Quillen VAMC Mountain Home, TN
621-18-102
07/24/2020 FFR JCF 89 149
NTS
WASTE AND VENT RISER SCHEMATIC
CAST IRON SANITARY
WYE FITTING.
CAST IRON
1/8 BEND.
ADJUSTABLE HOUSING.
FINISHED FLOOR.
SECURED RIM FLUSH WITH
FINISHED FLOOR.
HEAVY DUTY
STAINLESS STEEL NO-
HUB CLAMP. (TYPICAL)
FLOOR DRAIN WITH
ADJUSTABLE
STRAINER. - (REFER TO
SCHEDULE ON PLANS) FINISHED FLOOR.
CAST IRON - SIZE AS SHOWN
ON PLAN. REFER TO
SPECIFICATIONS FOR DETAILS.
DEEP SEAL "P" TRAP.
M A
X
IM
U M
NOTES:
1. FLOOR SHALL BE SLOPED TO DRAIN BY G.C. COORDINATE LOW POINT OF THE FLOOR AND
ELEVATION OF DRAIN WITH G.C. PRIOR TO INSTALLATION.
2. COORDINATE EXACT LOCATIONS WITH G.C.
3. REFER TO SPECIFICATIONS FOR PIPING MATERIAL DETAILS.
V A
R
IE
S
PROSET SYSTEMS
“TRAP GUARD”
HEAVY DUTY
STAINLESS STEEL NO-
HUB CLAMP. (TYPICAL)
NOT LESS THAN 2"
NOMINAL WIDTH (1-1/2").
B-LINE B3151 OR
EQUAL SHEET METAL
INSULATION SHIELD.
NOT LESS THAN 2" NOMINAL
WIDTH (1-1/2") UP TO 3-1/2"
PIPE. NOT LESS THAN 3"
NOMINAL WITH 4" & 5" PIPE.
MIN. 2-1/2" FROM BOTTOM FOR
BRANHC PIPES. MIN. 3" FROM
BOTTOM FOR MAIN PIPES.
EXCEPTION: THIS REQUIREMENT
SHALL NOT APPLY TO 2" OR
THICKER NAILING STRIPS
RESTING ON TOP OF STEEL
BEAMS.
SIDEWINDER (SWG) OR EQUAL.
THREADED ROD.THREADED ROD.
B-LINE B3100 OR
EQUAL CLEVIS
HANGER.
PIPE INSULATION
PIPING
SAMMY SUPER
SCREW GST-20 OR
EQUAL.
l
NOT LESS THAN 3"
NOMINAL THICKNESS.
(DEPTH OR SIDE OF
VERTICAL MEMBER)
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08$6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans
Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GHD Cons Services, Inc.
Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202
Phone: 704-342-4910 www.ghd.com
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202
Phone: 704-295-4263 www.ame-pc.com
STRATA Architecture,…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .