B-34 Plumbing.pdf

PDF 8 MB Posted

Attached to
Renovate Building #34 to Correct FCA Deficiencies
Solicitation number
36C24921R0010
Issued by

About this file

This package includes construction documents and specifications for the renovation of Building 34 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee to correct facility condition assessment deficiencies. The project involves demolishing existing plumbing fixtures and piping in multiple areas of the lower, first, second, and attic levels and installing new domestic cold and hot water, sanitary waste and vent, and medical gas systems. Drawings provide demolition plans, waste and vent routing, and water supply layouts. Specifications include general notes, material schedules, riser diagrams, and construction details. The solicitation is for contract number 36C24921R0010 to complete the work outlined in the construction documents issued by the Department of Veterans Affairs.

View the file

Other files

File Type Posted
36C24921R0010 0005.pdf PDF
Bldg 34 Spec Section 281300.pdf PDF
423-926.1171.Arch-Mtn_Home updated 2-10.pdf PDF
RFI 005 - 210205_Responded.pdf PDF
RFI 004 - 210129_Responded_02092021.pdf PDF
RFI 002 - 210120 (GLMV Comments) (002).pdf PDF
RFIs response clarifications.pdf PDF
RFI 001 - 210118_Responded.pdf PDF
Site visit 2 28 Jan 2020.pdf PDF
36C24921R0010 0004.pdf PDF
Site Visit 13 Jan 2021.PDF PDF
brick vault at slab infill4.jpg JPG image
B34 new ACM Survey.pdf PDF
brick vault at slab infill1.jpg JPG image
Protect in place equipment.pdf PDF
01-29-21 Reno Bldg. 34 - RFI 88-91_Responded.pdf PDF
LBP DOC-Word.pdf PDF
brick vault at slab infill2.jpg JPG image
01-20-21 Reno Bldg. 34 - RFI 44-51 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 1-16 Valiant_Responsed.pdf PDF
RFI 003 - 210129_Responded.pdf PDF
Advon RFIs response.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 26-34 Valiant_Responsed.pdf PDF
Building 34 ACM Report.pdf PDF
36C24921R0010 0003.pdf PDF
brick vault at slab infill3.jpg JPG image
brick vault at slab infill5.jpg JPG image
01-29-21 Reno Bldg. 34 - RFI 79-87_Responded.pdf PDF
423-926.1171.Arch-Mtn_Home 2.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 52-60 Valiant_Responsed.pdf PDF
brick vault at slab infill.jpg JPG image
TN20200111 01012021RFI BIC 4 1-20-21_Responded.pdf PDF
TN20200111 01012021RFI BIC 6 Responded.pdf PDF
TN20200111 01012021RFI BIC 2 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 17-25 Valiant_Responsed.pdf PDF
REQUEST FOR INFORMATION (RFI) 1 1-13-21 BIC_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 71-75 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 61-70 Valiant_Responsed.pdf PDF
TN20200111 01012021RFI BIC 3 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 35-43 Valiant_Responsed.pdf PDF
36C24921R0010 0002.pdf PDF
36C24921R0010 0001.pdf PDF
36C24921R0010 0001.docx DOCX document
Calculation of Self Performed Work.pdf PDF
Past Performance Questionnaire.pdf PDF
Copy of General Conditions Breakout.xlsx XLSX spreadsheet
36C24921R0010_1.docx DOCX document
Contractor EMR Certification Form.pdf PDF
B-34 Architectural.pdf PDF
WD - TN20200111 01012021.pdf PDF
Show 40 more

Latest 50 of 58 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING ABBREVIATIONS

DESCRIPTIONTYPE

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

BFF BELOW FINISH FLOOR

BTU BRITISH THERMAL UNIT

F FAHRENHEIT

FF FINISH FLOOR

FT FEET

GAL GALLON

HW HOT WATER

I.E. INVERT ELEVATION

LAV LAVATORY

MAX MAXIMUM

MIN MINIMUM

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

WC WATER COLUMN/WATER CLOSET

°F DEGREE FAHRENHEIT

NSF NATIONAL SANITATION FOUNDATION

GC GENERAL CONTRACTOR

PC PLUMBING CONTRACTOR

DFU DRAINAGE FIXTURE UNIT

DWV DRAIN, WASTE & VENT

WSB WATER SUPPLY BOX

WH WATER HEATER

ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS

DEG DEGREE

DIAM DIAMETER

EWC ELECTRIC WATER COOLER

IN INCH

OC ON CENTER

SF SQUARE FEET

VTR VENT THROUGH ROOF

TMV THERMOSTATIC MIXING VALVE

RCP RECIRCULATION PUMP

1. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0" AT

ROOF BEFORE ROOF PENETRATION.

2. ALL PLUMBING VENTS SHALL BE LOCATED NO CLOSER THAN 15'-0" FROM ANY

MECHANICAL UNIT OR OUTDOOR AIR INTAKE. COORDINATE WITH MECHANICAL

CONTRACTOR.

3. ALL PLUMBING AND PLUMBING MATERIALS SHALL MEET THE REQUIREMENTS OF THE

STATE AND LOCAL PLUMBING CODES.

4. THE USE OF HORIZONTAL CLEANOUTS ON SANITARY SEWERS IS PROHIBITED. USE

FLOOR OR WALL CLEANOUT.

5. ALL WALL HYDRANTS SHALL BE MOUNTED 24" ABOVE FINISHED GRADE UNLESS

OTHERWISE SPECIFIED.

6. ALL PIPING SHALL BE ROUTED TO AVOID CONFLICTS WITH OTHER TRADES.

7. COORDINATE WITH ARCHITECTURAL WORKING DRAWINGS BEFORE ROUGHING-IN

PLUMBING FIXTURES.

8. MAKE PROPER HOT AND COLD WATER, WASTE, AND VENT ETC., PIPING CONNECTIONS

TO ALL FIXTURES AND EQUIPMENT EVEN THOUGH ALL BRANCHES, FITTINGS AND

CONNECTIONS MAY NOT BE SHOWN.

9. COORDINATE LOCATION OF ALL EQUIPMENT, FIXTURES AND PIPING WITH STRUCTURAL

AND ALL OTHER TRADES. PIPING ROUTED ABOVE CEILING SHALL BE ROUTED AS HIGH

AS POSSIBLE.

10. ALL OPENINGS IN CEILINGS AND PLENUM WALLS FOR PLUMBING PIPES SHALL BE

SEALED AIR TIGHT.

11. THE USE OF DOUBLE SANITARY "WYE" FITTINGS IS PROHIBITED. USE SINGLE "WYE"

FITTINGS ONLY.

12. ALL HOT AND COLD WATER PIPING INDICATED TO ROUTED ABOVE FINISHED CEILINGS

OR IN EXTERIOR WALLS SHALL BE INSTALLED ON THE CONDITIONED SPACE SIDE OF

THE BUILDING INSULATION.

13. SLOPES AND INVERT ELEVATIONS OF EXISTING SEWERS, ETC., SHALL BE ESTABLISHED

AND VERIFIED BY PLUMBING CONTRACTOR BEFORE ANY PIPING IS INSTALLED IN

ORDER THAT PROPER SLOPES WILL BE MAINTAINED AND NECESSARY INVERT

ELEVATIONS OBTAINED.

14. IT IS THE INTENTION OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL FOR A

COMPLETE FIRST CLASS INSTALLATION. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM

HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH

NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, BUT WHICH MAY BE

NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY

THE ARCHITECT) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART

OF HIS TOTAL WORK.

15. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK OR ORDERING

EQUIPMENT, PIPING, FIXTURES, ETC.

16. SEAL AROUND ALL WALL PENETRATIONS AIR TIGHT AT FIRE RATED WALLS AND FILL

ANY VOIDS APPROVED FIRESTOPPING.

17. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS AND ALL APPLICABLE LISTING REQUIREMENTS. COORDINATE

BLOCKING AND NECESSARY SUPPORTS WITH THE GENERAL CONTRACTOR. PROVIDE

AND INSTALL UNLESS SPECIFICALLY ASSIGNED BY THE G.C. TO ANOTHER

CONTRACTOR.

18. ANY PIPES PENETRATING RATED WALLS, SMOKE WALLS, SMOKE BARRIERS, ETC.,

SHALL BE SEALED WITH A CODE COMPLIANT U.L. RATED ASSEMBLY THAT MAINTAINS

THE INTEGRITY AND FUNCTION OF THE WALL WHILE ACCOUNTING FOR THE PIPE

MATERIAL, SIZE AND INSULATION.

19. ALL PIPING, FITTINGS, VALVES, ETC. USED IN DOMESTIC WATER SYSTEMS SHALL BE

NSF 61 CERTIFIED.

20. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO DETERMINE FIELD

CONDITIONS AND EXTENT OF THE WORK UNDER THIS CONTRACT. LACK OF

KNOWLEDGE OF EXISTING FIELD CONDITIONS WILL NOT BE CONSIDERED A BASIS FOR

CHANGE ORDERS.

PLUMBING GENERAL NOTES

SUSPENDED PIPE ON

TRAPEZE

NOT REQUIRED

COMPONENT CERTIFICATION NOT REQUIRED 13.2.2

NOT REQUIRED

SUSPENDED NON DUCTILE

PIPING (CAST IRON, PLASTIC,

CERAMIC)

13.1.4.5NOT REQUIRED

NOT REQUIRED

NOT REQUIRED

NOT REQUIREDCOMPONENT SUPPORTS

WALL MOUNTED

FLOOR MOUNTED

ROOF MOUNTED

COMPONENT

IDENTIFICATION

SEISMIC

RESTRAINT

REQUIREMENT

ASCE 7-16

REFERENCE

1.0

COMPONENT IMPORTANCE FACTOR (Ip)

SEISMIC DESIGN CATEGORY C, OCCUPANCY GROUP II

SEISMIC AND WIND REQUIREMENTS

FOR PLUMBING SYSTEMS

INFORMATION FOR IBC-2018/ASCE 7-16

NOT REQUIRED

SUSPENDED DUCTILE PIPING

(STEEL,AL,CU.ETC.)

PIPE TURN UP

PIPE TURN DOWN

PIPE DROP OFF BOTTOM OF MAIN PIPE

DOMESTIC COLD WATER PIPE (CW)

DOMESTIC HOT WATER PIPE (HW)

SANITARY WASTE PIPE (S)

SANITARY VENT PIPE (V)

DESIGNATION DESCRIPTION

PLUMBING LEGEND

TABLE NOTES:

1. ALL PIPING, REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES MUST BE

RESTRAINED.

A. PER 2018 INTERNATIONAL BUILDING CODE, MECHANICAL EQUIPMENT AND COMPONENTS, INCLUDING THEIR SUPPORTS AND ATTACHMENTS, SHALL BE DESIGNED FOR SEISMIC FORCES IN ACCORDANCE WITH

CHAPTER 13 OF ASCE 7-16.

B. EXTERIOR EQUIPMENT (INCLUDING ROOF CURBS AND ROOF RAILS) EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH CHAPTERS 26

THROUGH 29 OF ASCE 7-16.

C. WHERE DESIGN FOR SEISMIC AND WIND LOADS IS REQUIRED, THE MORE DEMANDING FORCE MUST BE USED.

D. REFERENCE THE STRUCTURAL DRAWINGS FOR SITE SPECIFIC INFORMATION ON SEISMIC DESIGN

CATEGORY, WIND SPEED, ETC.

E. USE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH COMPONENT.

F. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS

SHALL BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.

G. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF

EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY

HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF APPROVED SEISMIC SUBMITTAL.

H. SEISMIC RESTRAINTS FOR DUCTWORK, PIPING AND CONDUIT MUST BE SHOWN ON SEISMIC SUBMITTAL LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS

AND CALCULATIONS.

DOMESTIC HOT WATER RETURN PIPE (HWR)

FLOOR CLEAN OUT (FCO)/GRADE CLEANOUT (GCO)

WALL CLEAN OUT (WCO)/CLEANOUT FITTING

FLOOR DRAIN (FD)

NEW WORK

DESIGNATION DESCRIPTION

PLUMBING NEW/EXISTING LEGEND

EXISTING TO REMAIN (ETR)

EXISTING TO BE DEMOLISHED (ETBD)

BEGINNING OR END OR NEW WORK OR

CONNECTION TO EXISTING (CTE)

CW COLD WATER

HR HOUR

S SANITARY

V VENT

ETBD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

CTE CONNECT TO EXISTING

13.1.4.5

13.1.4.5

13.1.4.5

13.1.4.5

13.1.4.5

13.1.4.5

SUSPENDED

EQUIPMENT

INLINE W/

PIPE

NOT INLINE

W/PIPE

NOT REQUIRED

NOT REQUIRED

13.1.4.5

13.1.4.5

PROPOSED WORK FOR PHASE II OF PROJECT

NOTE

PIPING MATERIAL SCHEDULE

MATERIALAPPLICATION

POLYPROPYLENE (SDR 7.4)DOMESTIC WATER (MAIN PIPING)

NOTES:

1. ALL POLYPROPYLENE AND PEX-A PIPING USED FOR HEATING HOT WATER

PIPING SHALL MEET THE FOLLOWING MINIMUM REQUIREMENTS:

A. MAXIMUM OPERATING TEMPERATURE: 180°F

B. MAXIMUM OPERATING PRESSURE: 100 PSI AT 180°F

2. ALL POLYPROPYLENE AND PEX-A FITTINGS SHALL BE SUPPLIED BY THE SAME

MANUFACTURER AS THE PIPING AND SHALL BE INSTALLED TO MATCH THE

APPLICATION LISTED ABOVE.

3. THE CONTRACTOR SHALL PROVIDE THE VA WITH A NEW POLYPROPYLENE

PIPE JOINING TOOL AT THE COMPLETION OF THE PROJECT. THE

POLYPROPYLENE PIPING TOOL SHALL BE PROVIDED WITH ALL

APPURTENANCES REQUIRED TO WORK ON THE RANGE OF PIPE SIZES USED

ON THIS PROJECT.

4. THE CONTRACTOR SHALL PROVIDE THE VA WITH A NEW PEX-A PIPE JOINING

TOOL AT THE COMPLETION OF THE PROJECT. THE PEX-A PIPING TOOL SHALL

BE PROVIDED WITH ALL APPURTENANCES REQUIRED TO WORK ON THE

RANGE OF PIPE SIZES USED ON THIS PROJECT.

5. REFER TO SPECIFICATION 22 11 00 FOR MORE INFORMATION REGARDING

ACCEPTABLE PIPING MATERIALS.

CROSS-LINKED POLYETHYLENE (PEX-A)DOMESTIC WATER (FIXTURE RUNOUTS)

PVC (SCHEDULE 40)SANITARY AND VENT

PEX-A CROSS-LINKED POLYETHYLENE (TYPE A)

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

/2

/2

:3

:0

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-P-001

PLUMBING - GENERAL NOTES,

SCHEDULES AND LEGENDS

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 70 149

Revisions: Date:

07/24/2020

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

URNIAL COMPLETE

DEMOLISH EXISTING CW, HW, AND

HWR PIPING TIGHT TO STRUCTURE

COMPLETE ALL AREAS.

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

SHOWER COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

URNIAL COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

SHOWERS COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

ROOM

TRANS VAULT

ROOM

ELECTRICAL

ROOM

026 CORRIDOR

HVAC

ROOM

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.

THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,

ETC.

2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS

INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.

3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN

REMOVED. FINISH SHALL MATCH EXISTING.

4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF

BUILDING. FINISH SHALL MATCH EXISTING.

5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER

COMPLIANT WITH ALL LOCAL AND STATE CODES.

DEMOLITION NOTES

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:1

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PD101

PLUMBING - LOWER LEVEL

DEMOLITION PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 71 149

1/8" = 1'-0"1

PLUMBING - LOWER LEVEL DEMOLITION WATER PLAN - AREA A

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH CW PIPING, BACKFLOW

DEVICES, PRV STATIONS COMPLETE.

DEMOLISH HW AND CW PIPING

AND HEAT EXCHANGER COMPLETE

(ETR)

DEMOLISH EXISTING

FLOOR DRAIN COMPLETE

DEMOLISH EXISTING CW, HW, AND

HWR PIPING TIGHT TO STRUCTURE

COMPLETE ALL AREAS.

ROOM

UNEXCAVATED

ROOM

CORRIDOR

ROOM

ROOM

MECHANICAL

ROOM

ELEV

ELEV EQUIP

UNEXCAVATED

TRANS VAULT

1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.

THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,

ETC.

2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS

INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.

3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN

REMOVED. FINISH SHALL MATCH EXISTING.

4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF

BUILDING. FINISH SHALL MATCH EXISTING.

5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER

COMPLIANT WITH ALL LOCAL AND STATE CODES.

DEMOLITION NOTES

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:2

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PD102

PLUMBING - LOWER LEVEL

DEMOLITION PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 72 149

1/8" = 1'-0"1

PLUMBING - LOWER LEVEL DEMOLITION WATER PLAN - AREA B

ETBD CW AND HW

RISER

ETBD CW AND HW

RISER

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

URINAL COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

WATER COOLER COMPLETE

DEMOLISH EXISTING

WATER COOLER COMPLETEDEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

FLOOR DRAIN COMPLETE

DEMOLISH EXISTING

MOP SINK COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

COMM CLOSET

CORRIDOR

ROOM

ROOM

CORRIDOR

ROOM

PORCH 2

STAIRS

ROOM

102b

FOYER

ROOM

PORCH 1

1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.

2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE.

3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN

REMOVED. FINISH SHALL MATCH EXISTING.

4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF

BUILDING. FINISH SHALL MATCH EXISTING.

5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER

COMPLIANT WITH ALL LOCAL AND STATE CODES.

DEMOLITION NOTES

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:2

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PD111

PLUMBING - FIRST FLOOR

DEMOLITION PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 73 149

1/8" = 1'-0"1

PLUMBING - FIRST FLOOR DEMOLITION WATER PLAN - AREA A

ETBD CW AND HW

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

ETBD CW AND HW

RISER

DEMOLISH COMPLETE EXISTING

MED GAS (OXYGEN AND VACUUM)

PIPING, PVDF WASTE AND VENT

SYSTEM, AND FIXTURES COMPLETE.

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

EMERGENCY SHOWER

COMPLETE

DEMOLISH EXISTING

FLOOR DRAIN COMPLETE

DEMOLISH EXISTING

EMERGENCY SHOWER

COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

EMERGENCY SHOWER

COMPLETE

DEMOLISH EXISTING

SINK COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

URINAL COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

ROOM

STAIR 3

CLOSET

ROOM

ROOM

CORRIDOR

ROOM

ELEV

WELDING

ENTRY

CORRIDOR

REF

ROOM

COMM CLOSET

CORRIDOR

1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.

THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,

ETC.

2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS

INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.

3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN

REMOVED. FINISH SHALL MATCH EXISTING.

4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF

BUILDING. FINISH SHALL MATCH EXISTING.

5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER

COMPLIANT WITH ALL LOCAL AND STATE CODES.

DEMOLITION NOTES

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:3

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PD112

PLUMBING - FIRST FLOOR

DEMOLITION PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 74 149

1/8" = 1'-0"1

PLUMBING - FIRST FLOOR DEMOLITION WATER PLAN - AREA B

MECHANICAL

MEZZANINE

BELL TOWER

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:3

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PD121

PLUMBING - SECOND FLOOR / ATTIC

DEMOLITION PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 75 149

1/8" = 1'-0"1

PLUMBING - SECOND FLOOR / ATTIC DEMOLITION WATER PLAN - AREA A

ROOM

STAIRS

ROOM

208?

ROOM

ROOM

ROOM

ROOM

CORRIDOR

DEMOLISH EXISTING LAB

EQUIPMENT COMPLETE

DEMOLISH EXISTING LAB

EQUIPMENT COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

DEMOLISH EXISTING

TOILET COMPLETE

DEMOLISH EXISTING

SHOWER COMPLETE

DEMOLISH EXISTING

LAVATORY COMPLETE

ROOM

1. CONTRACTOR SHALL REMOVE ALL EXISTING CW, HW, HWR PIPING COMPLETE.

THIS INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES,

ETC.

2. CONTRACTOR SHALL REMOVE ALL EXISTING DWV PIPING COMPLETE. THIS

INCLUDES PIPING ABOVE AND BELOW SLAB, CONCEALED IN WALL CAVITIES, ETC.

3. CONTRACTOR SHALL PATCH STRUCTURE WHERE EXISTING PIPING HAS BEEN

REMOVED. FINISH SHALL MATCH EXISTING.

4. CONTRACTOR SHALL PATCH EXISTING PENETRATIONS THROUGH EXTERIOR OF

BUILDING. FINISH SHALL MATCH EXISTING.

5. CONTRACTOR SHALL DISPOSE OF REMOVED MATERIAL IN PROPER MANNER

COMPLIANT WITH ALL LOCAL AND STATE CODES.

DEMOLITION NOTES

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:4

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PD122

PLUMBING - SECOND FLOOR / ATTIC

DEMOLITIONPLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 76 149

1/8" = 1'-0"1

PLUMBING - SECOND FLOOR / ATTIC DEMOLITION WATER PLAN - AREA B

TRANS VAULT

CORRIDOR

ROOM

ELEV

ELEV EQUIP

ROOM

ELECTRICAL

ROOM

HVAC

CORRIDOR

ROOM

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

FCO

4"S UP TO 2'-0"

AND CAP FOR

FUTURE.

4"S UP TO 2'-0"

AND CAP FOR

FUTURE.

FCO

4" S

4" S

4" S 4" S

FCO

EXTEND 4"S TO 5'-0"

OUTSIDE BUIDLING. SEE

CIVIL UTILITY PLAN FOR

CONTINUATION.

4" S

4" S

4" S

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:4

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL101

PLUMBING - LOWER LEVEL WASTE &

VENT PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 77 149

1/8" = 1'-0"1

PLUMBING - LOWER LEVEL IMPROVEMENT WASTE & VENT PLAN - AREA A

CORRIDOR

ROOM

CORRIDOR

070MECHANICAL

ROOM

ROOM

UNEXCAVATED

ROOM

ELEV EQUIP

ELEV

UNEXCAVATED

TRANS VAULT

CORRIDOR

ROOM

4"S UP TO 2'-0"

AND CAP FOR

FUTURE.

4"S UP TO 2'-0"

AND CAP FOR

FUTURE.

4"S UP TO 2'-0"

AND CAP FOR

FUTURE.

FCO

4" S

4" S

4" S

4" S

4" S

4" S

4" S

3"V STACK.

PROVIDE VENT CAPPED ABOVE

CEILING FOR FUTURE.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:5

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL102

PLUMBING - LOWER LEVEL WASTE &

VENT PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 78 149

1/8" = 1'-0"1

PLUMBING - LOWER LEVEL IMPROVEMENT WASTE & VENT PLAN - AREA B

PORCH 2

STAIRS

ROOM

102b

FOYER

ROOM

PORCH 1

ROOM

CORRIDOR

ROOM

ROOM

COMM CLOSET

EXTEND 4"S TO 5'-0"

OUTSIDE BUILDING. SEE

CIVIL UTILITY PLAN FOR

CONTINUATION.

4" S 4" S

FCO

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:0

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL111

PLUMBING - FIRST FLOOR WASTE &

VENT PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 79 149

1/8" = 1'-0"1

PLUMBING - FIRST FLOOR IMPROVEMENT WASTE & VENT PLAN - AREA A

COMM CLOSET

WELDING

REF

CORRIDOR

ENTRY

ELEV

ROOM

ROOM

CORRIDOR

ROOM

STAIR 3

CLOSET

ROOM

ROOM

3"V STACK.

PROVIDE VENT CAPPED ABOVE

CEILING FOR FUTURE.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:0

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL112

PLUMBING - FIRST FLOOR WASTE &

VENT PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 80 149

1/8" = 1'-0"1

PLUMBING - FIRST FLOOR IMPROVEMENT WASTE & VENT PLAN - AREA B

BELL TOWER

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:1

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL121

PLUMBING - SECOND FLOOR / ATTIC

WASTE & VENT PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 81 149

1/8" = 1'-0"1

PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WASTE & VENT PLAN - AREA A

CORRIDOR

STAIRS

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

3"V STACK.

PROVIDE VENT CAPPED ABOVE

CEILING FOR FUTURE.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:1

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL122

PLUMBING - SECOND FLOOR / ATTIC

WASTE & VENT PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 82 149

1/8" = 1'-0"1

PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WASTE & VENT PLAN - AREA B

1 1/2" CW

1 1/2"CW AND 1/2"HW

RISER

3"CW AND 1"HW

RISER

1 1/4" HW

1 1/4" HW

1 1/4" HW

1 1/4" HW

1 1/2" CW

1 1/4" HW

1 1/2" CW

2" CW1 1/4" HW

1 1/2" CW

1 1/4" HW

1 1/4" HW

1 1/2" CW

1 1/4" HW

1 1/4" HW

1/2" CW

2" CW1 1/4" HW

1 1/4" HW

2" CW

1 1/4" HW

1 1/4" HW

3" CW

1" HW

TRANS VAULT

CORRIDOR

ROOM

ELEV

ELEV EQUIP

ROOM

ELECTRICAL

ROOM

HVAC

CORRIDOR

ROOM

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:2

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL131

PLUMBING - LOWER LEVEL WATER

PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 83 149

1/8" = 1'-0"1

PLUMBING - LOWER LEVEL IMPROVEMENT WATER PLAN - AREA A

CONNECT NEW 4"CW TO

EXISTING CW SERVICE. PC

SHALL VERIFY CONDITION

OF EXISTING MAIN INTO

BUILDING PRIOR TO

CONNECTION.

REDUCED PRESSURE

BACKFLOW DEVICE. PROVIDE

FUNNEL DRAIN AND INDIRECT

WASTE PIPING TO SPILL OVER

ADJACENT SUMP BASIN.

2"CW AND 3/4"HW

RISER

1 1/4" HW

3" CW

1" HW

1" HW

3" CW

1 1/4" HW

1" HW

2" CW

3/4" HW

1" HW

2" CW

3/4" HW

ROOM

CORRIDOR

ROOM

CORRIDOR

070MECHANICAL

ROOM

ROOM

UNEXCAVATED

ROOM

ELEV EQUIP

ELEV

UNEXCAVATED

TRANS VAULT

CORRIDOR

ROOM

TERMINATE WITH VALVE

AND CAP FOR PHASE II

DEDUCT ALTERNATE: REFER TO

SPECIFICATION 01 00 00 GENERAL

REQUIREMENTS FOR MORE INFORMATION.

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:2

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL132

PLUMBING - LOWER LEVEL WATER

PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 84 149

1/8" = 1'-0"1

PLUMBING - LOWER LEVEL IMPROVEMENT WATER PLAN - AREA B

1 1/2"CW AND 1/2"HW

3"CW AND 1"HW

RISER

PORCH 2

STAIRS

ROOM

102b

FOYER

ROOM

PORCH 1

ROOM

CORRIDOR

ROOM

ROOM

COMM CLOSET

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:3

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL141

PLUMBING - FIRST FLOOR WATER

PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 85 149

1/8" = 1'-0"1

PLUMBING - FIRST FLOOR IMPROVEMENT WATER PLAN - AREA A

2"CW AND 3/4"HW

ROOM

COMM CLOSET

WELDING

REF

CORRIDOR

ENTRY

ELEV

ROOM

ROOM

CORRIDOR

ROOM

STAIR 3

CLOSET

ROOM

ROOM

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:3

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL142

PLUMBING - FIRST FLOOR WATER

PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 86 149

1/8" = 1'-0"1

PLUMBING - FIRST FLOOR IMPROVEMENT WATER PLAN - AREA B

BELL TOWER

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

A

KEYPLAN

TRUE NORTH

/2

/2

:3

:4

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL151

PLUMBING - SECOND FLOOR / ATTIC

WATER PLAN - AREA A

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 87 149

1/8" = 1'-0"1

PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WATER PLAN - AREA A

CORRIDOR

STAIRS

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

ROOM

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

B

KEYPLAN

TRUE NORTH

/2

/2

:3

:5

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-PL152

PLUMBING - SECOND FLOOR / ATTIC

WATER PLAN - AREA B

Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 88 149

1/8" = 1'-0"1

PLUMBING - SECOND FLOOR / ATTIC IMPROVEMENT WATER PLAN - AREA B

4" S

FCO

4" S

FCO

FCO

4" S

FCO

4" S

FCO

4" S

4" S

4" S

FCO

4" S

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture, Inc.

Historic Preservation Architect 1701 Oak Street, Suite 100, Kansas City, MO 64108

Phone: 816-474-0900 www.strata-arch.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

/2

/2

:3

:0

P

M C

U s e rs \J

F o rd \D o c u m e n ts \M

E P

R

J F o rd a m e -p c .c o m

.r v t

34-P-501

PLUMBING - RISERS Renovate Building 34 to Correct FCA Deficiencies

James H. Quillen VAMC Mountain Home, TN

621-18-102

07/24/2020 FFR JCF 89 149

NTS

WASTE AND VENT RISER SCHEMATIC

CAST IRON SANITARY

WYE FITTING.

CAST IRON

1/8 BEND.

ADJUSTABLE HOUSING.

FINISHED FLOOR.

SECURED RIM FLUSH WITH

FINISHED FLOOR.

HEAVY DUTY

STAINLESS STEEL NO-

HUB CLAMP. (TYPICAL)

FLOOR DRAIN WITH

ADJUSTABLE

STRAINER. - (REFER TO

SCHEDULE ON PLANS) FINISHED FLOOR.

CAST IRON - SIZE AS SHOWN

ON PLAN. REFER TO

SPECIFICATIONS FOR DETAILS.

DEEP SEAL "P" TRAP.

M A

X

IM

U M

NOTES:

1. FLOOR SHALL BE SLOPED TO DRAIN BY G.C. COORDINATE LOW POINT OF THE FLOOR AND

ELEVATION OF DRAIN WITH G.C. PRIOR TO INSTALLATION.

2. COORDINATE EXACT LOCATIONS WITH G.C.

3. REFER TO SPECIFICATIONS FOR PIPING MATERIAL DETAILS.

V A

R

IE

S

PROSET SYSTEMS

“TRAP GUARD”

HEAVY DUTY

STAINLESS STEEL NO-

HUB CLAMP. (TYPICAL)

NOT LESS THAN 2"

NOMINAL WIDTH (1-1/2").

B-LINE B3151 OR

EQUAL SHEET METAL

INSULATION SHIELD.

NOT LESS THAN 2" NOMINAL

WIDTH (1-1/2") UP TO 3-1/2"

PIPE. NOT LESS THAN 3"

NOMINAL WITH 4" & 5" PIPE.

MIN. 2-1/2" FROM BOTTOM FOR

BRANHC PIPES. MIN. 3" FROM

BOTTOM FOR MAIN PIPES.

EXCEPTION: THIS REQUIREMENT

SHALL NOT APPLY TO 2" OR

THICKER NAILING STRIPS

RESTING ON TOP OF STEEL

BEAMS.

SIDEWINDER (SWG) OR EQUAL.

THREADED ROD.THREADED ROD.

B-LINE B3100 OR

EQUAL CLEVIS

HANGER.

PIPE INSULATION

PIPING

SAMMY SUPER

SCREW GST-20 OR

EQUAL.

l

NOT LESS THAN 3"

NOMINAL THICKNESS.

(DEPTH OR SIDE OF

VERTICAL MEMBER)

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08$6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans

Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GHD Cons Services, Inc.

Fire Protection Engineer 222 S. Church St. #400, Charlotte, NC 28202

Phone: 704-342-4910 www.ghd.com

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

AME Consulting Engineers MEP Engineers 705 E. Morehead St., Charlotte, NC 28202

Phone: 704-295-4263 www.ame-pc.com

STRATA Architecture,…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .