RFI 004 - 210129_Responded_02092021.pdf

PDF 1 MB Posted

Attached to
Renovate Building #34 to Correct FCA Deficiencies
Solicitation number
36C24921R0010
Issued by

About this file

This document contains responses to contractor questions regarding a solicitation for renovations to Building 34 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee.

The solicitation seeks to renovate Building 34 to correct facility condition assessment deficiencies. A contractor submitted 21 questions to clarify specifications, drawings, and other project details. The responses provide additional details on the scope of brick tuckpointing and replacement work required, clarify that lead abatement of all painted surfaces is not mandatory but contractors must comply with OSHA lead standards and contain dust migration, and explain that painted materials may be removed with lead paint intact but dust control measures are still needed. The questions and answers provide supplementary details to help contractors fully understand renovation requirements and prepare accurate bids for the solicitation.

View the file

Other files

File Type Posted
36C24921R0010 0005.pdf PDF
Bldg 34 Spec Section 281300.pdf PDF
423-926.1171.Arch-Mtn_Home updated 2-10.pdf PDF
RFI 005 - 210205_Responded.pdf PDF
RFI 002 - 210120 (GLMV Comments) (002).pdf PDF
RFIs response clarifications.pdf PDF
RFI 001 - 210118_Responded.pdf PDF
Site visit 2 28 Jan 2020.pdf PDF
36C24921R0010 0004.pdf PDF
Site Visit 13 Jan 2021.PDF PDF
brick vault at slab infill4.jpg JPG image
B34 new ACM Survey.pdf PDF
brick vault at slab infill1.jpg JPG image
Protect in place equipment.pdf PDF
01-29-21 Reno Bldg. 34 - RFI 88-91_Responded.pdf PDF
LBP DOC-Word.pdf PDF
brick vault at slab infill2.jpg JPG image
01-20-21 Reno Bldg. 34 - RFI 44-51 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 1-16 Valiant_Responsed.pdf PDF
RFI 003 - 210129_Responded.pdf PDF
Advon RFIs response.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 26-34 Valiant_Responsed.pdf PDF
Building 34 ACM Report.pdf PDF
36C24921R0010 0003.pdf PDF
brick vault at slab infill3.jpg JPG image
brick vault at slab infill5.jpg JPG image
01-29-21 Reno Bldg. 34 - RFI 79-87_Responded.pdf PDF
423-926.1171.Arch-Mtn_Home 2.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 52-60 Valiant_Responsed.pdf PDF
brick vault at slab infill.jpg JPG image
TN20200111 01012021RFI BIC 4 1-20-21_Responded.pdf PDF
TN20200111 01012021RFI BIC 6 Responded.pdf PDF
TN20200111 01012021RFI BIC 2 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 17-25 Valiant_Responsed.pdf PDF
REQUEST FOR INFORMATION (RFI) 1 1-13-21 BIC_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 71-75 Valiant_Responsed.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 61-70 Valiant_Responsed.pdf PDF
TN20200111 01012021RFI BIC 3 1-20-21_Responded.pdf PDF
01-20-21 Reno Bldg. 34 - RFI 35-43 Valiant_Responsed.pdf PDF
36C24921R0010 0002.pdf PDF
36C24921R0010 0001.pdf PDF
36C24921R0010 0001.docx DOCX document
Calculation of Self Performed Work.pdf PDF
Past Performance Questionnaire.pdf PDF
Copy of General Conditions Breakout.xlsx XLSX spreadsheet
36C24921R0010_1.docx DOCX document
Contractor EMR Certification Form.pdf PDF
B-34 Architectural.pdf PDF
B-34 Plumbing.pdf PDF
WD - TN20200111 01012021.pdf PDF
Show 40 more

Latest 50 of 58 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

36C24921R0010

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: DATE:

REPLY NEEDED BY:

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: City/State:

PHONE NO.:

Semper Tek, Inc. Lexington, KY

ASAP

859-252-8339

Spec/DWG Reference:

Information Needed:

mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov joee Typewritten Text joee Typewritten Text 1/29/21 joee Typewritten Text The specs include a section 04 01 00 Maintenance of Masonry which details brick tuckpointing and replacement. However, there is no indication on the plans that any masonry tuckpointing or replacement is included in this project. Please clarify and provide details and quantities if it applies.

Zoe Typewritten Text Brick tuckpointing is only intended for areas of building penetrations being repaired. (GLMV)

Zoe Typewritten Text Hope Pittman, Atraix

Zoe Typewritten Text 2/9/21

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: DATE:

REPLY NEEDED BY:

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: City/State:

PHONE NO.:

Semper Tek, Inc. Lexington, KY

ASAP

859-252-8339

Spec/DWG Reference:

Information Needed:

mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov joee Typewritten Text joee Typewritten Text 1/29/21 joee Typewritten Text The lead paint spec 02 82 33.13 states in section 1.1 to assume all painted surfaces are lead contaminated. However, there does not appear to be any direction on what lead painted items to abate or in what quantities. Please provide additional information so an apples-to-apples bid can be provided from all GC’s.

Zoe Typewritten Text Answered in previous RFI Lead abatement to remove all lead-containing paint is not required for this project. Based on previous testing all paints should be considered lead-containing and any disturbance to painted surfaces during the course of renovations should comply with the OSHA lead standard. Any of the Contractor activities that may generate leaded dust or impact a leaded surface shall be responsible for regulating their work area so that dust migration is contained properly within the regulated area. Once the work is complete, the Contractor shall be responsible for the proper clean up and disposal of leaded dust and materials. The goal is to provide a safe working environment minimizing exposure to lead-containing dusts.

Zoe Typewritten Text Hope Pittman Atriax

Zoe

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: DATE:

REPLY NEEDED BY:

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: City/State:

PHONE NO.:

Semper Tek, Inc. Lexington, KY

ASAP

859-252-8339

Spec/DWG Reference:

Information Needed:

mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov joee Typewritten Text joee Typewritten Text 1/29/21 joee Typewritten Text The sprinkler and some other pipe/conduit and hangers appear to be painted with lead paint, do these items require abatement? Typically the lead painted pipe/conduit would be removed normally and recycled.

Zoe Typewritten Text Answered in previous RFI Painted building materials with lead-containing paints may be removed/demolished with the paint remaining on the surfaces. It is not required to remove the lead-containing paint from surfaces to remain. Any of the Contractor activities that may generate leaded dust or impact a leaded surface must comply with the OSHA lead standard and shall be responsible for regulating their work area so that dust migration is contained properly within the regulated area. Once the work is complete, the Contractor shall be responsible for the proper clean up and disposal of leaded dust and materials. The goal is to provide a safe working environment minimizing exposure to lead-containing dusts.

Zoe Typewritten Text Hope Pittman, Atraix

Zoe

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: DATE:

REPLY NEEDED BY:

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: City/State:

PHONE NO.:

Semper Tek, Inc. Lexington, KY

ASAP

859-252-8339

Spec/DWG Reference:

Information Needed:

mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov joee Typewritten Text joee Typewritten Text 1/29/21 joee Typewritten Text Regarding 02 82 33.13 lead paint abatement, when we encounter a lead painted surface such as a masonry wall, to receive a new opening, or a plaster ceiling to be demoed, can the lead paint be removed only from the small areas to be demo or must the lead paint be removed from all lead painted surfaces?

Zoe Typewritten Text Painted building materials with lead-containing paints may be removed/demolished with the paint remaining on the surfaces. It is not required to remove the lead-containing paint from surfaces to remain. Any of the Contractor activities that may generate leaded dust or impact a leaded surface must comply with the OSHA lead standard and shall be responsible for regulating their work area so that dust migration is contained properly within the regulated area. Once the work is complete, the Contractor shall be responsible for the proper clean up and disposal of leaded dust and materials. The goal is to provide a safe working environment minimizing exposure to lead-containing dusts.

Zoe Typewritten Text Answered in previous RFIs

Zoe Typewritten Text Hope Pittman, Atraix

Zoe

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: DATE:

REPLY NEEDED BY:

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: City/State:

PHONE NO.:

Semper Tek, Inc. Lexington, KY

ASAP

859-252-8339

Spec/DWG Reference:

Information Needed:

mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov joee Typewritten Text joee Typewritten Text 1/29/21 joee Typewritten Text Will lead abatement be required at new duct penetrations in existing walls with lead paint?

Zoe Typewritten Text Answered in previous RFI's 17, 19, 20 and 21.

Zoe Typewritten Text Hope Pittman, Atraix

Zoe Typewritten Text 2/9/21

Zoe

: Based on previous testing all paints should be considered lead-containing and any disturbance to painted surfaces during the course of renovations should comply with the OSHA lead standard. Contractors shall protect their employees from lead hazards during any disturbance, to control dust, and maintain a clean/safe work environment. See RFI 17 & 19.

PROJECT NUMBER: 621-18-102 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: Renovate Bldg. 34 to Correct FCA

Deficiencies

PROJECT LOCATION: James H. Quillen VA Medical

Center

P.O. Box 4000

Mt. Home, TN 37684

TO: Dewayne L. Knowles

Dewayne.Knowles@va.gov

Diana K. Grube

Diana.Grube@va.gov

RFI NO.: DATE:

REPLY NEEDED BY:

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: City/State:

PHONE NO.:

Semper Tek, Inc. Lexington, KY

ASAP

859-252-8339

Spec/DWG Reference:

Information Needed:

mailto:Dewayne.Knowles@va.gov mailto:diana.grube@va.gov joee Typewritten Text joee Typewritten Text 1/29/21 joee Typewritten Text Will lead abatement be required at new penetrations for pipe, conduit, etc., in existing walls with lead paint?

Zoe Typewritten Text Answered in previous RFI's 17, 19, 20 and 21.

Zoe Typewritten Text Hope Pittman, Atriax

Zoe