This document package includes specifications for variable frequency motor controllers and a related federal contract opportunity. The specifications call for separately enclosed preassembled combination variable frequency motor controllers rated 600V or less to provide speed control for three-phase squirrel-cage induction motors. Key requirements include NEMA and UL ratings, input and output characteristics, overload capabilities, control interfaces including analog and digital inputs and outputs, bypass systems, enclosures, accessories, source quality control testing, installation and commissioning. The related federal contract opportunity is a solicitation from the US Agency for International Development Mission in South Sudan seeking phase one proposals to provide electrical upgrade services for the USAID/South Sudan Juba compound, as described in the solicitation.
View the file
Other files for this federal contract opportunity
Show all 50
USAID/South Sudan Juba Compound Electrical Upgrade has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JUBA ELECTRICAL UPGRADE DEVELOPMENT July 13, 2020
JUBA SOUTH SUDAN Issued for Bid
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 1
SECTION 262923 - VARIABLE-FREQUENCY MOTOR CONTROLLERS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes separately enclosed, preassembled, combination VFCs, rated 600 V and less, for speed control of three-phase, squirrel-cage induction motors.
B. Related Requirements:
1. Section 262419 "Motor-Control Centers" for VFCs installed in motor-control centers.
1.3 DEFINITIONS
A. CE: Conformite Europeene (European Compliance).
B. CPT: Control power transformer.
C. DDC: Direct digital control.
D. EMI: Electromagnetic interference.
E. LED: Light-emitting diode.
F. NC: Normally closed.
G. NO: Normally open.
H. OCPD: Overcurrent protective device.
I. PID: Control action, proportional plus integral plus derivative.
J. RFI: Radio-frequency interference.
K. VFC: Variable-frequency motor controller.
1.4 ACTION SUBMITTALS
A. Product Data: For each type and rating of VFC indicated.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 2
1. Include dimensions and finishes for VFCs.
2. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
B. Shop Drawings: For each VFC indicated.
1. Include mounting and attachment details.
2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
3. Include diagrams for power, signal, and control wiring.
1.5 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Floor plans, drawn to scale, showing dimensioned layout on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Required working clearances and required area above and around VFCs.
2. Show VFC layout and relationships between electrical components and adjacent structural and mechanical elements.
3. Show support locations, type of support, and weight on each support.
4. Indicate field measurements.
B. Qualification Data: For testing agency.
C. Seismic Qualification Data: Certificates, for each VFC, accessories, and components, from manufacturer.
1. Certificate of compliance.
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.
3. Detailed description of equipment anchorage devices on which the certification is based, and their installation requirements.
D. Product Certificates: For each VFC from manufacturer.
E. Harmonic Analysis Report: Provide Project-specific calculations and manufacturer's statement of compliance with IEEE 519.
F. Source quality-control reports.
G. Field quality-control reports.
H. Sample Warranty: For special warranty.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For VFCs to include in emergency, operation, and maintenance manuals.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 3
1. In addition to items specified in Section 017823 "Operation and Maintenance Data," include the following:
a. Manufacturer's written instructions for testing and adjusting thermal-magnetic circuit breaker and motor-circuit protector trip settings.
b. Manufacturer's written instructions for setting field-adjustable overload relays.
c. Manufacturer's written instructions for testing, adjusting, and reprogramming microprocessor control modules.
d. Manufacturer's written instructions for setting field-adjustable timers, controls, and status and alarm points.
e. Load-Current and Overload-Relay Heater List: Compile after motors have been installed, and arrange to demonstrate that selection of heaters suits actual motor nameplate, full-load currents.
f. Load-Current and List of Settings of Adjustable Overload Relays: Compile after motors have been installed, and arrange to demonstrate that switch settings for motor-running overload protection suit actual motors to be protected.
1.7 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Power Fuses: Equal to [10] <Insert number> percent of quantity installed for each size and type, but no fewer than [three] <Insert number> of each size and type.
2. Control Power Fuses: Equal to [10] <Insert number> percent of quantity installed for each size and type, but no fewer than [two] <Insert number> of each size and type.
3. Indicating Lights: [Two] <Insert number> of each type and color installed.
4. Auxiliary Contacts: Furnish [one] <Insert number> spare(s) for each size and type of magnetic controller installed.
5. Power Contacts: Furnish [three] <Insert number> spares for each size and type of magnetic contactor installed.
6. <Insert extra materials>.
1.8 QUALITY ASSURANCE
A. Testing Agency Qualifications: Accredited by NETA.
1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing.
1.9 DELIVERY, STORAGE, AND HANDLING
A. If stored in space that is not permanently enclosed and air conditioned, remove loose packing and flammable materials from inside controllers and [install temporary electric heating, with at least 250 W per controller] [connect factory-installed space heaters to temporary electrical service].
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 4
B. Product Selection for Restricted Space: Drawings indicate maximum dimensions for VFCs, including clearances between VFCs, and adjacent surfaces and other items.
1.10 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace VFCs that fail in materials or workmanship within specified warranty period.
1. Warranty Period: [Five] <Insert number> years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. <Double click here to find, evaluate, and insert list of manufacturers and products.>
2.2 SYSTEM DESCRIPTION
A. General Requirements for VFCs:
1. VFCs and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2. Comply with NEMA ICS 7, NEMA ICS 61800-2, and [UL 508A] [UL 508C] <Insert standard>.
B. Application: [Constant torque] [and] [variable torque] <Insert application>.
C. VFC Description: Variable-frequency motor controller, consisting of power converter that employs pulse-width-modulated inverter, factory built and tested in an enclosure, with integral disconnecting means and overcurrent and overload protection; listed and labeled by an NRTL as a complete unit; arranged to provide self-protection, protection, and variable-speed control of one or more three-phase induction motors by adjusting output voltage and frequency.
1. Units suitable for operation of NEMA MG 1, Design A and Design B motors, as defined by NEMA MG 1, Section IV, Part 30, "Application Considerations for Constant Speed
Motors Used on a Sinusoidal Bus with Harmonic Content and General Purpose Motors
Used with Adjustable-Voltage or Adjustable-Frequency Controls or Both."
2. Units suitable for operation of inverter-duty motors as defined by NEMA MG 1, Section IV, Part 31, "Definite-Purpose Inverter-Fed Polyphase Motors."
3. Listed and labeled for integrated short-circuit current (withstand) rating by an NRTL acceptable to authorities having jurisdiction.
D. Design and Rating: Match load type, such as fans, blowers, and pumps; and type of connection used between motor and load such as direct or through a power-transmission connection.
E. Output Rating: Three phase; 10 to [60 Hz, with voltage proportional to frequency throughout voltage range] [66 Hz, with torque constant as speed changes]; maximum voltage equals input voltage.
http://www.specagent.com/LookUp/?ulid=2177&mf=04&src=wd
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 5
F. Unit Operating Requirements:
1. Input AC Voltage Tolerance: Plus 10 and minus [10] [15] percent of VFC input voltage rating.
2. Input AC Voltage Unbalance: Not exceeding [3] [5] percent.
3. Input Frequency Tolerance: Plus or minus 3 percent of VFC frequency rating.
4. Minimum Efficiency: [96] [97] <Insert number> percent at 60 Hz, full load.
5. Minimum Displacement Primary-Side Power Factor: [96] [98] <Insert number> percent under any load or speed condition.
6. Minimum Short-Circuit Current (Withstand) Rating: [10] [22] [65] [100] <Insert value> kA.
7. Ambient Temperature Rating: Not less than 32 deg F (0 deg C) and not exceeding 104 deg F (40 deg C).
8. Humidity Rating: Less than 95 percent (noncondensing).
9. Altitude Rating: Not exceeding 3300 feet (1000 m).
10. Vibration Withstand: Comply with NEMA ICS 61800-2.
11. Overload Capability: [1.1] [1.5] times the base load current for 60 seconds; minimum of
1.8 times the base load current for three seconds.
12. Starting Torque: Minimum 100 percent of rated torque from 3 to 60 Hz.
13. Speed Regulation: Plus or minus [5] [10] percent.
14. Output Carrier Frequency: Selectable; 0.5 to [15] <insert number> kHz.
15. Stop Modes: Programmable; includes fast, free-wheel, and dc injection braking.
G. Inverter Logic: Microprocessor based, [16] [32] bit, isolated from all power circuits.
H. Isolated Control Interface: Allows VFCs to follow remote-control signal over a minimum 40:1 speed range.
1. Signal: [Electrical] [Pneumatic].
I. Internal Adjustability Capabilities:
1. Minimum Speed: 5 to 25 percent of maximum rpm.
2. Maximum Speed: 80 to 100 percent of maximum rpm.
3. Acceleration: [0.1 to 999.9] <Insert range> seconds.
4. Deceleration: [0.1 to 999.9] <Insert range> seconds.
5. Current Limit: 30 to minimum of 150 percent of maximum rating.
6. <Insert adjustment and parameters>.
J. Self-Protection and Reliability Features:
1. Surge Suppression: Factory installed as an integral part of the VFC, complying with
UL 1449 SPD, Type 1 or Type 2.
2. Surge Suppression: Field-mounted surge suppressors complying with Section 264313
"Surge Protection for Low-Voltage Electrical Power Circuits," UL 1449 SPD, Type 2.
3. Loss of Input Signal Protection: Selectable response strategy, including speed default to a percent of the most recent speed, a preset speed, or stop; with alarm.
4. Under- and overvoltage trips.
5. Inverter overcurrent trips.
6. VFC and Motor-Overload/Overtemperature Protection: Microprocessor-based thermal protection system for monitoring VFCs and motor thermal characteristics, and for
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 6
providing VFC overtemperature and motor-overload alarm and trip; settings selectable via the keypad.
7. Critical frequency rejection, with [three] <Insert number> selectable, adjustable deadbands.
8. Instantaneous line-to-line and line-to-ground overcurrent trips.
9. Loss-of-phase protection.
10. Reverse-phase protection.
11. Short-circuit protection.
12. Motor-overtemperature fault.
13. <Insert protection or reliability feature>.
K. Automatic Reset/Restart: Attempt three restarts after drive fault or on return of power after an interruption and before shutting down for manual reset or fault correction; adjustable delay time between restart attempts.
L. Power-Interruption Protection: To prevent motor from re-energizing after a power interruption until motor has stopped, unless "Bidirectional Autospeed Search" feature is available and engaged.
M. Bidirectional Autospeed Search: Capable of starting VFC into rotating loads spinning in either direction and returning motor to set speed in proper direction, without causing damage to drive, motor, or load.
N. Torque Boost: Automatically varies starting and continuous torque to at least 1.5 times the minimum torque to ensure high-starting torque and increased torque at slow speeds.
O. Motor Temperature Compensation at Slow Speeds: Adjustable current fall-back based on output frequency for temperature protection of self-cooled, fan-ventilated motors at slow speeds.
P. Integral Input Disconnecting Means and OCPD: [UL 489, instantaneous-trip circuit breaker]
[UL 489, molded-case switch, with power fuse block and current-limiting fuses] [UL 489, thermal-magnetic circuit breaker] [NEMA KS 1, nonfusible switch, with power fuse block and current-limiting fuses] [NEMA KS 1, fusible switch] with pad-lockable, door-mounted handle mechanism.
1. Disconnect Rating: Not less than 115 percent of VFC input current rating.
2. Disconnect Rating: Not less than 115 percent of NFPA 70 motor full-load current rating or VFC input current rating, whichever is larger.
3. Auxiliary Contacts: NO or NC, arranged to activate before switch blades open.
4. Auxiliary contacts "a" and "b" arranged to activate with circuit-breaker handle.
5. [NC] [NO] alarm contact that operates only when circuit breaker has tripped.
2.3 PERFORMANCE REQUIREMENTS
A. Seismic Performance: VFCs shall withstand the effects of earthquake motions determined according to ASCE/SEI 7. The designated VFCs shall be tested and certified by an NRTL as meeting the ICC-ES AC 156 test procedure requirements.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 7
1. The term "withstand" means "the unit will remain in place without separation of any parts when subjected to the seismic forces specified[ and the unit will be fully operational after the seismic event]."
2.4 CONTROLS AND INDICATION
A. Status Lights: Door-mounted LED indicators displaying the following conditions:
1. Power on.
2. Run.
3. Overvoltage.
4. Line fault.
5. Overcurrent.
6. External fault.
7. <Insert condition>.
B. Panel-Mounted Operator Station: Manufacturer's standard front-accessible, sealed keypad and plain-English-language digital display; allows complete programming, program copying, operating, monitoring, and diagnostic capability.
1. Keypad: In addition to required programming and control keys, include keys for HAND, OFF, and AUTO modes.
2. Security Access: Provide electronic security access to controls through identification and password with at least three levels of access: View only; view and operate; and view, operate, and service.
a. Control Authority: Supports at least four conditions: Off, local manual control at
VFC, local automatic control at VFC, and automatic control through a remote source.
C. Historical Logging Information and Displays:
1. Real-time clock with current time and date.
2. Running log of total power versus time.
3. Total run time.
4. Fault log, maintaining last [four] <Insert number> faults with time and date stamp for each.
5. <Insert information or display>.
D. Indicating Devices: Digital display[ and additional readout devices as required,] mounted flush in VFC door and connected to display VFC parameters including, but not limited to:
1. Output frequency (Hz).
2. Motor speed (rpm).
3. Motor status (running, stop, fault).
4. Motor current (amperes).
5. Motor torque (percent).
6. Fault or alarming status (code).
7. PID feedback signal (percent).
8. DC-link voltage (V dc).
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 8
9. Set point frequency (Hz).
10. Motor output voltage (V ac).
11. <Insert parameter>.
E. Control Signal Interfaces:
1. Electric Input Signal Interface:
a. A minimum of [two] <Insert number> programmable analog inputs: [0- to 10-
V dc] [4- to 20-mA dc] [Operator-selectable "x"- to "y"-mA dc] <Insert signal parameters>.
b. A minimum of [six] <Insert number> multifunction programmable digital inputs.
2. Pneumatic Input Signal Interface: 3 to 15 psig (20 to 104 kPa).
3. Remote Signal Inputs: Capability to accept any of the following speed-setting input signals from the DDC system for HVAC or other control systems:
a. 0- to 10-V dc.
b. 4- to 20-mA dc.
c. Potentiometer using up/down digital inputs.
d. Fixed frequencies using digital inputs.
e. <Insert signal input>.
4. Output Signal Interface: A minimum of [one] <Insert number> programmable analog output signal(s) ([0- to 10-V dc] [4- to 20-mA dc] [operator-selectable "x"- to "y"-mA dc] <Insert signal parameters>), which can be configured for any of the following:
a. Output frequency (Hz).
b. Output current (load).
c. DC-link voltage (V dc).
d. Motor torque (percent).
e. Motor speed (rpm).
f. Set point frequency (Hz).
g. <Insert indication>.
5. Remote Indication Interface: A minimum of [two] <Insert number> programmable dry-circuit relay outputs (120-V ac, 1 A) for remote indication of the following:
a. Motor running.
b. Set point speed reached.
c. Fault and warning indication (overtemperature or overcurrent).
d. PID high- or low-speed limits reached.
e. <Insert indication>.
F. PID Control Interface: Provides closed-loop set point, differential feedback control in response to dual feedback signals. Allows for closed-loop control of fans and pumps for pressure, flow, or temperature regulation.
1. Number of Loops: [One] [Two] <Insert number>.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 9
G. Interface with DDC System for HVAC: Factory-installed hardware and software shall interface with DDC system for HVAC to monitor, control, display, and record data for use in processing reports. VFC settings shall be retained within VFC's nonvolatile memory.
1. Hardwired Points:
a. Monitoring: On-off status, <Insert monitoring point>.
b. Control: On-off operation, <Insert control point>.
2. Communication Interface: Comply with [ASHRAE 135] <Insert type of interface>.
Communication shall interface with DDC system for HVAC to remotely control and monitor lighting from a DDC system for HVAC operator workstation. Control features and monitoring points displayed locally at lighting panel shall be available through the
DDC system for HVAC.
2.5 LINE CONDITIONING AND FILTERING
A. Input Line Conditioning: Based on the manufacturer's harmonic analysis study and report, provide input filtering, as required, to limit total demand (harmonic current) distortion and total harmonic voltage demand at the defined point of common coupling to meet IEEE 519 recommendations.
B. Output Filtering: <Insert requirements>.
C. EMI/RFI Filtering: CE marked; certify compliance with IEC 61800-3 for [Category C2]
<Insert category>.
D. EMI/RFI Filtering: <Insert requirements>.
2.6 BYPASS SYSTEMS
A. Bypass Operation: Safely transfers motor between power converter output and bypass circuit, manually, automatically, or both. Selector switches set modes and indicator lights indicate mode selected. Unit is capable of stable operation (starting, stopping, and running) with motor completely disconnected from power converter.
B. Bypass Mode: Manual operation only; requires local operator selection at VFC. Transfer between power converter and bypass contactor, and retransfer shall only be allowed with the motor at zero speed.
C. Bypass Mode: Field-selectable automatic or manual, allows local and remote transfer between power converter and bypass contactor and retransfer, either via manual operator interface or automatic-control system feedback.
D. Bypass Controller: Two-contactor-style bypass allows motor operation via the power converter or the bypass controller[; with input isolating switch and barrier arranged to isolate the power converter and permit safe troubleshooting and testing, both energized and de-energized, while motor is operating in bypass mode].
1. Bypass Contactor: Load-break, [IEC] [NEMA]-rated contactor.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 10
2. Output Isolating Contactor: Non-load-break, [IEC] [NEMA]-rated contactor.
3. Isolating Switch: Non-load-break switch arranged to isolate power converter and permit safe troubleshooting and testing of the power converter, both energized and de-energized, while motor is operating in bypass mode; pad-lockable, door-mounted handle mechanism.
E. Bypass Controller: Three-contactor-style bypass allows motor operation via the power converter or the bypass controller[; with input isolating switch and barrier] arranged to isolate the power converter input and output and permit safe testing[ and troubleshooting] of the power converter, both energized and de-energized, while motor is operating in bypass mode.
1. Bypass Contactor: Load-break, [IEC] [NEMA]-rated contactor.
2. Input and Output Isolating Contactors: Non-load-break, [IEC] [NEMA]-rated contactors.
3. Isolating Switch: Non-load-break switch arranged to isolate power converter and permit safe troubleshooting and testing of the power converter, both energized and de-energized, while motor is operating in bypass mode; pad-lockable, door-mounted handle mechanism.
F. Bypass Contactor Configuration: [Full-voltage (across-the-line)] [Reduced-voltage
(autotransformer)] <Insert type> type.
1. NORMAL/BYPASS selector switch.
2. HAND/OFF/AUTO selector switch.
3. NORMAL/TEST Selector Switch: Allows testing and adjusting of VFC while the motor is running in the bypass mode.
4. Contactor Coils: Pressure-encapsulated type[ with coil transient suppressors].
a. Operating Voltage: Depending on contactor NEMA size and line-voltage rating, manufacturer's standard matching control power or line voltage.
b. Power Contacts: Totally enclosed, double break, and silver-cadmium oxide;
assembled to allow inspection and replacement without disturbing line or load wiring.
5. Control Circuits: [120] <Insert number>-V ac; obtained from [integral CPT, with primary and secondary fuses] <Insert source of control power>, with [CPT] [control power source] of sufficient capacity to operate all integral devices and remotely located pilot, indicating, and control devices.
a. CPT Spare Capacity: [50] [100] [200] <Insert number> VA.
6. Overload Relays: NEMA ICS 2.
a. Melting-Alloy Overload Relays:
1) Inverse-time-current characteristic.
2) [Class 10] [Class 20] [Class 30] tripping characteristic.
3) Heaters in each phase matched to nameplate full-load current of actual protected motor and with appropriate adjustment for duty cycle.
b. Bimetallic Overload Relays:
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 11
1) Inverse-time-current characteristic.
2) [Class 10] [Class 20] [Class 30] tripping characteristic.
3) Heaters in each phase matched to nameplate full-load current of actual protected motor and with appropriate adjustment for duty cycle.
4) Ambient compensated.
5) Automatic resetting.
c. Solid-State Overload Relays:
1) Switch or dial selectable for motor-running overload protection.
2) Sensors in each phase.
3) [Class 10] [Class 20] [Class 10/20 selectable] tripping characteristic selected to protect motor against voltage and current unbalance and single phasing.
4) Class II ground-fault protection, with start and run delays to prevent nuisance trip on starting.
5) Analog communication module.
d. [NC] [NO] isolated overload alarm contact.
e. External overload, reset push button.
2.7 OPTIONAL FEATURES
A. Multiple-Motor Capability: VFC suitable for variable-speed service to multiple motors.
Overload protection shuts down VFC and motors served by it, and generates fault indications when overload protection activates.
1. Configure to allow two or more motors to operate simultaneously at the same speed;
separate overload relay for each controlled motor.
2. Configure to allow two motors to operate separately; operator selectable via local or remote switch or contact closures; single overload relay for both motors; separate output magnetic contactors for each motor.
3. Configure to allow two motors to operate simultaneously and in a lead/lag mode, with one motor operated at variable speed via the power converter and the other at constant speed via the bypass controller; separate overload relay for each controlled motor.
B. Damper control circuit with end-of-travel feedback capability.
C. Sleep Function: Senses a minimal deviation of a feedback signal and stops the motor. On an increase in speed-command signal deviation, VFC resumes normal operation.
D. Motor Preheat Function: Preheats motor when idle to prevent moisture accumulation in the motor.
E. Firefighter's Override (Smoke Purge) Input: On a remote contact closure from [the firefighter's control station] [smoke-control fan controller] <Insert location>, this password-protected input:
1. Overrides all other local and external inputs (analog/digital, serial communication, and all keypad commands).
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 12
2. Forces VFC to operate motor, without any other run or speed command, at a field-adjustable, preset speed.
3. Forces VFC to transfer to bypass mode and operate motor at full speed.
4. Causes display of override mode on the VFC display.
5. Reset VFC to normal operation on removal of override signal [automatically]
[manually].
F. Remote Indicating Circuit Terminals: Mode selection, controller status, and controller fault.
G. Remote digital operator kit.
H. Communication Port: RS-232 port, USB 2.0 port, or equivalent connection capable of connecting a printer[ and a notebook computer].
I. <Insert feature>.
2.8 ENCLOSURES
A. VFC Enclosures: NEMA 250, to comply with environmental conditions at installed location.
1. Dry and Clean Indoor Locations: [Type 1] <Insert type>.
2. Outdoor Locations: [Type 3R] [Type 4X] <Insert type>.
3. [Kitchen] [Wash-Down] Areas: [Type 4X] <Insert type>, [stainless steel] <Insert material>.
4. Other Wet or Damp Indoor Locations: [Type 4] <Insert type>.
5. Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive Liquids:
Type 12.
6. <Insert enclosure requirements>.
B. Plenum Rating: UL 1995; NRTL certification label on enclosure, clearly identifying VFC as
"Plenum Rated."
2.9 ACCESSORIES
A. General Requirements for Control-Circuit and Pilot Devices: NEMA ICS 5; factory installed in
VFC enclosure cover unless otherwise indicated.
1. Push Buttons: [Covered] [Lockable] [Shielded] [Unguarded].
2. Pilot Lights: Push to test.
3. Selector Switches: [Rotary] <Insert description> type.
4. Stop and Lockout Push-Button Station: Momentary-break, push-button station with a factory-applied hasp arranged so padlock can be used to lock push button in depressed position with control circuit open.
B. [NC] [NO] [Reversible NC/NO] bypass contactor auxiliary contact(s).
C. Control Relays: Auxiliary and adjustable [pneumatic] [solid-state] time-delay relays.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 13
D. Phase-Failure, Phase-Reversal, and Undervoltage and Overvoltage Relays: Solid-state sensing circuit with isolated output contacts for hard-wired connections. Provide adjustable undervoltage, overvoltage, and time-delay settings.
1. Current Transformers: Continuous current rating, basic impulse insulating level (BIL) rating, burden, and accuracy class suitable for connected circuitry. Comply with
IEEE C57.13.
E. Supplemental Digital Meters:
1. Elapsed-time meter.
2. Kilowatt meter.
3. Kilowatt-hour meter.
F. Breather and drain assemblies, to maintain interior pressure and release condensation in
NEMA 250, [Type 4] [Type 4X] [Type 12] <Insert type> enclosures installed outdoors or in unconditioned interior spaces subject to humidity and temperature swings.
G. Space heaters, with NC auxiliary contacts, to mitigate condensation in NEMA 250, [Type 3R]
[Type 4X] [Type 12] <Insert type> enclosures installed outdoors or in unconditioned interior spaces subject to humidity and temperature swings.
H. Cooling Fan and Exhaust System: For NEMA 250, [Type 1] [Type 12] <Insert enclosure type>; UL 508 component recognized: Supply fan, with [composite] [stainless-steel] <Insert material> intake and exhaust grills [and filters]; [120] <Insert number>-V ac; obtained from
[integral CPT] <Insert source of control power>.
I. Sun shields installed on fronts, sides, and tops of enclosures installed outdoors and subject to direct and extended sun exposure.
J. Spare control-wiring terminal blocks[; unwired][; wired].
K. <Insert accessory>.
2.10 SOURCE QUALITY CONTROL
A. Testing: Test and inspect VFCs according to requirements in [NEMA ICS 61800-2] <Insert standard>.
1. Test each VFC while connected to [its specified motor] [a motor that is comparable to that for which the VFC is rated].
2. Verification of Performance: Rate VFCs according to operation of functions and features specified.
B. VFCs will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 14
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas, surfaces, and substrates to receive VFCs, with Installer present, for compliance with requirements for installation tolerances, <insert Project-specific conditions,> and other conditions affecting performance of the Work.
B. Examine VFC before installation. Reject VFCs that are wet, moisture damaged, or mold damaged.
C. Examine roughing-in for conduit systems to verify actual locations of conduit connections before VFC installation.
D. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work
E. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Wall-Mounting Controllers: Install with tops at uniform height and with disconnect operating handles not higher than 79 inches (2000 mm) above finished floor, unless otherwise indicated, and by bolting units to wall or mounting on lightweight structural-steel channels bolted to wall.
For controllers not on walls, provide freestanding racks complying with Section 260529
"Hangers and Supports for Electrical Systems."
B. Floor-Mounting Controllers: Install VFCs on 4-inch (100-mm) nominal thickness concrete base.
Comply with requirements for concrete base specified in Section 033000 "Cast-in-Place
Concrete."
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch (450-mm) centers around the full perimeter of concrete base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported equipment.
C. Roof-Mounting Controllers: Install VFC on roofs with tops at uniform height and with disconnect operating handles not higher than 79 inches (2000 mm) above finished roof surface unless otherwise indicated, and by bolting units to curbs or mounting on freestanding, lightweight, structural-steel channels bolted to curbs. Seal roof penetrations after raceways are installed.
1. Curbs and roof penetrations are specified in Section 077200 "Roof Accessories."
2. Structural-steel channels are specified in Section 260529 "Hangers and Supports for
Electrical Systems."
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 15
D. Seismic Bracing: Comply with requirements specified in Section 260548.16 "Seismic Controls for Electrical Systems."
E. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from enclosures and components.
F. Install fuses in each fusible-switch VFC.
G. Install fuses in control circuits if not factory installed. Comply with requirements in
Section 262813 "Fuses."
H. Install heaters in thermal-overload relays. Select heaters based on actual nameplate full-load amperes after motors are installed.
I. Install, connect, and fuse thermal-protector monitoring relays furnished with motor-driven equipment.
J. Comply with NECA 1.
3.3 CONTROL WIRING INSTALLATION
A. Install wiring between VFCs and remote devices[ and facility's central-control system].
Comply with requirements in Section 260523 "Control-Voltage Electrical Power Cables."
B. Bundle, train, and support wiring in enclosures.
C. Connect selector switches and other automatic-control devices where applicable.
1. Connect selector switches to bypass only those manual- and automatic-control devices that have no safety functions when switches are in manual-control position.
2. Connect selector switches with control circuit in both manual and automatic positions for safety-type control devices such as low- and high-pressure cutouts, high-temperature cutouts, and motor-overload protectors.
3.4 IDENTIFICATION
A. Identify VFCs, components, and control wiring. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."
1. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs.
2. Label each VFC with engraved nameplate.
3. Label each enclosure-mounted control and pilot device.
B. Operating Instructions: Frame printed operating instructions for VFCs, including control sequences and emergency procedures. Fabricate frame of finished metal, and cover instructions with clear acrylic plastic. Mount on front of VFC units.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 16
3.5 FIELD QUALITY CONTROL
A. Testing Agency: [Owner will engage] [Engage] a qualified testing agency to perform tests and inspections.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.
C. Perform tests and inspections[ with the assistance of a factory-authorized service representative].
D. Acceptance Testing Preparation:
1. Test insulation resistance for each VFC element, bus, component, connecting supply, feeder, and control circuit.
2. Test continuity of each circuit.
E. Tests and Inspections:
1. Inspect VFC, wiring, components, connections, and equipment installation.[ Test and adjust controllers, components, and equipment.]
2. Test insulation resistance for each VFC element, component, connecting motor supply, feeder, and control circuits.
3. Test continuity of each circuit.
4. Verify that voltages at VFC locations are within 10 percent of motor nameplate rated voltages. If outside this range for any motor, notify [Architect] [Construction
Manager] [Owner] before starting the motor(s).
5. Test each motor for proper phase rotation.
6. Perform tests according to the Inspection and Test Procedures for Adjustable Speed
Drives stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.
7. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.
8. Perform the following infrared (thermographic) scan tests and inspections, and prepare reports:
a. Initial Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each VFC. Remove front panels so joints and connections are accessible to portable scanner.
b. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each VFC 11 months after date of Substantial Completion.
c. Instruments and Equipment: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.
9. Test and adjust controls, remote monitoring, and safeties. Replace damaged and malfunctioning controls and equipment.
F. VFCs will be considered defective if they do not pass tests and inspections.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 17
G. Prepare test and inspection reports, including a certified report that identifies the VFC and describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations made after remedial action.
3.6 STARTUP SERVICE
A. [Engage a factory-authorized service representative to perform] [Perform] startup service.
1. Complete installation and startup checks according to manufacturer's written instructions.
2. <Insert startup steps if any>.
3.7 ADJUSTING
A. Program microprocessors for required operational sequences, status indications, alarms, event recording, and display features. Clear events memory after final acceptance testing and prior to
Substantial Completion.
B. Set field-adjustable switches, auxiliary relays, time-delay relays, timers, and overload-relay pickup and trip ranges.
C. Adjust the trip settings of instantaneous-only circuit breakers and thermal-magnetic circuit breakers with adjustable, instantaneous trip elements. Initially adjust to 6 times the motor nameplate full-load amperes and attempt to start motors several times, allowing for motor cool-down between starts. If tripping occurs on motor inrush, adjust settings in increments until motors start without tripping. Do not exceed 8 times the motor full-load amperes (or 11 times for NEMA Premium Efficient motors if required). Where these maximum settings do not allow starting of a motor, notify [Architect] [Construction Manager] [Owner] before increasing settings.
D. Set the taps on reduced-voltage autotransformer controllers.
E. Set field-adjustable circuit-breaker trip ranges[ as specified in Section 260573.16
"Coordination Studies."]
F. Set field-adjustable pressure switches.
3.8 PROTECTION
A. Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's written instructions until controllers are ready to be energized and placed into service.
B. Replace VFCs whose interiors have been exposed to water or other liquids prior to Substantial
Completion.
3.9 DEMONSTRATION
A. [Engage a factory-authorized service representative to train] [Train] Owner's maintenance personnel to adjust, operate, reprogram, and maintain VFCs.
VARIABLE-FREQUENCY MOTOR CONTROLLERS SECTION 262923 - 18
END OF SECTION 262923