J.3.7_E1-102_Existing Residential Site Plan_AMD003.pdf

PDF 843 KB Posted

Attached to
USAID/South Sudan Juba Compound Electrical Upgrade
Solicitation number
72066821R00014
Issued by

About this file

This document includes an existing residential site plan and details for a USAID federal contract opportunity for electrical upgrades at the USAID compound in Juba, South Sudan. The site plan drawing shows the existing layout of buildings, structures, and electrical equipment at the compound. The federal contract opportunity is a solicitation from USAID/South Sudan seeking phase one proposals to provide services for upgrading the electrical systems as depicted. Services will include disconnecting and removing existing electrical equipment, feeders, and panels shown on the site plan drawing and installing new equipment and connections per the design. The solicitation number is 72066821R00014 with responses due from qualified organizations by the dates specified in the solicitation documentation.

View the file

Other files

File Type Posted
RFP No. 72066821R00014_Amendment No. 4_28 October, 2021.pdf PDF
Amendment 03 RFP 72066821R00014 Juba Elec. Upgrade..pdf PDF
J.3.8_E1-702_Existing Residential Compound Singe Line Diagram_AMD003.pdf PDF
J.3.8_E1-704_Residential Compound Single Line Diagram_AMD003.pdf PDF
J.3.7_E1-104_Residential Compound Site Plan_AMD003.pdf PDF
J.3.3.2_Design Intent Report_AMD003.pdf PDF
J.3.7_E1-001_General Notes, Legend and Abbreviations_AMD003.pdf PDF
J.3.7_E1-101_Existing Office Compound Site Plan_AMD003.pdf PDF
J.3.8_E1-701_Existing Office Single Diagram. AMD003.pdf PDF
J.3.7_E1-103_Office Compound Site Plan_AMD003.pdf PDF
J.3.3.2_Design Intent Report Cover_AMD003.pdf PDF
J.3.8_E1-703_Office Compound Single Line Diagram_AMD003.pdf PDF
J.3.7_G001_Compound Electrical Upgrade_Cover Page_AMD003.pdf PDF
J.3.8_E1-701_Existing Office Compound Single Line Diagram_AMD003.pdf PDF
Q and A 72066821R00014 for USAID South Sudan Juba Compound Electrical Upgrade.pdf PDF
RFP 72066821R00014 Juba Compound Electrical Upgrade Amendment 0002.pdf PDF
72066821R00014 Amendment 01 - Electrical Retrofit.pdf PDF
Attachment 1 -013550 ConSec Juba Electrical Upgrade Project Final.pdf PDF
Attachment 3 - 230905 INSTRUMENTATION AND CONTROLS FOR HVAC OBO.pdf PDF
Attachment 3 - 262500 ENCLOSED BUS ASSEMBLIES.pdf PDF
Attachment 1 -013525 Safety Juba Electrical Upgrades Final.pdf PDF
Attachment 1 -019115 Commissioning Juba Electrical Upgrades Final.pdf PDF
Attachment 4 - E1-104 RESIDENTIAL COMPOUND SITE PLAN.pdf PDF
Attachment 4 - E1-101 EXISTING OFFICE COMPOUND SITE PLAN.pdf PDF
Attachment 3 - 261214 MEDIUM-VOLTAGE TRANSFORMERS.pdf PDF
Attachment 1 -017905 DemonstrationTraining Juba Electrical Upgrades Final.pdf PDF
Attachment 1 -017825 O and M Juba Electrical Upgrades Final.pdf PDF
Attachment 4 - E1-103 OFFICE COMPOUND SITE PLAN.pdf PDF
Attachment 5-Design Submittal Requirements.xlsx XLSX spreadsheet
Attachment 3 - 262300 LOW-VOLTAGE SWITCHGEAR JAN17RR.pdf PDF
Attachment 1 -ToC SM DB wo CW Juba Electrical Upgrades Final.pdf PDF
Attachment 4 - M1-706 GENERATOR DIESEL FUEL SYSTEM PIPING SCHEMATIC.pdf PDF
Attachment 4 - M1-705 GENERATOR DIESEL FUEL SYSTEM PIPING SCHEMATIC.pdf PDF
Attachment 4 - E1-701 EXISTING OFFICE COMPOUND SINGLE LINE DIAGRAM.pdf PDF
Attachment 4 - E1-102 EXISTING RESIDENTIAL COMPOUND SITE PLAN.pdf PDF
Attachment 4 - E1-704 RESIDENTIAL COMPOUND SINGLE LINE DIAGRAM.pdf PDF
Attachment 4 - M1-101 EXISTING OFFICE COMPOUND ENLARGED SITE PLAN.pdf PDF
Attachment 3 - 260518 LOW-VOLT POWER CONDUCTORS JAN19.pdf PDF
Attachment 4 - M1-104 RESIDENTIAL COMPOUND ENLARGED SITE PLAN.pdf PDF
Attachment 1 - 011005 Exec and Coord Juba Electrical Upgrades Final.pdf PDF
Attachment 3 - 335617 UNDERGROUND FUEL STORAGE TANKS AND DISTRIBUTION OBO.pdf PDF
Attachment 3 - 260915 ELECTRICAL POWER MONITOR JAN20.pdf PDF
Attachment 3 - 260525 GROUNDING-BONDING-ELEC-SYSTEMS JAN19.pdf PDF
Attachment 7 - Juba USAID Geotechnical Report dated Feb 2008.pdf PDF
Attachment 4 - E1-001 GENERAL NOTES LEGEND AND ABBREVIATIONS.pdf PDF
Attachment 1 -ds1663.PDF PDF
Attachment 3 - 262413 SWITCHBOARDS FL.pdf PDF
Attachment 3 - 262923 VARIABLE-FREQUENCY MOTOR CONTROLLERS FL.pdf PDF
Attachment 3 - 62816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS FL.pdf PDF
Attachment 1 -014010 Quality Juba Electrical Upgrades Final.pdf PDF
Show 40 more

Latest 50 of 87 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7 9 11 13

1412108

19 20

HOUSE 4

HOUSE 2

HOUSE 3

MISSION DIRECTOR

MSGQ

HOUSE 5

SOUTH CAC

NORTH

CAC

24A

24B

23A

23B

22B22A

21B21A20B20A19B19A

18B18A

17B

17A

16B

16A

15A15B

25A25B26A26B

27A 27B

28A

28B

29A

29B

30A 30B

31A

31B

32A 32B

33B

33A

34A

34B

35A

35B

6A 6B 7A 7B 9A 9B 11A 11B 13A 13B

14B14A12B12A10B10A8B8A

CH2-DP

(TOWNHOUSE)

DP 2

RHU-2

RHU-1

RHU-3

RHU-4

PNL1

(ALAMO

VILLAGE)

22 (TOWNHOUSE)

20 (TOWNHOUSE)

HOUSE 3

GYM-DPGYM OFFICE

KITCHEN

(NEW KITCHEN)

MDP-01 (PERIMETER WALL)

MDP2

MDP2A

LS

(LOCAL

STAFF)

BLUE

SAFE

HAVEN

BSH (BLUE

SAFE HAVEN)

GB1(NORTH CAC)

ORANGE

SAFE

HAVEN

MDP1A

MDP1

RC ANNEX

HOUSE 5

HS5

(HOUSE 5)

E

HOUSE 4

KP (OLD

KITCHEN)

HOUSE 2

TOC

GUARD BOOTH

HOUSE NO

CMR

ATS

CMR GENERATOR

1 TYP

TEMP GEN

TECH HOUSE

LIFT

STATION

WASTE WATER

TREATMENT PLANT

SDP1 (GEN BLDG

PANELBOARD)

PLAN REFRENCE NOTES:

TR

A

FFIC

LIG

H T

TR

A

FFIC

LIG

H T

38 37

MULTIPURPOSE

MPR

MOTOR

POOL

OSH

WASTE WATER

TREATMENT PLANT

CONTROL

ROOM

TONER

RADIO ROOM (VOA)

AEM

NEW

LAUNDRY

PNL L1

OLD

LAUNDRY

GEN - RC

AIR CONDITIONER GEN YARD

WTP

ATS ROOM

IT

PUMP

HOUSE

GYM AREA

TOILETS

DP1

PNL L2

PNL 38

DISCONNECT AND REMOVE EQUIPMENT AND EXISTING FEEDER SEGMENTS FROM

GENERATORS THROUGH MPD1, MDP1A, MDP2, MDP2A AS WELL AS THOSE BETWEEN

MDP1, MDP1A, MDP2, MDP2A AND THEIR LOADS.

DISCONNECT AND REPLACE EXISTING PANELBOARD AND CIRCUIT BREAKERS WITH NEW

PANELBOARD. MATCH EXISTING EQUIPMENT AND PROVIDE NEMA 3R ENCLOSURE IF

MOUNTED ON THE EXTERIOR. REFER TO DWG. E1-104 FOR NEW LOCATION.

DISCONNECT, REMOVE, AND RELOCATE PANELBOARD. EXTEND FEEDER WIRING AND

CONDUIT AS REQUIRED. REFER TO DWG. E1-104 FOR NEW LOCATION.

CONTACTOR FOR PUMPS NEEDS TO BE REMOVED FROM PANEL WITH NEW

STARTER/CIRCUIT.

REMOVE EXISTING UNDERGROUND FEEDER AND REPLACE WITH NEW UNDERGROUND

FEEDER. MATCH FEEDER SIZE AS REQUIRED.

REMOVE AND REPLACE EXISTING DISCONNECT SWITCH WITH A NEW NEMA 3R

DISCONNECT SWITCH. REFER TO DWG. E1-104 FOR NEW LOCATION.

REMOVE AND REPLACE J-BOX ON EXTERIOR WITH A NEW DISTRIBUTION PANEL. THE

J-BOX IS FED BY AN 80 AMP CIRCUIT BREAKER WITH TWO BRANCH CIRCUIT BREAKERS IN

THE J-BOX RATED FOR 225 AMPS. ONE FEEDS THE TOC AND THE UNIT ABOVE.

REMOVE AND REPLACE EXISTING DISCONNECT SWITCH WITH A NEW PANEL, THE

SERVICE HAS 2 FEEDERS.

REMOVE AND REPLACE DISCONNECT SWITCH & ENCLOSED BREAKER WITH A NEW

PANEL, THE SERVICE HAS 4 FEEDERS.

EXISTING ELECTRICAL SERVICE TO BE CONNECTED TO NEW DISTRIBUTION SYSTEM.

REFER TO DWG. E1-104 FOR NEW LOCATION OF CONNECTION.

CONTRACTOR TO DETERMINE THE FEEDER WIRE CONDITION AND REPLACE AS

REQUIRED. DISCONNECT FEEDER AND INSTALL UNDERGROUND.

METAL

SHED

PNL H2

PNL H4

SECURE

STORAGE

UTILITY

AREA

MEDICAL

PNL H1

PNL 40

LIFT STATION

CONTROL

PNL 3910

PNL 3710

PNL 4110

PNL H3

WWTP

PNL - CPN2

PNL - CMU1

DR1

ALCOVE GAZEBO

UP TO UNIT

ABOVE

EFF APT (4-TDY) ON

TOP OF SAFE HAVEN 10

DINING

KP

POOL PUMP

UP TO 2ND

FLOOR

ATS SPLICE

BOX

AFX

GENERAL NOTES:

THE FOLLOWING FACILITIES ARE UNDER DESIGN THAT ARE TO BE

CONSTRUCTED PRIOR TO THE COMPOUND ELECTRICAL PROJECT. COORDINATE

WITH OBO / COR.

· TEMPORARY GENERATOR PLANT WITH SWITCHBOARD SWBD-TGEN

· 1 OVER 1 HOUSING

· 3 OVER 3 HOUSING

· NEW KITCHEN

PNL 2 IT

RADIO IT

E1-102

0.039:1

PDM

WFS

049901E1-102.DWG

EXISTING RESIDENTIAL COMPOUND

SITE PLAN

A

B

C

1 2 3

D

E

F

G

H

4 5 6 7 98 10

I

J

K

L

M

N

O

P

1 2 3 4 5 6 7 98 10

11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

11 12 13 14 15 16 17

I

J

K

L

M

N

O

P

0 4M1M 2M

1:50

UNCLASSIFIED

UNCLASSIFIED

As Indicated

WARNING: This document is the property of the U.S. Government. Further reproduction and/or distribution outside the contractor team is prohibited without the express written approval of USAID.

CADD Plot Scale

Drawing Scale

USAID/PE/PBD

OBO Project Number

CADD File Name

USAID/PE/PM

Drawing Title

Release For Construction:

Drawn By

Checked By

Project Number

Classification

Date NumberSheet

0499.01

JULY 13, 2020

COMPOUND ELECTRICAL

UPGRADE

Juba, South Sudan

Revision Schedule

Rev Number Description Date

UNCLASSIFIED

ISSUE FOR BID

BRIDGING DOCUMENTS

N

N

Bridging

ISSUE FOR BID100% 100% BACK-CK

1 ADDENDUM 1 09/27/2021

EXISTING RESIDENTIAL SITE PLAN

SCALE: 1:300

E1-102

AutoCAD SHX Text Guard

AutoCAD SHX Text Bridge

AutoCAD SHX Text Lifting station

AutoCAD SHX Text

EX ROAD

AutoCAD SHX Text

EX ROAD

AutoCAD SHX Text Observation

AutoCAD SHX Text Tower

AutoCAD SHX Text Generator

AutoCAD SHX Text Building

AutoCAD SHX Text Surface Run-off Drain

AutoCAD SHX Text Tap

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

WV

AutoCAD SHX Text Multipurpose

AutoCAD SHX Text

AutoCAD SHX Text Air Container

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Gen = RC

File details come from the government source that posted it. Updated .