Attachment 3 - 260518 LOW-VOLT POWER CONDUCTORS JAN19.pdf

PDF 127 KB Posted

Attached to
USAID/South Sudan Juba Compound Electrical Upgrade Federal contract opportunity
Solicitation number
72066821R00014
Issued by
US Agency for International Development South Sudan

About this file

This document contains specifications for low-voltage electrical power conductors and cables for the USAID/South Sudan Juba Compound Electrical Upgrade project. The specifications require copper conductors rated 600V or less, with insulation types including THHN-THWN, XHHW, SO, or XHHW-2. Approved cable types depend on the intended use, such as XHHW or XHHW-2 for service entrance cables. Conductors must be properly supported and identified. After installation, field testing is required to certify compliance with electrical testing standards. Cables must be concealed where possible and sealed when penetrating fire barriers. The related federal contract opportunity is a solicitation from USAID/South Sudan seeking proposals from qualified organizations to provide services for the Juba Compound Electrical Upgrade project, with the goal of upgrading the electrical infrastructure at the USAID facility in Juba, South Sudan.

View the file

Other files for this federal contract opportunity

Other files attached to USAID/South Sudan Juba Compound Electrical Upgrade, newest first.
File Type Posted
RFP No. 72066821R00014_Amendment No. 4_28 October, 2021.pdf PDF
J.3.8_E1-704_Residential Compound Single Line Diagram_AMD003.pdf PDF
J.3.8_E1-701_Existing Office Single Diagram. AMD003.pdf PDF
J.3.7_E1-102_Existing Residential Site Plan_AMD003.pdf PDF
J.3.7_E1-101_Existing Office Compound Site Plan_AMD003.pdf PDF
Amendment 03 RFP 72066821R00014 Juba Elec. Upgrade..pdf PDF
J.3.8_E1-702_Existing Residential Compound Singe Line Diagram_AMD003.pdf PDF
J.3.7_E1-104_Residential Compound Site Plan_AMD003.pdf PDF
RFP 72066821R00014 Juba Compound Electrical Upgrade Amendment 0002.pdf PDF
Q and A 72066821R00014 for USAID South Sudan Juba Compound Electrical Upgrade.pdf PDF
Attachment 1 -013550 ConSec Juba Electrical Upgrade Project Final.pdf PDF
Attachment 1 - 011005 Exec and Coord Juba Electrical Upgrades Final.pdf PDF
Attachment 3 - 230905 INSTRUMENTATION AND CONTROLS FOR HVAC OBO.pdf PDF
Attachment 3 - 260508 COMMON WORK ELEC-COMM.pdf PDF
Attachment 3 - 261214 MEDIUM-VOLTAGE TRANSFORMERS.pdf PDF
Attachment 3 - 262725 WIRING DEVICES JAN19.pdf PDF
Attachment 3 - 262417 PANELBOARDS JAN19.pdf PDF
Attachment 3 - 262913 ENCLOSED CONTROLLERS JAN12.pdf PDF
Attachment 4 - E1-102 EXISTING RESIDENTIAL COMPOUND SITE PLAN.pdf PDF
Attachment 4 - E1-101 EXISTING OFFICE COMPOUND SITE PLAN.pdf PDF
Attachment 4 - M1-705 GENERATOR DIESEL FUEL SYSTEM PIPING SCHEMATIC.pdf PDF
Attachment 4 - M1-104 RESIDENTIAL COMPOUND ENLARGED SITE PLAN.pdf PDF
Attachment 4 - E1-701 EXISTING OFFICE COMPOUND SINGLE LINE DIAGRAM.pdf PDF
Attachment 6 - Design Intent Report.pdf PDF
Attachment 8-Past Performance Information Sheet.xlsx XLSX spreadsheet
SF1442-14b Juba Compound Electrical Upgrade.pdf PDF
Attachment 3 - 262500 ENCLOSED BUS ASSEMBLIES.pdf PDF
Attachment 1 -017825 O and M Juba Electrical Upgrades Final.pdf PDF
Attachment 3 - 260573 OVERCURRENT PROTECTIVE DEVICE STUDY JAN17R.pdf PDF
Attachment 3 - 260915 ELECTRICAL POWER MONITOR JAN20.pdf PDF
Attachment 3 - 260815 FIELD TESTING-INSPECTION ELECTRICAL.pdf PDF
Attachment 3 - 262300 LOW-VOLTAGE SWITCHGEAR JAN17RR.pdf PDF
Attachment 3 - 263354 JUCR UPS JAN19.pdf PDF
Attachment 3 - 335617 UNDERGROUND FUEL STORAGE TANKS AND DISTRIBUTION OBO.pdf PDF
Attachment 3 - 337105 UNDERGROUND DUCTS AND RACEWAYS JAN19.pdf PDF
Attachment 3 - 263600 TRANSFER SWITCHES FL.pdf PDF
Attachment 4 - E1-103 OFFICE COMPOUND SITE PLAN.pdf PDF
Attachment 4 - E1-104 RESIDENTIAL COMPOUND SITE PLAN.pdf PDF
Attachment 4 - M1-701 EXISTING GENERATOR DIESEL FUEL SYSTEM PIPING SCHEMATIC.pdf PDF
Attachment 4 - M1-501 SCHEDULE AND DETAILS.pdf PDF
Attachment 4 - M1-101 EXISTING OFFICE COMPOUND ENLARGED SITE PLAN.pdf PDF
Attachment 5-Design Submittal Requirements.xlsx XLSX spreadsheet
Attachment 7 - Juba Electrical Distribution Study - Final (For Information Only).pdf PDF
Attachment 1 -017825A CMMS Template v2-00-02.xlsx XLSX spreadsheet
Attachment 1 -017705 Closeout Juba Electrical Upgrades Final.pdf PDF
Attachment 1 -015005 TempFa Juba Electrical Upgrades Final.pdf PDF
Attachment 1 -013525 Safety Juba Electrical Upgrades Final.pdf PDF
Attachment 1 -013205 Scheduling Juba Electrical Upgrades Final.pdf PDF
Attachment 3 - 000000 TABLE OF CONTENTS.pdf PDF
Attachment 3 - 262313 PARALLELING SWITCHGEAR JAN20.pdf PDF
Show all 50

USAID/South Sudan Juba Compound Electrical Upgrade has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JUBA ELECTRICAL UPGRADE DEVELOPMENT July 13, 2020

JUBA SOUTH SUDAN Issued for Bid

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 260518 - 1

SECTION 260518 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes building wires and cables and associated connectors, splices, and terminations for wiring systems rated 600 V and less.

B. Related Sections include the following:

1. Division 07 Section on “Penetration Firestopping.”

2. Section 260505 “Common Work Results for Electrical, Communications, and Electronic

Safety.”

3. Division Section 26 on “Identification for Electrical Systems.”

4. Division 27 Sections for communications cables.

5. Section 337105 "Underground Ducts and Raceways."

1.2 SUBMITTALS

A. Product Data - General: For each type of product indicated.

B. Product Data - Products Manufactured to International Standards: Identify variations from U.S.

standards.

C. Qualification Data: For testing agency.

D. Field quality-control test reports.

1.3 QUALITY ASSURANCE

A. Testing Agency Qualifications: Testing agency as defined by OSHA in 29 CFR 1910.7 or a member company of the InterNational Electrical Testing Association (NETA), or is nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to Contracting Officer/COR based upon input from OBO/PDCS/DE/EE.

1. Testing Agency's Field Supervisor: Person currently certified by the InterNational

Electrical Testing Association or the National Institute for Certification in Engineering

Technologies to supervise on-site testing specified in Article on FIELD QUALITY

CONTROL.

B. Comply with the OBO Electrical Code (NFPA 70 “National Electrical Code” as amended by

OBO).

1. Electrical Components, Devices, and Accessories: Listed and labeled as defined in the

NFPA 70, Article 100 by a testing agency acceptable to Contracting Officer/COR based upon input from OBO/PDCS/DE/EE, and marked for intended use.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 260518 - 2

C. Products Manufactured to International Standards: Variations from U.S. standards require evaluation and approval by Contracting Officer/COR with input from OBO/PDCS/DE/EE.

PART 2 - PRODUCTS

2.1 CONDUCTORS AND CABLES

A. Conductor Material: Copper only complying with NEMA WC 70; solid conductor for 6.0 mm2 and smaller, stranded for 10.0 mm2 and larger. Copper shall be 98 percent conductivity and hard drawn.

B. Conductor Insulation Types: Type THHN-THWN, XHHW, SO, or XHHW-2 complying with

NEMA WC 70

1. International Type Conductors and Cables: If requests are approved for international type conductors and cables, conductor and cable ampacities for applications of 600-VAC or less shall not exceed ampacities listed in National Electrical Code Table 310.16.

2.2 CONNECTORS AND SPLICES

A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.

PART 3 - EXECUTION

3.1 CONDUCTOR AND INSULATION APPLICATIONS

A. Service Entrance: Type XHHW or XHHW-2, single conductors in raceway.

B. Exposed Feeders: Type THHN-THWN, single conductors in raceway.

C. Feeders Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN, single conductors in raceway.

D. Feeders Concealed in Concrete, below Slabs-on-Grade, and in Crawlspaces: Type THHN-

THWN, single conductors in raceway.

E. Exposed Branch Circuits, including in Crawlspaces: Type THHN-THWN, single conductors in raceway.

F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN, single conductors in raceway.

G. Branch Circuits Concealed in Concrete and below Slabs-on-Grade: Type THHN-THWN, single conductors in raceway.

H. Underground Feeders and Branch Circuits: Type THHN-THWN, single conductors in raceway.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 260518 - 3

I. Cord Drops and Portable Appliance Connections: Type SO, hard service cord.

J. Fire Alarm Circuits: Type THHN-THWN, in raceway.

K. Class 1 Control Circuits: Type THHN-THWN, in raceway.

L. Class 2 Control Circuits: Type THHN-THWN, in raceway.

M. Class 3 Control Circuits: Type THHN-THWN, in raceway.

N. Control wiring shall be minimum of 2.5 mm2 (#14 AWG) stranded copper and shall be rated for

600-volt service.

O. Neutral Conductor: Where a secondary distribution system requires a neutral conductor, a full-sized neutral conductor shall be used throughout the system, such that neutral conductor is not shared with any other branch circuit or feeder. If the secondary distribution system supports computers or other equipment that generates harmonics, double size neutrals shall be run from the subpanel boards feeding this equipment back to the MDP or service entrance. Neutral buses shall be sized to accommodate these conductors.

P. Ground Conductor: Insulated equipment grounding conductors run with branch circuits shall be installed such that that conductor is not shared with any other branch circuit.

3.2 INSTALLATION

A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.

B. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

E. Support cables according to Section 260505 "Common Work Results for Electrical, Communications and Electronic Safety."

F. Seal around cables penetrating fire-rated elements according to Division 07 Section on

"Penetration Firestopping."

G. Identify and color-code conductors and cables according to Division 26 Section on

“Identification for Electrical Systems.”

H. Install outdoor underground feeders in concrete encased ductbank in accordance with Section

337105 “Underground Ducts and Raceways.”

I. Each electronic equipment rack shall be fed by an individual circuit breaker protected branch circuit.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 260518 - 4

3.3 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in

UL 486A and UL 486B.

B. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

C. Wiring at Outlets: Install conductor at each outlet, with at least 300 mm of slack.

3.4 FIELD QUALITY CONTROL

A. Testing: Perform the following field quality-control testing:

1. After installing conductors and cables and before electrical circuitry has been energized, test for compliance with requirements.

2. Perform each electrical test and visual and mechanical inspection stated in

NETA Acceptance Testing Specification (ATS), Section 7.3. Certify compliance with test parameters.

B. Test Reports: Prepare a written report to record the following:

1. Test procedures used.

2. Test results that comply with requirements.

3. Test results that do not comply with requirements and corrective action taken to achieve compliance with requirements.

END OF SECTION 260518