This document includes a technical specification section for fuses and a related federal contract opportunity notice. The technical specification provides requirements for cartridge fuses rated 600V or less to be used in control circuits, motor control centers, panelboards, switchboards, enclosed controllers, and enclosed switches. It specifies fuse types, electrical characteristics, dimensions, coordination information to be submitted, and spare fuse cabinet requirements. The related federal contract opportunity is a solicitation from the US Agency for International Development seeking phase one proposals to provide electrical upgrade services at its Juba, South Sudan compound. Services include upgrading fuse applications and installations according to the technical specification section. The solicitation number and requesting agency are identified.
View the file
Other files for this federal contract opportunity
Show all 50
USAID/South Sudan Juba Compound Electrical Upgrade has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JUBA ELECTRICAL UPGRADE DEVELOPMENT July 13, 2020
JUBA SOUTH SUDAN Issued for Bid
FUSES SECTION 262813 - 1
SECTION 262813 - FUSES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Cartridge fuses rated 600 V ac and less for use in the following:
a. Control circuits.
b. Motor-control centers.
c. Panelboards.
d. Switchboards.
e. Enclosed controllers.
f. Enclosed switches.
2. Spare-fuse cabinets.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for spare-fuse cabinets. Include the following for each fuse type indicated:
1. Ambient Temperature Adjustment Information: If ratings of fuses have been adjusted to accommodate ambient temperatures, provide list of fuses with adjusted ratings.
a. For each fuse having adjusted ratings, include location of fuse, original fuse rating, local ambient temperature, and adjusted fuse rating.
b. Provide manufacturer's technical data on which ambient temperature adjustment calculations are based.
2. Dimensions and manufacturer's technical data on features, performance, electrical characteristics, and ratings.
3. Current-limitation curves for fuses with current-limiting characteristics.
4. Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse. Submit [in electronic format suitable for use in coordination software] [and] [in PDF format].
5. Coordination charts and tables and related data.
6. Fuse sizes for elevator feeders and elevator disconnect switches.
FUSES SECTION 262813 - 2
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fuses to include in emergency, operation, and maintenance manuals. In addition to items specified in [Section 017700 "Closeout
Procedures,"] [Section 017823 "Operation and Maintenance Data,"] include the following:
1. Ambient temperature adjustment information.
2. Current-limitation curves for fuses with current-limiting characteristics.
3. Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse used on the
Project. Submit [in electronic format suitable for use in coordination software] [and]
[in PDF format].
4. Coordination charts and tables and related data.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Fuses: Equal to [10] <Insert number> percent of quantity installed for each size and type, but no fewer than [three] <Insert number> of each size and type.
1.6 FIELD CONDITIONS
A. Where ambient temperature to which fuses are directly exposed is less than [40 deg F (5 deg C)] <Insert temperature> or more than [100 deg F (38 deg C)] <Insert temperature>, apply manufacturer's ambient temperature adjustment factors to fuse ratings.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. <Double click here to find, evaluate, and insert list of manufacturers and products.>
B. Source Limitations: Obtain fuses, for use within a specific product or circuit, from single source from single manufacturer.
2.2 CARTRIDGE FUSES
A. Characteristics: NEMA FU 1, current-limiting, nonrenewable cartridge fuses with voltage ratings consistent with circuit voltages.
1. Type RK-1: [250] [600]-V, zero- to 600-A rating, 200 kAIC[, time delay].
2. Type RK-5: [250] [600]-V, zero- to 600-A rating, 200 kAIC[, time delay].
3. Type CC: 600-V, zero- to 30-A rating, 200 kAIC[, fast acting] [, time delay].
4. Type CD: 600-V, 31- to 60-A rating, 200 kAIC[, fast acting] [, time delay].
5. Type J: 600-V, zero- to 600-A rating, 200 kAIC[, time delay].
http://www.specagent.com/LookUp/?ulid=2150&mf=04&src=wd
FUSES SECTION 262813 - 3
6. Type L: 600-V, 601- to 6000-A rating, 200 kAIC[, time delay].
7. Type T: [250-V, zero- to 1200-A] [600-V, zero- to 800-A] rating, 200 kAIC[, very fast acting] [, time delay].
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. Comply with NEMA FU 1 for cartridge fuses.
D. Comply with NFPA 70.
E. Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size and with system short-circuit current levels.
2.3 SPARE-FUSE CABINET
A. Characteristics: Wall-mounted steel unit with full-length, recessed piano-hinged door and key-coded cam lock and pull.
1. Size: Adequate for storage of spare fuses specified with [15] <Insert number> percent spare capacity minimum.
2. Finish: Gray, baked enamel.
3. Identification: "SPARE FUSES" in 1-1/2-inch- (38-mm-) high letters on exterior of door.
4. Fuse Pullers: For each size of fuse, where applicable and available, from fuse manufacturer.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine fuses before installation. Reject fuses that are moisture damaged or physically damaged.
B. Examine holders to receive fuses for compliance with installation tolerances and other conditions affecting performance, such as rejection features.
C. Examine utilization equipment nameplates and installation instructions. Install fuses of sizes and with characteristics appropriate for each piece of equipment.
D. Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to fuse ratings.
E. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 FUSE APPLICATIONS
A. Cartridge Fuses:
FUSES SECTION 262813 - 4
1. Service Entrance: [Class L, fast acting] [Class L, time delay] [Class RK1, fast acting]
[Class RK1, time delay] [Class J, fast acting] [Class J, time delay] [Class T, fast acting].
2. Feeders: [Class L, fast acting] [Class L, time delay] [Class RK1, fast acting]
[Class RK1, time delay] [Class RK5, fast acting] [Class RK5, time delay] [Class J, fast acting] [Class J, time delay].
3. Motor Branch Circuits: [Class RK1] [Class RK5] [Class CC, motor duty], time delay.
4. Large Motor Branch (601-4000 A): Class L, time delay.
5. Power Electronics Circuits: [Class J, high speed] [Class T, fast acting].
6. Other Branch Circuits: [Class RK1, time delay] [Class RK5, time delay] [Class J, fast acting] [Class J, time delay] [Class CC, fast acting].
7. Control Transformer Circuits: Class CC, time delay, control transformer duty.
8. Provide open-fuse indicator fuses or fuse covers with open fuse indication.
3.3 INSTALLATION
A. Install fuses in fusible devices. Arrange fuses so rating information is readable without removing fuse.
B. Install spare-fuse cabinet(s) in location shown on the Drawings or as indicated in the field by
[Architect] [Construction Manager] [Owner].
3.4 IDENTIFICATION
A. Install labels complying with requirements for identification specified in Section 260553
"Identification for Electrical Systems" and indicating fuse replacement information inside of door of each fused switch and adjacent to each fuse block, socket, and holder.
END OF SECTION 262813