Addendum 2 270500 DATA COMMUNICATION SYSTEM 220428.docx
DOCX document 38 KB Posted
- Attached to
- 511/21187. CAK; Albion Armory - Renovate Armory
- Solicitation number
- RFQ - 171 - 220000000461
- Issued by
- Calhoun County, Alden CDP, Michigan
About this file
This document is an addendum to a state and local contract opportunity for the Renovate Armory - Albion Armory project in Calhoun County, Michigan. The addendum specifies the requirements for the data communication system, including the provision of premise wiring for data and network distribution, as indicated on the drawings. It provides detailed technical specifications for the twisted pair cable, connectors, fiber-optic cabling, faceplates, fiber optic data switches and modules, uninterrupted power source, rack, interconnect tray, patch panels, and installation requirements. The contract calls for the installation and testing of the cabling and network equipment to meet industry standards and specifications. No approved equals, refurbished, or substitutes are allowed for certain critical components.
The contract opportunity is identified as 511/21187. CAK; Albion Armory - Renovate Armory, and the jurisdictions involved are Calhoun County and Alden CDP. Pricing terms, set asides, incumbent information, funding requirements and sources, and other salient details are not included in this addendum document.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENOVATE ARMORY – ALBION ARMORY
SECTION 27 0500 - DATA COMMUNICATION SYSTEM
PART 1 - GENERAL
SUMMARY
Provide premise wiring for data and Net distribution, as indicated on the Drawings.
SUBMITTALS
Product data for each product indicated/specified.
Cables.
Faceplates.
Uninterrupted Power Source.
Racks.
Interconnect Tray.
Patch panels.
Fiber Switch and Modules.
Field Test Report.
SUBMITTALS
Product data for each type of product specified.
Test data and as-built drawings. Test Data is due to DMVA design department before substantial completion is reached. All data jacks and cable connections systems shall be certified Category 6.
SYSTEM OVERVIEW
This section specifies the requirements for wire, cable, connections devices, installation, and testing for wiring systems to be used as signal pathways for high-speed data transmission.
QUALITY ASSURANCE
All cable shall be installed and terminated to meet 100-Base T standards as defied by EIA-TIA-568 standards.
The contractor shall be responsible for the most efficient routing of the cable in conduit. The cable route must avoid any electrical equipment, such as fluorescent lighting, transformers, etc. that could induce noise on the cable.
Codes and Standards
IEEE Compliance - Comply with Std 241, "IEEE Recommended Practice for Electric Power Systems in Commercial Buildings" pertaining to communication systems.
EIA Compliance - Comply with EIA Standards RS-453, 455, and 464 pertaining to installation of telephone systems.
ANSI/ICEA S-80-576 (1988) Communication Wire and Cable for Wiring Premises.
NFPA National Electrical Code.
REA 345-52 Service Entrance and Station Protector Installations (PC-5A).
REA 345-78 Carbon Arrestor Assemblies for Use in Protectors ANSI/T1A/EIA – 568-B.2-1 Transmission Performance Specifications for 4-Pair 100 ohm Category 6 Cabling.
PART 2 - PRODUCTS
CONDUIT, OUTLET BOXES, AND COVER
Provide boxes and conduit in accordance with Sections GENERAL ELECTRICAL REQUIREMENTS.
Mount boxes flush in finish walls to match height of 120-volt receptacles, unless indicated otherwise.
TWISTED PAIR CABLE
All of the voice and data locations shall be wired with unshielded twisted pair (UTP) cable that is category 6 rated and has a total of four (4) pair of copper conductors. The two data cables, shall be separate cables. All of the category 6 rated cable shall be plenum rated.
Data Cable Jacket Color: Cable jacket color shall be factory applied and continuous along the entire length of the cable. Colors as follows:
Jacket color for the data cable shall be blue in color.
Jacket color for the second data cable shall be blue in color.
The wiring code of the cable will follow the ANSI/TIA/EIT-T568B (AT&T), option B standards
| Pair 1 | Blue/White | Pin 4 | ||
| White/Blue | Pin 5 | |||
| Pair 2 | White/Orange | Pin 1 | ||
| Orange/White | Pin 2 | |||
| Pair 3 | White/Green | Pin 3 | ||
| Green/White | Pin 6 | |||
| Pair 4 | White/Brown | Pin 7 | ||
| Brown/White | Pin 8 |
CONNECTORS
All category 6 UTP cabling (Wall Jacks) shall be terminated into snap-in 110 type CAT 6 RJ-45 connectors and meet TIA/EIA-568-B2.1, Cabling Transmission Performance Specifications for 4-Pair 100 ohm Category 6 Cabling. Products from Hubbell are preferred, RJ-45 Model HXJ 6 OR-orange, HXJ 6BL-blue. A minimum of two data jacks will be provided at each customer interface point (voice/data outlet).
The top data jack shall be blue in color.
The bottom data jack shall be orange in color.
FIBER-OPTIC CABLING
Basis-of-Design Product – Subject to compliance with requirements, provide ”Draka F-ETH-1A1J-24-ES-E3”or a comparable product by one of the following:
Avaya Inc.
Berk-Tek; an Alcatel Company.
Draka Mohawk/CDT; a division of Belden CDT.
Nordex/CDT; a Subsidiary of Cable Design Technologies.
Optical Cable Corporation.
Panduit Corp.
Superior Essex; Superior Telecommunications Inc.
Cable shall be:
Direct Bury.
Single Mode.
Single Armored.
Single Jacketed.
Loose Tube.
ITU-T - G.652.D.
Fiber count: Provide the fiber count as scheduled and/or directed on the Drawings.
Cables shall be rated for direct burial and suitable for CWDM.
Color codes: Conductor insulation is color coded in accordance with industry standards.
Inner jacket: Cable shall have an inner polyethylene jacket with a corrugated steel armor covering.
Outer jacket: polyethylene jacket.
Splice Enclosures
Shall be “Multilink Starfighter” fiber optic dome splice closures or approved equal.
Mount and support per manufacturers’ recommendations.
Cable Connecting Hardware:
Comply with TIA/EIA-568-B.3. Terminate with quick-connect, simplex- and duplex-Type SC couplers. Insertion loss shall be not more than 0.7 dB
FACEPLATES
Faceplates shall be high impact 94V-O rated thermoplastic of the appropriate type. Each faceplate shall fit a single-gang box opening and hold four jacks in a vertical orientation. The jack layout and size of the faceplate shall be as follows:
Faceplate size: single-gang box opening.
Jack orientation: Two jacks in vertical alignment next to two more jacks in vertical alignment.
Voice, Data faceplate color shall match the electrical device plate color. If the electrical device plate is metallic, then the voice and data faceplate shall be ivory in color.
CABLE AND FACEPLATE IDENTIFICATION
The finished installation shall have labeling provided at each end of each cable with a permanent wrap around tag that is 6" from the end of the cable. This label should not be discarded during the installation process.
All faceplates shall have each jack location identified with a permanent label that is neatly applied. This label will include the category of use, and the cable number (EX. To-001); coordinate labeling with DMVA telecommunications mechanic.
FIBER OPTIC DATA SWITCH AND SWITCH MODULES
Provide and install two (2) new rack mounted fiber optic data switches. The new switches shall be: one Cisco C9200L-24P-4X 24-port switch & one Cisco Meraki Cloud Managed MS120 24-port switch and a Cisco LIC-MS120-24P 5 Year license. No approved equals, no refurbished, nor any substitutes. Switches must have Power Over Ethernet (POE+) capability.
Each switch shall be provided with two (2) single mode fiber optic switch modules as follows:
Single mode SFP by Cisco, product # GLC-LH-SMD (SFP); no approved equals, no refurbished, nor any substitutes.
FIBER OPTIC DATA SWITCH AND SWITCH MODULES
Provide and install two (2) new rack mounted fiber optic data switches. The new switches shall be: one Cisco C9200L-48P-4X 48-port switch & one Cisco Meraki Cloud Managed MS120 24-port switch and a Cisco LIC-MS120-24P 5 Year license. No approved equals, no refurbished, nor any substitutes. Switches must have Power Over Ethernet (POE+) capability.
Each switch shall be provided with two (2) single mode fiber optic switch modules as follows:
Single mode SFP by Cisco, product # GLC-LH-SMD (SFP); no approved equals, no refurbished, nor any substitutes.
UNINTERRUPTED POWER SOURCE
Rack Mounted Liebert GXT4 1000VA UPS or approved equal.
RACK, INTERCONNECT TRAY, AND PATCH PANELS AND ADDITIONAL ITEMS:
RACK: Basis-of-Design, Hoffman, model # EWMW362425.
19U rack units, 14ga. steel: provides 300 pounds of equipment support with tapped holes on both the front and rear surfaces of the mounting channels.
EIA 19” rack which is lockable/reversible double-hinged wall bracket and allows the cabinet to swing away from the wall for rear access to equipment cabling.
Front door: Solid steel, field-reversible (left or right) hinge, quarter-turn key lock. Provide with 2 keys.
Center section: Welded 14 gauge steel, steel solid top, hinged ventilated sides with provisions for future addition of fans, self-latching closure for connecting center section to wall section with self-alignment ramp to support center section to wall section, heavy duty hinge with quick-release self-retained hinge pins.
Rear wall section: Welded 14 gauge steel with gland plates, cable tie-down for cable management, and solid steel back wall.
EIA-310-D COMPLIANT, NEMA / EEMAC Type 1, & UL Listed 2416; Type 1.
EIA equipment mounting dimensions: width-standard 19”, Height-12U, Depth-20.5”, Finish –RAL 9005 black.
The rack shall also have adjustable 12 gauge steel mounting rails, and square hole mounting which is RU marked from bottom to top and are tapped 10-32 holes.
Mount the rack angles (vertical service bars that the equipment connects to) 3.5” from the inside of the closing front door.
PATCH PANEL: Basis-of-Design: Hubbell P624 patch panels. Provide the quantity of patch panels to meet requirements of the project (from wall jack count) plus 25% future ports. Patch panel shall have the following specifications.
Front access.
Category 6E.
T568B 24 port.
110 punch-down on rear of panels.
FIBER OPTIC INTERCONNECT TRAY: Basis-of-Design: Hubbell Optichannel hinged Fiber Rack Mount #FPR048ST patch panels.
PART 3 - EXECUTION
3.01 INSTALLATION
A. All customer interface (data outlet) boxes shall be 4”x4” boxes with a 2-gang plaster ring.
B. Install cabling concealed in ceiling and walls. Cabling to be parallel and perpendicular to surfaces, and follow surface contours. Secure and support cables by straps, staples, or similar fittings so designed and installed to avoid damage to cables. Secure cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, or fitting.
C. Install cabling using techniques, practices, and methods that are consistent with categories and RG type rating at components and that ensure category 6 and RG type performance of completed and linked signal path, end to end.
D. Install cables without damaging conductor’s shields or jackets. A minimum cable installation bending radius shall be observed. Minimum bend radius is defined as a radius of curvature no less than 4 times the outside diameter of the cable.
| E. | The contractor shall be responsible for the most efficient routing of the cable in conduit. The cable route must avoid any electrical equipment, such as fluorescent lighting, transformers, etc. that could induct noise on the cable. |
| F. | Each wall jack location shall have a single, continuous two (2) 4-pair cable pulled to it from the source location. No splices between the patch panel and the wall jack will be accepted. A minimum of 12-inches of excess cable will be left after termination, coiled neatly inside the 4”x4” wall box, and the minimum bend radius for the coil will be observed. A service loop of no less than six feet of excess cable will be neatly coiled above the equipment rack while ensuring that minimum bend radius is observed. |
G. 100% of the category 6 (UTP) cabling will be installed and tested in accordance with T1A/EIA-568-B2.1 Clause 11, Cabling Transmission Performance and Test Requirements. The contractor shall use an electronic testing device to test each cable for the following: (Submit printed output from this test device to DMVA for review.)
Attenuation Impedance Capacity Resistance Length dB loss Pin Assignments Continuity Polarity Near end cross talk
H. Scan and test each cable using industry standard equipment for items 1 – 10 above. The results shall be produced in electronic copies and provided to the DOIM/DMVA Network Engineer in MS Excel format.
I. Fiber-Optic Cable Tests:
Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-B.1. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.
Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.
Link End-to-End Attenuation Tests:
Horizontal and multimode backbone link measurements: Test at 850 or 1300 nm in 1 direction according to TIA/EIA-526-14-A, Method B, One Reference Jumper.
Attenuation test results for horizontal links shall be less than 2.0 dB. Attenuation test results shall be less than that calculated according to equation in TIA/EIA-568-B.1
J. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDM, or transferred from the instrument to the computer, saved as text files, and submitted. Electronic submittals are sufficient.
K. Remove and replace cabling where test results indicate that they do not comply with specified requirements.
L. Retest and inspect cabling to determine compliance of replaced or additional work with specified requirements.
3.02 CABLE IDENTIFICATION
A. Common Areas & Office Marking Standard:
The connection boxes placed on walls or in the bases of cubical furniture shall be labeled clockwise from the main entrance door A1-1, B1-1, A1-2, B1-2, etc around the outside wall, then to interior walls and cubical connections until all interfaces are designated. A1/B1 specifies the patch panel number. The -# specifies the patch panel port number. Top, or blue data jacks, will be labeled as the A drops. Bottom, or orange data jacks, will be labeled as the B drops.
Blue data jacks, (A labeled jacks), will be terminated in patch panels and labeled accordingly at the rack. Orange data jacks, (B labeled jacks), will be terminated in SEPARATE patch panels and labeled accordingly at the rack. The end state is to have A drops and B drops on separate physical patch panels.
Patch panels will be labeled as PP A-1 and PP B-1. When there are more than 24 data drop locations, additional patch panels will be added and labeled PP A-2/PP B-2 and so on. Data drops will reflect this as A2-1, B2-1. This marking would specify PatchPanel A2 Drop #1, PatchPanel B2 Drop #1.
END OF SECTION 27 0500
DATA COMMUNICATION SYSTEM 27 0500 - 1