76-Sheet Nos. 16 thru 19.pdf

PDF 5 MB Posted

Attached to
Route 54 Sanitary Sewer Extension Project
Solicitation number
Not on record
Issued by
Lycoming County, Pennsylvania

About this file

This document comprises electrical construction drawings and specifications prepared by EEL Levine Engineering, LLC for the West Branch Regional Authority's Route 54 Sanitary Sewer Extension Project (Contract No. WB-1) in Clinton Township, Lycoming County, Pennsylvania. The electrical work includes the complete installation of a duplex sewage pumping station with all associated electrical systems, underground service laterals, conduit installations, grounding systems, control panels, and area lighting. The project requires strict compliance with the 2017 National Electrical Code, all applicable state and local codes, and Pennsylvania One-Call System regulations. Key electrical components include a 240-volt single-phase service from PP&L with a 200-ampere meter socket and service disconnect, a duplex control panel for two 2-horsepower grinder pumps operating in lead-lag configuration, underground PVC conduit installations at minimum depths of 24 inches below finished grade, copper grounding systems with exothermic welds, and exterior area lighting fixtures. All material must be copper conductors with appropriate insulation ratings, and all equipment must be UL-listed and labeled.

The contractor is responsible for providing all trenching, backfill, compaction, conduit, cable, and conductors for underground electrical services and control wiring, while PP&L furnishes and installs service conductors and the meter. All underground conduits are specified as PVC Schedule 40 with conversion to PVC Schedule 80 for vertical sweeps to above-ground routing. Interior wet well areas require Class 1, Division 1 hazardous area classification with PVC-coated rigid steel raceways and NEMA 8 explosion-proof enclosures. The project includes a 60-inch diameter concrete foundation pad for the pump station with utility riser pole details, manual transfer switch provisions for portable generator connection, and ground rod installations using 5/8-inch by 8-foot copper-clad rods with exothermic weld connections. Contractor coordination with PP&L is mandatory, with the utility company's design contact identified as Tianna Andrews at 484-816-7964. Field changes and modifications must be recorded on construction documents and provided to the owner upon project completion.

View the file

Other files

File Type Posted
63-REV 1.19.26 16000 Elect Gen Prov.pdf PDF
17-00700 Gen Cond.pdf PDF
31-01600 Mat and Equp.pdf PDF
4-00250 Experience Equipmt and Finan Stmt.pdf PDF
52-05900 Miscelanous Metals.pdf PDF
47-02820 Topsoil Seeding.pdf PDF
14-00660 Form Change Order No 1.pdf PDF
1-1 CD COVER.pdf PDF
36-02000 Site Wrk.pdf PDF
42-02310 Horizontal DD.pdf PDF
7-00630 Public Verification Form.pdf PDF
26-01340 Shop Draw.pdf PDF
70-REV 1.19.26 16402 Underground Construction.pdf PDF
27-01380 Construct Photos.pdf PDF
50-03200 Concrete Reinforcement.pdf PDF
11-00610 Release of Lien.pdf PDF
32-01700 Cont Close.pdf PDF
24-01090 Ref Stand.pdf PDF
8-00350 Non-Discrimination.pdf PDF
66-REV 1.19.26 16130 Boxes.pdf PDF
56-15015 NonPress PVC.pdf PDF
30-01570 Traffic Reg.pdf PDF
38-02110 Demolition.pdf PDF
69-REV 1.19.26 16161 Grounding.pdf PDF
60-15100 Basic Req Plumb Wrk.pdf PDF
10-00600 Bonding Forms.pdf PDF
34-01720 Proj Rec Doc.pdf PDF
67-REV 1.19.26 16140 Wiring Devices.pdf PDF
64-REV 1.19.26 16111 Conduit.pdf PDF
44-02600 Paving Surface.pdf PDF
53-09900 Painting.pdf PDF
48-02900 Landscaping.pdf PDF
46-02710 Chain Link Fence.pdf PDF
62-15136 Basic Pip Mat and Meth.pdf PDF
5-00300 Bid Form.pdf PDF
61-15115 Supp and Anchors.pdf PDF
35-01740 Warranty and Bonds.pdf PDF
3-00200 Instructions to Bidders.pdf PDF
51-03300 Cast in Place.pdf PDF
37-02102 Clear Grub.pdf PDF
58-2 TOC.pdf PDF
21-01000 Summ of Work.pdf PDF
18-00800 Supp Cond.pdf PDF
45-02607 Manholes.pdf PDF
55-11930 Pump Equp.pdf PDF
71-REV 1.19.26 16511 Led Exterior Lighting.pdf PDF
19-Wage Rates.pdf PDF
68-REV 1.19.26 16160 Panelboards.pdf PDF
41-02300 HDPE Pipe.pdf PDF
15-00670 Payment Application.pdf PDF
Show 40 more

Latest 50 of 75 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EEL

Levine Engineering, LLC Municipal - Environmental - CivilL

GENERAL ELECTRICAL SYSTEM REQUIREMENTS:

1. CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, AND EQUIPMENT NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM AS INDICATED ON THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS.

2. ALL MATERIAL, SYSTEMS AND EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE 2017 NATIONAL ELECTRICAL CODE, ALL STATE, AND LOCAL CODES, AND ALL MANUFACTURER'S PUBLISHED

INSTRUCTIONS.

3. CONTRACTOR SHALL MAINTAIN ACCURATE RECORDS OF ALL FIELD CHANGES AND MODIFICATIONS PERFORMED DURING THE CONSTRUCTION PROCESS. THESE CHANGES SHALL BE RECORDED ON A CLEAN SET OF CONSTRUCTION DOCUMENTS, AND GIVEN TO THE OWNER FOLLOWING COMPLETION OF THE PROJECT.

4. ALL EQUIPMENT SHALL BE UL LISTED AND LABELED.

5. ALL WORK SHALL BE IN STRICT COMPLIANCE WITH THE 2017 NEC, AND ALL APPLICABLE NATIONAL, STATE, AND

LOCAL CODES AS DICTATED BY THE AUTHORITY HAVING JURISDICTION.

6. CONTRACTOR SHALL CONTACT THE PA ONE-CALL SYSTEM (800-242-1776) A MINIMUM OF FOUR (4) WORKING

DAYS PRIOR TO ANY EXCAVATION.

GENERAL ELECTRICAL NOTES

XX

UNDERGROUND WORK:

1. CONTRACTOR SHALL PROVIDE FOR ALL TRENCHING, BACKFILL, COMPACTION, CONDUIT, CABLE AND

CONDUCTORS FOR ALL UNDERGROUND ELECTRICAL SERVICES AND CONTROL WIRING AS SHOWN.

2. ALL UNDERGROUND CONDUITS SHALL BE INSTALLED 24" BFG TO TOP OF CONDUIT, EXCEPT AS NOTED FOR

UTILITY CONDUIT INSTALLATIONS.

3. ALL UNDERGROUND DIRECT BURIED RACEWAYS SHALL BE PVC SCH40 UNLESS OTHERWISE INDICATED.

UNDERGROUND RACEWAYS SHALL BE CONVERTED TO PVC SCH80 PRIOR TO VERTICAL SWEEP FOR ABOVE GROUND ROUTING, UNLESS OTHERWISE NOTED. REFER TO AREA CLASSIFICATIONS FOR SPECIFIC RACEWAY

REQUIREMENTS.

AREA CLASSIFICATIONS:

1. ALL EQUIPMENT RATINGS, RACEWAYS, BOXES, AND DEVICES SHALL BE INSTALLED IN COMPLIANCE WITH THE

FOLLOWING AREA CLASSIFICATION REQUIREMENTS:

A. INTERIOR WET WELLS: CLASS 1, DIVISION 1, GROUPS C AND D:

· RACEWAYS: PVC COATED RIGID STEEL

· ENCLOSURES: NEMA 8 EXPLOSION PROOF

B. WET WELL EXTERIOR (UP TO 18" ABOVE STRUCTURE AND 3FT HORIZONTAL FROM OUTER EDGE OF ANY

HATCH OPENING): CLASS 1, DIVISION 1, GROUPS C AND D:

· RACEWAYS: PVC COATED RIGID STEEL

· ENCLOSURES: NEMA 4X STAINLESS, CLASS 1 DIV 2 RATED OR NEMA 8 WHERE REQUIRED.

C. EXTERIOR EXPOSED ABOVE GRADE BEYOND THE HAZARDOUS AREA CLASSIFICATION: WET LOCATION

· RACEWAYS: PVC COATED RIGID STEEL

· ENCLOSURES: NEMA 4X, STAINLESS STEEL, OR TYPES AS INDICATED

D. EXTERIOR BELOW GRADE

· RACEWAYS: PVC SCH 40, OR PVC COATED RIGID STEEL WHERE INDICATED OR REQUIRED BY NEC

BETWEEN HAZARDOUS AND NON-HAZARDOUS CLASSIFICATIONS

· ALL RACEWAYS SHALL BE CONVERTED TO PVC SCH80 PRIOR TO VERTICAL SWEEP FOR ABOVE

GRADE ROUTING.

· ENCLOSURES: AS INDICATED

E. BUILDING INTERIOR

· RACEWAYS: SCHEDULE 40 PVC, OR PVC COATED RIGID STEEL WHERE INDICATED OR REQUIRED BY NEC

BETWEEN HAZARDOUS AND NON-HAZARDOUS CLASSIFICATIONS

· ENCLOSURES: NEMA 1

F. UTILITY SERVICE RACEWAYS

· PVC SCH 40 UNDERGROUND

· LONG RADIUS RIGID STEEL ELBOWS FOR ALL BENDS

· CONVERT TO PVC SCH80 PRIOR TO VERTICAL SWEEP FOR ABOVE GROUND EXPOSED ROUTING.

RACEWAYS:

1. REFER TO THE AREA CLASSIFICATIONS FOR SPECIFIC RACEWAY TYPE IN EACH DEFINED AREA.

2. ALL RACEWAYS SHALL BE A MINIMUM 3/4" TRADE SIZE.

3. ALL RACEWAYS ENTERING ABOVE GRADE ENCLOSURES FROM UNDERGROUND SHALL BE SEALED WATERTIGHT

PRIOR TO ENCLOSURE ENTRY UNLESS A CONDUIT SEALING EYS FITTING IS REQUIRED PRIOR TO ENCLOSURE

ENTRY. SEAL SHALL BE POLYWATER FST DUCT SEALANT SYSTEM OR EQUAL.

4. PROVIDE 200LB NYLON PULL STRING IN ALL SPARE RACEWAYS.

WORK RESPONSIBILITY - ELECTRIC UTILITY SYSTEMS

MATERIAL FURNISHED BY INSTALLED BY

TRENCH/BACKFILL CONTRACTOR CONTRACTOR

SERVICE LATERAL DIRECT BURIED

CONDUIT

SERVICE LATERAL CONDUCTORS

240V METER

240V METER SOCKET

GROUNDING:

1. ALL EQUIPMENT AND SYSTEMS SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL

ELECTRICAL CODE.

2. ALL GROUND RODS SHALL BE 5/8" X 8FT COPPER CLAD.

3. ALL UNDERGROUND CONNECTIONS SHALL BE EXOTHERMIC WELDS.

4. A GREEN INSULATED COPPER EQUIPMENT GROUND WIRE SHALL BE INSTALLED IN ALL POWER CONDUITS SIZED

PER NEC TABLE 250-122.

GENERAL ELECTRICAL REQUIREMENTS

CONDUCTORS:

1. ALL CONDUCTORS SHALL BE COPPER.

2. CONDUCTOR INSULATION RATINGS SHALL BE AS FOLLOWS:

A. SERVICE ENTRANCE: BY PP&L

B. FEEDERS:

· ABOVE GRADE: TYPE THHN/THWN IN RACEWAYS

· BELOW GRADE: TYPE THWN ON RACEWAYS

C. BRANCH CIRCUITS: TYPE THHN/THWN IN RACEWAYS

D. SIGNAL CABLES: 18AWG TWISTED SHIELDED PAIR SUITABLE FOR WET LOCATIONS; BELDEN 9341 OR EQUIV. IN

METAL RACEWAY.

E. CONTROL CONDUCTORS: 14AWG MINIMUM, TYPE THHN/THWN IN RACEWAY.

F. TYPE MC CABLE OR ROMEX SHALL NOT BE USED.

G. CONDUCTORS SHALL BE SOLID FOR 10AWG AND SMALLER; STRANDED FOR ALL CONDUCTORS LARGER THAN 10

AWG.

CONTRACTOR CONTRACTOR

CONTRACTOR CONTRACTOR

UTILITY REQUIREMENTS:

1. ALL FEES ASSOCIATED WITH ELECTRICAL SERVICES SHALL BE PAID DIRECTLY BY THE OWNER.

2. CONTRACTOR SHALL COORDINATE ALL REQUIRED WORK WITH THE UTILITY COMPANY TO PROVIDE A COMPLETE

INSTALLATION.

3. REFER TO THE UTILITY SYSTEMS WORK RESPONSIBILITY TABLE ON THIS DRAWING. CONTRACTOR SHALL COMPLY

WITH ALL UTILITY RULES FOR THE ELECTRICAL SERVICES AND METER REQUIREMENTS.

4. CONTRACTOR SHALL CONTACT EACH UTILITY UPON AWARD OF CONTRACT TO INITIATE THE DESIGN AND

SCHEDULING OF THE WORK TO BE PERFORMED.

5. CONTACTS FOR THE ELECTRICAL UTILITY PROVIDER ARE AS FOLLOWS:

PP&L PP&L

PP&L PP&L

PP&L WORK ORDER# 14731866

54 RTE MONTGOMERY, PA 17752

DESIGN CONTACT: TIANNA ANDREWS

EMAIL: tianna.andrews@execpower.com

CELL: 484-816-7964

ADDRESS: 555 CROTON ROAD, SUITE 307, KING OF PRUSSIA PA 19406

AutoCAD SHX Text 2703 Washington Avenue

AutoCAD SHX Text Altoona, PA 16601

AutoCAD SHX Text Telephone: (814) 935-1928

AutoCAD SHX Text Fax: (814) 941-2630

AutoCAD SHX Text Email:tmlevine81@gmail.com

AutoCAD SHX Text

ALL COPYRIGHTS RESERVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

TML

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

JJD/DLK

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text 1/15/26

AutoCAD SHX Text

CONTRACT NO WB-1

AutoCAD SHX Text

WEST BRANCH REGIONAL AUTHORITY

AutoCAD SHX Text

CLINTON TOWNSHIP, LYCOMING COUNTY, PENNSYLVANIA

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHK'D

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

SITUATE IN

AutoCAD SHX Text

RT 54 SANITARY SEWER EXTENSION

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text V

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text P

AutoCAD SHX Text

THOMAS M. LEVINE

AutoCAD SHX Text C

AutoCAD SHX Text No.042548-E

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text

127 GIRTON DRIVE MUNCY, PA 17756

AutoCAD SHX Text

ELECTRICAL LEGEND AND GENERAL NOTES

AutoCAD SHX Text

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

1. CONTRACTOR SHALL PROVIDE FOR ALL TRENCHING, BACKFILL, COMPACTION, CONDUIT, CABLE AND CONDUCTORS FOR ALL UNDERGROUND ELECTRICAL SERVICES AND CONTROL WIRING AS SHOWN. 2. CONTRACTOR SHALL LABEL ALL BRANCH CIRCUIT CONDUCTORS INSIDE PANELBOARDS AND CONTROL DEVICES INDICATING DEVICES SERVED AND CIRCUIT DESIGNATIONS. PROVIDE REVISED TYPED PANEL DIRECTORIES IN ALL EXISTING PANELBOARDS EFFECTED BY WORK OF THIS PROJECT. 3. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2017 EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) AND ALL APPLICABLE STATE AND LOCAL CODES. 4. ALL WIRE SHALL BE COPPER, TYPE THHN/THWN INSULATION UNLESS OTHERWISE NOTED. ALL RUNS SHALL INCLUDE AN APPROPRIATELY SIZED COPPER GROUND WIRE INSIDE RACEWAY.

AutoCAD SHX Text

5. ALL SPARE CONDUITS SHALL CONTAIN A 200LB NYLON PULL STRING. 6. ALL UNDERGROUND RACEWAYS SHALL BE INSTALLED A MINIMUM 24" BELOW FINISHED GRADE IN ALL EARTH/GRASS AREAS AND 24" BELOW ROADWAYS, PARKING AREAS, AND VEHICULAR AREAS, OR AS INDICATED ON DRAWINGS BASED ON UTILITY REQUIREMENTS. REFER TO GENERAL ELECTRICAL REQUIREMENT NOTES FOR ADDITIONAL INFORMATION. 7. ALL CARPENTRY WORK, NAILING, FASTENING, ETC, SHALL BE PERFORMED WITH TYPICAL INDUSTRY STANDARDS FOR ADEQUATE FASTENING METHODS TO RESULT IN A STABLE, WIND-RESISTANT STRUCTURE. 8. INSTALL ALL MATERIALS PER MANUFACTURERS PRINTED INSTRUCTIONS. 9. CONTRACTOR SHALL COORDINATE ALL REQUIRED UTILITY RELATED WORK, INCLUDING METER SOCKET REQUIREMENTS, RISER POLE CONDUIT SYSTEMS, OWNER METERING POLES, AND RELATED EQUIPMENT WITH EACH RESPECTIVE UTILITY COMPANY. 10. CONTRACTOR SHALL FURNISH AND INSTALL NFPA70E ARC FLASH LABELS AS DESIGNATED ON DRAWINGS FOR NON-STUDY APPLICATION. LABELS SHALL COMPLY WITH THE LATEST EDITION OF NFPA70E. 11. ALL EXTERIOR RECEPTACLES SHALL BE INSTALLED IN GASKETED CAST BOXES WITH WEATHERPROOF WHILE-IN-USE COVERPLATE, WITH LOCKABLE IMPACT RESISTANT COVER. 12. ALL CONDUITS ENTERING ENCLOSURES FROM UNDERGROUND SHALL BE SEALED WATERTIGHT PRIOR TO ENCLOSURE ENTRY UNLESS A CONDUIT EYS SEALING FITTING IS REQUIRED PRIOR TO ENCLOSURE ENTRY. SEAL SHALL BE POLYWATER FST DUCT SEALANT SYSTEM OR EQUAL. 13. ALL PANELBOARDS SHALL HAVE BOLT-ON BREAKERS, COPPER BUSSING, AND BE FULLY RATED.

AutoCAD SHX Text

GFI

AutoCAD SHX Text

6"AFC

AutoCAD SHX Text

48"AFF

AutoCAD SHX Text SINGLE POWER RECEPTACLE (208 1ɸ OR 208 3ɸ) SINGLE 15A, 120V RECEPTACLE 20A, 120V DUPLEX RECEPTACLE POWER POLE RECEPTACLE FLUSH MOUNTED IN SUSP CLG JUNCTION BOX TELEPHONE/DATA OUTLET COAX CABLE TV OUTLET GROUND FAULT CIRCUIT INTERRUPTER 6" ABOVE FINISHED COUNTER 6" BELOW FINISHED CEILING 48" ABOVE FINISHED FLOOR UNDER COUNTER WEATHER-PROOF KEYED NOTE CIRCUIT HOMERUN CIRCUIT BREAKER TRANSFORMER DISCONNECT SWITCH - NONFUSED DISCONNECT SWITCH - FUSED 20A, 120V HP RATED TOGGLE SWITCH

AutoCAD SHX Text

UC

AutoCAD SHX Text

WP

AutoCAD SHX Text

6" BFC

AutoCAD SHX Text SURFACE/PENDANT MOUNTED 1'X4' FLUORESCENT EXIT SIGN REMOTE LOW-VOLTAGE EMERGENCY LIGHT SELF-CONTAINED EMERGENCY LIGHTING UNIT WALL MOUNTED EXTERIOR LIGHTING FIXTURE 20 AMP, 120/277V SINGLE POLE TOGGLE SWITCH

AutoCAD SHX Text AFF ABOVE FINISHED FLOOR AFC ABOVE FINISHED COUNTER AFG ABOVE FINISHED GRADE A AMPERE BFC BELOW FINISHED CEILING BFG BELOW FINISHED GRADE CATV CABLE TV CT CURRENT TRANSFORMER CFL COMPACT FLUORESCENT CLG CEILING DETD DUAL ELEMENT TIME DELAY EA EACH EGC EQUIPMENT GROUND FWU FURNISHED WITH UNIT DISC DISCONNECT G GROUND GEC GROUNDING ELECTRODE CONDUCTOR HID HIGH INTENSITY DISCHARGE HZ HERTZ MCA MINIMUM CIRCUIT AMPACITY MFR MANUFACTURER MOCP MAXIMUM OVERCURRENT PROTECTION MOD MOTOR OPERATED DAMPER N NEUTRAL PS PULSE START TYP TYPICAL V VOLT

AutoCAD SHX Text

ELECTRICAL LEGEND (NOT ALL SYMBOLS APPEAR ON DRAWINGS)

AutoCAD SHX Text

LIGHTING

AutoCAD SHX Text

POWER / COMMUNICATIONS

AutoCAD SHX Text

ABBREVIATIONS

AutoCAD SHX Text

ONE-LINE DIAGRAMS/PLANS

AutoCAD SHX Text M

AutoCAD SHX Text 70A 3P T/M

AutoCAD SHX Text

FVNR NEMA 2

AutoCAD SHX Text

GF

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text

VFD

AutoCAD SHX Text

CURRENT TRANSFORMER

AutoCAD SHX Text

400AF 400AT 3P

AutoCAD SHX Text

METER

AutoCAD SHX Text

GROUND FAULT RELAY

AutoCAD SHX Text

CIRCUIT BREAKER: (AF) AMPERE FRAME, (AT) AMPERE TRIP (3P) 3-POLE

AutoCAD SHX Text COMBINATION STARTER: (T/M) THERMAL MAGNETIC, (FVNR) FULL VOLTAGE NON-REVERSING, (NEMA 2) NEMA SIZE 2 STARTER

AutoCAD SHX Text

NON-FUSED DISCONNECT SWITCH

AutoCAD SHX Text

VARIABLE FREQUENCY DRIVE

AutoCAD SHX Text

MOTOR (25) HP

AutoCAD SHX Text

TRANSFER SWITCH

AutoCAD SHX Text

GENERATOR ALTERNATOR

AutoCAD SHX Text

GROUND

AutoCAD SHX Text T

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

AREA POLE MOUNTED LIGHT

AutoCAD SHX Text

DIRECT BURIED HANDHOLE

AutoCAD SHX Text

SPD

AutoCAD SHX Text

SURGE PROTECTIVE DEVICE

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text

OVERHEAD (AERIAL) ELECTRIC

AutoCAD SHX Text

E-OH

AutoCAD SHX Text

UNDERGROUND ELECTRIC

AutoCAD SHX Text

E-UG

AutoCAD SHX Text

OVERHEAD TELEPHONE

AutoCAD SHX Text

T-OH

AutoCAD SHX Text

UNDERGROUND TELEPHONE

AutoCAD SHX Text

T-UG

AutoCAD SHX Text

UNDERGROUND CONTROL/MONITORING/ALARM

AutoCAD SHX Text

CNTL-UG

AutoCAD SHX Text S

AutoCAD SHX Text

RVSS

AutoCAD SHX Text

REDUCED VOLTAGE SOLID-STATE STARTER

E-U G

E-UG

E-U G

E-UG

EEL

Levine Engineering, LLC Municipal - Environmental - CivilL

LOCATION OF EXISTING PP&L POLE FOR NEW ELECTRICAL SERVICE. COORDINATE

ALL WORK ON POLE WITH PP&L. PP&L WORK ORDER# 14731866

NEW UNDERGROUND ELECTRICAL SERVICE FROM PP&L POLE. CONTRACTOR SHALL

PROVIDE ONE (1) 3" PVC CONDUIT, EXCAVATION AND BACKFILL FROM POLE TO NEW

PUMP STATION METER. PP&L WILL FURNISH AND INSTALL SERVICE CONDUCTORS

FROM POLE TO METER.

NEW CONCRETE PAD AND PUMP STATION ELECTRICAL EQUIPMENT. REFER TO

DETAILS AND SCHEDULES FOR INFORMATION.

NEW UNDERGROUND ELECTRICAL FEED TO PUMP STATION.

PUMP STATION EQUIPMENT SERVICE SCHEDULE

AutoCAD SHX Text

EX. UTILITY POLE

AutoCAD SHX Text

18" RCP INV. 604.39

AutoCAD SHX Text

CONC. BOX CULVERT INV. 603.76

AutoCAD SHX Text

GUIDERAIL

AutoCAD SHX Text

8" PVC

AutoCAD SHX Text

RT 54 PUMP STATION

AutoCAD SHX Text 2703 Washington Avenue

AutoCAD SHX Text Altoona, PA 16601

AutoCAD SHX Text Telephone: (814) 935-1928

AutoCAD SHX Text Fax: (814) 941-2630

AutoCAD SHX Text Email:tmlevine81@gmail.com

AutoCAD SHX Text

ALL COPYRIGHTS RESERVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

TML

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

JJD/DLK

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text 1/15/26

AutoCAD SHX Text

CONTRACT NO WB-1

AutoCAD SHX Text

WEST BRANCH REGIONAL AUTHORITY

AutoCAD SHX Text

CLINTON TOWNSHIP, LYCOMING COUNTY, PENNSYLVANIA

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHK'D

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

SITUATE IN

AutoCAD SHX Text

RT 54 SANITARY SEWER EXTENSION

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text V

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text P

AutoCAD SHX Text

THOMAS M. LEVINE

AutoCAD SHX Text C

AutoCAD SHX Text No.042548-E

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text

127 GIRTON DRIVE MUNCY, PA 17756

AutoCAD SHX Text

ELECTRICAL SITE PLAN AND DETAILS

AutoCAD SHX Text

AutoCAD SHX Text 1" = 10'

AutoCAD SHX Text

PA NORTH NAD83

AutoCAD SHX Text

HORIZONTAL

AutoCAD SHX Text

GRAPHIC SCALE

AutoCAD SHX Text

VERTICAL

AutoCAD SHX Text -10

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text -5

AutoCAD SHX Text

AutoCAD SHX Text 2.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KEYED NOTES-ELECTRICAL SERVICE PLAN

AutoCAD SHX Text

ITEM

AutoCAD SHX Text

AMPERES/

AutoCAD SHX Text

HP

AutoCAD SHX Text

VOLTAGE/

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

MCA

AutoCAD SHX Text

MOCP

AutoCAD SHX Text

UNIT DISCONNECT

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

SOURCE PANEL

AutoCAD SHX Text 1.0

AutoCAD SHX Text ALL DISCONNECT DEVICES AND OVERCURRENT PROTECTIVE DEVICES FOR LISTED LOADS ARE FURNISHED WITH CONTROL PANEL.

AutoCAD SHX Text A

AutoCAD SHX Text PROVIDE 240V CONNECTION TO CONTROL PANEL LINE TERMINALS. PUMPS OPERATE IN LEAD-LAG

AutoCAD SHX Text

GRINDER PUMP 1

AutoCAD SHX Text 240V 1

AutoCAD SHX Text

15A 2HP

AutoCAD SHX Text 18.75

AutoCAD SHX Text A

AutoCAD SHX Text

KEY

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

DUPLEX CONTROL PANEL

AutoCAD SHX Text

GRINDER PUMP 2

AutoCAD SHX Text

CONTROL POWER

AutoCAD SHX Text 120V

AutoCAD SHX Text N/A

AutoCAD SHX Text 1" = 10'-0"

AutoCAD SHX Text

ELECTRICAL SERVICE PLAN

AutoCAD SHX Text

POLE MOUNTED 1-PHASE TRANSFORMER BY PP&L

AutoCAD SHX Text

CONTRACTOR SHALL INSTALL 90D 36" RADIUS PVC SCH 40 ELBOW

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text 39"

AutoCAD SHX Text

WARNING RIBBON INSTALLED 12" ABOVE SERVICE LATERAL CONDUIT

AutoCAD SHX Text

TO METERING EQUIPMENT

AutoCAD SHX Text

CONDUIT END SEAL

AutoCAD SHX Text

PVC SCH40 CONDUIT

AutoCAD SHX Text

PP&L POLE

AutoCAD SHX Text 240V 1

AutoCAD SHX Text

15A 2HP

AutoCAD SHX Text 18.75

AutoCAD SHX Text 30A 2P

AutoCAD SHX Text 30A 2P

AutoCAD SHX Text 20A 1P

AutoCAD SHX Text

INSTALL PULLING LINE IN CONDUIT, BACKFILL ENTIRE CONDUIT RUN

AutoCAD SHX Text

NO SCALE

UTILITY RISER POLE DETAILS

CIRCUIT BREAKER

SERVICE DISCONNECT

SERVICE METER

8"X8"X1/4" THICK ALUM BASE

PLATE SECURED TO CONCRETE

BASE WITH 3/8" S.S. EXP

ANCHORS (3 REQ'D)

4"X4"X4"X1/4" ALUMINUM

U-CHANNEL, LENGTH AS

REQUIRED, WELD TO BASE (3

REQ'D)

FINISHED GRADE

12" DIA CONCRETE

FOUNDATION, ONE FOR

EACH OUTER COLUMN

48"

RIGID STEEL

FRONT ELEVATION

PARTIAL PLAN VIEW

8'

5/8" X 8' CU GND ROD

(TYP)

PVC SCH80

6" MIN PENNDOT

No 2A CRUSHED

STONE (TYP).

2"4"

6"

60"

CONCRETE PAD

6"

(TYP)

SERVICE

METER

3"x1/4" ALUMINUM FLAT STOCK

FOR MOUNTING METER AND

DISCONNECT. WELD TO

COLUMNS

CENTER POST

TO PP& RISER POLE.

CONDUIT BY

CONTRACTOR, WIRE BY

PP&L

3"x1/4" ALUMINUM FLAT STOCK.

WELD TO COLUMNS. PROVIDE

AS NEEDED FOR MOUNTING OF

EQUIPMENT

CONCRETE FOUNDATION

PANEL A

FINISHED GRADE

12" DIA CONCRETE

FOUNDATION, ONE FOR

EACH OUTER COLUMN

REAR ELEVATION

2" EXPOSURE4"

6"

MANUAL

TRANSFER

SWITCH

AREA LIGHTAREA LIGHT

PUMP CONTROLLER

PVC SLIP RISER. INSTALL

CONDUIT MIN OF 14" INTO

RISER

3" PVC SCH80

(2) 1/4" HOLES IN BACK

OF CONDUIT

(2) 1/4" HOLES IN

BOTTOM OF

ELBOW

3" PVC NIPPLE WITH

THREADED CAP FOR

OWNER PORTABLE GEN

CONNECTION.

GFI RECEPT

1-1/4" PVC SCH80

TO PUMP STATION

SERVICE

DISCONNECT

MANUAL TRANSFER

DISCONNECT

PANEL A PUMP CONTROL

PANEL

AREA LIGHT ABOVE

AREA LIGHT ABOVE

64" +/-

68" +/-

AREA LIGHT SHALL BE RAB

MODEL SLIM22-S-30 OR EQUAL

(TYP).

6"X6"-W2.9XW2.9 WWFDOWEL (TYP)

NOTE: MODIFY ALL PAD AND STRUCTURE

DIMENSIONS BASED ON FINAL EQUIPMENT

SELECTIONS AND DIMENSIONS

112"

PROVIDE HORIZONTAL MEMBERS

AS REQUIRED.

EEL

Levine Engineering, LLC Municipal - Environmental - CivilL

AutoCAD SHX Text 2703 Washington Avenue

AutoCAD SHX Text Altoona, PA 16601

AutoCAD SHX Text Telephone: (814) 935-1928

AutoCAD SHX Text Fax: (814) 941-2630

AutoCAD SHX Text Email:tmlevine81@gmail.com

AutoCAD SHX Text

ALL COPYRIGHTS RESERVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

TML

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

JJD/DLK

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text 1/15/26

AutoCAD SHX Text

CONTRACT NO WB-1

AutoCAD SHX Text

WEST BRANCH REGIONAL AUTHORITY

AutoCAD SHX Text

CLINTON TOWNSHIP, LYCOMING COUNTY, PENNSYLVANIA

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHK'D

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

SITUATE IN

AutoCAD SHX Text

RT 54 SANITARY SEWER EXTENSION

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text V

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text P

AutoCAD SHX Text

THOMAS M. LEVINE

AutoCAD SHX Text C

AutoCAD SHX Text No.042548-E

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text

127 GIRTON DRIVE MUNCY, PA 17756

AutoCAD SHX Text

ELECTRICAL DETAILS

AutoCAD SHX Text

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text 5/8" x 8' COPPER CLAD GROUND ROD

AutoCAD SHX Text

SOFT DRAWN TINNED COPPER CONDUCTOR

AutoCAD SHX Text

EXOTHERMIC WELD CONNECTION

AutoCAD SHX Text

GROUND ROD DETAIL

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

BACKFILL EXCAVATION MATERIAL, TO BE FREE OF LARGE STONES, BLOCKS, ETC.

AutoCAD SHX Text

SAND FILL (15" MIN COVERAGE)

AutoCAD SHX Text

PLASTIC MARKING TAPE (WIDTH=6" MIN)

AutoCAD SHX Text

DIRECT BURIED CONDUIT

AutoCAD SHX Text 12"

AutoCAD SHX Text 39"

AutoCAD SHX Text

NOTE: DETAIL INTENDED TO REPRESENT METHODS

AutoCAD SHX Text

FOR DIRECT BURIAL CONDUIT AND DOES NOT

AutoCAD SHX Text

NECESSARILY REPRESENT QUANTITY AND USE

AutoCAD SHX Text

OF EACH.

AutoCAD SHX Text

RESTORE SURFACE FEATURES AND

AutoCAD SHX Text

PLANTINGS TO MATCH EXISTING

AutoCAD SHX Text

CONDITIONS.

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

UTILITY DIRECT BURIED CONDUIT INSTALLATION DETAIL

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

BACKFILL EXCAVATION MATERIAL, TO BE FREE OF LARGE STONES, BLOCKS, ETC.

AutoCAD SHX Text

SAND FILL (6" MIN COVERAGE)

AutoCAD SHX Text

PLASTIC MARKING TAPE (WIDTH=6" MIN)

AutoCAD SHX Text

DIRECT BURIED CONDUIT

AutoCAD SHX Text 12"

AutoCAD SHX Text

24" MIN

AutoCAD SHX Text

NOTE: DETAIL INTENDED TO REPRESENT METHODS

AutoCAD SHX Text

FOR DIRECT BURIAL CONDUIT AND DOES NOT

AutoCAD SHX Text

NECESSARILY REPRESENT QUANTITY AND USE

AutoCAD SHX Text

OF EACH.

AutoCAD SHX Text

RESTORE SURFACE FEATURES AND

AutoCAD SHX Text

PLANTINGS TO MATCH EXISTING

AutoCAD SHX Text

CONDITIONS.

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

DIRECT BURIED CONDUIT INSTALLATION DETAIL

AutoCAD SHX Text 15"

AutoCAD SHX Text 3/4" = 1'-0"

AutoCAD SHX Text

ELECTRICAL SERVICE DETAILS

AutoCAD SHX Text

NOT TO SCALE

PA NORTH NAD83

EEL

Levine Engineering, LLC Municipal - Environmental - CivilL

CONDUCTOR AMPACITY TABLE

M

NG

PUMP 1

LEAD

PUMP 2

LAG

PU

M

P

C O

N

TA

C

TO

R

NG

120/240V 1Ø

PANEL

A

120/240V 1Ø

TRANSFORMER

BANK BY PP&L

PORTABLE GENSET

BY OWNER

DOUBLE-THROW MANUAL

TRANSFER SWITCH

1 200 AMP, 240VAC, SELF-CONTAINED, SINGLE-POSITION, SINGLE-PHASE,

THREE-WIRE METER SOCKET. SOCKET SHALL BE UL LISTED AND LABELED, WITH

LEVER-OPERATED JAW RELEASE AND 100% RATED BY-PASS. METER FURNISHED

AND INSTALLED BY PP&L. COORDINATE FINAL SOCKET REQUIREMENTS WITH PP&L.

200 AMP, 2-POLE 250VAC SELF ENCLOSED CIRCUIT BREAKER IN NEMA 4X STAINLESS

ENCLOSURE WITH SOLID NEUTRAL, GROUND BUS AND SERVICE LABEL.

200 AMP, 240VAC, 1Ø, NEMA 4X STAINLESS DOUBLE-THROW MANUAL TRANSFER

SWITCH WITH SOLID NEUTRAL.

200 AMP, 120/240V 1-PHASE 3-WIRE PANEL "A" HOUSED IN NEMA 4X STAINLESS

ENCLOSURE.

PUMP STATION DUPLEX CONTROL PANEL FURNISHED WITH PUMP STATION,

INSTALLED BY CONTRACTOR. COORDINATE ALL FINAL INSTALLATION AND WIRING

REQUIREMENTS IN-FIELD WITH FINAL STATION SELECTION.

SERVICE FEEDER FURNISHED

AND INSTALLED BY PP&L. 3"C

FURNISHED AND INSTALLED

BY CONTRACTOR

NG

NEMA 4X BOX INSIDE

PUMP STATION BASIN

FURNISHED WITH STATION

DUPLEX CONTROL

PANEL FURNISHED

WITH STATION,

INSTALLED BY

CONTRACTOR

AREA

LIGHTING WITH

INTEGRAL

PHOTOCELLS

TEMPORARY GEN CONNECTION

BY OWNER AS REQUIRED

DO NOT

BOND

N-G BOND

N

GEC

DO NOT

BOND

GEC

WP

GFI

PU

M

P

C O

N

TA

C

TO

R

CONTROLS

ALARM BEACON

AL

AR

M H

O R

N

2HP 2HP

FLOAT

FLOAT

FLOAT

PUMP AND FLOAT POWER CABLES

FURNISHED WITH STATION, INSTALLED BY

CONTRACTOR. PROVIDE ONE (1) 1-1/4" PVC

CONDUIT FOR CABLE INSTALLATION

BETWEEN CONTROL PANEL AND BASIN.

FLOAT

FLOAT

FLOAT

PANEL "A"4

SURGE PROTECTIVE DEVICE

2AWG CU

COORDINATE ALL PP&L WORK WITH PP&L AND ALL APPLICABLE STANDARD RULES

AutoCAD SHX Text 2703 Washington Avenue

AutoCAD SHX Text Altoona, PA 16601

AutoCAD SHX Text Telephone: (814) 935-1928

AutoCAD SHX Text Fax: (814) 941-2630

AutoCAD SHX Text Email:tmlevine81@gmail.com

AutoCAD SHX Text

ALL COPYRIGHTS RESERVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

TML

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

JJD/DLK

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text 1/15/26

AutoCAD SHX Text

CONTRACT NO WB-1

AutoCAD SHX Text

WEST BRANCH REGIONAL AUTHORITY

AutoCAD SHX Text

CLINTON TOWNSHIP, LYCOMING COUNTY, PENNSYLVANIA

AutoCAD SHX Text

DATE

AutoCAD SHX Text

CHK'D

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

SITUATE IN

AutoCAD SHX Text

RT 54 SANITARY SEWER EXTENSION

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text V

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text P

AutoCAD SHX Text

THOMAS M. LEVINE

AutoCAD SHX Text C

AutoCAD SHX Text No.042548-E

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text

127 GIRTON DRIVE MUNCY, PA 17756

AutoCAD SHX Text

ELECTRICAL DIAGRAMS AND SCHEDULES

AutoCAD SHX Text

AutoCAD SHX Text

AS NOTED

AutoCAD SHX Text

AMPACITY (MAX)

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

ALUMINUM CONDUCTOR

AutoCAD SHX Text

COPPER GROUND

AutoCAD SHX Text

ALUMINUM GROUND

AutoCAD SHX Text

MIN RACEWAY (BASED ON 3 ,N+G)

AutoCAD SHX Text 20 (60°C)

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text 1/

AutoCAD SHX Text

12AWG

AutoCAD SHX Text

AutoCAD SHX Text

12AWG

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 30 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

10AWG

AutoCAD SHX Text

AutoCAD SHX Text

10AWG

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text 40 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

8AWG

AutoCAD SHX Text

AutoCAD SHX Text

10AWG

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text 50 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text

10AWG

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text

MIN RACEWAY (BASED ON 3 ,N+G)

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text 60 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text

10AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text 70 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text

8AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text 80 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

3AWG

AutoCAD SHX Text

AutoCAD SHX Text

8AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text 90 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text

8AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text 100 (60°C)

AutoCAD SHX Text 1/

AutoCAD SHX Text

1AWG

AutoCAD SHX Text

AutoCAD SHX Text

8AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

2/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

3/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

4/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

250KCM

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

350KCM

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

AMPACITY (MAX)

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

ALUMINUM CONDUCTOR

AutoCAD SHX Text

COPPER GROUND

AutoCAD SHX Text

ALUMINUM GROUND

AutoCAD SHX Text

MIN RACEWAY (BASED ON 3 ,N+G)

AutoCAD SHX Text

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text 1/

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

AutoCAD SHX Text

3AWG

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text 1/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text 1/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MIN RACEWAY (BASED ON 3 ,N+G)

AutoCAD SHX Text

QTY

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

3AWG

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

2AWG

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text

450(PAR)

AutoCAD SHX Text

4/0AWG

AutoCAD SHX Text

2AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

AutoCAD SHX Text

250KCM

AutoCAD SHX Text

2AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

AutoCAD SHX Text

350KCM

AutoCAD SHX Text

1AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

AutoCAD SHX Text

400KCM

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text 3/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

AutoCAD SHX Text

350KCM

AutoCAD SHX Text

2/0AWG

AutoCAD SHX Text 3/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

AutoCAD SHX Text

400KCM

AutoCAD SHX Text

2/0AWG

AutoCAD SHX Text 3/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

3/0AWG

AutoCAD SHX Text 4/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

4/0AWG

AutoCAD SHX Text 5/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

250KCM

AutoCAD SHX Text 6/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

250KCM

AutoCAD SHX Text 8/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

400KCM

AutoCAD SHX Text

COPPER ONLY

AutoCAD SHX Text

COPPER ONLY

AutoCAD SHX Text

COPPER ONLY

AutoCAD SHX Text

COPPER ONLY

AutoCAD SHX Text 1/

AutoCAD SHX Text

3AWG

AutoCAD SHX Text

AutoCAD SHX Text

8AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4"

AutoCAD SHX Text 1/

AutoCAD SHX Text

3AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 1/

AutoCAD SHX Text

1AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text 1-1/2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

6AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

3/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

4/0AWG

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

250AWG

AutoCAD SHX Text

AutoCAD SHX Text

4AWG

AutoCAD SHX Text

AutoCAD SHX Text 2-1/2"

AutoCAD SHX Text 1/

AutoCAD SHX Text

300AWG

AutoCAD SHX Text

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text 1/

AutoCAD SHX Text

350AWG

AutoCAD SHX Text

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text 1/

AutoCAD SHX Text

500AWG

AutoCAD SHX Text

AutoCAD SHX Text

2AWG

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text 1/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

1AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

250KCM

AutoCAD SHX Text

1AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

300KCM

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

300KCM

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

350KCM

AutoCAD SHX Text

1/0AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

2/0AWG

AutoCAD SHX Text 2/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

3/0AWG

AutoCAD SHX Text 3/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3"

AutoCAD SHX Text

400KCM

AutoCAD SHX Text

3/0AWG

AutoCAD SHX Text 3/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

4/0AWG

AutoCAD SHX Text 3/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

4/0AWG

AutoCAD SHX Text 4/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

500KCM

AutoCAD SHX Text

250KCM

AutoCAD SHX Text 5/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

350KCM

AutoCAD SHX Text 6/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

400KCM

AutoCAD SHX Text 8/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

600KCM

AutoCAD SHX Text 9/

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 4"

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

600KCM

AutoCAD SHX Text

KEY

AutoCAD SHX Text 20.4.G

AutoCAD SHX Text 30.4.G

AutoCAD SHX Text 40.4.G

AutoCAD SHX Text 50.4.G

AutoCAD SHX Text 60.4.G

AutoCAD SHX Text 70.4.G

AutoCAD SHX Text 80.4.G

AutoCAD SHX Text 90.4.G

AutoCAD SHX Text 100.4.G

AutoCAD SHX Text 110.4.G

AutoCAD SHX Text 125.4.G

AutoCAD SHX Text 150.4.G

AutoCAD SHX Text 175.4.G

AutoCAD SHX Text 200.4.G

AutoCAD SHX Text 225.4.G

AutoCAD SHX Text 250.4.G

AutoCAD SHX Text 300.4.G

AutoCAD SHX Text

KEY

AutoCAD SHX Text 350.4.G

AutoCAD SHX Text 400.4.G

AutoCAD SHX Text 450.4.G

AutoCAD SHX Text

COPPER CONDUCTORS

AutoCAD SHX Text

ALUMINUM CONDUCTORS

AutoCAD SHX Text

COPPER CONDUCTORS

AutoCAD SHX Text

ALUMINUM CONDUCTORS

AutoCAD SHX Text 450.4.G

AutoCAD SHX Text 500.4.G

AutoCAD SHX Text 600.4.G

AutoCAD SHX Text 700.4.G

AutoCAD SHX Text 800.4.G

AutoCAD SHX Text 900.4.G

AutoCAD SHX Text 1000.4.G

AutoCAD SHX Text 1200.4.G

AutoCAD SHX Text 1600.4.G

AutoCAD SHX Text 2000.4.G

AutoCAD SHX Text 2500.4.G

AutoCAD SHX Text 3000.4.G

AutoCAD SHX Text

TABLE NOTES

AutoCAD SHX Text

1. CONDUCTOR SIZES BASED ON 60°CRATING FOR 100 AMP AND LESS, AND 75° FOR AMPACITIES GREATER THAN 100AMP 2. SCHEDULE DENOTES 4-WIRE CIRCUITRY (3 , NEUTRAL AND GROUND).THE FOLLOWING DENOTES OTHER THAN 4-WIRE:

AutoCAD SHX Text 350.3.G

AutoCAD SHX Text

3-WIRE + GROUND

AutoCAD SHX Text 350.3

AutoCAD SHX Text

3-WIRE NO GROUND

AutoCAD SHX Text 350.4

AutoCAD SHX Text

4-WIRE NO GROUND

AutoCAD SHX Text 350.2.G

AutoCAD SHX Text

2-WIRE + GROUND

AutoCAD SHX Text

350.2.IG

AutoCAD SHX Text

2-WIRE + GROUND + ISOLATED GROUND

AutoCAD SHX Text

3. ALL 100% RATED BREAKERS SHALL UTILIZE 90°C CONDUCTORS AT 75°RATING

AutoCAD SHX Text

PP&L STANDARD RULES

AutoCAD SHX Text

EXTERIOR SITE LIGHTING FIXTURE

AutoCAD SHX Text 200,2P

AutoCAD SHX Text G

AutoCAD SHX Text 200,2P

AutoCAD SHX Text 20,1P

AutoCAD SHX Text

SPD

AutoCAD SHX Text 200,2P

AutoCAD SHX Text S/N

AutoCAD SHX Text 20,1P

AutoCAD SHX Text 20,1P

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

PUMP STATION ONE-LINE DIAGRAM

AutoCAD SHX Text

KEY NOTES

AutoCAD SHX Text 30,2P

AutoCAD SHX Text 30,2P

AutoCAD SHX Text 30,2P

AutoCAD SHX Text 200.3

AutoCAD SHX Text 200.3.G

AutoCAD SHX Text 200.3.G

AutoCAD SHX Text 20.2.G

AutoCAD SHX Text 20.2.G

AutoCAD SHX Text 30,2P

AutoCAD SHX Text 20.2.G

AutoCAD SHX Text 30.2.G

AutoCAD SHX Text 30.2.G

STATION CONTROL PANEL DETAIL

Sheets and Views
SHEET 7 - PUMP STATION-BND - TO TOM-SHT 16
SHEET 7 - PUMP STATION-BND - TO TOM-SHT 17
SHEET 7 - PUMP STATION-BND - TO TOM-SHT 18
SHEET 7 - PUMP STATION-BND - TO TOM-SHT 19

File details come from the government source that posted it. Updated .