COVER PAGE OF SELLER’S SUBMITTAL
City Name: Hanford, WA - MSA
Pall Project No.: 01.000287
Job Number: Project L-897, Subcontract 70816
Task Register 6 (Task 1 – VI Submittal Package)
To: (Contractor)
Mission Support Alliance, LLC (MSA)
PO Box 650
Richland, WA 99352
From: (Subcontractor)
Pall Water
A Division of Pall Corporation
839 State Route 13
Cortland, NY 13045
Patty Willis
Phone: 607-758-1699
Name of Project: Hanford, WA, Central Plateau WTF
Pall Document Number: NYCS000008949 Rev: 02
Description of Item: Module, MF, USA-620A
Specification Section: N/A
Deviations: N/A
INDEX:
Page 1: Cover Page Information
Page 2: Revision History and Approvals
Page 3: Tab 1 – UNA-620A Data Sheet
Pages 4-5: Tab 2 – UNA-620A Chemical Compatibility Table
Pages 6-12: Tab 3 – Calcium Chloride MSDS
Page 13: Tab 4 – 1000025497R01, Module Install Parts, 6inch
Date: 12/19/2019
PALL ADVANCED SEPARATIONS SYSTEMS
DIVISION OF PALL CORPORATION, CORTLAND, NY
Rev Name Date Created By
Approved By
Created By
Approved By
Created By
Approved By
Created By
Approved By
Revision Description
Title
Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.
Filtration. Separation. Solution.TM
Product Data Sheet
Part Number UNA-620A
Description Hollow Fiber Membrane Water Filter
Dimensions
Membrane Area ((m ) 50
Module Length (mm) 2160
Module Diameter (mm) 165
Nominal Pore Size (µm) 0.1
Operating Conditions
Filtration Mode Outside/In
Max. Operating Temp. (Deg. C) 40 pH Range (Long Term Operation) 1 - 10 pH Range (Short Term for Cleaning) 1 – 13
Max. Transmembrane Pressure (bar) 3.0
Max. Inlet Pressure (bar) 3.0*
Max. Inlet Pressure (bar) 4.0**
* Standard locknut
** High pressure locknut
Materials of Construction
Membrane Polyvinylidenefluoride (PVDF)
Housing ABS Resin
Potting Material Polyurethane Resin
Antifreeze/Bacteriostat 40% Calcium Chloride Solution larkind Highlight
LarkinD Text Box 104 degrees F
LarkinD Text Box
538.2 square feet
LarkinD Text Box
85.04 inches
LarkinD Text Box
6.50 inches
LarkinD Text Box 3.937x10-6 inches
LarkinD Text Box
43.5 psig
LarkinD Text Box
43.5 psig
LarkinD Text Box
58.0 psig larkind Highlight larkind Highlight
Pall MF / Membrane Compatibility
Chemical Condition Compatibility
Concentration Temperature Sodium hypochlorite 1 % 25 Excellent Hydrogen peroxide 2 % 25 Excellent Formaldehyde 3 % 25 Excellent Ethanol 100 % 25 Good1 Caustic soda 1 N 25 Excellent2 Caustic soda and Sodium hypochlorite
NaOH (1N) NaClO (0.5%)
25 Excellent
Citric acid 10 % 25 Excellent Nitric acid 1 N 25 Excellent Hydrochloric acid 1 N 25 Excellent Sulfuric acid 1 N 25 Excellent Glycerin 100 % 25 Excellent Chlorinated solvents 25 Not compatible Aromatic base solvent 25 Not compatible Ester base solvents 25 Not compatible Ether base solvents 25 Not compatible Ketone base solvents 25 Not compatible
Notes:
1. Compatible up to 30 days exposure.
2. Use of caustic soda alone will result in the slight discoloration of the membrane and extraction of F- ion, however, there is no deterioration in the physical properties of membrane.
Therefore, the cleaning of module by caustic soda alone should be limited and use of caustic soda with sodium hypochlorite is recommended.
Facscan Text Box C396
DRAWING NUMBER
MATERIAL MASTER
DRAWING NAME
PROJECT ID
DWG SIZE
REVISION
SHEET OF
Copyright PALL CORPORATION This document may contain confidential technical data, including trade secrets proprietary to Pall Corporation. The drawing, design rights and all other disclosures in this document are the property of Pall Corporation. Unauthorized use, copying, distribution to third parties, manufacture, or reproduction in whole or in part is prohibited.
PALL Corporation
PROJECT ENGINEER
ENGINEER
ENGINEER
ENGINEER
CHECKER
DRAWN BY
NAME DATE
UNLESS OTHERWISE SPECIFIED, THE FOLLOWING
INFORMATION PERTAINS ONLY TO THIS SHEET
SCALE
CODE INDENTIFICATION NO.
DO NOT SCALE
FROM DRAWING
THIRD ANGLE
PROJECTION
TOLERANCE
X. ±
.X ±
.XX ±
.XXX ±
FRACTION ±
ANGLE ± DEG
DIMENSIONS ARE IN
INCHES
ONLY
MILLIMETER
ONLY
IN [mm] mm [IN]
ALL FINISHED SURFACES
μIN μm
SEE SHEET 1 FOR REVISION
17238
These commodities, technology or software may only be exported from the United States in accordance with the
Export Administration
Regulations. Diversion contrary to U.S. law is prohibited.
IMPORTANT: BEFORE ATTEMPTING TO OPERATE OR INSTALL THIS SYSTEM, IT IS ESSENTIAL TO READ AND UNDERSTAND
THIS PRODUCT'S OPERATION AND MAINTENANCE MANUAL (SHIPPED UNDER SEPARATE COVER). FAILURE TO READ THE
OPERATION AND MAINTENANCE MANUAL BEFORE ATTEMPTING TO OPERATE ANY PALL CORPORATION EQUIPMENT MAY
RESULT IN SERIOUS PERSONAL INJURY AND/OR PRODUCT DAMAGE, AND VOID ANY AND/OR ALL WARRANTIES
.XXXX ±
Pall Advanced Separation Systems Industrial, Cortland NY
D. LEONARD
WH061509
STANDARD
B
19MAY2010
L. BENJAMIN 18MAY2010
S. SMITH 19MAY2010
TEMPLATE REV: R2013.1
1:8
X
1/8
N/A
N/A
N/A
N/A
N/A
UPDATED MATERIAL MASTER NUMBERS AND NEW FORMAT
FOR VAULT.01 RLH
06MAR2013
JMG
06MAR2013
P. BRAME
06MAR2013
ENGINEERING
STANDARD
DOCUMENT
L T
L E D B Y
ORTNOC
ANDARD S
GR
O
U P
SGNIREE
NI
G
N E
MODIFY
TON
OD
| Title: Module, MF, UNA-620A |
| Document: NYCS000008949 |
| Revision: 02 |
| RevRow1: 00 |
| NameCreated By: DMLarkin |
| DateCreated By: 10-OCT-2016 |
| NameApproved By: JHoskins |
| DateApproved By: 10-OCT-2016 |
| Revision DescriptionRow1: Initial Issue |
| RevRow2: 01 |
| NameCreated By_2: DMLarkin |
| DateCreated By_2: 28-NOV-2017 |
| NameApproved By_2: N/A |
| DateApproved By_2: N/A |
| Revision DescriptionRow2: Added Citric Acid to Chemical Compability Table, TAB 2 |
| RevRow3: 02 |
| NameCreated By_3: DMLarkin |
| DateCreated By_3: 21-SEP-2018 |
| NameApproved By_3: N/A |
| DateApproved By_3: N/A |
| Revision DescriptionRow3: Added English units to module datasheet. Added module install drawing, TAB 4 |
| RevRow4: |
| NameCreated By_4: |
| DateCreated By_4: |
| NameApproved By_4: |
| DateApproved By_4: |
| Revision DescriptionRow4: |
File details come from the government source that posted it. Updated .