COVER PAGE OF SELLER’S SUBMITTAL
City Name: Hanford, WA - MSA
Pall Project No.: 01.000287
Job Number: Project L-897, Subcontract 70816
Task Register 6 (Task 1 – VI Submittal Package)
To: (Contractor)
Mission Support Alliance, LLC (MSA)
PO Box 650
Richland, WA 99352
From: (Subcontractor)
Pall Water
A Division of Pall Corporation
839 State Route 13
Cortland, NY 13045
Patty Willis
Phone: 607-758-1699
Name of Project: Hanford, WA, Central Plateau WTF
Pall Document Number: NYCS000015132 Rev: 01
Description of Item: Immersion Heaters
Specification Section: 43 53 49
Deviations: See document NYCS000015388
INDEX:
Page 1: Cover Page Information
Page 2: Revision History and Approvals
Page 3: Tab 1 - NYCS000015393,CSS,Immersion Heaters,01.287
Page 4: Tab 2 - NYCS000015347,Heater,Indecco,Incoloy,80kW,460V,WH075290
Page 5: Tab 3 - NYCS000015352,Heater,Indecco,Titanium,80kW,10in,WH075289
Date: 12/19/2019
PALL ADVANCED SEPARATIONS SYSTEMS
DIVISION OF PALL CORPORATION, CORTLAND, NY
Rev Name Date Created By
Approved By
Created By
Approved By
Created By
Approved By
Created By
Approved By
Revision Description
Title
Document # Revision griffinju Text Box These commodities, technology, or software may only be exported from the United States in accordance with the Export Administration Regulations. Diversion contrary to U.S. law is prohibited.
Doc Number: NYCS000015393R01 Doc Title: NYCS000015393,CSS,Immersion Heaters,01.287.docx
Components Specification Sections
The following specification sections are relevant to the approval of submittal NYCS000015132, Immersion Heaters,01.287:
L‐897, Attachment No. 2 ‐ HNF‐SPEC‐63538, Section 43 53 49, Membrane Filtration System ‐ General.
Any exceptions and clarifications to the specification section above can be found in submittal NYCS000015388,L‐897,Section 43 53 49,Es and Cs,01.287.
Pall has not taken any exceptions or clarifications relevant to the immersion heaters proposed.
Status Part # Description Heater Key Revision
Confirmed 725DU311525 HTR FLG 10X150 80KW 480/3/4 SST/INC 100016432 0
Application Data
Heated Substance: Water
Process Max Temp. (°F): 212
Process Max Press.(PSIG): 160
Heater Orientation: Horizontal
Pipe Flange Data
Size: 10
Flange Material: 304 SST
Class/Std: 150/ANSI B16.5
Gasket Material: Fiber - Garlock 2900
0.062 Thk.
Accessories: None
Element Data
Watts Per Sq.In: 20.56
Moisture Seal Type: Epoxy Seal
Quantity: 24
Quantity Per Circuit: 6
Sheath Material: Incoloy 800
O.D. (in): 0.475
Watts: 3333.33
Volts: 480
Sensor Data
Sensor #1
Type: Sheath Type K Inconel
Location: Standard
XDim: 9.03
Control: See WD
Sensor #2
Type: N/A
Location: N/A
XDim: N/A
Note: See Drawing for referenced XDim Tolerance +/-0.500 in. (12.7mm)
General Data
KW +5/-10%: 80.00
KW per Circuit: 20.00
Voltage: 480
Phase: 3
Circuit Quantity: 4
Line Amps: 96.23
Amps Per Circuit: 24.06
Connection Type: Delta
Connection: Permanent Bussing
Certification Data
UL Recognized & CSA Certified
Enclosure Data
Type 4X - SST Octagon
Designed For Outdoor Use
Wire Connection Data
Power
Min. Wire Temp. Rating: 200 Deg. C
Wire Size: 10 AWG
Wire Qty: 12
Connection Size: 1 1/2" NPT Hub
Connection Qty: 1
Control
Connection Size: 1/2" NPT Hub
Connection Qty: 1
Note: See Drawing for Supplied Location, Size and Type
"B": 60 in (1524.0mm) +/-0.5 (12.7mm) "D": 9.5 in (241.3mm) +0/-0.03 (0.76mm) "OAE": 6.375 in (162.3mm) +/-0.25 (6.3mm)
"Cold Zone": 6 in (152.4mm) +/-0.625 in (16.2mm) "N": N/A "OAZ": 4.1875 in (106.4mm) +/-0.25 (6.3mm)
304 SST Spacers and Rods Required | Lifting Lugs Are Provided
Connection Locations, Sizes and Types: [H1: 1 1/2" NPT Hub] [H2: 1/2" NPT Hub] [H3: NA] [H4: NA]
Drawing
Suitable Pipe Schedules
5s, 5, 10s, 10, 20, 30, STD, 40, 60, SchXH
INDEECO - 425 Hanley Industrial Ct-St. Louis,MO 63144
HEATER SPECIFICATION Page 1 of 1
Date Dec 03, 2019
LarkinD Text Box
NYCS000015347R00
LarkinD Text Box
WH075290
NKUTIL
Callout 6-inch cold zone is likely not enough. Cannot verify without FRP tank drawings. Approval pending FRP submittal.
NKUTIL
Callout Spacers will be immersed in chemicals, SST may not be correct material selection
NKUTIL
Callout Interior face of flange will be immersed in chemicals, SST may not be correct material selection
Status Part # Description Heater Key Revision
Confirmed 725DU311524 HTR FLG 10X150 80KW 480/3/4 STL/SST 100016386 0
Application Data
Heated Substance: Water
Process Max Temp. (°F): 212
Process Max Press.(PSIG): 160
Heater Orientation: Horizontal
Pipe Flange Data
Size: 10
Flange Material: Steel
Class/Std: 150/ANSI B16.5
Gasket Material: Fiber - Garlock 2900
0.062 Thk.
Accessories: None
Element Data
Watts Per Sq.In: 20.56
Moisture Seal Type: Epoxy Seal
Quantity: 24
Quantity Per Circuit: 6
Sheath Material: 304 SST
O.D. (in): 0.475
Watts: 3333.33
Volts: 480
Sensor Data
Sensor #1
Type: Sheath Type K 316SST
Location: Standard
XDim: 9.81
Control: See WD
Sensor #2
Type: N/A
Location: N/A
XDim: N/A
Note: See Drawing for referenced XDim Tolerance +/-0.500 in. (12.7mm)
General Data
KW +5/-10%: 80.00
KW per Circuit: 20.00
Voltage: 480
Phase: 3
Circuit Quantity: 4
Line Amps: 96.23
Amps Per Circuit: 24.06
Connection Type: Delta
Connection: Permanent Bussing
Certification Data
UL Recognized & CSA Certified
Enclosure Data
Type 4X - SST Octagon
Designed For Outdoor Use
Wire Connection Data
Power
Min. Wire Temp. Rating: 200 Deg. C
Wire Size: 10 AWG
Wire Qty: 12
Connection Size: 1 1/2" NPT Hub
Connection Qty: 1
Control
Connection Size: 1/2" NPT Hub
Connection Qty: 1
Note: See Drawing for Supplied Location, Size and Type
"B": 60 in (1524.0mm) +/-0.5 (12.7mm) "D": 9.5 in (241.3mm) +0/-0.03 (0.76mm) "OAE": 6.375 in (162.3mm) +/-0.25 (6.3mm)
"Cold Zone": 6 in (152.4mm) +/-0.625 in (16.2mm) "N": N/A "OAZ": 4.1875 in (106.4mm) +/-0.25 (6.3mm)
304 SST Spacers and Rods Required | Lifting Lugs Are Provided
Connection Locations, Sizes and Types: [H1: 1 1/2" NPT Hub] [H2: 1/2" NPT Hub] [H3: NA] [H4: NA]
Drawing
Suitable Pipe Schedules
5s, 5, 10s, 10, 20, 30, STD, 40, 60, SchXH
Special Construction Flange, Elements and Spacers are all made from Titanium.
Optional Features
INDEECO - 425 Hanley Industrial Ct-St. Louis,MO 63144
Information has been added to this item that cannot be fully evaluated by the I Heat program. Any technical information contained herein is subject to change upon review by INDEECO. If any such changes are required, INDEECO will notify the customer for approval prior to the start of manufacturing.
HEATER SPECIFICATION Page 1 of 1
Date Dec 05, 2019
LarkinD Text Box
NYCS000015352R00
LarkinD Text Box
WH075289
NKUTIL
Callout 6-inch cold zone is likely not enough. Cannot verify without FRP tank drawings. Approval pending FRP submittal.
NKUTIL
Callout Spacers will be immersed in chemicals, SST may not be correct material selection
| Cover Page Information |
| Revision History and Approvals |
| Tab 01 - NYCS000015393,CSS,Immersion Heaters,01.287 |
| Tab 02 - NYCS000015347,Heater,Indeeco,Incoloy,80kW,460V,WH075290 |
| Tab 03 - NYCS000015352,Heater,Indeeco,Titanium,80kW,10in,WH075289 |
| Title: Immersion Heaters, 01.287 |
| Document: NYCS000015132 |
| Revision: 01 |
| RevRow1: 0 |
| NameCreated By: DMLarkin |
| DateCreated By: 09-DEC-2019 |
| NameApproved By: JHoskins |
| DateApproved By: 09-DEC-2019 |
| Revision DescriptionRow1: Initial Issue |
| RevRow2: 1 |
| NameCreated By_2: DMLarkin |
| DateCreated By_2: 16-DEC-2019 |
| NameApproved By_2: JHoskins |
| DateApproved By_2: 16-DEC-201 |
| Revision DescriptionRow2: Tab 1 changed |
| RevRow3: |
| NameCreated By_3: |
| DateCreated By_3: |
| NameApproved By_3: |
| DateApproved By_3: |
| Revision DescriptionRow3: |
| RevRow4: |
| NameCreated By_4: |
| DateCreated By_4: |
| NameApproved By_4: |
| DateApproved By_4: |
| Revision DescriptionRow4: |
File details come from the government source that posted it. Updated .