This document package includes final bid documents and calculations for an infrastructure upgrades project at a Department of Veterans Affairs medical center in New Orleans, Louisiana. The project number is 629-22-700 and involves modernizing electronic health record systems. Calculations cover HVAC load and system sizing for multiple building zones. The solicitation is number 36C77623B0038 and was issued by the VA Technology Acquisition Center in Austin, Texas for construction services related to the infrastructure upgrades. Response due dates and award timing are not provided. The calculations indicate design conditions, equipment specifications, and airflow requirements for cooling and heating various exam and treatment room zones to meet occupancy needs.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Final Bid Documents – 100% Submittal: Calculations April 25, 2023
Department of Veterans Health Administration
Electronic Health Record Modernization (EHRM) Infrastructure Upgrades – New Orleans, LA Project No. 629‐22‐700
Contract No. 36C77622C0049
Southeast Louisiana Veterans Health Care System (SLVHCS) New Orleans
2400 Canal Street, New Orleans, LA 70119
US Department of Veterans Affairs
Program Contracting Activity Central (PCAC)
6100 Oak Tree Blvd., Suite 490
Independence, OH 44131
Prepared by:
GDM of Oregon
1401 W 34th Ave Suite 200
Anchorage, Alaska 99503
SLVHCS Design Narrative New Orleans, LA 4/25/2023 100% FINAL BID SUBMITTAL
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – New Orleans, LA VA Project No. 629‐22‐700 Page 2 of 3
1 Table of Contents
2. HVAC LOAD CALCULATIONS
SLVHCS Design Narrative New Orleans, LA 4/25/2023 100% FINAL BID SUBMITTAL
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades – New Orleans, LA VA Project No. 629‐22‐700 Page 3 of 3
2 HVAC LOAD CALCULATIONS
By Chkd. of
Location:
Elevation 10 Dry Bulb Temperature
Air Density
Humidity Ratio
Humidity Obtained thru Permeation x x ( - ) = x x ( - ) = gr/hr
Wall 2 x x ( - ) = gr/hr
Wall 3 x x ( - ) = gr/hr
Wall 4 x x ( - ) = gr/hr
Floor x x ( - ) = gr/hr
Ceiling x x ( - ) = gr/hr total gr/hr
Humidity Obtained thru infiltration x ( - ) x = x x ( - ) x = gr/hr total gr/hr
SAFETY FACTOR 25 %
ACH equivalent TOTAL WITH 25% SF gr/hr lbs/hr
0.0753 min per hour
14235.52
17794.39
2.542
Wall 4 33 152.1 58.4 0.0753 14118.28
Fresh
Air
(CFM)
Moisture
Outside
(gr/lb)
Moisture
Inside
(gr/lb)
1.00
Air
Density
(lb/cu.ft.)
Infiltration
Load
(gr/hr)
150 0.21 1.005 0.350 20.6325
117.24
18.9819
174 0.21 1.005 0.350 23.9337
150 0.21 0.692 0.350 10.776465
174 0.21 1.005 0.350 23.9337
Wall 1 138 0.21 1.005 0.350
138 0.21 1.005 0.350
150 0.2 103.3 46.7 150
18.9819
1.005
Surface
Area
(sq.ft.)
Permeance factor
(gr/hr/sq.ft.)
Larger
Vapor
Pressure
(in.hg)
Smaller
Vapor
Pressure
(in.hg)
Permeation
Load
(gr/hr)
Vapor Pressure 1.005 0.001 0.692 0.350
Room Building
107 35.6 68 64 107
Dewpoint 87 24(16) 68 48.6
New Orleans Weather Extremes Ground
Water
Internal Conditions
Summer
DM (MUNTERS)Sheet 1 1
Job# 22-012 Job Name EHRM New Orleans
Subject Dehumidification Calculations Date 3/15/2023
SDB
Winter
Air System Sizing Summary for BC TR 1B179 Project Name: 22-012 EHRM NOLA 03092023 03/15/2023 Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 1B179 Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 124.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data Total coil load 2.7 Tons Total coil load 32.7 MBH Sensible coil load 28.0 MBH Coil CFM at Jul 1500 700 CFM Max block CFM 700 CFM Sum of peak zone CFM 700 CFM Sensible heat ratio 0.854 CFM/Ton 256.6 ft²/Ton 45.4 BTU/(hr·ft²) 264.1 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1500
OA DB / WB 93.3 / 82.4 °F
Entering DB / WB 95.8 / 71.2 °F Leaving DB / WB 58.8 / 56.6 °F Coil ADP 54.7 °F Bypass Factor 0.100 Resulting RH 29 % Design supply temp. 58.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data Max coil load 12.9 MBH Coil CFM at Des Htg 700 CFM Max coil CFM 700 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg BTU/(hr·ft²) 104.3 Ent. DB / Lvg DB 40.9 / 58.0 °F
Humidifier Sizing Data Max steam flow at Jan 0200 4.31 lb/hr Airflow Rate 700 CFM
Air mass flow 3147.87 lb/hr Moisture gain .00137 lb/lb
Supply Fan Sizing Data Actual max CFM 700 CFM Standard CFM 700 CFM Actual max CFM/ft² 5.65 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 7 CFM CFM/ft² 0.06 CFM/ft²
CFM/person 0.00 CFM/person
Hourly Analysis Program 5.11 Page 1 of 88
Zone Sizing Summary for BC TR 1B179
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 1B179 Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 124.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/ft²
Reheat Coil Load
(MBH)
Reheat Coil
Water gpm
@ 20.0 °F
Zone Htg Unit
Coil Load
(MBH)
Zone Htg Unit Water gpm
@ 20.0 °F
Mixing Box Fan Airflow
(CFM)
Zone 1 700 700 5.65 0.0 - 0.0 - 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 28.0 Jan 2300 0.0 124.0
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Zone 1
BC TR 1B179 1 28.0 Jan 2300 700 0.0 124.0 5.65
Hourly Analysis Program 5.11 Page 2 of 88
Air System Design Load Summary for BC TR 1B179
Prepared by: GDM-AE 01:08PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.3 °F / 82.4 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 124 ft² 0 - 124 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 124 W 423 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 7000 W 23884 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 3646 0 25% 0 0
>> Total Zone Loads - 27953 0 - 0 0
Zone Conditioning - 27986 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 700 CFM 0 - 700 CFM 0 -
Ventilation Load 7 CFM -21 386 7 CFM 88 1
Supply Fan Load 700 CFM 0 - 700 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 27966 386 - 88 1
Central Cooling Coil - 27966 4780 - 0 0
Central Heating Coil - 0 - - 12932 -
Humidification Load - - -4394 - - 0
>> Total Conditioning - 27966 386 - 12932 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
Hourly Analysis Program 5.11 Page 3 of 88
Space Design Load Summary for BC TR 1B179
Prepared by: GDM-AE 01:08PM
TABLE 1.1.A. Component Loads For Space "BC TR 1B179" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 64.5 °F / 64.0 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
OCCUPIED T-STAT 95.0 °F OCCUPIED T-STAT 41.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 124 ft² 0 - 124 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 124 W 423 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 7000 W 23884 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 3646 0 25% 0 0
>> Total Zone Loads - 27953 0 - 0 0
TABLE 1.1.B. Envelope Loads For Space "BC TR 1B179" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
Hourly Analysis Program 5.11 Page 4 of 88
System Psychrometrics for BC TR 1B179
Prepared by: GDM-AE 01:08PM
July DESIGN COOLING DAY, 1500
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 93.3 0.02153 7 400 -21 386
Vent - Return Mixing Outlet 95.8 0.01070 700 796 - -
Central Cooling Coil Outlet 58.8 0.00926 700 796 27966 4780
Central Heating Coil Outlet 58.8 0.00926 700 796 0 -
Supply Fan Outlet 58.8 0.00926 700 796 0 -
Humidifier Outlet 58.8 0.01059 700 796 - 4394
Cold Supply Duct Outlet 58.8 0.01059 700 796 - -
Zone Air - 95.9 0.01059 700 800 27986 0
Return Plenum Outlet 95.9 0.01059 700 800 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 27953 Cooling 27986 95.9 700 800 0 0
Hourly Analysis Program 5.11 Page 5 of 88
Prepared by: GDM-AE 01:08PM
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 30.0 0.00172 7 400 -88 -1
Vent - Return Mixing Outlet 40.9 0.00176 700 796 - -
Central Cooling Coil Outlet 40.9 0.00176 700 796 0 0
Central Heating Coil Outlet 58.0 0.00176 700 796 12932 -
Supply Fan Outlet 58.0 0.00176 700 796 0 -
Humidifier Outlet 58.0 0.00176 700 796 - 0
Cold Supply Duct Outlet 41.0 0.00176 700 796 - -
Zone Air - 41.0 0.00176 700 800 0 0
Return Plenum Outlet 41.0 0.00176 700 800 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband 0 41.0 700 800 0 0
Hourly Analysis Program 5.11 Page 6 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Humidifier Outlet
6. Room Air 1
5 6
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0.022
0.024
30 40 50 60 70 80 90 100
Location: New Orleans IAP, Louisiana Altitude: 30.0 ft.
Data for: July DESIGN COOLING DAY, 1500
S p e c ific
H u m id ity ( lb
/lb
Temperature ( °F )
Hourly Analysis Program 5.11 Page 7 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet
5. Room Air
1 2 345
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
30 40 50 60 70 80 90
Data for: WINTER DESIGN HEATING
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 8 of 88
Air System Sizing Summary for BC TR 1C228
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 1C228 Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 154.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data Total coil load 2.7 Tons Total coil load 33.0 MBH Sensible coil load 28.1 MBH Coil CFM at Jul 1800 703 CFM Max block CFM 703 CFM Sum of peak zone CFM 703 CFM Sensible heat ratio 0.852 CFM/Ton 256.0 ft²/Ton 56.1 BTU/(hr·ft²) 214.1 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1800
OA DB / WB 90.0 / 81.7 °F
Entering DB / WB 95.9 / 71.3 °F Leaving DB / WB 58.9 / 56.7 °F Coil ADP 54.8 °F Bypass Factor 0.100 Resulting RH 29 % Design supply temp. 58.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data Max coil load 13.0 MBH Coil CFM at Des Htg 703 CFM Max coil CFM 703 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg BTU/(hr·ft²) 84.5 Ent. DB / Lvg DB 40.9 / 58.0 °F
Humidifier Sizing Data Max steam flow at Jan 1100 4.30 lb/hr Airflow Rate 703 CFM
Air mass flow 3161.13 lb/hr Moisture gain .00136 lb/lb
Supply Fan Sizing Data Actual max CFM 703 CFM Standard CFM 702 CFM Actual max CFM/ft² 4.57 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 9 CFM CFM/ft² 0.06 CFM/ft²
Hourly Analysis Program 5.11 Page 9 of 88
Zone Sizing Summary for BC TR 1C228
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 1C228 Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 154.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/ft²
Reheat Coil Load
(MBH)
Reheat Coil
Water gpm
@ 20.0 °F
Zone Htg Unit
Coil Load
(MBH)
Zone Htg Unit Water gpm
@ 20.0 °F
Mixing Box Fan Airflow
(CFM)
Zone 1 703 703 4.57 0.0 - 0.0 - 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 28.1 Jan 2300 0.0 154.0
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Zone 1
BC TR 1C228 1 28.1 Jan 2300 703 0.0 154.0 4.57
Hourly Analysis Program 5.11 Page 10 of 88
Air System Design Load Summary for BC TR 1C228
Prepared by: GDM-AE 01:08PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 °F / 81.7 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 121 ft² 0 - 121 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 154 W 525 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 7000 W 23884 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 3661 0 25% 0 0
>> Total Zone Loads - 28071 0 - 0 0
Zone Conditioning - 28133 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 703 CFM 0 - 703 CFM 0 -
Ventilation Load 9 CFM -59 478 9 CFM 110 1
Supply Fan Load 703 CFM 0 - 703 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 28074 478 - 110 1
Central Cooling Coil - 28074 4891 - 0 0
Central Heating Coil - 0 - - 13007 -
Humidification Load - - -4413 - - 0
>> Total Conditioning - 28074 478 - 13007 0
Key: Positive values are clg loads Positive values are htg loads
Hourly Analysis Program 5.11 Page 11 of 88
Space Design Load Summary for BC TR 1C228
Prepared by: GDM-AE 01:08PM
TABLE 1.1.A. Component Loads For Space "BC TR 1C228" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 64.5 °F / 64.0 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
OCCUPIED T-STAT 95.0 °F OCCUPIED T-STAT 41.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 121 ft² 0 - 121 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 154 W 525 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 7000 W 23884 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 3661 0 25% 0 0
>> Total Zone Loads - 28071 0 - 0 0
TABLE 1.1.B. Envelope Loads For Space "BC TR 1C228" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
Hourly Analysis Program 5.11 Page 12 of 88
System Psychrometrics for BC TR 1C228
Prepared by: GDM-AE 01:08PM
July DESIGN COOLING DAY, 1800
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 90.0 0.02153 9 400 -59 478
Vent - Return Mixing Outlet 95.9 0.01076 703 795 - -
Central Cooling Coil Outlet 58.9 0.00929 703 795 28074 4891
Central Heating Coil Outlet 58.9 0.00929 703 795 0 -
Supply Fan Outlet 58.9 0.00929 703 795 0 -
Humidifier Outlet 58.9 0.01062 703 795 - 4413
Cold Supply Duct Outlet 58.9 0.01062 703 795 - -
Zone Air - 96.0 0.01062 703 800 28133 0
Return Plenum Outlet 96.0 0.01062 703 800 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 28071 Cooling 28133 96.0 703 800 0 0
Hourly Analysis Program 5.11 Page 13 of 88
Prepared by: GDM-AE 01:08PM
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 30.0 0.00172 9 400 -110 -1
Vent - Return Mixing Outlet 40.9 0.00174 703 795 - -
Central Cooling Coil Outlet 40.9 0.00174 703 795 0 0
Central Heating Coil Outlet 58.0 0.00174 703 795 13007 -
Supply Fan Outlet 58.0 0.00174 703 795 0 -
Humidifier Outlet 58.0 0.00174 703 795 - 0
Cold Supply Duct Outlet 41.0 0.00174 703 795 - -
Zone Air - 41.0 0.00174 703 800 0 0
Return Plenum Outlet 41.0 0.00174 703 800 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband 0 41.0 703 800 0 0
Hourly Analysis Program 5.11 Page 14 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Humidifier Outlet
6. Room Air 1
5 6
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0.022
Data for: July DESIGN COOLING DAY, 1800
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 15 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet
5. Room Air
1 2 345
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
Data for: WINTER DESIGN HEATING
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 16 of 88
Air System Sizing Summary for BC TR 2B161A
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 2B161A Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 110.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data Total coil load 2.0 Tons Total coil load 23.8 MBH Sensible coil load 20.0 MBH Coil CFM at Jul 1500 502 CFM Max block CFM 502 CFM Sum of peak zone CFM 502 CFM Sensible heat ratio 0.841 CFM/Ton 253.2 ft²/Ton 55.4 BTU/(hr·ft²) 216.4 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1500
OA DB / WB 93.3 / 82.4 °F
Entering DB / WB 95.9 / 71.4 °F Leaving DB / WB 58.9 / 56.8 °F Coil ADP 54.8 °F Bypass Factor 0.100 Resulting RH 29 % Design supply temp. 58.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data Max coil load 9.4 MBH Coil CFM at Des Htg 502 CFM Max coil CFM 502 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg BTU/(hr·ft²) 85.2 Ent. DB / Lvg DB 40.7 / 58.0 °F
Humidifier Sizing Data Max steam flow at Jan 1500 2.95 lb/hr Airflow Rate 502 CFM
Air mass flow 2257.95 lb/hr Moisture gain .00131 lb/lb
Supply Fan Sizing Data Actual max CFM 502 CFM Standard CFM 502 CFM Actual max CFM/ft² 4.57 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 13 CFM CFM/ft² 0.12 CFM/ft²
Hourly Analysis Program 5.11 Page 17 of 88
Zone Sizing Summary for BC TR 2B161A
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 2B161A Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 110.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/ft²
Reheat Coil Load
(MBH)
Reheat Coil
Water gpm
@ 20.0 °F
Zone Htg Unit
Coil Load
(MBH)
Zone Htg Unit Water gpm
@ 20.0 °F
Mixing Box Fan Airflow
(CFM)
Zone 1 502 502 4.57 0.0 - 0.0 - 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 20.1 Jan 2300 0.0 110.0
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Zone 1
BC TR 2B155B 1 20.1 Jan 2300 502 0.0 110.0 4.57
Hourly Analysis Program 5.11 Page 18 of 88
Air System Design Load Summary for BC TR 2B161A
Prepared by: GDM-AE 01:08PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.3 °F / 82.4 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 110 W 375 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2615 0 25% 0 0
>> Total Zone Loads - 20051 0 - 0 0
Zone Conditioning - 20047 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 502 CFM 0 - 502 CFM 0 -
Ventilation Load 13 CFM -37 682 13 CFM 157 0
Supply Fan Load 502 CFM 0 - 502 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 20010 682 - 157 0
Central Cooling Coil - 20010 3797 - 0 0
Central Heating Coil - 0 - - 9369 -
Humidification Load - - -3115 - - 0
>> Total Conditioning - 20010 682 - 9369 0
Key: Positive values are clg loads Positive values are htg loads
Hourly Analysis Program 5.11 Page 19 of 88
Space Design Load Summary for BC TR 2B161A
Prepared by: GDM-AE 01:08PM
TABLE 1.1.A. Component Loads For Space "BC TR 2B155B" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 64.5 °F / 64.0 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
OCCUPIED T-STAT 95.0 °F OCCUPIED T-STAT 41.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 110 W 375 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2615 0 25% 0 0
>> Total Zone Loads - 20051 0 - 0 0
TABLE 1.1.B. Envelope Loads For Space "BC TR 2B155B" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
Hourly Analysis Program 5.11 Page 20 of 88
System Psychrometrics for BC TR 2B161A
Prepared by: GDM-AE 01:08PM
July DESIGN COOLING DAY, 1500
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 93.3 0.02153 13 400 -37 682
Vent - Return Mixing Outlet 95.9 0.01091 502 769 - -
Central Cooling Coil Outlet 58.9 0.00932 502 769 20010 3797
Central Heating Coil Outlet 58.9 0.00932 502 769 0 -
Supply Fan Outlet 58.9 0.00932 502 769 0 -
Humidifier Outlet 58.9 0.01063 502 769 - 3115
Cold Supply Duct Outlet 58.9 0.01063 502 769 - -
Zone Air - 95.9 0.01063 502 779 20047 0
Return Plenum Outlet 95.9 0.01063 502 779 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 20051 Cooling 20047 95.9 502 779 0 0
Hourly Analysis Program 5.11 Page 21 of 88
Prepared by: GDM-AE 01:08PM
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 30.0 0.00172 13 400 -157 0
Vent - Return Mixing Outlet 40.7 0.00172 502 769 - -
Central Cooling Coil Outlet 40.7 0.00172 502 769 0 0
Central Heating Coil Outlet 58.0 0.00172 502 769 9369 -
Supply Fan Outlet 58.0 0.00172 502 769 0 -
Humidifier Outlet 58.0 0.00172 502 769 - 0
Cold Supply Duct Outlet 41.0 0.00172 502 769 - -
Zone Air - 41.0 0.00172 502 779 0 0
Return Plenum Outlet 41.0 0.00172 502 779 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband 0 41.0 502 779 0 0
Hourly Analysis Program 5.11 Page 22 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Humidifier Outlet
6. Room Air 1
5 6
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0.022
Data for: July DESIGN COOLING DAY, 1500
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 23 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet
5. Room Air
1 2 345
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
Data for: WINTER DESIGN HEATING
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 24 of 88
Air System Sizing Summary for BC TR 2C152G
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 2C152G Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 75.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data Total coil load 2.0 Tons Total coil load 23.5 MBH Sensible coil load 20.0 MBH Coil CFM at Jul 1500 499 CFM Max block CFM 499 CFM Sum of peak zone CFM 499 CFM Sensible heat ratio 0.848 CFM/Ton 254.2 ft²/Ton 38.2 BTU/(hr·ft²) 314.0 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1500
OA DB / WB 93.3 / 82.4 °F
Entering DB / WB 96.0 / 71.4 °F Leaving DB / WB 58.9 / 56.7 °F Coil ADP 54.8 °F Bypass Factor 0.100 Resulting RH 29 % Design supply temp. 58.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data Max coil load 9.3 MBH Coil CFM at Des Htg 499 CFM Max coil CFM 499 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg BTU/(hr·ft²) 123.4 Ent. DB / Lvg DB 40.8 / 58.0 °F
Humidifier Sizing Data Max steam flow at Jan 1400 3.06 lb/hr Airflow Rate 499 CFM
Air mass flow 2242.48 lb/hr Moisture gain .00137 lb/lb
Supply Fan Sizing Data Actual max CFM 499 CFM Standard CFM 498 CFM Actual max CFM/ft² 6.65 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 9 CFM CFM/ft² 0.12 CFM/ft²
Hourly Analysis Program 5.11 Page 25 of 88
Zone Sizing Summary for BC TR 2C152G
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 2C152G Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 75.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/ft²
Reheat Coil Load
(MBH)
Reheat Coil
Water gpm
@ 20.0 °F
Zone Htg Unit
Coil Load
(MBH)
Zone Htg Unit Water gpm
@ 20.0 °F
Mixing Box Fan Airflow
(CFM)
Zone 1 499 499 6.65 0.0 - 0.0 - 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 19.9 Jan 2300 0.0 75.0
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Zone 1
BC TR 2C152G 1 19.9 Jan 2300 499 0.0 75.0 6.65
Hourly Analysis Program 5.11 Page 26 of 88
Air System Design Load Summary for BC TR 2C152G
Prepared by: GDM-AE 01:08PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.3 °F / 82.4 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 75 W 256 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2597 0 25% 0 0
>> Total Zone Loads - 19913 0 - 0 0
Zone Conditioning - 19983 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 499 CFM 0 - 499 CFM 0 -
Ventilation Load 9 CFM -27 466 9 CFM 107 0
Supply Fan Load 499 CFM 0 - 499 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 19957 466 - 107 0
Central Cooling Coil - 19957 3591 - 0 0
Central Heating Coil - 0 - - 9256 -
Humidification Load - - -3125 - - 0
>> Total Conditioning - 19957 466 - 9256 0
Key: Positive values are clg loads Positive values are htg loads
Hourly Analysis Program 5.11 Page 27 of 88
Space Design Load Summary for BC TR 2C152G
Prepared by: GDM-AE 01:08PM
TABLE 1.1.A. Component Loads For Space "BC TR 2C152G" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 64.5 °F / 64.0 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
OCCUPIED T-STAT 95.0 °F OCCUPIED T-STAT 41.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 75 W 256 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2597 0 25% 0 0
>> Total Zone Loads - 19913 0 - 0 0
TABLE 1.1.B. Envelope Loads For Space "BC TR 2C152G" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
Hourly Analysis Program 5.11 Page 28 of 88
System Psychrometrics for BC TR 2C152G
Prepared by: GDM-AE 01:08PM
July DESIGN COOLING DAY, 1500
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 93.3 0.02153 9 400 -27 466
Vent - Return Mixing Outlet 96.0 0.01082 499 793 - -
Central Cooling Coil Outlet 58.9 0.00930 499 793 19957 3591
Central Heating Coil Outlet 58.9 0.00930 499 793 0 -
Supply Fan Outlet 58.9 0.00930 499 793 0 -
Humidifier Outlet 58.9 0.01062 499 793 - 3125
Cold Supply Duct Outlet 58.9 0.01062 499 793 - -
Zone Air - 96.0 0.01062 499 800 19983 0
Return Plenum Outlet 96.0 0.01062 499 800 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 19913 Cooling 19983 96.0 499 800 0 0
Hourly Analysis Program 5.11 Page 29 of 88
Prepared by: GDM-AE 01:08PM
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 30.0 0.00172 9 400 -107 0
Vent - Return Mixing Outlet 40.8 0.00172 499 793 - -
Central Cooling Coil Outlet 40.8 0.00172 499 793 0 0
Central Heating Coil Outlet 58.0 0.00172 499 793 9256 -
Supply Fan Outlet 58.0 0.00172 499 793 0 -
Humidifier Outlet 58.0 0.00172 499 793 - 0
Cold Supply Duct Outlet 41.0 0.00172 499 793 - -
Zone Air - 41.0 0.00172 499 800 0 0
Return Plenum Outlet 41.0 0.00172 499 800 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband 0 41.0 499 800 0 0
Hourly Analysis Program 5.11 Page 30 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Humidifier Outlet
6. Room Air 1
5 6
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0.022
Data for: July DESIGN COOLING DAY, 1500
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 31 of 88
Prepared by: GDM-AE 01:08PM
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet
5. Room Air
1 2 345
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
Data for: WINTER DESIGN HEATING
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 32 of 88
Air System Sizing Summary for BC TR 3B161A
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 3B161A Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 110.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data Total coil load 2.0 Tons Total coil load 23.8 MBH Sensible coil load 20.0 MBH Coil CFM at Jul 1500 502 CFM Max block CFM 502 CFM Sum of peak zone CFM 502 CFM Sensible heat ratio 0.841 CFM/Ton 253.2 ft²/Ton 55.4 BTU/(hr·ft²) 216.4 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1500
OA DB / WB 93.3 / 82.4 °F
Entering DB / WB 95.9 / 71.4 °F Leaving DB / WB 58.9 / 56.8 °F Coil ADP 54.8 °F Bypass Factor 0.100 Resulting RH 29 % Design supply temp. 58.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data Max coil load 9.4 MBH Coil CFM at Des Htg 502 CFM Max coil CFM 502 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg BTU/(hr·ft²) 85.2 Ent. DB / Lvg DB 40.7 / 58.0 °F
Humidifier Sizing Data Max steam flow at Jan 1500 2.95 lb/hr Airflow Rate 502 CFM
Air mass flow 2257.95 lb/hr Moisture gain .00131 lb/lb
Supply Fan Sizing Data Actual max CFM 502 CFM Standard CFM 502 CFM Actual max CFM/ft² 4.57 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 13 CFM CFM/ft² 0.12 CFM/ft²
Hourly Analysis Program 5.11 Page 33 of 88
Zone Sizing Summary for BC TR 3B161A
Prepared by: GDM-AE 01:08PM
Air System Information Air System Name BC TR 3B161A Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 110.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/ft²
Reheat Coil Load
(MBH)
Reheat Coil
Water gpm
@ 20.0 °F
Zone Htg Unit
Coil Load
(MBH)
Zone Htg Unit Water gpm
@ 20.0 °F
Mixing Box Fan Airflow
(CFM)
Zone 1 502 502 4.57 0.0 - 0.0 - 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 20.1 Jan 2300 0.0 110.0
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Zone 1
BC TR 3B161A 1 20.1 Jan 2300 502 0.0 110.0 4.57
Hourly Analysis Program 5.11 Page 34 of 88
Air System Design Load Summary for BC TR 3B161A
Prepared by: GDM-AE 01:08PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.3 °F / 82.4 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 110 W 375 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2615 0 25% 0 0
>> Total Zone Loads - 20051 0 - 0 0
Zone Conditioning - 20047 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 502 CFM 0 - 502 CFM 0 -
Ventilation Load 13 CFM -37 682 13 CFM 157 0
Supply Fan Load 502 CFM 0 - 502 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 20010 682 - 157 0
Central Cooling Coil - 20010 3797 - 0 0
Central Heating Coil - 0 - - 9369 -
Humidification Load - - -3115 - - 0
>> Total Conditioning - 20010 682 - 9369 0
Key: Positive values are clg loads Positive values are htg loads
Hourly Analysis Program 5.11 Page 35 of 88
Space Design Load Summary for BC TR 3B161A
Prepared by: GDM-AE 01:09PM
TABLE 1.1.A. Component Loads For Space "BC TR 3B161A" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 64.5 °F / 64.0 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
OCCUPIED T-STAT 95.0 °F OCCUPIED T-STAT 41.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 110 W 375 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2615 0 25% 0 0
>> Total Zone Loads - 20051 0 - 0 0
TABLE 1.1.B. Envelope Loads For Space "BC TR 3B161A" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
Hourly Analysis Program 5.11 Page 36 of 88
System Psychrometrics for BC TR 3B161A
Prepared by: GDM-AE 01:09PM
July DESIGN COOLING DAY, 1500
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 93.3 0.02153 13 400 -37 682
Vent - Return Mixing Outlet 95.9 0.01091 502 769 - -
Central Cooling Coil Outlet 58.9 0.00932 502 769 20010 3797
Central Heating Coil Outlet 58.9 0.00932 502 769 0 -
Supply Fan Outlet 58.9 0.00932 502 769 0 -
Humidifier Outlet 58.9 0.01063 502 769 - 3115
Cold Supply Duct Outlet 58.9 0.01063 502 769 - -
Zone Air - 95.9 0.01063 502 779 20047 0
Return Plenum Outlet 95.9 0.01063 502 779 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 20051 Cooling 20047 95.9 502 779 0 0
Hourly Analysis Program 5.11 Page 37 of 88
Prepared by: GDM-AE 01:09PM
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 30.0 0.00172 13 400 -157 0
Vent - Return Mixing Outlet 40.7 0.00172 502 769 - -
Central Cooling Coil Outlet 40.7 0.00172 502 769 0 0
Central Heating Coil Outlet 58.0 0.00172 502 769 9369 -
Supply Fan Outlet 58.0 0.00172 502 769 0 -
Humidifier Outlet 58.0 0.00172 502 769 - 0
Cold Supply Duct Outlet 41.0 0.00172 502 769 - -
Zone Air - 41.0 0.00172 502 779 0 0
Return Plenum Outlet 41.0 0.00172 502 779 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4741.5 BTU/(hr-CFM) Site Altitude = 30.0 ft
TABLE 2: ZONE DATA
Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Hourly Analysis Program 5.11 Page 38 of 88
Prepared by: GDM-AE 01:09PM
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Humidifier Outlet
6. Room Air 1
5 6
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0.022
Data for: July DESIGN COOLING DAY, 1500
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 39 of 88
Prepared by: GDM-AE 01:09PM
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet
5. Room Air
1 2 345
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
Data for: WINTER DESIGN HEATING
S p e c ific
H u m id ity ( lb
/lb
Hourly Analysis Program 5.11 Page 40 of 88
Air System Sizing Summary for BC TR 3C152E
Prepared by: GDM-AE 01:09PM
Air System Information Air System Name BC TR 3C152E Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 109.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Central Cooling Coil Sizing Data Total coil load 2.0 Tons Total coil load 23.9 MBH Sensible coil load 20.1 MBH Coil CFM at Jul 1600 502 CFM Max block CFM 502 CFM Sum of peak zone CFM 502 CFM Sensible heat ratio 0.841 CFM/Ton 252.5 ft²/Ton 54.8 BTU/(hr·ft²) 219.0 Water flow @ 10.0 °F rise N/A
Load occurs at Jul 1600
OA DB / WB 92.8 / 82.3 °F
Entering DB / WB 95.9 / 71.4 °F Leaving DB / WB 58.9 / 56.7 °F Coil ADP 54.8 °F Bypass Factor 0.100 Resulting RH 29 % Design supply temp. 58.0 °F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °F
Central Heating Coil Sizing Data Max coil load 9.4 MBH Coil CFM at Des Htg 502 CFM Max coil CFM 502 CFM Water flow @ 20.0 °F drop N/A
Load occurs at Des Htg BTU/(hr·ft²) 85.9 Ent. DB / Lvg DB 40.7 / 58.0 °F
Humidifier Sizing Data Max steam flow at Jan 1500 3.05 lb/hr Airflow Rate 502 CFM
Air mass flow 2257.50 lb/hr Moisture gain .00135 lb/lb
Supply Fan Sizing Data Actual max CFM 502 CFM Standard CFM 502 CFM Actual max CFM/ft² 4.61 CFM/ft²
Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in wg
Outdoor Ventilation Air Data Design airflow CFM 13 CFM CFM/ft² 0.12 CFM/ft²
Hourly Analysis Program 5.11 Page 41 of 88
Zone Sizing Summary for BC TR 3C152E
Prepared by: GDM-AE 01:09PM
Air System Information Air System Name BC TR 3C152E Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1 Floor Area 109.0 ft² Location New Orleans IAP, Louisiana
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/ft²
Reheat Coil Load
(MBH)
Reheat Coil
Water gpm
@ 20.0 °F
Zone Htg Unit
Coil Load
(MBH)
Zone Htg Unit Water gpm
@ 20.0 °F
Mixing Box Fan Airflow
(CFM)
Zone 1 502 502 4.61 0.0 - 0.0 - 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 20.0 Jan 2300 0.0 109.0
Space Loads and Airflows
Zone Name / Space Name Mult.
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (ft²)
Space CFM/ft²
Zone 1
BC TR 3C152E 1 20.0 Jan 2300 502 0.0 109.0 4.61
Hourly Analysis Program 5.11 Page 42 of 88
Air System Design Load Summary for BC TR 3C152E
Prepared by: GDM-AE 01:09PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 92.8 °F / 82.3 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 109 W 372 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2615 0 25% 0 0
>> Total Zone Loads - 20047 0 - 0 0
Zone Conditioning - 20115 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 502 CFM 0 - 502 CFM 0 -
Ventilation Load 13 CFM -45 678 13 CFM 155 0
Supply Fan Load 502 CFM 0 - 502 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 20070 678 - 155 0
Central Cooling Coil - 20070 3796 - 0 0
Central Heating Coil - 0 - - 9366 -
Humidification Load - - -3118 - - 0
>> Total Conditioning - 20070 678 - 9366 0
Key: Positive values are clg loads Positive values are htg loads
Hourly Analysis Program 5.11 Page 43 of 88
Space Design Load Summary for BC TR 3C152E
Prepared by: GDM-AE 01:09PM
TABLE 1.1.A. Component Loads For Space "BC TR 3C152E" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 64.5 °F / 64.0 °F HEATING OA DB / WB 30.0 °F / 25.3 °F
OCCUPIED T-STAT 95.0 °F OCCUPIED T-STAT 41.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 109 W 372 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 5000 W 17060 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 2615 0 25% 0 0
>> Total Zone Loads - 20047 0 - 0 0
TABLE 1.1.B. Envelope Loads For Space "BC TR 3C152E" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
Hourly Analysis Program 5.11 Page 44 of 88
System Psychrometrics for BC TR 3C152E
Prepared by: GDM-AE 01:09PM
July DESIGN COOLING DAY, 1600
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 92.8 0.02153 13 400 -45 678
Vent - Return Mixing Outlet 95.9 0.01089 502 770 - -
Central Cooling Coil Outlet 58.9 0.00930 502 770 20070 3796
Central Heating Coil Outlet 58.9 0.00930 502 770 0 -
Supply Fan Outlet 58.9 0.00930 502 770 0 -
Humidifier Outlet 58.9 0.01061 502 770 - 3118
Cold Supply Duct Outlet 58.9 0.01061 502 770 - -
Zone Air - 96.0 0.01061 502 779 20115 0
Return Plenum Outlet 96.0 0.01061 502 779 0 -
Air Density x Heat Capacity x Conversion…