This document provides details on a federal contract opportunity for infrastructure upgrades at a Veterans Affairs facility in New Orleans, Louisiana. The solicitation number is 36C77623B0038 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity is for construction services related to EHRM infrastructure upgrades at the New Orleans location. The file attached is a set of drawings numbering 15 of 17 that are designated 01-EJ-001 through 00-EJ-026. The solicitation seeks bids and proposals related to upgrading and improving infrastructure systems at the New Orleans facility.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E)UNIT SECONDARY SUBSTATION
USS01
LVN-2001
(3) 4"C.
(4) #900 XHHW-AL
(1) #250 XHHW-AL GND
CT
2 SETS OF:
(1) 4"C.
(4) #600
(1) #1/0 GND
CT NB111FEEDER BUSWAY
800A, 3Ø, 4W, 100% G
F
F XFMR
208/120V 480V:
(E)T5
400AF
150AT
400AF
100AT
(1) 3/4"C.
(1) #2 GND
(E)R12421 208/ 120V
A
(E)R12421 208/ 120V
B
(4) #250
(1) #2 GND
(1) 3"C.
(4) #250
(1) #2 GND
F
F XFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D1232 208/ 120V
(E)R12322 208/ 120V
A
(E)R12322 208/ 120V
B
(1) 4"C.
(4) #600
(1) #1/0 GND
F
F XFMR
208/120V 480V:
(E)T6
(E)D1422 480/ 277V
400AF
400AT
400AF
400AT
(1) 3/4"C.
(1) #1/0 GND
(E)D1222 208/ 120V
(E)R12222 208/ 120V
A
(E)R12222 208/ 120V
B
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(2) 4"C.
(4) #600
(1) #1/0 GND
XFMR
208/120V 480V:
(E)T7 (E)D1212
208/ 120V
2 SETS OF:
(1) 2 1/2"C.
(4) #250
(1) #1/0 GND
35K AIC
35K AIC
(1) 2"C.
(3) #1/0
(1) #6 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 3"C.
(3) #350
(1) #4 GND
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
35K AIC
35K AIC
(1) 4"C.
(4) #600
(1) #3 GND
(E)R12223 208/ 120V
A
(E)R12223 208/ 120V
B
(4) #250
(1) #4 GND
(1) 3"C.
(4) #250
(1) #4 GND
(1) 3/4"C.
(1) #1/0 GND
(E)D1412 480/ 277V
(1) 4"C.
(4) #600
(1) #3 GND
F
FXFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D1241 208/ 120V
(1) 4"C.
(4) #600
(1) #1/0 GND
F
FXFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D1231 208/ 120V
(1) 4"C.
(4) #600
(1) #1/0 GND
F
FXFMR
208/120V 480V:
(E)T6
(E)D1421 480/ 277V
400AF
400AT
400AF
400AT
(1) 3/4"C.
(1) #1/0 GND
(E)D1221 208/ 120V
(1) 4"C.
(4) #600
(1) #1/0 GND
XFMR
208/120V 480V:
(E)T6 (E)D1211
208/ 120V
LVN-2100
(2) 4"C.
(4) #600
(1) #1/0 GND
35K AIC
35K AIC
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
35K AIC
35K AIC
35K AIC
35K AIC
(1) 4"C.
(4) #600
(1) #3 GND
(1) 3/4"C.
(1) #1/0 GND
(E)D1411 480/ 277V
(1) 4"C.
(4) #600
(1) #3 GND
POINT OF SERVICE
NB112
BUSWAY CABLE CONNECTION FEED BOX BUSWAY CABLE CONNECTION FEED BOX
PENTHOUSE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
TO
(E)ATS-EIT1-1
TO
(E)ATS-EQ1-1
TO
(E)ATS-EC1-2
TO
(E)ATS-EL1-1
TO
(E)ATS-ELS1-1
TO
(E)ATS-EC1-1
FEEDER BUSWAY
800A, 3Ø, 4W, 100% G
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)R12411 208/ 120V
A
(E)R12411 208/ 120V
B
(E)R12413 208/ 120V
A
(E)R12413 208/ 120V
B
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R12311 208/ 120V
A
(E)R12311 208/ 120V
B
(E)R12313 208/ 120V
A
(E)R12313 208/ 120V
B
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R12323 208/ 120V
A
(E)R12323 208/ 120V
B
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R12212 208/ 120V
A
(E)R12212 208/ 120V
B
(E)R12213 208/ 120V
A
(E)R12213 208/ 120V
B
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
35K AIC
35K AIC
(E)R12121 208/ 120V
A
(E)R12121 208/ 120V
B
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)R12123 208/ 120V
A
(E)R12123 208/ 120V
B
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)R12112 208/ 120V
A
(E)R12112 208/ 120V
B
(E)R12113 208/ 120V
A
(E)R12113 208/ 120V
B
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
TO
(E)P1412
TO
(E)L1412
TO
(E)L1411
TO
(E)P1411
TO
(E)R12121A
TO
(E)L1421
TO
(E)L1431
TO
(E)L1441
TO
(E)D1451
TO
(E)L1422
TO
(E)L1432
TO
(E)L1442
TO
(E)R12111A
TO
(E)R12221A
TO
(E)R12211A
TO
(E)R12321A
TO
(E)R12312A
TO
(E)R12412A
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
01-EJ-001
BUILDING 1 - NORMAL ONE-LINE DIAGRAM
MER AJW
SCALE: NTS
1 BUILDING 1 - NORMAL ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
PERFORMING ANY OTHER WORK.
GENERAL NOTES
CT
400AF
150AT
35K AIC
LEVEL 4
FEEDER BUSWAY
800A, 3Ø, 4W, 100%G
EB114
LEVEL 3
LEVEL 2
EN
(E)ATS-EC1-1
480/277V
EN
(E)ATS-EIT1-1
480/277V
EN
(E)ATS-EL1-1
480/277V
EN
(E)ATS-ELS1-1
480/277V
(E)EITD1251
480/ 277V
TO
USS01
TO
EUSS02
TO
USS01
TO
EITD2451
TO
EUSS02
LEVEL 1
PENTHOUSE
BUSWAY CABLE CONNECTION FEED BOX
2 SETS OF:
(1) 3"C.
(4) #350
(1) #1 GND
3 SETS OF:
(4) #300 MI
(1) #1/0 MI GND
TO
USS01
CT
FEEDER BUSWAY
400A, 3Ø, 4W, 100%G
EB112BUSWAY CABLE CONNECTION FEED BOX
400AF
225AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)KT8
400AF
150AT
35K AIC
(E)EIT1241
208/ 120V
(E)EIT1243
208/ 120V
400AF
150AT
35K AIC
400AF
150AT
35K AIC
400AF
100AT
35K AIC
400AF
150AT
35K AIC
400AF
100AT
35K AIC
CT
400AF
150AT
35K AIC
FEEDER BUSWAY
800A, 3Ø, 4W, 100%G
EB113 BUSWAY CABLE CONNECTION FEED BOXCT
FEEDER BUSWAY
400A, 3Ø, 4W, 100%G
EB111BUSWAY CABLE CONNECTION FEED BOX
400AF
150AT
35K AIC
400AF
100AT
35K AIC
400AF
150AT
35K AIC
(E)EIT1242
208/ 120V
400AF
150AT
35K AIC
400AF
150AT
35K AIC
400AF
100AT
35K AIC
400AF
150AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T5
(E)ECD1222
208/ 120V
EN
(E)ATS-EQ1-1
480/277V
TO
USS01
TO
EUSS02
(E)EQD1451
480/ 277V
EN
(E)ATS-EC1-2
480/277V
TO
USS01
TO
EUSS02
(E)EIT1231
208/ 120V
A
(E)EIT1221
208/ 120V
(E)EIT1211
208/ 120V
(4) #1 MI
(1) #8 MI GND
(E)EIT1231
208/ 120V
B
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(E)EIT1234
208/ 120V
(E)EIT1232
208/ 120V
A
(E)EIT1232
208/ 120V
B
(4) #1 MI
(1) #8 MI GND
(E)EIT1222
208/ 120V
(E)EIT1212
208/ 120V
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(E)EIT1224
208/ 120V
(E)EIT1214
208/ 120V
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(4) #1 MI
(1) #8 MI GND
(1) 3 1/2"C.
(3) #600
(1) #3 GND
(1) 3/4"C.
(1) #3/0 GND
2 SETS OF:
(1) 5"C.
(3) #600
(2) #600 N
(1) #3/0 GND
2 SETS OF:
(1) 4"C.
(4) #600
(1) #3 GND
2 SETS OF:
(4) #350 MI
(1) #1 MI GND
2 SETS OF:
(1) 3 1/2"C.
(3) #600
(1) #1/0 GND
3 SETS OF:
(3) #400 MI
(1) #2/0 MI GND
3 SETS OF:
(1) 3 1/2"C.
(3) #600
(1) #3/0 GND
5 SETS OF:
(3) #400 MI
(1) #4/0 MI GND
3 SETS OF:
(1) 3 1/2"C.
(3) #600
(1) #3/0 GND
(1) 2"C.
(3) #4/0
(1) #4 GND
TO
ELSD24511
TO
USS01
(1) 4"C.
(4) #600
(1) #3 GND
2 SETS OF:
(4) #350 MI
(1) #1 MI GND
2 SETS OF:
(1) 3"C.
(4) #350
(1) #1 GND
3 SETS OF:
(4) #300 MI
(1) #1/0 MI GND
(4) #1 MI
(1) #6 MI GND
2 SETS OF:
(3) #3/0 MI
(1) #3 MI GND
2 SETS OF:
(3) #3/0 MI
(1) #3 MI GND
2 SETS OF:
(4) #350 MI
(1) #1 MI GND
2 SETS OF:
(4) #350 MI
(1) #1 MI GND
(E)EIT1233
208/ 120V
(4) #1/0 MI
(1) #8 MI GND
(4) #1/0 MI
(1) #6 MI GND
(E)EIT1223
208/ 120V
(4) #1 MI
(1) #8 MI GND
(1) 2"C.
(3) #1/0
(1) #6 GND
(1) 3"C.
(4) #250
(1) #2 GND
(1) 3/4"C.
(1) #2 GND
(E)EIT1213
208/ 120V
(4) #1 MI
(1) #8 MI GND
(E)ECR1212
208/ 120V
(4) #1 MI
(1) #8 MI GND
TO
(E)ECL1421
TO
(E)ECD1221
TO
(E)ELSD1451
TO
(E)ELD1451
TO
(E)EQP1451
TO
(E)EQR1251
TO
(E)ECD1241
TO
(E)ECL1441
TO
(E)ECL1422
TO
(E)EQP1422
TO
(E)EQP1421
TO
(E)EQP1431
TO
(E)EQP1441
TO
(E)ECL1431
TO
(E)ECD1231
TO
(E)ECD1232
TO
(E)ECL1432
TO
(E)ECD12421
TO
(E)ECL1442
TO
(E)EQP1432
TO
(E)EQP1442
EIT1213
208/ 120V
(4) #1 MI
(1) #8 MI GND
NEW WORK INSIDE BORDER
TO
(E)ECR12221A/B
TO
(E)ECR12222
01-EJ-002
BUILDING 1 - EMERGENCY ONE-LINE
DIAGRAM 01
MER AJW
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
SCALE: NTS
1 BUILDING 1 - EMERGENCY ONE-LINE DIAGRAM
EXISTING PANEL TO BE REMOVED. REMOVE CONDUIT AND
CONDUCTORS BACK TO SOURCE.
1. EXISTING PANELS TO BE REMOVED SHALL ONLY BE REMOVED
AFTER NEW PANEL HAS BEEN INSTALLED.
2. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
PERFORMING ANY OTHER WORK.
D1
DEMOLITION PLAN NOTES
GENERAL NOTES
PROVIDE NEW 100A PANEL AND FEED-THROUGH LUGS.1
PLAN NOTES
D1
22,000 AIC
XFMR
208/120V 480V:
(E)T6
(E)UNIT SECONDARY SUBSTATION
USS02-1
LVN-2005
(1) 4"C.
(4) #900 XHHW-AL
(1) #1 XHHW-AL GND
(E)D2451 480/ 277V
(E)D2251 208/ 120V
LVN-2019
(1) 4"C.
(4) #600
(1) #1/0 GND
LVN-2018
(1) 2 1/2"C.
(4) #250
(1) #1 GND
(E)R22511 208/ 120V
A
(E)R22511 208/ 120V
B
LVN-2022
(1) 2"C.
(4) #3/0
(1) #4 XHHW-AL GND
(1) 3/4"C.
(1) #1/0 GND
LVN-2020
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2001
(3) 4"C.
(4) #900 XHHW-AL
(1) #250 XHHW-AL GND
CT
LVN-2006
(3) 4"C.
(4) #900 XHHW-AL
(1) #250 XHHW-AL GND
CT NB211FEEDER BUSWAY
1200A, 3Ø, 4W, 100% G
F
F XFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2241 208/ 120V
(E)R22411 208/ 120V
A
(E)R22411 208/ 120V
B
LVN-2032
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2030
(1) 2"C.
(4) #1/0
(1) #6 GNDLVN-2029
(1) 4"C.
(4) #600
(1) #1/0 GND
F
F XFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2231 208/ 120V
(E)R22312 208/ 120V
A
(E)R22312 208/ 120V
B
LVN-2041
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2038
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2036
(1) 4"C.
(4) #600
(1) #1/0 GND
F
F XFMR
208/120V 480V:
(E)T7
(E)D2421 480/ 277V
400AF
400AT
400AF
400AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2221 208/ 120V
(E)R22211 208/ 120V
A
(E)R22211 208/ 120V
B
(E)R22212 208/ 120V
A
(E)R22212 208/ 120V
B
LVN-2051
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2052
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2047
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2048
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2046
(2) 2 1/2"C.
(4) #250
(1) #1/0 GND
XFMR
208/120V 480V:
(E)T7 (E)D2211
208/ 120V
(E)R22112 208/ 120V
A
LVN-2060
(1) 1 1/2"C.
(4) #1
(1) #8 GND
LVN-2058
(2) 2 1/2"C.
(4) #250
(1) #1/0 GND
65K AIC
65K AIC
LVN-2028
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2035
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2045
(1) 3"C.
(3) #350
(1) #4 GND
LVN-2057
(1) 3"C.
(3) #350
(1) #4 GND
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
65K AIC
65K AIC
65K AIC
65K AIC
LVN-2043
(1) 4"C.
(4) #900 XHHW-AL
(1) #1 XHHW-AL GND
(E)R22213 208/ 120V
A
(E)R22213 208/ 120V
B
LVN-2053
(1) 2 1/2"C.
(4) #300
(1) #2 AL GND
LVN-2049
(1) 2 1/2"C.
(4) #300 XHHW-AL
(1) #2 XHHW-AL GND
(E)R22214 208/ 120V
LVN-2050
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #1/0 GND
(E)D2411 480/ 277V
LVN-2054
(1) 4"C.
(4) #900
(1) #1 AL GND
F
FXFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D22421 208/ 120V
(E)R22421 208/ 120V
LVN-2068
(1) 1 1/2"C.
(4) #1
(1) #8 GND LVN-2067
(1) 4"C.
(4) #600
(1) #1/0 GND
F
FXFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2232 208/ 120V
(E)R22322 208/ 120V
LVN-2077
(1) 1 1/2"C.
(4) #1
(1) #8 GND
LVN-2075
(1) 4"C.
(4) #600
(1) #1/0 GND
F
FXFMR
208/120V 480V:
(E)T7
(E)D2422 480/ 277V
400AF
400AT
400AF
400AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2222 208/ 120V
(E)R22221 208/ 120V
A
(E)R22221 208/ 120V
B
(E)R22222 208/ 120V
A
LVN-2088
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2084
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2085
(1) 1 1/2"C.
(4) #1
(1) #8 GND
LVN-2083
(1) 4"C.
(4) #600
(1) #1/0 GND
XFMR
208/120V 480V:
(E)T6 (E)D2212
208/ 120V
(E)R22121 208/ 120V
A
(E)R22121 208/ 120V
B
LVN-2106
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2101
(1) 2"C.
(4) #1/0
(1) #6 CU GND LVN-2100
(2) 4"C.
(4) #600
(1) #1/0 GND
65K AIC
65K AIC
LVN-2066
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2074
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2082
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2099
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
65K AIC
65K AIC
65K AIC
65K AIC
LVN-2080
(1) 4"C.
(4) #900 XHHW-AL
(1) #1 XHHW-AL GND
(E)R22223 208/ 120V
A
(E)R22223 208/ 120V
B
LVN-2089
(1) 2 1/2"C.
(4) #300
(1) #2 AL GND
LVN-2086
(1) 2 1/2"C.
(4) #300 XHHW-AL
(1) #2 XHHW-AL GND
(1) 3/4"C.
(1) #1/0 GND
(E)D2412 480/ 277V
LVN-2096
(1) 4"C.
(4) #900 XHHW-AL
(1) #1 XHHW-AL GND
POINT OF SERVICE
NB221
BUSWAY CABLE CONNECTION FEED BOX BUSWAY CABLE CONNECTION FEED BOX
LEVEL 5
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(E)R22224 208/ 120V
LVN-2087
(1) 1 1/2"C.
(4) #1
(1) #8 GND
TO
(E)ATS-EQ2-4
TO
(E)ATS-EL2-2
TO
(E)ATS-EC2-3
TO
(E)ATS-EIT2-2
TO
(E)ATS-EC2-4
TO
(E)ATS-EQ2-6
FEEDER BUSWAY
1200A, 3Ø, 4W, 100% G
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
TO
(E)XD2421
TO
(E)D2452
TO
(E)D2461
TO
(E)L2451
TO
(E)L2441
TO
(E)L2431
TO
(E)L2421
TO
(E)L2411
TO
(E)P2411
TO
(E)L2432
TO
(E)L2442
TO
(E)L2422
TO
(E)P2412
TO
(E)L2412
TO
(E)R22123A
TO
(E)R22113A
TO
(E)R22114
TO
(E)R22313ATO
(E)R22312A
TO
(E)R22321A
TO
(E)R22323
TO
(E)LA22421
TO
(E)LA22422
TO
(E)R22422
TO
(E)R22423
TO
(E)R22412A
TO
(E)R22512A
TO
(E)R22111A
TO
(E)R22122
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/
2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
02-EJ-001
BUILDING 2 - NORMAL ONE-LINE DIAGRAM
MER AJW
SCALE: NTS
1 BUILDING 2 - NORMAL ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
USS02-2
TO
(E)ATS-EL2-1
TO
(E)ATS-EQ2-2
TO
(E)ATS-EQ2-1
TO
(E)ATS-EQ2-5
TO
(E)ATS-EC2-2
TO
(E)ATS-ELS2-1
LVN-2108
(3) 4"C.
(4) #900 XHHW-AL
(1) #250 XHHW-AL GND
CT
LVN-2116
(3) 4"C.
(4) #900 XHHW-AL
(1) #250 XHHW-AL GND
CT NB231
FEEDER BUSWAY
1200A, 3Ø, 4W, 100%G
F
F XFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D22431 208/ 120V
(E)R22431 208/ 120V
A
(E)R22431 208/ 120V
B
LVN-2154
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2149
(1) 2"C.
(4) #1/0
(1) #6 GNDLVN-2148
(1) 4"C.
(4) #600
(1) #1/0 GND
F
F XFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2233 208/ 120V
(E)R22331 208/ 120V
A
(E)R22331 208/ 120V
B
LVN-2162
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2158
(1) 4"C.
(4) #600
(1) #1/0 GND
F
F XFMR
208/120V 480V:
(E)T6
(E)D2423 480/ 277V
400AF
400AT
400AF
400AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2223 208/ 120V
(E)R22232 208/ 120V
A
(E)R22232 208/ 120V
B
LVN-2175
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2171
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2169
(1) 4"C.
(4) #6
(1) #1/0 GND
XFMR
208/120V 480V:
(E)T6 (E)D2213
208/ 120V
(E)R22131 208/ 120V
A
(E)R22131 208/ 120V
B
LVN-2196
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2191
(2) 4"C.
(4) #600
(1) #1/0 GND
65K AIC
65K AIC
LVN-2147
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2157
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2168
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2190
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
65K AIC
65K AIC
65K AIC
65K AIC
LVN-2165
(1) 4"C.
(4) #250
(1) #1 AL GND
(1) 3/4"C.
(1) #1/0 GND
(E)D2413 480/ 277V
F
FXFMR
208/120V 480V:
(E)T6
400AF
250AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2244 208/ 120V
(E)R22442 208/ 120V
LVN-2201
(1) 4"C.
(4) #600
(1) #1/0 GND
F
FXFMR
208/120V 480V:
(E)T7
400AF
300AT
400AF
100AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2234 208/ 120V
(E)R22342 208/ 120V
A
LVN-2209
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2207
(2) 2 1/2"C.
(4) #250
(1) #1/0 GND
F
FXFMR
208/120V 480V:
(E)T7
(E)D2424 480/ 277V
400AF
400AT
400AF
400AT
(1) 3/4"C.
(1) #1/0 GND
(E)D2224 208/ 120V
(E)R22242 208/ 120V
LVN-2221
(1) 1 1/2"C.
(4) #1
(1) #8 GND
LVN-2219
(2) 2 1/2"C.
(4) #250
(1) #1/0 GND
XFMR
208/120V 480V:
(E)T7 (E)D2214
208/ 120V
(E)R22141 208/ 120V
A
(E)R22141 208/ 120V
B
LVN-2240
(1) 2 1/2"C.
(4) #300
(1) #2 AL GND
LVN-2237
(1) 2 1/2"C.
(4) #300
(1) #2 AL GND LVN-2236
(2) 2 1/2"C.
(4) #250
(1) #1/0 GND
65K AIC
65K AIC
LVN-2200
(1) 2 1/2"C.
(3) #250
(1) #4 GND
LVN-2206
(1) 3"C.
(3) #350
(1) #4 GND
LVN-2218
(1) 3"C.
(3) #350
(1) #4 GND
LVN-2235
(1) 3"C.
(3) #350
(1) #4 GND
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
65K AIC
65K AIC
65K AIC
65K AIC
LVN-2215
(1) 4"C.
(4) #900
(1) #1 AL GND
(1) 3/4"C.
(1) #1/0 GND
(E)D2414 480/ 277V
LVN-2232
(1) 4"C.
(4) #900
(1) #1 AL GND
POINT OF SERVICE
FEEDER BUSWAY
1200A, 3Ø, 4W, 100%G
LVN-2203
(1) 1 1/2"C.
(4) #1
(1) #8 GND
NB241
BUSWAY CABLE CONNECTION FEED BOX BUSWAY CABLE
CONNECTION FEED
BOX
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
TO
(E)ATS-EQ2-3
TO
(E)ATS-EIT2-1
TO
(E)ATS-EC2-1
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(E)R22342 208/ 120V
B
LVN-2213
(1) 2"C.
(4) #3/0
(1) #4 AL GND
LVN-2159
(1) 2"C.
(4) #1/0
(1) #6 GND
LVN-2187
(1) 4"C.
(4) #250
(1) #1 AL GND
LVN-2193
(1) 2"C.
(4) #1/0
(1) #6 GND
TO
(E)KD2444
TO
(E)D24541
TO
(E)P2414
TO
(E)L2414TO
(E)R22142A
TO
(E)R22143A
TO
(E)KD2414
TO
(E)XD2423
TO
(E)P2424
TO
(E)L2424
TO
(E)L2434
TO
(E)L2444
TO
(E)L2413
TO
(E)P2413
TO
(E)L2423
TO
(E)P2423
TO
(E)L2433
TO
(E)L2443
TO
(E)P2213
TO
(E)R22132A
TO
(E)R22133A
TO
(E)R22234
TO
(E)R22233A
TO
(E)R22231A
TO
(E)R22244
TO
(E)R22245
TO
(E)R22243 TO
(E)R22241A
TO
(E)R22332A
TO
(E)R22333A
TO
(E)R22343
TO
(E)R22344 TO
(E)R22341
TO
(E)R22441A
TO
(E)LA22432
TO
(E)LA22431
TO
(E)R22432A
TO
(E)LA22433
TO
(E)D24542
02-EJ-002
BUILDING 2 - NORMAL ONE-LINE DIAGRAM
MER AJW
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/
2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
SCALE: NTS
1 BUILDING 2 - NORMAL ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
100AT
400AF
80AT
400AF
225AT
35K AIC 65K AIC
LEVEL 4
FEEDER BUSWAY
800A, 3Ø, 4W, 100%G
EB212
65K AIC
LEVEL 3
400AF
100AT
65K AIC
LEVEL 2
EN
(E)ATS-EL2-2
480/277V
EN
(E)ATS-EQ2-4
480/277V
EN (E)ATS-EC2-3
480/277V
EN (E)ATS-EC2-4
480/277V
(E)EC3D2453
480/ 277V
TO
USS02-1
TO
EUSS02
TO
USS02-1
TO
EUSS02
TO
EUSS02
TO
USS02-1
TO
EUSS02
LVE-2057
(2) #350
(1) #1/0 MI GND
TO
LVE-2014
TO
LVE-2012
TO
LVE-2010
TO
LVE-2003
(E)EIT2242
208/ 120V
(E)EIT2232
208/ 120V
(E)EIT2222
208/ 120V
(E)EIT2212
208/ 120V
LVE-2068
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2069
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2070
(1) 2"C.
(4) #1/0
(1) #6 GND
LEVEL 1
400AF
250AT
400AF
250AT
35K AIC
35K AIC
EN (E)ATS-EQ2-6
480/277V
EN (E)ATS-EIT2-2
480/277V
(E)EC4D2454
480/ 277V
XFMR
208/120V 480V:
(E)KT8
(E)EITD2252
208/ 120V
TO
USS02-1
TO
EUSS02
TO
USS02-1
TO
EITD2451
TO
LVE-2003
SEE SHEET 02-EJ-004
FOR CONTINUATION
(E)EIT2241
208/ 120V
(E)EIT2231
208/ 120V
(E)EIT2221
208/ 120V
(E)EIT2211
208/ 120V
(E)P BOX
LVE-2063
(1) 2"C.
(4) #1/0
(1) #6 MI GND
LVE-2064
(1) 2"C.
(4) #1/0
(1) #6 MI GND
LVE-2065
(1) 2"C.
(4) #1/0
(1) #6 MI GND
LVE-2066
(1) 2"C.
(4) #1/0
(1) #6 MI GND
LEVEL 5
LEVEL 6
BUSWAY CABLE CONNECTION FEED BOX
LVE-2067
(1) 2"C.
(4) #1/0
(1) #6 GND
SEE SHEET 02-EJ-004
FOR CONTINUATION
LVE-2034
(2) 5"C.
(5) #600
(2) #3/0 GND
LVE-2033
(1) 3 1/2"C.
(3) #600
(1) #3 GND
LVE-2019
(2) 4"C.
(4) #600
(1) #1/0 GND
LVE-2020
(2) 4"C.
(4) #600
(1) #1/0 GND
LVN-2009
(2) 3 1/2"C.
(3) #900
(1) #3/0 AL GND
LVE-2014
(2) 3 1/2"C.
(3) #600
(1) #1/0 GND
LVN-2012
(3) 3 1/2"C.
(3) #900
(1) #250 GND
LVE-2012
(3) 3 1/2"C.
(3) #600
(1) #3/0 GND
LVN-2007
(2) 4"C.
(4) #900
(1) #3/0 AL GND
LVE-2010
(1) 4"C.
(4) #600
(1) #1/0 GND
LVN-2004
(2) 4"C.
(4) #900
(1) #3/0 AL GND
LVE-2003
(2) 4"C.
(4) #600
(1) #1/0 GND
LVN-2003
(4) 3 1/2"C.
(3) #900
(1) #250 GND
LVE-2013
(4) 3 1/2"C.
(3) #900
(1) #250 GND
LVN-2010
(1) 4"C.
(4) #900
(1) #1 AL GND
LVE-2030
(1) 4"C.
(4) #600
(1) #3 GND
TO
USS02-1
TO
(E)EC3L2442 TO
(E)EC3R2242
TO
(E)EC3L2432 TO
(E)EC3D22321
TO
(E)EC3L2422 TO
(E)EC3D2222
TO
(E)EQ4D2454
TO
(E)EQ6D2456
TO
(E)EC3D24321
TO
(E)EC3D24311
TO
(E)EC4D24322
TO
(E)EC4D2451
TO
(E)EC4D24312
TO
(E)ELD2452
MA
TC
H
LIN
E
- 0
2-
EJ
-0
MA
TC
H
LIN
E
- 0
2-
EJ
-0
MA
TC
H
LIN
E
- 0
2-
EJ
-0
02-EJ-003
BUILDING 2 - EMERGENCY ONE-LINE
DIAGRAM 02
MER AJW
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/
2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
SCALE: NTS
1 BUILDING 2 - EMERGENCY ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
CT EB211
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
400AF
125AT
400AF
100AT
35K AIC
35K AIC
SEE SHEET 02-EJ-003
FOR CONTINUATION
LEVEL 5
LEVEL 6
FEEDER BUSWAY
800A, 3Ø, 4W, 100%G
BUSWAY CABLE CONNECTION FEED BOX
LVE-2054
(2) 3"C.
(4) #350
(1) #1 GND
SEE SHEET 02-EJ-003
FOR CONTINUATION
400AF
100AT
35K AIC
(E)EIT2251
480/ 277V
LEVEL 7
400AF
150AT
65K AIC
(E)EC4R22311
208/ 120V
A
400AF
80AT
65K AIC
XFMR
208/120V 480V:
(E)T4
LVE-2078
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2077
(1) 1 1/4"C.
(3) #3
(1) #8 GND (E)EC4R22311
208/ 120V
B
LVE-2289
(1) 2 1/2"C.
(4) #1/0
(1) #4 GND
400AF
250AT
65K AIC
LVE-2062
(4) #1
(1) #8 MI GND
TO
(E)EC4L2441
TO
(E)EC4R2241A
TO
(E)EC4L2431
TO
(E)EC4L2421
TO
(E)EC4D2221
MA
TC
H
LIN
E
- 0
2-
EJ
-0
MA
TC
H
LIN
E
- 0
2-
EJ
-0
MA
TC
H
LIN
E
- 0
2-
EJ
-0
02-EJ-004
BUILDING 2 - EMERGENCY ONE-LINE
DIAGRAM 02
MER AJW
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/
2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
SCALE: NTS
1 BUILDING 2 - EMERGENCY ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
100AT
400AF
80AT
400AF
125AT
65K AIC 65K AIC
LEVEL 4
FEEDER BUSWAY
800A, 3Ø, 4W, 100%G
EB214
65K AIC
LEVEL 3
400AF
100AT
65K AIC
LEVEL 2
EN
(E)ATS-EIT2-1
480/277V
EN (E)ATS-EQ2-5
480/277V
(E)EITD2451
480/ 277V
TO
USS02-2
TO
EUSS02
(E)EIT2244
208/ 120V
(E)EIT2234
208/ 120V
(E)EIT2224
208/ 120V
(E)EIT2214
208/ 120V
LVE-2182
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2183
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2184
(1) 2"C.
(4) #1/0
(1) #6 GND
LEVEL 1
400AF
250AT
400AF
250AT
65K AIC
65K AIC
XFMR
208/120V 480V:
(E)KT8
(E)EITD2251
208/ 120V
(E)EIT2243
208/ 120V
(E)EIT2233
208/ 120V
(E)EIT2223
208/ 120V
(E)EIT2213
208/ 120V
LVE-2177
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2178
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2179
(1) 2"C.
(4) #1/0
(1) #6 GND
LVE-2180
(1) 2"C.
(4) #1/0
(1) #6 GND
LEVEL 5
LEVEL 6
BUSWAY CABLE CONNECTION FEED BOX
LVE-2181
(1) 2"C.
(4) #1/0
(1) #6 GND
TO
(E)ATS EQUIPMENT
LVE-2032
(2) 5"C.
(5) #600
(1) #3/0 GND
LVE-2007
(4) 4"C.
(4) #600
(1) #4/0 GND
ENTO
USS02-2
POINT OF SERVICE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(E)EC1D2451
480/ 277V
ENTO
USS02-2
TO
EUSS02
EN (E)ATS-EQ2-2
480/277V
TO
EUSS02
LVN-2118
(3) 3 1/2"C.
(3) #900
(1) #250 AL GND
LVE-2011
(3) 3 1/2"C.
(3) #600
(1) #3/0 GND
TO
USS02-2
(E)UNIT SUBSTATION
EUSS02
LVE-1003
(4) 3 1/2"C.
(3) #600
(1) #4/0 GND
LVE-1004
(2) 4"C.
(4) #600
(1) #1/0 GND
LVE-1001
(2) 4"C.
(4) #600
(1) #1/0 GND
TO ATS-EIT1-1
LVE-2002
(2) 4"C.
(4) #600
(1) #1/0 GND
LVE-2001
(2) 4"C.
(4) #600
(1) #1/0 GND
LVE-2017
(2) 4"C.
(4) #600
(1) #1/0 GND
TO
USS02-2
LVN-2114
(4) 4"C.
(4) #900
(1) #350 AL GND
LVE-2160
(1) 2"C.
(3) #4/0
(1) #4 GND
LVE-2008
(2) 4"C.
(4) #600
(1) #1/0 GND
TO ATS-EIT2-2
LVE-2030
(1) 4"C.
(4) #600
(1) #3 GND
LVE-1005
(2) 3 1/2"C.
(4) #350
(1) #1 GND
LVE-2031
(1) 3 1/2"C.
(3) #600
(1) #3 GND
LVE-2029
(1) 4"C.
(4) #600
(1) #3 GND
(E)ATS-EC2-1
480/277V
(E)ATS-ELS2-1
480/277V
LVN-2122
(2) 4"C.
(4) #900
(1) #3/0 AL GND
LVN-2119
(1) 4"C.
(4) #900
(1) #1 AL GND
LVE-2165
(2) 3 1/2"C.
(4) #350
(1) #1 GND
LVN-2112
(1) 4"C.
(4) #900
(1) #1 AL GND
LVE-2161
(3) #4/0
(1) #4 MI GND
LVE-2012
LVE-2003
LVE-2013
LVE-2014
TO
(E)EC3D24311
TO
(E)ELSD24512
TO
(E)EC1L2444
TO
(E)EC1L2434
TO
(E)EC1L2424
TO
(E)EC1R2244
TO
(E)EQ2D2452
TO
(E)ELSD24511 TO
(E)EQ5R2244
TO
(E)EC1D2234
TO
(E)EC1D2224
LVN-2119
(1) 4"C.
(4) #900
(1) #1 AL GND
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/
2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
02-EJ-005
BUILDING 2 - EMERGENCY ONE-LINE
DIAGRAM 02
MER AJW
SCALE: NTS
1 BUILDING 2 - EMERGENCY ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
250AT
35K AIC
FEEDER BUSWAY
1200A, 3Ø, 4W, 100%G
NB321
LEVEL 1
BUSWAY CABLE CONNECTION FEED BOX
CT
FEEDER BUSWAY
1200A, 3Ø, 3W, 100%G
NB311
BUSWAY CABLE
CONNECTION FEED BOX
(1) 2 1/2"C.
(3) #250
(1) #4 GND
400AF
225AT
35K AIC
400AF
100AT
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T6 (E)D3272
208/ 120V
(1) 4"C.
(4) #600
(1) #1/0 GND
(E)R32721 208/ 120V
A
(E)R32721 208/ 120V
B
400AF
225AT
35K AIC
400AF
250AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T6 (E)D3262
208/ 120V
(E)R32621 208/ 120V
A
(E)R32621 208/ 120V
B
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T6 (E)D3252
208/ 120V
(E)R32521 208/ 120V
A
(E)R32521 208/ 120V
B
CT
400AF
250AT
35K AIC
FEEDER BUSWAY
1200A, 3Ø, 4W, 100%G
NB341
BUSWAY CABLE CONNECTION FEED BOX
CT
FEEDER BUSWAY
1200A, 3Ø, 3W, 100%G
NB331
BUSWAY CABLE CONNECTION FEED BOX
400AF
225AT
35K AIC
400AF
100AT
35K AIC
400AF
225AT
35K AIC
XFMR
208/120V 480V:
(E)T6
400AF
225AT
35K AIC
400AF
250AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T6
400AF
250AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T6
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 3/4"C.
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
3 SETS OF:
(1) 3 1/2"C.
(3) #600
(1) #3/0 GND
(1) 3/4"C.
(1) #2 GND
(1) 3/4"C.
(1) #2 GND
(E)UNIT SECONDARY SUBSTATION
USS03-1
TO
(E)D3482
TO
(E)ATS-EQ3-1
TO
(E)ATS-EL3-1
TO
(E)ATS-ELS3-1
TO
(E)ATS-EC3-1
TO
(E)D3481
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
LEVEL 6
LEVEL 7
LEVEL 8
3 SETS OF:
(1) 4"C.
(4) #600
(1) #3/0 GND
POINT OF SERVICE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
3 SETS OF:
(1) 3 1/2"C.
(3) #600
(1) #3/0 GND
3 SETS OF:
(1) 4"C.
(4) #600
(1) #3/0 GND
35K AIC
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T6 (E)D3242
208/ 120V
(E)R32421 208/ 120V
A
(E)R32421 208/ 120V
B
400AF
225AT
35K AIC
400AF
300AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T7
(1) 3/4"C.
(1) #2 GND
35K AIC
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T6 (E)D3232
208/ 120V
(E)R32321 208/ 120V
A
(E)R32321 208/ 120V
B
400AF
225AT
35K AIC
400AF
250AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T6
(1) 3/4"C.
(1) #2 GND
400AF
400AT
35K AIC
XFMR
208/120V 480V:
(E)T6 (E)D3222
208/ 120V
(E)R32221 208/ 120V
A
(E)R32221 208/ 120V
B
400AF
225AT
35K AIC
400AF
300AT
35K AIC
400AF
300AT
35K AIC
XFMR
208/120V 480V:
(E)T6
(1) 3/4"C.
(1) #2 GND
400AF
300AT
35K AIC
400AF
300AT
35K AIC
400AF
225AT
35K AIC
400AF
250AT
35K AIC
TO
(E)P3472
TO
(E)P3462
TO
(E)P3452
TO
(E)P3442
TO
(E)P3432
TO
(E)D34222
TO
(E)P3412
TO
(E)L3472
TO
(E)L3462
TO
(E)L3452
TO
(E)L3442
TO
(E)L3432
XFMR
208/120V 480V:
(E)T6 (E)D3212
208/ 120V
(E)R32121 208/ 120V
A
(E)R32121 208/ 120V
B
(E)R32722 208/ 120V
A
(E)R32722 208/ 120V
B
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32622 208/ 120V
A
(E)R32622 208/ 120V
B
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 3"C.
(4) #350
(1) #4 GND
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 3/4"C.
(1) #1/0 GND
(1) 3/4"C.
(1) #1/0 GND
(1) 3/4"C.
(1) #1/0 GND
(1) 3/4"C.
(1) #1/0 GND
(1) 3/4"C.
(1) #1/0 GND
(1) 3/4"C.
(1) #1/0 GND
(E)R32522 208/ 120V
A
(E)R32522 208/ 120V
B
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32523 208/ 120V
(1) 1 1/2"C.
(4) #1
(1) #8 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32422 208/ 120V
A
(E)R32422 208/ 120V
B
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32322 208/ 120V
A
(E)R32322 208/ 120V
B
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32222 208/ 120V
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 1 1/2"C.
(4) #1
(1) #8 GND
(E)D3412 480/ 277V
(E)R32122 208/ 120V
A
(E)R32122 208/ 120V
B
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)R32123 208/ 120V
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)D3422 480/ 277V
(1) 2 1/2"C.
(3) #250
(1) #4 GND
TO
(E)L3422
TO
(E)L3412
(1) 3"C.
(3) #350
(1) #4 GND
400AF
225AT
400AF
250AT
400AF
100AT
400AF
225AT
400AF
250AT
400AF
100AT
400AF
225AT
400AF
250AT
400AF
100AT
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)D3273 208/ 120V
(E)R32731 208/ 120V
A
(E)R32731 208/ 120V
B
(1) 3/4"C.
(1) #1/0 GND
(E)R32732 208/ 120V
A
(E)R32732 208/ 120V
B
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32733 208/ 120V
(1) 1 1/2"C.
(4) #1
(1) #8 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)D3263 208/ 120V
(1) 4"C.
(4) #600
(1) #1/0 GND
(E)R32631 208/ 120V
A
(E)R32631 208/ 120V
B
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32632 208/ 120V
A
(E)R32632 208/ 120V
B
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)D3253 208/ 120V
(1) 4"C.
(4) #600
(1) #1/0 GND
(E)R32531 208/ 120V
A
(E)R32531 208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)R32532 208/ 120V
A
(E)R32532 208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
XFMR
208/120V 480V:
(E)T6
(1) 3/4"C.
(1) #1/0 GND
(E)D3412 480/ 277V
(1) 4"C.
(4) #600
(1) #1/0 GND
TO
(E)L3412
(1) 3"C.
(3) #350
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
(1) 2 1/2"C.
(3) #250
(1) #4 GND
TO
(E)L3473
TO
(E)L3463
TO
(E)L3453
TO
(E)L3443
TO
(E)L3433
(1) 2 1/2"C.
(3) #250
(1) #4 GND
TO
(E)P3473
TO
(E)P3463
TO
(E)P3453
TO
(E)P3443
TO
(E)P3433
TO
(E)P3423
TO
(E)P3413
(E)D3243 208/ 120V
(E)R32431 208/ 120V
A
(E)R32431 208/ 120V
B
(E)R32433 208/ 120V
A
(E)R32433 208/ 120V
B
2 SETS OF:
(1) 2 1/2"C.
(4) #250
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32434 208/ 120V
(1) 1 1/2"C.
(4) #1
(1) #8 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32432 208/ 120V
A
(E)R32432 208/ 120V
B
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 3"C.
(3) #350
(1) #4 GND
(E)D3233 208/ 120V
(E)R32331 208/ 120V
A
(E)R32331 208/ 120V
B
(E)R32332 208/ 120V
A
(E)R32332 208/ 120V
B
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32333 208/ 120V
(1) 1 1/2"C.
(4) #1
(1) #8 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)D3223 208/ 120V
(E)R32231 208/ 120V
A
(E)R32231 208/ 120V
B
(E)R32232 208/ 120V
A
(E)R32232 208/ 120V
B
(1) 4"C.
(4) #600
(1) #1/0 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)R32233 208/ 120V
(1) 1 1/2"C.
(4) #1
(1) #8 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(E)D3212 208/ 120V
(E)R32131 208/ 120V
A
(E)R32131 208/ 120V
B
(E)R32132 208/ 120V
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 1 1/2"C.
(4) #1
(1) #8 GND
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
AREA H AREA J
(E)D3421 480/ 277V
(1) 4"C.
(4) #600
(1) #3 GND
(E)L3411 480/ 277V
XFMR
208/120V 480V:
(E)T5 (E)D3211
208/ 120V
(E)R32112 208/ 120V
(1) 3"C.
(4) #250
(1) #2 GND
(1) 2"C.
(3) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #2 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 1 1/2"C.
(4) #1
(1) #8 GND
XFMR
208/120V 480V:
(E)T4(E)R32211 208/ 120V
B
(E)R32211 208/ 120V
A
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)L3431 480/ 277V
(E)L3441 480/ 277V
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
(1) 2 1/2"C.
(4) #4/0
(1) #4 GND
TO
(E)R32111A/B
(1) 1 1/4"C.
(3) #3
(1) #8 GND
TO
(E)L3421
XFMR
208/120V 480V:
(E)T4(E)R32311 208/ 120V
B
(E)R32311 208/ 120V
A
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
XFMR
208/120V 480V:
(E)T4(E)R32411 208/ 120V
B
(E)R32411 208/ 120V
A
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
XFMR
30KVA
208/120V 480V:
T3 R32212
208/ 120V
100A
[30H]
[30L]
03-EJ-001
BUILDING 3 - NORMAL ONE-LINE DIAGRAM
MER AJW
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
SCALE: NTS
1 BUILDING 3 - NORMAL ONE-LINE DIAGRAM
1. EXISTING PANELS TO BE REMOVED SHALL ONLY BE REMOVED
AFTER NEW PANEL HAS BEEN INSTALLED AND TESTED.
2. REFER TO 00-EG-001 FOR FEEDER SIZING SCHEDULE.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
PERFORMING ANY OTHER WORK.
PLAN NOTES
GENERAL NOTES
PROVIDE NEW 100A PANEL WITH 100A MAIN BREAKER.
PROVIDE NEW 30KVA TRANSFORMER.
1 2 NEW WORK IN BOLD
80AT
35K AIC
FEEDER BUSWAY
600A, 3Ø, 4W, 100%G
EB311
LEVEL 1
BUSWAY CABLE CONNECTION FEED BOX
(1) 1 1/4"C.
(3) #3
(1) #8 GND
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T4
(E)ECR32721
208/ 120V
A
(E)ECR32721
208/ 120V
B
400AF
80AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T4
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
CT
FEEDER BUSWAY
600A, 3Ø, 4W, 100%G
EB312
BUSWAY CABLE CONNECTION FEED BOX
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)UNIT SECONDARY SUBSTATION
EUSS03
TO
(E)ATS-EQ3-1
TO
(E)ATS-EL3-1
TO
(E)ATS-ELS3-1
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
LEVEL 6
LEVEL 7
LEVEL 8
2 SETS OF:
(4) #350
(1) #1 GND
POINT OF SERVICE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(4) 4" RGS PRIMARY
CONDUIT RISERS
(2) ACTIVE
(2) SPARE
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
(E)24"W X 48"H 12G
GALVANIZED STEEL
PULLBOX
W/ 3HR RATED
ACCESS PANEL
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
400AF
150AT
35K AIC
400AF
100AT
35K AIC
TO
(E)ECL3472
TO
(E)ECL3462
TO
(E)ECL3452
TO
(E)ECL3442
TO
(E)ECL3432
400AF
80AT
400AF
100AT
400AF
80AT
400AF
100AT
400AF
80AT
400AF
100AT
(1) 3/4"C.
(1) #6 MI GND
XFMR
208/120V 480V:
(E)T5
(1) 2"C.
(3) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #2 MI GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)ECR32621
208/ 120V
A
(E)ECR32621
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)ECR32521
208/ 120V
A
(E)ECR32521
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)ECR32421
208/ 120V
A
(E)ECR32421
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)ECR32321
208/ 120V
A
(E)ECR32321
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)ECD3222
208/ 120V
(E)ECR32221
208/ 120V
A
(E)ECR32221
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0 MI
(1) #6 MI GND
(4) #1/0 MI
(1) #6 MI GND
(1) 3"C.
(4) #250
(1) #2 GND
(1) 3/4"C.
(1) #6 MI GND
(1) 3/4"C.
(1) #6 MI GND
(1) 3/4"C.
(1) #6 MI GND
(1) 3/4"C.
(1) #6 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(4) #1/0 MI
(1) #6 MI GND
(E)ECR32121
208/ 120V
A
(E)ECR32121
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0 MI
(1) #6 MI GND
2 SETS OF:
(4) #350
(1) #1 GND
400AF
80AT
35K AIC
(1) 1 1/4"C.
(3) #3
(1) #8 GND
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T4
(E)ECR32731
208/ 120V
A
(E)ECR32731
208/ 120V
B
400AF
80AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T4
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
400AF
150AT
35K AIC
400AF
100AT
35K AIC
TO
(E)ECL3473
TO
(E)ECL3463
TO
(E)ECL3453
TO
(E)ECL3443
TO
(E)ECL3433
400AF
80AT
400AF
100AT
400AF
80AT
400AF
100AT
400AF
80AT
400AF
100AT
(1) 3/4"C.
(1) #6 MI GND
XFMR
208/120V 480V:
(E)T5
(1) 2"C.
(3) #1/0
(1) #6 GND
(1) 3/4"C.
(1) #2 MI GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)ECR32631
208/ 120V
A
(E)ECR32631
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)ECR32531
208/ 120V
A
(E)ECR32531
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)ECR32431
208/ 120V
A
(E)ECR32431
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(E)ECR32331
208/ 120V
A
(E)ECR32331
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)ECD3223
208/ 120V
(E)ECR32231
208/ 120V
A
(E)ECR32231
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0 MI
(1) #6 MI GND
(4) #1/0 MI
(1) #6 MI GND
(1) 3"C.
(4) #250
(1) #2 GND
(1) 3/4"C.
(1) #6 MI GND
(1) 3/4"C.
(1) #6 MI GND
(1) 3/4"C.
(1) #6 MI GND
(1) 3/4"C.
(1) #6 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 1 1/4"C.
(3) #3
(1) #8 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(1) 2"C.
(4) #1/0
(1) #6 GND
(4) #1/0 MI
(1) #6 MI GND
(E)ECR32131
208/ 120V
A
(E)ECR32131
208/ 120V
B
(1) 2 1/2"C.
(4) #1/0 MI
(1) #6 MI GND
TO
(E)ECL3422
TO
(E)ECL3423
AREA H AREA J
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
EN
(E)ATS-EC3-1
480/277V
TO
USS03-1
3 SETS OF:
(1) 4"C.
(4) #600
(1) #3/0 GND
3 SETS OF:
(1) 4"C.
(4) #600
(1) #3/0 GND(E)ECD3481
480/ 277V
3 SETS OF:
(1) 4"C.
(4) #600
(1) #3/0 GND
(E)ECR32211
208/ 120V
(4) #1 MI
(1) #8 MI GND
03-EJ-002
BUILDING 3 - EMERGENCY DEMOLITION
ONE-LINE DIAGRAM ----
MER AJW
PROJECT NO.
BUILDING NO.
DRAWING NO.
PROJECT TITLE
FLS
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASEARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
STAMP
LOCATION
1/ 2'
3' 0'
1'
1/ 2' 0'
1' 4'
4' 8'
8' 8'
4' 2'
2'
1/ 8' 0'
1/ 0'
1/ 4' 0'
1' 2'
1' 1/ 2'
2'
1' 0'
3/ 8' 0'
1'
2' 4'
1/ 2' 0'
1/ 2'
1' 3'
6' 0'
1/ 4"
1/ 2"
3/ 0'
8'
4' 4'
Fi le
P at h
Revisions: Date:
10% BASIS OF DESIGN 07.08.2022 CONSULTANTS
TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon
1000 W. STEUBEN ST., UNIT 3
BINGEN, WA 98605
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
FOR OFFICIAL USE ONLY (FOUO)
04/25/2023
FULLY
SPRINKLEDSPRINKLED
PROGRAMMING
CONTRACTING
ACTIVITY
CENTAL (PCAC)
Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver
100% CONSTRUCTION
DOCUMENTS
VA NEW ORLEANS (EHRM) ELECTRONIC
HEALTH RECORD MODERNIZATION
INFRASTRUCTURE UPGRADES
2400 CANAL STREET, NEW ORLEANS, LA 70119
629-22-700
35% SCHEMATIC DESIGN 11.10.2022
65% DESIGN DEVELOPMENT 01.13.2023
95% CONSTRUCTION DOCUMENTS 03.17.2023
FINAL BID DOCUMENTS 04.25.2023
SCALE: NTS
1 BUILDING 3 - EMERGENCY DEMOLITION ONE-LINE DIAGRAM
1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO
ASCERTAIN THE CONDITIONS AND LIMITS OF DEMOLITION AND
CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES
WITH THE COR PRIOR TO INITIATION OF WORK. NO DEMOLITION
SHALL OCCUR UNTIL AFTER THE NEW OR REPLACEMENT SYSTEMS
ARE IN PLACE AND READY FOR CUT OVER.
3. CONTRACTOR SHALL PROVIDE PEAK DEMAND METERING ON ALL
AFFECTED FEEDERS SERVING BRANCH-CIRCUIT PANELBOARDS,
DISTRIBUTION PANELBOARDS/SWITCHBOARDS, BUSWAYS AND
TRANSFORMERS AFFECTED BY THE SCOPE OF WORK. CONTRACTOR
TO PROVIDE DEMAND METERING AT EACH POINT FOR A MINIMUM OF
7 DAYS EACH. CONTRACTOR TO SUBMIT REPORT OF FINDINGS AND
DEMAND METER INFORMATION TO A/E AND COR FOR REVIEW. STUDY
SHALL BE COMPLETED AND REVIEWED BY A/E AND COR PRIOR TO
PERFORMING ANY OTHER WORK.
D1
DEMOLITION PLAN NOTES
GENERAL DEMOLITION NOTES
D2
EXISTING 150A DISCONNECT MOUNTED ON BUSWAY TO BE
REMOVED.
EXISTING 75KVA TRANSFORMER TO BE REMOVED. REMOVE
CONDUIT AND CONDUCTORS BACK TO SOURCE.
EXISTING CONDUIT AND CONDUCTORS FEEDING ECD3222
FROM EXISTING TRANSFORMER TO BE REMOVED.
D3
D1 D2 D3
80AT
35K AIC
FEEDER BUSWAY
600A, 3Ø, 4W, 100%G
EB311
LEVEL 1
BUSWAY CABLE CONNECTION FEED BOX
(1) 1 1/4"C.
(3) #3
(1) #8 GND
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T4
(E)ECR32721
208/ 120V
A
(E)ECR32721
208/ 120V
B
400AF
80AT
35K AIC
400AF
100AT
35K AIC
XFMR
208/120V 480V:
(E)T4
35K AIC
35K AIC
XFMR
208/120V 480V:
(E)T4
CT
FEEDER BUSWAY
600A, 3Ø, 4W, 100%G
EB312
BUSWAY CABLE CONNECTION FEED BOX
(1) 2 1/2"C.
(4) #1/0
(1) #6 GND
(E)UNIT SECONDARY SUBSTATION
EUSS03
TO
(E)ATS-EQ3-1
TO
(E)ATS-EL3-1
TO
(E)ATS-ELS3-1
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
LEVEL 6
LEVEL 7
LEVEL 8
2 SETS OF:
(4…