2.17 - Drawings 17 of 17 - 04-FP-100 to 11-FP-110.pdf

PDF 16 MB Posted

Attached to
NOLA EHRM Infrastructure Upgrades Construction - New Orleans, LA 629-22-700
Solicitation number
36C77623B0038
Issued by

About this file

This document provides details on a federal contract opportunity for infrastructure upgrades at a Veterans Affairs facility in New Orleans, Louisiana. The solicitation number is 36C77623B0038 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas for NOLA EHRM Infrastructure Upgrades Construction. The opportunity type is a solicitation for construction services to upgrade infrastructure at the New Orleans VA facility, as indicated by the file name which references drawings numbered 04-FP-100 to 11-FP-110. The agency issuing this solicitation is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The location where services will be provided is in New Orleans, Louisiana.

View the file

Other files

File Type Posted
36C77623B0038 0007.pdf PDF
Tech Questions Tracker - NOLA - 8-25-23.pdf PDF
Brand Name JA - NOLA EHRM.pdf PDF
Tech Questions Tracker - NOLA - 8-23-23.pdf PDF
36C77623B0038 0006.pdf PDF
36C77623B0038 0005.pdf PDF
Tech Questions Tracker - NOLA - 8-9-23.pdf PDF
36C77623B0038 0004.pdf PDF
Specs and Drawings - NOLA EHRM - Addendum No 2.pdf PDF
36C77623B0038 0003.pdf PDF
Specs and Drawings - NOLA EHRM - Addendum No 1.pdf PDF
36C77623B0038 0002.pdf PDF
NOLA EHRM Site Visit Sign-In Sheet 19 July 23.pdf PDF
36C77623B0038 0001.pdf PDF
Site Visit Instructions.pdf PDF
2.12 - Drawings 12 of 17 - 00-EG-001 to 02-ED-051.pdf PDF
2.2 - Drawings 02 of 17 - 000-AJ-601 to 000-AJ-606.pdf PDF
2.4 - Drawings 04 of 17 - 01-AE-011 to 02-AE-052.pdf PDF
1 - Specifications.pdf PDF
2.10 - Drawings 10 of 17 - 04-TD-011 to 08-TD-051.pdf PDF
2.13 - Drawings 13 of 17 - 02-EP-011 to 03-EP-071.pdf PDF
2.5 - Drawings 05 of 17 - 02-AC-011 to 03-AE-071.pdf PDF
2.16 - Drawings 16 of 17 - 00-FP-000 to 03-FP-111.pdf PDF
2.11 - Drawings 11 of 17 - 08-TN-011 to 00-TJ-028.pdf PDF
2.9 - Drawings 09 of 17 - 02-TN-011 to 03-TN-071.pdf PDF
IFB 36C77623B0038 - 6-29-23.pdf PDF
6 - Contractor Safety and Environmental Record.docx DOCX document
4 - DBA Wage Rates - Orleans County - 06-16-23.pdf PDF
2.1 - Drawings 01 of 17 - GI001 to GI003.pdf PDF
2.6 - Drawings 06 of 17 - 03-AC-011 to 11-AE-011.pdf PDF
2.8 - Drawings 08 of 17 - 00-TG-001 to 02-TD-052.pdf PDF
2.14 - Drawings 14 of 17 - 04-ED-011 to 10-EP-011.pdf PDF
2.15 - Drawings 15 of 17 - 01-EJ-001 to 00-EJ-026.pdf PDF
2.7 - Drawings 07 of 17 - 00-MK-001 to 10-MJ-011.pdf PDF
3 - HVAC Load Calculations.pdf PDF
5 - Limitations on Subcontracting - Construction.docx DOCX document
2.3 - Drawings 03 of 17 - 00-CG-001 to CJ-A102.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UPUP

UP

DN

LOUNGE

1K116

ST

1K116A

ST

1K116B

DISPATCH & CUBICLES

1K114

TRANS SUPV

1K114A

SECURITY

1K106

TR

1K104 1K104

ELEC

1K108

ATTENDANT OFFICE

1K112

WC STOR

1K109

STAIR

STK-1

STAIR

STK-2

EQUIPMENT STORAGE

1K105

EQUIPMENT STORAGE

1K107

MECHANICAL

1K110

SECURITY

1K101

TR

1K103 1K103

STAIR

STK-3

OIL / WATER

INTERCEPTOR

1K128

04-FP-110

F2

04-FP-110

F1

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

04-FP-100

K

OVERALL FIRE PROTECTION PLAN -

BUILDING K

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. SEISMIC BRACING REQUIRED IN ACCORDANCE

WITH NFPA 13.

4. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

5. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

3/32" = 1'-0"F1 OVERALL PLAN - LEVEL 1__BUILDING K

5/11/2023

SECURITY

1K101

TR

1K103 1K103

SECURITY

1K106

TR

1K104 1K104

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

04-FP-110

K

ENLARGED FIRE PROTECTION

PLANS - BUILDING K

100% FINAL BID

DOCUMENTS

3/8" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1K103 / X-MATRIX RM # 1K103 3/8" = 1'-0"F2 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1K104 / X-MATRIX RM # 1K104

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

UP

F

F

STAIR

STL-1

STAIR

STL-2

ATTENDANT OFFICE

1L106

SECURITY

1L108

TR

1L110 1L110

SECURITY

1L105

TR

1L107 1L107

OIL WATER

INTERCEPTOR

1L111

05-FP-110

F1

05-FP-110

F2

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

05-FP-100

L

OVERALL FIRE PROTECTION PLAN -

BUILDING L

100% FINAL BID

DOCUMENTS

3/32" = 1'-0"F1 OVERALL PLAN - LEVEL 1__BUILDING L

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

5/11/20235/11/20235/11/20235/11/20235/11/20235/11/20235/11/2023

F

SECURITY

1L105

TR

1L107 1L107

F

SECURITY

1L108

TR

1L110 1L110

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

05-FP-110

L

ENLARGED FIRE PROTECTION

PLANS - BUILDING L

100% FINAL BID

DOCUMENTS

3/8" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1L107 / X-MATRIX RM # 1L107 3/8" = 1'-0"F2 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1L110 / X-MATRIX RM # 1L110

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

DN

UP

DN?

F

CONF/ CLASSRM

2M142

OUT TER

2M143A

CONF/ CLASSRM

2M142

OUT TER

2M143A

TR

2M066A

PAT

2M021

BAR PAT

2M019

PAT

2M108

MEDS

2M016

PANTRY

2M004

MULTI-PUR

2M003

EQUIP

2M034

QUIET/ DEN

2M032CARE TEAM

2M061

BAR PAT

2M099

ISO PAT

2M020

T 2M021A

T 2M022A

PAT

2M022

PAT

2M023

PAT

2M024

PAT

2M025

PAT

2M026

PAT

2M115

PAT

2M114

PAT

2M112

PAT

2M111 PAT

2M110

T 2M108A

CARE TEAM

2M065

BAR T

2M099A

ISO PAT

2M101

QUIET/ DEN

2M121

LAUN

2M012

VT

2M015

NOUR

2M030

VEST

2M031

CORR E

2M018

VEST

2M120

LIVING/DINING

2M116

CORR E

2M107

ACAD WKRM

2M062

LAUN

2M037

QUIET/ DEN

2M057

QUIET/ DEN

2M094

ACAD WKRM

2M064

PHY THER

2M128

CONF/ CLASSRM

2M142SOC WORK

2M137

DIETITIAN

2M136

MDS COORD

2M139

PANTRY

2M127A

NURSE MAN

2M138

MED DIR

2M132

THERAPIST

2M128A

VEST

2M093

LIVING/DINING

2M052

VEST

2M056HK

2M055

PAT

2M046

CORR E

2M043

CLEAN LINEN

2M010A

LIVING/DINING

2M090

SOIL

2M008

MEDS

2M041

NOUR

2M053

VT

2M054

CLEAN LINEN

2M035A

LIVING/DINING

2M029

CORR B

2M001

CORR E

2M079

WC ALC B

2M059

WC ALC B

2M125

CORR B

2M063

T

2M024AT

2M023A

T 2M026A

T 2M025A

T

2M028AT

2M027A

PAT

2M027

PAT

2M028

PAT

2M113

T 2M114A

T 2M115A

T 2M112A

T 2M113A

T 2M110A

T 2M111A

T 2M020A

BAR PAT

2M080

BAR PAT

2M044

PAT

2M040

ISO PAT

2M045

T 2M081A

ISO PAT

2M081

PAT

2M082

PAT

2M083PAT

2M084

PAT

2M085

PAT

2M051

T 2M088A

PAT

2M050

PAT

2M049

PAT

2M048

PAT

2M047

BAR T

2M044A BAR T

2M080A

T 2M040A

PAT

2M038

T 2M083A

T 2M082A

T 2M085A

T 2M084A

T 2M087A

T 2M086A

PAT

2M086

PAT

2M087

PAT

2M088

T 2M050A

T 2M051A

T 2M048A

T 2M049A

T 2M046A

T 2M047A

VT

2M118

HK

2M103

SOIL

2M070

MEDS

2M106

NOUR

2M117

EMER ELEC

2M119

CLEAN LINEN

2M097A

VT

2M092

MEDS

2M078

LAUN

2M074A

NOUR

2M091

CLEAN LINEN

2M074

HK

2M073

PAT

2M109

T 2M126

HK

2M011

T 2M109A

LAUN

2M102

NORM ELEC

2M007

EMER ELEC

2M009

CARE GIVER

2M014

CG

2M039

T 2M045A

PAT

2M089

T 2M089A

CG

2M076

ASST MAN

2M140

STOR

2M134A

CG

2M104

BAR T

2M019A

EXTERIOR COURTYARD

2M033

EXTERIOR COURTYARD

2M122

EXTERIOR COURTYARD

2M058

EXTERIOR COURTYARD

2M095

RECEP

2M002

ST

2M098

ST

2M017

MP-01

2M005A

STAIR M1

2M006

STAIR M2

2M124

SERV ELEV LOBBY

2M067

MS-03

2M068

CLEAN

2M013

EQUIP

2M096

ST

2M075

CHUTE ROOM

2M069

CLEAN

2M100

CLEAN

2M072

CORR B

2M123

VT

2M002A

COPY/ FAX

2M133

FOOD PREP

2M060

FOOD PREP

2M030A

LOUNGE

2M143

MULTI-PUR

2M127

ST

2M130

CORR G

2M129

DR OFFICE 2

2M135

T 2M101A

T 2M038A

CLEAN

2M036

ST

2M042

CORR F

2M010

CORR F

2M097

CORR F

2M071

CORR F

2M035

MP-02

2M005B

LVSR

2M066

OUT TER

2M143A

STOR

2M131

SEC

2M134

CONF/ CLASSRM

2M142

OUT TER

2M143A

DN

UP

UP

DN

F

PMRS SCI EXAM

1M028

PMRS SCI EXAM

1M030

PMRS EXAM

1M036

PMRS EXAM

1M038

PMRS EXAM

1M040

PMRS EXAM

1M037

PMRS EXAM

1M039

PMRS EXAM

1M035

PMRS SCI EXAM

1M031

PMRS SCI EXAM

1M029

CONSULT

1M042

PROS EXAM

1M045

T 1M034

DRESS

1M044

CAST ROOM

1M076

PROS EXAM

1M043

PROS EXAM

1M047

PROS EXAM

1M049

ELEV EQUIP

1M015

MOLD ROOM

1M055

CLEAN LINEN

1M077

RESTR LAB

1M054

DUST ROOM

1M062

FUME ROOM

1M066

MAINT

1M064

LAB

1M056

LAB

1M058 LAB

1M060

WC PARTS

1M069

SEWING RM

1M052

CAD/CAM

1M075

P/O PARTS

1M057

WC REPAIR

1M068

SOIL HOLD

1M071

HK

1M073

SHOE

1M053

WC HOLDING

1M063

TRASH

1M072

TRTMT

1M112

BAR TRTMT

1M111

TRTMT

1M110

MAT AREA

1M114

NURSE STATION

1M033

PT OFFICE

1M137

PT OFFICE

1M142

CONF/ CLASSRM

1M143

RESID

1M135

RESID

1M131

RESID

1M132

RESID

1M129

RESID

1M128

RESID

1M134

RESID

1M130

RESID

1M133

SEC

1M125

COPY/ FAX

1M126

WAITING

1M124

TR

1M115A

STAFF LCKR

1M146

STAFF LOUNGE

1M147

WOMEN LCKR

1M161

MEN LCKR

1M156

REC OFFICE

1M154

REC OFFICE

1M153

CLEAN

1M160

POOL ROOM

1M162

OT GYM

1M113PT GYM

1M095

LINEN

1M108

WC ALC A

1M067

EQUIP STOR

1M061

MAIL AREA

1M074

TRTMT

1M107

BAR TRTMT

1M106

CERVICAL TRTMT

1M105

REC THER STOR

1M163

SOIL HOLD

1M158

DR

1M032B

DR

1M032A

DR

1M139

DR

1M140

DR

1M141

HK

1M109

MAIN STREET

1M019

HK

1M159

PROS CONF

1M093

AISLE C

1M144

ST

1M050

ELECTRO

1M046

WC ACTIVE

1M065

PROS OFFICE

1M080

CHIEF OFFICE

1M083

PURCH AGNT

1M085

GAIT LANE

1M078

PROS OFFICE

1M081

SEC/ WAIT

1M079A

ST

1M121

STOR

1M082

MULTI-PUR RM

1M092

PURCH AGNT

1M087 PURCH AGNT

1M089

PURCH AGNT

1M091

PURCH AGNT

1M084

PURCH AGNT

1M086

COPY/ FAX

1M088 PURCH AGNT

1M090

CORR A

1M026

ST

1M148

NORM ELEC

1M014

EMER ELEC

1M013

NORM ELEC

1M116

POOL EQUIP

1M165

DEHUMIDIFICATION

EQUIP

1M164

FILE ROOM

1M127

SALON

1M024

FEMALE

1M016

MALE

1M017

PT/ OT ADMIN

1M103

UTILITY AREA

1M104

SOIL HOLD

1M097

DRESS

1M098

DRESS

1M099

CARDIO AREA

1M118BAL QUEST

1M102

WC STOR

1M119A

OT STOR/ PAT PROJ

1M117

T 1M101

SUB WAIT

1M100

PT STOR

1M119

VESTIBULE

1M151

DR

1M138

WAITING

1M007

SERV ELEV LOBBY

1M122

MP-01

1M021A

STAIR M1

1M022

MS-03

1M123

STAIR M2

1M150

PROS REP

1M006

MEDS

1M048

BRAIN TRAIN

1M096

CHUTE ROOM

1M149

LOBBY

1M152

CORR C

1M041

CORR D

1M059

AISLE

1M079

AISLE B

1M051

AISLE A

1M094

AISLE

1M136

CORR

1M010

CORR

1M018

CORR C

1M027

CORR D

1M070

STOR

1M157

RECEP

1M155

CORR A

1M120

T 1M025A

STOR

1M025B

SANCTUARY

1M023

ADMIN WKRM

1M005A

SUNDRY SHOP

1M025

CHECK OUT

1M005B

CHECK OUT

1M005D

STOR

1M023A

RECEPT

1M004

FAMILY T

1M011

ST

1M145

SECUR DESK

1M003

ENTRY

1M002

VESTIBULE

1M001

WC ALC

1M012

MP-02

1M021B

PUB ELEV LOBBY

1M020

LVSR

1M115

STAFF COURT

1M147A

PASS

1M005C

CORR A

1M151A

06-FP-110

F1

06-FP-110

F2

DN

UP

CB

CB

CB

CB

CB

CB

CB

CB

F

EMER ELEC ROOM

4M009

WET MECH

4M010

ELEC SWITCHGEAR

4M003

CENTRAL STOR

4M005

HK STOR

4M014

CART STAGING

4M008

FOOD PREP

4M012

RESIDENT STOR

4M002

CLEAN STAG

4M011

TR

4M015A

CORR B

4M001

CORR B

4M006

MS-03

4M013

STAIR M2

4M004

VEST

4M004A

LVSR

4M015

CHUTE

4M007

GENERAL STORAGE

4M016

DN

UP

UP

DN

F

F

ON CALL ROOM

3M079

MULTI-PUR

3M074

PANTRY

3M074A

MECH ROOM

3M081

CORR B

3M001

LOUNGE/ LOCKERS

3M078

CORR

3M071

OUTDOOR TERRACE

3M037

ASST. MANG.

3M073

PANTRY

3M004

MULTI-PUR

3M003

QUIET/ DEN

3M034CARE TEAM

3M036

BAR T

3M021A

QUIET/ DEN

3M069

VEST

3M033

CORR

3M020

VEST

3M068

LIVING/DINING

3M064

CORR

3M055

LIVING/DINING

3M031

HK

3M051

SOIL

3M010

NORM ELEC

3M009

EMER ELEC

3M011

TR

3M040A

T 3M076

MEDS

3M018

EQUIP

3M044

LAUN

3M014

VT

3M017

NOUR

3M032

CLEAN LINEN

3M012A

HK

3M013

CG

3M016

PAT

3M023

BAR PAT

3M021

PAT

3M056

ISO PAT

3M022

T 3M023A

T 3M024A

PAT

3M024

PAT

3M025

PAT

3M026

PAT

3M027

PAT

3M028

PAT

3M063

PAT

3M062

PAT

3M060

PAT

3M059

PAT

3M058

T 3M056A

T 3M026A

T 3M025A

T 3M028A

T 3M027A

T 3M030A

T 3M029A

PAT

3M029

PAT

3M030

PAT

3M061

T 3M062A

T 3M063A

T 3M060A

T 3M061A

T 3M058A

T 3M059A

T 3M022A

PAT

3M057

T 3M057A

ACAD WKRM

3M039

VT

3M066

MEDS

3M054

NOUR

3M065

NORM ELEC

3M067

CLEAN LINEN

3M045A

LAUN

3M050

CG

3M052 T

3M049A

BAR PAT

3M047

BAR T

3M047A

ISO PAT

3M049

SERV ELEV LOBBY

3M041

ST

3M046

ST

3M019

STAIR M1

3M006

MP-01

3M005A STAIR M2

3M072

MS-03

3M042

CLEAN

3M015

T/SHWR

3M079A

CLEAN

3M048

WC ALC B

3M007

EQUIP

3M008

CHUTE ROOM

3M043

FOOD PREP

3M032A

VT

3M002A

CORR F

3M012

CORR F

3M045

OUTDOOR TERRACE

3M035

OUTDOOR TERRACE

3M070

MP-02

3M005B

LVSR

3M040

ST

3M080

WC ALC B

3M075

PASS

3M077

TR

3M104

06-FP-110

F4

06-FP-110

F3

06-FP-110

F5

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

06-FP-100

M

OVERALL FIRE PROTECTION PLANS -

BUILDING M

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

1/32" = 1'-0"F1 OVERALL PLAN - LEVEL 1_BUILDING M

1/32" = 1'-0"F2 OVERALL PLAN - LEVEL 2_BUILDING M

1/32" = 1'-0"F3 OVERALL PLAN - LEVEL 3_BUILDING M

1/32" = 1'-0"F4 OVERALL PLAN - LEVEL 4_BUILDING M

TR

1M115A

NORM ELEC

1M116

F

TR

2M066A

EMER ELEC ST

2M100

LVSR

F

TR

3M040A

3M066

NORM ELEC

ST

3M048

LVSR

F

TR

3M104

F

TR

4M015A

LVSR

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

06-FP-110

M

ENLARGED FIRE PROTECTION

PLANS - BUILDING M

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

3/8" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1M115A / X-MATRIX RM # 1M240 3/8" = 1'-0"F2 ENLARGED SECOND FLOOR PLAN - RENOVATION

TR 2M066A / X-MATRIX RM # 2M252 3/8" = 1'-0"F3 ENLARGED THIRD FLOOR PLAN - RENOVATION

TR 3M040A / X-MATRIX RM # 3M111

3/8" = 1'-0"F4 ENLARGED THIRD FLOOR PLAN - RENOVATION

TR 3M104 / X-MATRIX RM # 3M104 3/8" = 1'-0"F5 ENLARGED FOURTH FLOOR PLAN - RENOVATION

TR 4M015A / X-MATRIX RM # 4M113

UP

FD FD

UP

FD

FD

FD

FD

UP

FD

FD

UP

UP

RECEIVING & ISSUE

1N119

STOREKEEP

1N123

STOREKEEP

1N121

CUBICLES

1N123B

LINEN CHUTE

COLLECTION

1N113

HAZ WASTE HOLDING

1N117

RMW/ SHARPS HOLDING

1N111

AL RECYCLE HOLD

1N115

CART WASH

1N109

GROUNDS OUTSIDE

STORAGE

1N114

GROUNDS WORKSHOP

1N116

FLAM STORAGE

1N106

TR

1N118A

MASON SHOP

1N131

AC SHOP

1N129

CLEAN DOCKS

1N110

SOILED DOCKS

1N108

STORAGE MED GAS

1N104

FOREMAN

1N116A

CIM COMMUNICATIONS

STOR

1N120

SECURITY

1N112

CORR

1N-C02

ENGINEERING STORES

1N133

WELDING

1N129B

UTILITY ACCESS

1N102

VEST

1N-C02A

ELEC

1N100

FOREMAN

1N129C

SECURITY

1N118

WASH AREA

1N109A

FUEL OIL TRANSFER

PUMP ROOM

1N152

FUEL TANK STORAGE

1N148

ENGINEERING STORAGE

1N135

ELEC SHAFT

1N149

SUPPLIES

1N150

CORR

1N146

ELEC SHAFT

1N151

STAIR

STN-1

07-FP-110

F1

UP

DN

FD FD FD

DN

UP

UP

DN

UP

FD FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD FD FD FD

FD

FD FD

LOCKSMITH

2N115

FOREMAN

2N119A

CARPENTRY SHOP

2N119

MACHINE SHOP

2N102

WELDING

2N102A

ELECTRICAL SHOP

2N106

PAINT AREA

2N108A

PAINT SHOP

2N108

PAINT TOOLS/EQ

2N108B

MEN'S LOCKER

2N111

ELEC

2N100

ENGINEERING STORES

2N117

CORR94

2N-C02

CORR

2N-C03

SHAFT

SHN101

SHN02

SHN102

SIGN SHOP

2N113

FOREMAN

2N106A

PLUMBING SHOP

2N104

FOREMAN

2N104A

ST/SHOW

2N111A

WOMEN'S LOCKER

2N109

ST/SHOW

2N109A

TR

2N110A

SECURITY

2N110

ELEVATOR

NS-01

ELEVATOR

NS-02

GENERATORS

2N128

SHAFT

2N145

SWITCHGEAR

2N131

CORR

2N127

GENERATOR INTAKE

SHAFT

2N135

FUEL STO.

2N129

FIRE PUMPS

2N125

HOUSE PUMPS

2N126

ELEC SHAFT

SUPPLIES

2N143

LOBBY

2N123

TOILET

2N142

TOILET

2N141HK

2N140

CORR

2N124

TR

2N134B

178 SF

GENERATORS

2N128

7329 SF

FUEL STO.

2N130

212 SF

GEN. CONTROL ROOM

2N133

549 SF

ELECTRICAL

2N136

4324 SF

VESTIBULE

2N138

181 SF

STAIR

319 SF

CORR

2N132

138 SF

ENTERGY VAULT

2N137

3927 SF

ENTRANCE ROOM

2N134A

189 SF

LV SYSTEM ROOM

2N134C

133 SF

SHAFT

2N146

30 SF

07-FP-110

F4

07-FP-110

F3

07-FP-110

F2

UP

UP

DN

UP

DN

PHARMACY CACHE

4N111

LINEN DISTRIBUTION

4N102

STORAGE

4N102A

LINEN STORAGE

4N102B

TR

4N108A

MSD/SPD STORAGE

4N104

WKSTATION

4N104B

SECTION LEADER

4N104A

WKSTATION

4N106A

PROSTHETIC STORAGE

4N106B

ELEC

4N100

WAREHOUSE

4N106

SECURITY

4N108

CORR

4N-C02

BOILER PLANT

CONTROL

3.5N134

CHILLERS/ PUMPS

3.5N135

BOILERS

3.5N133

TREATMENT PLANT

3.5N139

ELEVATOR SHAFT

STAIR

LOBBY

4N103CORR

4N101

CHILLERS/ PUMPS

3.5N135

ELECTRICAL CHILLER

SWITCHGEAR

3.5N136

EMERGENCY ELECTRIC

3.5N138

CHILLERS/PUMPS

3.5N137

07-FP-110

F6

UP

DN

UP

DN

DN UP

FDFD

FD

FD

FD

FD

FD

FD

SERVICE BAY

3N127

REF LIB

3N113

PLANS, DRAFTING,

WORK

3N118

COPY/FAX

3N106

STOR/OFF

3N117

CHIEF OF SERV

3N116

OPS ENG

3N123

ASST CHIEF

3N114

PROJ ENG

3N112

PROJ ENG

3N110

PROJ ENG

3N108

CONF

3N104

CLERK

3N115

CLERK/REC

3N111

CLERK

3N121

WAITING

3N109

TR

3N128A

CHUTE FAN ROOM

3N124

FAN ROOM

3N126

CORR

3N-C06

LOUNGE

3N125

CORR

3N-C05

CORR

3N-C03

CORR

3N-C02

CORR

3N-C04

ELEC

3N100

KITCH

3N125A

CONTROL CENTER

3N119

CORRIDOR

3N120

SECURITY

3N128

PLENUM

2MN100

CORR

3N129

ELEVATOR SHAFT

LOBBY

3N133

STAIR

TOILET

3N132

TOILET

3N131HK

3N130

PLENUM

2MN100

07-FP-110

F5

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

07-FP-100

N

OVERALL FIRE PROTECTION PLANS -

BUILDING N

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

1/32" = 1'-0"F2 OVERALL PLAN - LEVEL 1_EAST_BUILDING N

1/32" = 1'-0"F1 OVERALL PLAN - LEVEL 1_WEST_BUILDING N

1/32" = 1'-0"F4 OVERALL PLAN - LEVEL 2_EAST_BUILDING N

1/32" = 1'-0"F3 OVERALL PLAN - LEVEL 2_WEST_BUILDING N

1/32" = 1'-0"F6 OVERALL PLAN - LEVEL 3_EAST_BUILDING N

1/32" = 1'-0"F5 OVERALL PLAN - LEVEL 3_WEST_BUILDING N

1/32" = 1'-0"F8 OVERALL PLAN - LEVEL 4_EAST_BUILDING N

1/32" = 1'-0"F7 OVERALL PLAN - LEVEL 4_WEST_BUILDING N

1N118A

SECURITY

TR

2N110A

SECURITY

GEN. CONTROL ROOM

2N133

549 SF

ENTRANCE ROOM

TR

2N134B

178 SF

ENTRANCE ROOM

LV SYSTEM ROOM

2N134C

UP

DN

TR

3N128A

SECURITY

3N128

TR

4N108A

SECURITY

4N108

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

07-FP-110

N

ENLARGED FIRE PROTECTION

PLANS - BUILDING N

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

3/8" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1N118A / X-MATRIX RM # 1N115 3/8" = 1'-0"F2 ENLARGED SECOND FLOOR PLAN - RENOVATION

TR 2N110A / X-MATRIX RM # 2N121A

3/8" = 1'-0"F4 ENLARGED SECOND FLOOR PLAN - RENOVATION

TR 2N134B / X-MATRIX RM # 2N130

3/8" = 1'-0"F3 ENLARGED SECOND FLOOR PLAN - RENOVATION

TR 2N134B / X-MATRIX RM # 2N130

3/8" = 1'-0"F5 ENLARGED THIRD FLOOR PLAN - RENOVATION

TR 3N128A / X-MATRIX RM # 3N117A 3/8" = 1'-0"F6 ENLARGED FOURTH FLOOR PLAN - RENOVATION

TR 4N108A / X-MATRIX RM # 4N109A

DN

UPDN

FD FD

FD FD

F

OFF CH

1P103E

OFF DEP

1P103A

BID OPEN

1P103B

STOR

1P106

CONF

1P105

CH LOG

1P107C

TECH

1P107A

OFF

1P102Q

OFF

1P102P

OFF

1P102N

INV

1P102M

OFF

SUP

1P102L

INV

1P102K

INV

1P102J

INV

1P102H

INV

1P102G

INV

1P102F

OFF

1P101F

SUP

1P107F

ASST CH

1P107B

OFF

1P101G

OFF

1P101H

OFF

1P101J

STOR

1P101D

OFF

1P101E

INV

1P101B

INV

1P101A

RD PI

1P101N

RD PI

1P101M

CONF

1P108

TR

1P110

INV

1P102D

INV

1P102C

GROUP

1P112B

CLASS

1P112C

GROUP

1P112D

TLT

1P109

TLT

1P111

RECY

1P115A

LAB STOR

1P115B

SEC

1P100B

ELEC

1P115C

BIO MED

1P114 EMS

1P116

DOCK

1P115

REC

1P100C

COPY

1P101C

RECP + W

1P101

TECH

1P107D

CPY

1P102E

MULTI PURP

1P112

WAITING

1P100D

GROUP

1P112A

REC

1P102PSA, RN

1P102R

DATA WORK

1P101L

HK

1P104

ELEC

1P116A

RAD WST

1P115E

STOR

1P115D

COPY

1P107E

SEC WAIT

1P107

SEC

1P103

VESTIBULE

1P100A

CLER TECH

1P103D

HS CUBES

1P101K

CORR

1P-C02

CORR

1P-C06

CORR

1P-C07

CORR

1P-C01

CORR

1P-C05

CORR

1P-C03

CORR

1P-C04

ALCOVE

1F-CO4A

STAIR

STP-2

STAIR

STP-1

SHAFT UTILITY ACCESS

1P115H

ELEV

PS-02

ELEV

PS-01

SHOWER

1P109A

SHOWER

1P111A

ELEC

1P1025

BIO HAZ WST

1P115F

STORAGE

1P112G

LOBBY

1P100LVSR

1P110A

CORR

1P-C11

SHELL

1P113A

UP

DN

UP

DN

FD

FD

FD FD

FD

FD

FD

FD FD

FD

FD

FD

FD

FD

FD FD FD FD

FD

FD

F F

STAIR

STP-2

STAIR

STP-1

ELEV

PS-02

ELEV

PS-01

LVSR

2P100A

ELEC

2P169

ELEC

2P137

TC

2P139

MIC D

2P139A

TC

2P141

MIC D

2P135A

FRZ UL

2P143

REFRIG/FRZ

2P149A

ELEC MIC

2P150

TC

2P145

TC

2P147

FZ-20

2P149B

TC

2P135B

MIC D

2P135BB

PI

2P134

PI

2P132

PI

2P130

PI

2P128

PI

2P126

PI

2P124

PI

2P122

PI CONF

2P120

TC

2P151

CELL

S

2P153D

TC

2P153C

HPLC

2P153B

MIC D

2P153A

MIC D

2P157A

TC

2P157

TC

2P155

IM HIST

2P159

HK

2P161 GLASS WASH

2P163

CELL BANK

2P165

LER

2P135

LER

2P149

LER

2P153

TL

2P116

TL

2P115

LAB 1

2P138

LAB 4 & 5

2P152

LAB 6

2P162

LAB 7 & 8

2P168

CYL

2P167

LAB 2

2P142

LAB 3

2P148

CORR

2P-C04.1

CORR

2P-C02

CORR

2P-C01A

CORR

2P-C01

CORR

2P-C03A

EQUIP RM

2P163A

ELEC MIC

EQUIP

2P150A

LAB 7 & 8 HOODS

2P168B

LAB 7 & 8 ENTRY

2P168A LAB 7 & 8 HOODS

2P168C

LAB 6 HODDS

2P162B

LAB 1 ENTRY

2P138A

LAB 1 FUME HOOD

2P138B LAB 2 ENTRY

2P142A

LAB 2 HOODS

2P142B LAB 3 ENTRY

2P148A

LAB 3 HOODS

2P148B

LAB 4 & 5 HOODS

2P152B

LAB 4 & 5 ENTRY

2P152A

LAB 4 & 5 HOODS

2P152C

LAB 4 & 5 HOODS

2P152D

LAB 4 & 5 HOODS

2P152E

LAB 6 ENTRY

2P162A

CORR

2P-C04.2

WORK/COLAB

2P100B

AISLE

2P-C01BCORR

2P-C03B

TR

2P100C

COPY/ STG

HS OFFICE

HS OFFICE

HS WKSTNS

8HS WKSTNS

HS WKSTNS

PI

HS

WORK/ COLAB

PI EQ

08-FP-110

F1

08-FP-110

F2

DNUP

UP

UP

DN

FD FD FD

FD

FD

FD

FD

FD

FD

FD FD

FD

FD

FD

FD

FD

FD FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD FD

FD

FDFD

FD

FD

FD

F

STAIR

STP-2

STAIR

STP-1

ELEV

PS-02

ELEV

PS-01

HS

4P102A

HS

4P105A

HS

4P101A

HS

4P103A

HOLD

4P327

TREAT

4P329

HOLD RABBIT

4P331

TREAT

4P333

HOLD RABBIT

4P335

ELEC

4P115B

HK

4P113

HOLD

4P302A

HOLD

4P323

TREAT

4P321

HOLD

4P317

HOLD

4P324

TREAT

4P322

ISO HOLDING

4P320B

ISO HOLDING

ANTE-ROOM

4P320A

HOLD

4P316

OR SUP

4P318D

OR

4P318C

GOWN PREP

4P318B

FEED & BED STOR

4P314B

CLEAN CAGE

4P314A

CLEAN CAGE WASH

4P314

SOIL CAGE WASH

4P304

WOMEN LOCKER

4P300F

VET OFF

4P300B

LOUNGE

4P300

OFF

4P300A

MEN LOCKER

4P300C

HAZ WASTE STOR

4P303

FRZ/STOR

4P305

TR

4P103

WATER SYS

4P311

CARC HOLD

4P309

NECRO

4P307

EQUIP

4P305AUNASSIGNED

4P315

ENVIRO PROC

4P313A

ENV HOLD

4P313

ELEC

4P301

TL

4P104

TL

4P102

REC + W

4P101

RECPT

4P100

X RAY

4P318A

UNASSIGNED

4P100A

HK

4P319

QUAR HOLD

4P302B

DIAG HOLD

4P302C

CORR

4P-C03

CORR

4P-C03A

CORR

4P-C03B

CORR

4P-C01

CORR

4P-C02

T/S 4P300E

T/S 4P300D

VESTIBULE

4P-C01A

VESTIBULE

4P-C03C

UNAS

4P106A

VESTIBULE

4P115A

CORR

4P-CO1B

LOBBY

4P100B

LVSR

4P103B

ACOS CONF

4P204

FILE/COPY

4P203

OFFICE

4P202E

RCO

AO

CORR

OFFICE

ACOS OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

UP

DN UP

UP

UP

FD FD

FD

FD

FD

FD

FD FD FD FDFDFD

FF

ELEV

PS-02

ELEV

PS-01

ELEV

ELEV

TC

3P139

MIC D

3P139A

ELEC

3P137

ELEC

3P173

LVSR

3P100A

PI

3P134

PI

3P132

PI

3P130

PI

3P128

PI

3P126

PI

3P124

PI

3P122

PI CONF

3P120

OFF

3P107

TL

3P105

TL

3P103

WORK/ COLAB

3P100

LER

3P135

LER

3P149

LER

3P155

TC

3P141

FRZ UL

3P143

MIC D

3P135A

COLD

3P149A

TC

3P145

TC

3P147

TC

3P153

MIC D

3P153A

MIC D

3P149B

TC

3P135B MIC D

3P135BB

TC

3P155C

TC

3P155B

EQ ROOM

3P155A

TC

3P157

CON FOC

3P159

IM HIST

3P161

HK

3P163

RAD LAB

3P165

TC

3P167

FLAM STOR

3P171

ACID STOR

3P169

LAB 11

3P148

LAB 14

3P162

LAB 10

3P142

LAB 9

3P138

LAB 15

3P168

SERV

3P102

LABS 12 & 13

3P152

CORR

3P-C20

CORR

3P-C04

CORR

3P-C04A

CORR

3P-C01

CORR

3P-C03A

CORR

3P-C02

LAB 9 ENTRY

3P138A

LAB 9 HOODS

3P138B

LAB 10 ENTRY

3P142A

LAB 10 HOODS

3P142B

LAB 11 ENTRY

3P148A

LAB 11 HOODS

3P148B

LABS 12 & 13 HOODS

3P152B

LABS 12 & 13 ENTRY

3P152A

LABS 12 & 13 HOODS

3P152C

LABS 12 & 13 HOODS

3P152D

LABS 12 & 13 HOODS

3P152E LAB 14 ENTRY

3P162A

LAB 14 HOODS

3P162B

LAB 15 HOODS

3P168B

LAB 15 ENTRY

3P168A LAB 15 HOODS

3P168C

ELEV

ELEV

CORR

CP-CO3B

TR

3P100C

COLLABORATION

3P202D

HS WKSTNS

3P104

HS WKSTNS

COPY

HS OFFICE

HS OFFICE

HS WKSTNS

HS CONF

MASS SP

HS

HS

LOUNGE

ELEV

ELEV

ELEV

ELEV

STAIR

STP-2

236 SF

STAIR

STP-1

Redundant Room

08-FP-110

F3

08-FP-110

F4

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

08-FP-100

P

OVERALL FIRE PROTECTION PLANS -

BUILDING P

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

1/32" = 1'-0"F1 OVERALL PLAN - LEVEL 1_BUILDING P

1/32" = 1'-0"F2 OVERALL PLAN - LEVEL 2_BUILDING P

1/32" = 1'-0"F3 OVERALL PLAN - LEVEL 3_BUILDING P

1/32" = 1'-0"F4 OVERALL PLAN - LEVEL 4_BUILDING P

1P110

HK

1P104LVSR

1P110A

FD

F F

LVSR

2P100A

IM HIST

2P159

HK

2P161 EQUIP RM

2P163A

TR

2P100C

FF

LVSR

3P100A

IM HIST RAD LAB

3P165

TR

3P100C

F

TR

4P103

ENVIRO PROC

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

08-FP-110

P

ENLARGED FIRE PROTECTION

PLANS - BUILDING P

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

3/8" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1P110 / X-MATRIX RM # 1P140 3/8" = 1'-0"F2 ENLARGED SECOND FLOOR PLAN - RENOVATION

TR 2P100C / X-MATRIX RM # 2P120A

3/8" = 1'-0"F3 ENLARGED THIRD FLOOR PLAN - RENOVATION

TR 3P100C / X-MATRIX RM # 3P102A 3/8" = 1'-0"F4 ENLARGED FOURTH FLOOR PLAN - RENOVATION

TR 4P103 / X-MATRIX RM # 4P103

DN

UP

UP

FF

F F

F

STAIR

STAIR

STQ-2

ELEC./AV

1Q126

CONF

1Q132

CONF

1Q130

CONF

1Q135

PANTRY

1Q129

CONF

1Q137

AUDITORIUM

1Q136

MALE

1Q118

FEMALE

1Q113

SUPPLIES

1Q112

PREFUNCTION SPACE

1Q134

MANAGER

1Q105

SUPERVISOR

1Q108A

LOAN OFFICER

1Q108B

VAULT

1Q109

ATM

1Q127

LOBBY

1Q108

OFFICE

1Q115

CLASSRM

1Q116

RECEPT

1Q114A

SEATING

1Q114B

COMPUTERS

1Q114F

AV

1Q114E

CLASSROOM

1Q104

SIM LAB

1Q100

CLASSROOM

1Q102

SERVICE WINDOW

1Q110

PERIODICALS

1Q114C

ADMIN.

1Q114D

SUPPLIES

1Q119

TR

1Q140

ELEC

1Q111

EMER ELEC

1Q111A

TELECOM

DEMARCATION

1Q103

IT CLASSRM

1Q121

IT CLASSRM

1Q122

ASST./ WAITING

1Q123A

ACOS

1Q123B

IT SUPPLIES

1Q120

CAFE

1Q125

STAIR

STQ-4

STAIR

STQ-3

PREFUNCTION SPACE

1Q138

WRKSTN

1Q107

HK

1Q131

CHILLED WATER PUMP

1Q117

CHAIRS

1Q144

MALE

1Q133

FEMALE

1Q128

ELEC

CORR

1Q-C01

LOBBY

1Q139

ELEV

QP-1 ELEV

QP-2

SHAFT

SHQ01

SHAFT

SHQ03

LIBRARY

1Q114

SHAFT

SHQ04

SHAFT

SHQ09

CORR

1Q-C06

CORR

1Q-C04

CORR

1Q-C03

ELEV

SUPPLIES

1Q106

CAFE WRKRM

1Q141

LVSR

1Q101

ELEV LOBBY

1Q139A

PREFUNCTION SPACE

1Q146

PREFUNCTION SPACE

1Q145

TELEPHONE EQUIP

1Q124

SHAFT

SHQ10

SHAFT

ELEC

SHQ12

09-FP-110

F3

09-FP-110

F1

09-FP-110

F2

DN

UP UPDN

F

STAIR

STQ-1MALE

2Q113

STAIR

WFD INSTR (6)

2Q138

VIDEO EDT

2Q127

CONFERENCE

2Q122CONF

2Q118

SECTRY/RECEP

2Q117

ILLSTN PREP

2Q103

DEPUTY PAO

2Q104

PA OFFICER

2Q100

FEMALE

2Q111

TR

2Q112A

ELEC

2Q105

EMER ELEC

2Q107

CLERICAL (2)

2Q108

LOUNGE

2Q106

WKRM

2Q128

CHIEF

2Q115

CENTRAL COPY CNTR

2Q101

WFD COORD

2Q136

ILL WKRM (2)

2Q103A

PHOTO/VIDEO STUDIO

2Q131

AV STOR/ CHECK OUT

2Q121

TECH WKRM

2Q123

MMS/MMEC SUPPLIES

2Q129

VIDEO CONF

VIDEO CONF

2Q116

PHOTO/ DIGITAL EDIT/

PRINT

2Q109

DEPUTY PAO

2Q102

SECTRY/ WAITING

2Q110

MOVE WELL COORD

2Q132

DLO

2Q126

WELL ADMIN

2Q134

CHANGING

2Q119

HK

2Q114

PAPER

2Q133

ELEC

SAFE PAT HANDL

2Q130

LOBBY

2Q124

ELEV

ELEV

QP-3

ELEV

SHAFT

SHAFT

26 CORR

2Q-C02

CORR

2Q-C03

CORR

2Q-C01

CORR

2Q-C04

RECYCLE

2Q135

LVSR

2Q112

SHAFT

SHQ11

SHAFT

SHAFT

09-FP-110

F4

DNUP DN UPUP

F

STAIR

RCRD FILE

3Q110

FEMALE

3Q105

MALE

3Q107

CLEAN

3Q101C

NURSE

3Q101K PRSNL MGMT

3Q121

LOUNGE

3Q114WKRM

3Q106

PRSNL MGMT

3Q124

PRSNL MGMT

3Q119

EXAM1

3Q101H

EAP

3Q103

RECEP WAITING

3Q128

PRSNL MGMT

3Q146

SPRVSR

3Q102

NURSE

3Q101A

PRSNL MGMT

3Q142

PRSNL MGMT

3Q104

TR

3Q118A

ELEC

3Q101F

EMER ELEC

3Q101E

CHIEF

3Q138

PRSNL MGMT

3Q129

PRSNL MGMT

3Q116

PRSNL MGMT

3Q112

SPRVSR

3Q100

PRSNL MGMT

3Q108

PRSNL MGMT

3Q123

PRSNL MGMT

3Q131

PRSNL MGMT

3Q144

CONF

3Q126

PRSNL MGMT

3Q122

FNGRPRNT MACH

3Q132

PRSNL MGMT

3Q127

ASST CHIEF

3Q134

SCTRY

3Q136

EXAM2

3Q101J

SOILED UTILITY

3Q101B

T 3Q101D

CLERK/WAITING

3Q101G

PERSONNEL ASSTS.

3Q140

WORKSTATIONS

HK

3Q120

RECPT

3Q111

CONF

3Q113

UNION PRES

3Q109

RECPT

3Q115

UNION PRES

3Q117

EMER ELEC

3Q125

ELEC

CORR

3Q-C01A

LOBBY

3Q130

CORR

3Q-C01

EMPLY HEALTH

3Q101

CORR

3Q-C02

CORR

3Q-C02A

ELEV

ELEV

ELEV

STAIR

SHAFT

SHAFT

HR CARRELS

3Q128A

FILES

3Q101L

LVSR

3Q118

SHAFT

SHAFT

SHAFT

09-FP-110

F5

UP DN UPDNDN

F

STAIR

3MALE

4Q113

FEMALE

4Q111

CONF

4Q121

ELEC

4Q107

TR

4Q112A

EMER ELEC

4Q105

WKRM

4Q101B

CNSLR

4Q101G

CNSLR

4Q101H CONF

4Q103

CNSLR

4Q101J

INFCT CONTROL MNGRS

(2)

4Q100

QM ADMIN

4Q104

ACOS QM

4Q106 RSK MNGR

4Q118

ASST QM

4Q102

PSA

4Q110 RECEPTION

4Q126

INFMTC MNGR

4Q144PTNT SAFETY

4Q138

ANALYST

4Q140

ACRDTN COORD

4Q124

CNSLR

4Q101F

WKRM

4Q132

BREAK

4Q108

CRDNTL MNGR

4Q130B

CRDNTL

4Q130

SWITCH GEAR

4Q131

ANALYST

4Q116 ANALYST

4Q122WKRM

4Q120

FILES

4Q136

STAIR

HK

4Q114

EEO SCTRY/ WAITING

4Q119EEO OFFICE

4Q117

EEO HEARING ROOM

4Q109

CLNL CORD (4)

4Q142SUPPLIES

4Q101D

PRLGL

4Q101A

CNSLR

4Q101C

RECEPTION

4Q101E

ELEC

COUNCIL

4Q101

CORR

4Q-C04

CORR

4Q-C03

LOBBY

4Q128

CORR

4Q-C02

CORR

4Q-C01

ELEV

ELEV

ELEV

39 SHAFT

SHAFT

SUPPLIES

4Q137

PTNT SAFETY

4Q134

CRDNTL CARRELS

4Q130A

SFTY CHIEF

4Q139

TECH

4Q133

TECH

4Q129

TECH

4Q127

TECH

4Q125

LIBRARY/STRG

4Q123 SCRTY

4Q135

OFFICE

4Q141

LVSR

4Q112

SHAFT

SHAFT

SHAFT

09-FP-110

F6

DN DN UPUP

F

STAIR

TR

5Q104A

MALE

5Q117

FEMALE

5Q115

ELEC

5Q109

STAIR

EMER ELEC

5Q107

HK

5Q106

SUPPLIES

5Q100A

NE ANALYST

5Q138

ITAC

5Q140ASST CHIEF

5Q144

SCTRY

5Q116FCLTY PLNR

5Q110

CONF/ CLASSROOM

5Q100

RECEPTION

5Q123

EMRGY PRPDNS

5Q113

DIRECTOR

5Q132

DEPUTY COS

5Q125

SCTRY

5Q137 ASSOC DRCTR

5Q141

COS ADMIN

5Q127

T 5Q132A

DRCTR ADMIN

5Q128

SCTRY

5Q130

NS ADMIN

5Q124NRS SRV

5Q122

PSA

5Q119

SYST RDSN

5Q102

TRAINEES (3)

5Q126

BSNS CNTR

5Q105

ASST DRCTR

5Q114

COS

5Q129

ASSOC ADMIN

5Q143

PSA

5Q139

PSA

5Q135

CONF

5Q136

ASST ADMIN

5Q112

CSTMR SERV

5Q121

PSA

5Q108

COPY

5Q134

CONF

5Q101

SCTRY

5Q142

SCTRY

5Q133

SCTRY

5Q118

SRVG

5Q100B

SHAFT

ELEV

ELEV

ELEV

LOBBY

5Q120

CORR

5Q-C04

CORR

5Q-C01

CORR

5Q-C03

CORR

5Q-C02

SHAFT

CORR

5Q-C03A

BREAK

5Q103 OFFICE

5Q111

FILE/VAULT

5Q145

LVSR

5Q104

SHAFT

SHAFT

09-FP-110

F7

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

09-FP-100

Q

OVERALL FIRE PROTECTION PLANS -

BUILDING Q

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

1/32" = 1'-0"F1 OVERALL PLAN - LEVEL 1_BUILDING Q

1/32" = 1'-0"F2 OVERALL PLAN - LEVEL 2_BUILDING Q

1/32" = 1'-0"F3 OVERALL PLAN - LEVEL 3_BUILDING Q

1/32" = 1'-0"F4 OVERALL PLAN - LEVEL 4_BUILDING Q

1/32" = 1'-0"F5 OVERALL PLAN - LEVEL 5_BUILDING Q

FF

TR

1Q140

EMER ELEC

LVSR

1Q101

SHAFT

SHQ10

F F

SUPPLIES

TELECOM

DEMARCATION

1Q103

TELEPHONE EQUIP

1Q124

FF

F

CORR

1Q-C01

LVSR

1Q101

F

TR

2Q112A

LVSR

2Q112

F

TR

3Q118ALVSR

3Q118

F

TR

4Q112A

LVSR

4Q112

F

TR

5Q104A

ELEC

LVSR

5Q104

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.27.2022

10% BASIS OF DESIGN 07.08.2022

35% BASIS OF DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

-0

_N

O

LA

E H

R M

_C on co ur se

0_ Ar ch P ro du ct io n- R

_d et ac he d.

rv t

JRD MRP

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011

629-22-700 Revisions: Date:

ROOM ALLOCATION LEGEND

EXISTING TO REMAIN - NO FIRE PROTECTION SYSTEM WORK IS ANTICIPATED.

RELOCATED - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED FOR

NEW CEILING CONFIGURATIONS AND OBSTRUCTIONS IN ACCORDANCE WITH

NFPA 13. SPACES NOT PROVIDED DEDICATED ROOM USE AND DESIGNATION

WILL BE PROTECTED AS STORAGE.

NEW LOCATION - EXISTING FIRE SPRINKLERS WILL BE RELOCATED AS NEEDED

FOR NEW CEILING CONFIGURATIONS WITHIN AND AROUND THE NEW TR.

Room Name

LEGEND

LEGACY ROOM NUMBER

SIGNAGE ROOM NUMBER

Q B

C

D

E

F

G

J

H

K

L M

P

N

SH

O

TG

U

N

FI

SH

ER

NORTH

09-FP-110

Q

ENLARGED FIRE PROTECTION

PLANS - BUILDING Q

100% FINAL BID

DOCUMENTS

NOTES:

1. ADDITIONS TO EXISTING FIRE PROTECTION

WET PIPE SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL - EIGHTH

EDITION AND NFPA 13-2022.

2. REFER TO THE ARCHITECTURAL LIFE SAFETY

SHEETS FOR LOCATION AND TYPE OF FIRE

EXTINGUISHERS.

3. EXISTING AND NEW TRS WILL BE PROTECTED

BY THE EXISTING SPRINKLER SYSTEM AND

WILL NOT BE PROVIDED WITH ANY

ADDITIONAL FIRE PROTECTION SUCH AS

FIRE-RATED WALLS, SMOKE DETECTION, OR

GASEOUS SUPPRESSION SYSTEM.

4. EXISTING FIRE SPRINKLERS WILL BE

RELOCATED AS NEEDED FOR NEW CEILING

CONFIGURATIONS AND OBSTRUCTIONS IN

ACCORDANCE WITH NFPA 13.

3/8" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1Q140 / X-MATRIX RM # 1Q129 3/8" = 1'-0"F2 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1Q124 / X-MATRIX RM # 1Q122 3/8" = 1'-0"F3 ENLARGED FIRST FLOOR PLAN - RENOVATION

TR 1Q101 / X-MATRIX RM # 1Q129A

3/8" = 1'-0"F4 ENLARGED SECOND FLOOR PLAN - RENOVATION

TR 2Q112A / X-MATRIX RM # 2Q133A 3/8" = 1'-0"F5 ENLARGED THIRD FLOOR PLAN - RENOVATION

TR 3Q118A / X-MATRIX RM # 3Q134A 3/8" = 1'-0"F6 ENLARGED FOURTH FLOOR PLAN - RENOVATION TR 4Q112A / X-MATRIX RM # 4Q136A 3/8" = 1'-0"F7 ENLARGED FIFTH FLOOR PLAN - RENOVATION

TR 5Q104A / X-MATRIX RM # 5Q137A

KITCHEN

1R005

STORE/ BANK/ ATM

1R018

OFFICE

1R017

ELEC

1R009

STOR

1R015

T 1R011

HALL

1R013

ENTRY

1R010

ENTRY

1R001

STOR

1R008 ELEC

1R002

LIVING

1R007

HALL

1R006

TL STAFF

1R039

TL PATIENT

1R033

WORK STATION/

RECEPTION

1R031

GROUP ROOM

1R036

OFFICE

1R038

EXAM

1R034

WAITING

1R030

CORRIDOR

1R032

OFFICE

1R028

SMALL CONF

1R029

WORK SPACE

1R026

WORK SPACE

1R027

WORK SPACE

1R025

T 1R022

WORK SPACE

1R024

VESTIBULE

1R020

TR

1R021

LOUNGE

1R023

INJECTION

1R037

MEDS

1R035HK

1R040

HK

1R012

MULTI

1R014

DINER

1R016

T 1R004

COPY/FAX

1R025A

10-FP-110

F1

NORTH

KEY PLAN

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

1/ 2'

3' 0' '1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

CONSULTANT

CONSULTANT: A/E:

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

03/17/2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

REVISION 01 07.