2.12 - Drawings 12 of 17 - 00-EG-001 to 02-ED-051.pdf

PDF 19 MB Posted

Attached to
NOLA EHRM Infrastructure Upgrades Construction - New Orleans, LA 629-22-700
Solicitation number
36C77623B0038
Issued by

About this file

This document provides details on a federal contract opportunity for infrastructure upgrades at a Veterans Affairs facility in New Orleans, Louisiana. The solicitation number is 36C77623B0038 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It involves construction services for NOLA EHRM Infrastructure Upgrades at the New Orleans location, as outlined in drawings numbered 00-EG-001 to 02-ED-051 contained in a 19MB PDF file. Responses are due by the date specified in the solicitation. The opportunity type is for an invitation for bids on a firm-fixed-price construction contract to be awarded to the responsible bidder with the lowest price. Small businesses, veteran-owned small businesses, service-disabled veteran-owned small businesses, and HUBZone small businesses are encouraged to respond.

View the file

Other files

File Type Posted
36C77623B0038 0007.pdf PDF
Tech Questions Tracker - NOLA - 8-25-23.pdf PDF
Brand Name JA - NOLA EHRM.pdf PDF
Tech Questions Tracker - NOLA - 8-23-23.pdf PDF
36C77623B0038 0006.pdf PDF
36C77623B0038 0005.pdf PDF
Tech Questions Tracker - NOLA - 8-9-23.pdf PDF
36C77623B0038 0004.pdf PDF
Specs and Drawings - NOLA EHRM - Addendum No 2.pdf PDF
36C77623B0038 0003.pdf PDF
Specs and Drawings - NOLA EHRM - Addendum No 1.pdf PDF
36C77623B0038 0002.pdf PDF
NOLA EHRM Site Visit Sign-In Sheet 19 July 23.pdf PDF
36C77623B0038 0001.pdf PDF
Site Visit Instructions.pdf PDF
2.2 - Drawings 02 of 17 - 000-AJ-601 to 000-AJ-606.pdf PDF
2.4 - Drawings 04 of 17 - 01-AE-011 to 02-AE-052.pdf PDF
2.17 - Drawings 17 of 17 - 04-FP-100 to 11-FP-110.pdf PDF
1 - Specifications.pdf PDF
2.10 - Drawings 10 of 17 - 04-TD-011 to 08-TD-051.pdf PDF
2.13 - Drawings 13 of 17 - 02-EP-011 to 03-EP-071.pdf PDF
2.5 - Drawings 05 of 17 - 02-AC-011 to 03-AE-071.pdf PDF
2.16 - Drawings 16 of 17 - 00-FP-000 to 03-FP-111.pdf PDF
2.11 - Drawings 11 of 17 - 08-TN-011 to 00-TJ-028.pdf PDF
2.9 - Drawings 09 of 17 - 02-TN-011 to 03-TN-071.pdf PDF
IFB 36C77623B0038 - 6-29-23.pdf PDF
6 - Contractor Safety and Environmental Record.docx DOCX document
4 - DBA Wage Rates - Orleans County - 06-16-23.pdf PDF
2.1 - Drawings 01 of 17 - GI001 to GI003.pdf PDF
2.6 - Drawings 06 of 17 - 03-AC-011 to 11-AE-011.pdf PDF
2.8 - Drawings 08 of 17 - 00-TG-001 to 02-TD-052.pdf PDF
2.14 - Drawings 14 of 17 - 04-ED-011 to 10-EP-011.pdf PDF
2.15 - Drawings 15 of 17 - 01-EJ-001 to 00-EJ-026.pdf PDF
2.7 - Drawings 07 of 17 - 00-MK-001 to 10-MJ-011.pdf PDF
3 - HVAC Load Calculations.pdf PDF
5 - Limitations on Subcontracting - Construction.docx DOCX document
2.3 - Drawings 03 of 17 - 00-CG-001 to CJ-A102.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

00-EG-001

LEGEND, ABBREVIATION LIST, AND

GENERAL REQUIREMENTS

MER AJW

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

STAMP

LOCATION

1/ 2'

3' 0'

1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

Fi le

P at h

Revisions: Date:

10% BASIS OF DESIGN 07.08.2022 CONSULTANTS

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

04/25/2023

FULLY

SPRINKLEDSPRINKLED

PROGRAMMING

CONTRACTING

ACTIVITY

CENTAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

100% CONSTRUCTION

DOCUMENTS

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

629-22-700

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

FINAL BID DOCUMENTS 04.25.2023

A, AMP AMPERE

ACP ACCESSIBLE CARD PATH

ADA AMERICAN DISABILITY ACT

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AG ABOVE GROUND

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AL ALUMINUM

BCT BONDING CONDUCTOR FOR TLECOMMUNICATIONS

BKR BREAKER

C CONDUIT

CKT CIRCUIT

CO CONDUIT AND PULL-ROPE ONLY

COMM COMMUNICATION

CTRL CONTROL

CU COPPER

(E) EXISTING

EC, E.C. ELECTRICAL CONTRACTOR

ELEC ELECTRICAL

EM EMERGENCY

EQPT EQUIPMENT

(F) FUTURE

FA FIRE ALARM

FDR FEEDER

G, GND GROUND

GC, G.C. GENERAL CONTRACTOR

HH HANDHOLE

IDF INTERMEDIATE DISTRIBUTION FRAME

J-BOX JUNCTION BOX

LCP LIGHTING CONTROL PANEL

LIU LINE INTERFACE UNIT

LTG LIGHTING

LTS LIGHTS

LV LOW-VOLTAGE

MH MANHOLE

MM MULTI-MODE

N NEUTRAL

NEC NATIONAL ELECTRICAL CODE

OC ON-CENTER

OFCI OWNER-FURNISHED CONTRACTOR-INSTALLED

OFOI OWNER-FURNISHED OWNER-INSTALLED

OL OVERLOAD

P POLE

PB PULLBOX, PUSHBUTTON

PRI PRIMARY

(G) REVISED

REF REFERENCE, REFRIGERATOR

SEC SECONDARY

SM SINGLE-MODE

SOW SCOPE OF WORK

SPECS SPECIFICATIONS

SS STAINLESS STEEL

SW SWITCH

TEL TELEPHONE

TC TELECOMMUNICATION

TGB TELECOMMUNICATIONS BUS BAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

THRU THROUGH

(TYP) TYPICAL

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

VLT VAULT

W WIRE, WATT

WP WEATHERPROOF

(X) EXISTING TO BE REMOVED

ABBREVIATION LIST GENERAL REQUIREMENTS

PRIMARY FIBER TAG. SEE NEW CAMPUS FIBER SCHEDULE

SECONDARY FIBER TAG. SEE NEW CAMPUS FIBER SCHEDULE

(N)MH-#X

xxxP

NEW MANHOLE

xxxS

(E)MH-#X EXISTING MANHOLE

P

S SECONDARY FIBER LOOP

PRIMARY FIBER LOOP

FIBER ROUTING, SUPPORTED WITH J-HOOKS

FIBER/CAT 6A ROUTING IN CONDUIT

J

C

TELECOMMUNICATIONS OUTLET, SUBNUMBER=QUANTITY OF DROPS

CJ CJ CAT 6A ROUTING, SUPPORTED WITH NEW J-HOOKS

C

WAP

TELECOMMUNICATIONS OUTLET, WIRELESS ACCESS POINT

SECURITY SYSTEM CARD READER/KEYPADCR

IS INERGEN SYSTEM SMOKE DETECTOR

IH INERGEN SYSTEM HEAD

SD FIRE ALARM SMOKE DETECTOR

PAGING SYSTEM SPEAKER

CAMERA

EXISTING REQUEST TO EXIT

TR ROOM

FIRE ALARM STROBE LIGHT

XXX-X-XX-PX

RACK NUMBER

PATCH PANEL LOCATON (RU#)

PORT NUMBER

TYPICAL TELECOMM OUTLET IDENTIFIERS:

TELECOMM OUTLET MOUNTED IN FLOOR BOX.

C

21. CONTRACTOR SHALL BE RESPONSIBLE TO TEMPORARILY MOVE AND

RETURN FURNITURE, FIXTURES, AND EQUIPMENT WITHIN SPACES AS

REQUIRED TO COMPLETE EACH DAY'S WORK. THE VA WILL REMOVE,

OR SECURE, PHI, PPI, AND PERSONAL PROPERTY. COORDINATE THIS

WORK WITH THE COR.

22. PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF

EXISTING STRUCTURE AND FINISHES TO PREVENT ANY DAMAGE OF

EXISTING FINISHES. ANY ACCIDENTAL DAMAGE INCURRED TO

EXISTING CONDITIONS WILL BE THE RESPONSIBILITY OF THE

CONTRACTOR TO REPAIR OR CORRECT.

GENERAL REQUIREMENTS - CONT.

TELECOMMUNICATIONS OUTLET, VOICE ONLY

EQUIPMENT CALLOUT.

EQUIPMENT CONNECTION, SEE EQUIPMENT CONNECTION

SCHEDULES FOR SPECIFIC REQUIREMENTS.

HOME RUN

AHU-01

SPECIAL PURPOSE RECEPTACLE

4 PLEX RECEPTACLE

LIGHTING OR POWER PANEL

A

A

A

CONDUIT CONCEALED IN GROUND OR FLOOR

CONDUIT CONCEALED IN CEILING OR WALL

FLUSH FLOOR BOX WITH DEVICES AS INDICATED

J CODE SIZED JUNCTION BOX WITH COVER PLATE

DUPLEX RECEPTACLE, ISOLATED GROUND TYPE,

A = ABOVE COUNTER, E = EMERGENCY

DUPLEX RECEPTACLE, A = ABOVE COUNTER

DUPLEX RECEPTACLE, GFCI TYPE, A = ABOVE

COUNTER, E = EMERGENCY, IG = ISOLATED GROUND.

CONDUIT DOWN

MECHANICAL VAV BOX, SEE MECHANICAL EQUIPMENT

SCHEDULES FOR SPECIFIC REQUIREMENTS

A 4 PLEX RECEPTACLE, GFCI TYPE, A = ABOVE

COUNTER, E = EMERGENCY, IG = ISOLATED GROUND.

CONDUIT UP

F FUSED DISCONNECT SWITCH

DISCONNECT SWITCH

SINGLE-POLE SWITCH

LIGHT FIXTURE, SEE SCHEDULE FOR TYPE

LIGHT FIXTURE, SEE SCHEDULE FOR TYPE

LIGHT FIXTURE, SHADING INDICATES EMERGENCY BATTERY BACKUP

EXIT LIGHT, SHADING INDICATES SIGN DIRECTION

WALL MOUNTED LIGHT, SEE SCHEDULE FOR TYPE

EXIT LIGHT WITH ARROWS, SHADING INDICATES SIGN DIRECTION

OC

WALL MOUNT OCCUPANCY SENSOR SWITCH

LV LOW-VOLTAGE SWITCH

1. PROVIDE COMPLETE WORK FOR REQUIREMENTS AS DESCRIBED

ON LEGEND.

2. ALL FLUSH MOUNT EQUIPMENT, CABINETS, AND PANELBOARDS

SHALL HAVE FACTORY TYPE FLUSH MOUNT TRIM KIT FOR

COMPLETE INSTALLATION.

3. PROVIDE ALL MATERIAL AND LABOR RELATED TO THE

INSTALLATION OF ELECTRICAL DEVICES PENETRATING INTO OR

THROUGH FIRE RATED WALLS, FLOORS, OR CEILINGS SUCH THAT

THE FIRE RATING OF THE WALL IS MAINTAINED.

4. DO NOT TAKE MEASUREMENTS FROM PLANS FOR DEVICE

LOCATIONS. FIELD VERIFY EXACT DEVICE, EQUIPMENT

LOCATIONS, AND MOUNTING HEIGHTS WITH OWNER'S

REPRESENTATIVE FOR PROPER INSTALLATION.

5. BRANCH CIRCUIT HOME RUNS ARE NOT INDICATED WITH NUMBER

OF CONDUCTORS/ WIRES. PROVIDE ALL BRANCH CIRCUIT

CONDUCTORS/ WIRES AS REQUIRED FOR COMPLETE OPERATION

OF ALL DEVICES AND EQUIPMENT INDICATED. PROVIDE

INDIVIDUAL NEUTRALS FOR EACH CIRCUIT.

6. REFER TO EQUIPMENT SCHEDULES FOR WIRING REQUIREMENTS

NOT INDICATED ON POWER PLANS.

7. PROVIDE ALL WIRING TO PANELS AND POWER DISTRIBUTION

EQUIPMENT IN ACCORDANCE WITH ONE-LINE POWER DIAGRAM.

8. INCLUDE COST OF PROVIDING ALL ELECTRICAL CONNECTIONS AS

REQUIRED FOR FULL OPERATION OF ALL OWNER FURNISHED,

CONTRACTOR INSTALLED EQUIPMENT. SEE ARCHITECTURAL

DRAWINGS TO VERIFY LOCATIONS.

9. COORDINATE PAINTING WORK OF ELECTRICAL ITEMS WITH

GENERAL CONTRACTOR. SEE PAINTING SPECIFICATIONS FOR

REQUIREMENTS.

10. PROVIDE SEPARATE NEUTRALS FOR ALL BRANCH CIRCUITS.

11. WIRING SYSTEMS SHALL BE CONCEALED WHERE POSSIBLE,

EXCEPT IN ELECTRICAL ROOM, MECHANICAL ROOM, AND UTILITY

AREAS, OR AS OTHERWISE NOTED.

12. PROVIDE SURFACE METAL RACEWAY AS WIRING METHOD WHERE

OUTLETS AND WIRING CANNOT BE CONCEALED.

13. EXTERIOR MOUNTED ELECTRICAL DEVICES (SUCH AS

DISCONNECT SWITCH, STARTER, SPEAKER, FIRE ALARM HORN,

ETC.) AND COVERS SHALL BE NEMA-3R WEATHERPROOF RATED.

14. PROVIDE CONDUIT AND WIRE FROM ALL HVAC UNITS 2000 CFM OR

ABOVE TO FIRE ALARM PANEL FOR HVAC UNIT CONTROL.

CONDUIT AND WIRE MAY NOT BE INDICATED IN ELECTRICAL

DRAWINGS.

15. PROVIDE TEMPORARY POWER FOR CONSTRUCTION. TEMPORARY

POWER MAY BE IN THE FORM OF PORTABLE GENERATOR SET;

CONNECTION TO UTILITIES COMPANY'S POWER POLE OR

EXISTING FACILITY'S ELECTRICAL SYSTEM.

16. VERIFY WITH CABINET INSTALLER FOR ALL CABINET LOCATIONS,

DIMENSIONS, AND COUNTER HEIGHTS PRIOR TO OUTLET

ROUGH-IN. OUTLETS LOCATED ABOVE COUNTER SHALL BE

INSTALLED TO CENTERLINE ABOVE COUNTERTOP BACKSPLASH,

AS DIRECTED OR INDICATED IN SPECIFICATIONS. VERIFY HEIGHT

WITH OWNER'S REPRESENTATIVE OF ANY LOCATION THAT

CANNOT ACCOMMODATE MOUNTING HEIGHT.

17. INSTALLATION OF UNDERGROUND WIRING SYSTEMS SHALL

INCLUDE EXCAVATION, CUTTING, PATCHING, BACKFILL, AND

COMPACTION. DO NOT CUT OR DAMAGE ANY EXISTING UTILITIES,

STRUCTURAL MEMBERS, OR BUILDING FOUNDATIONS. VERIFY

EXISTING CONDITIONS PRIOR TO EXCAVATION WORK. INCLUDE

COST FOR UNDERGROUND LOCATOR SERVICE TO IDENTIFY

LOCATIONS OF EXISTING COMPONENTS. HAND EXCAVATE IN

LOCATIONS WHERE EXISTING UNDERGROUND COMPONENTS ARE

SUBJECT TO DAMAGE. REPAIR DAMAGE TO EXISTING UTILITIES

OR BUILDING STRUCTURE TO OWNER'S SATISFACTION AT THE

CONTRACTORS EXPENSE.

18. ALL ONE-LINE DIAGRAMS AND RACEWAY ROUTING ARE

SCHEMATIC AND DO NOT SHOW EXACT PHYSICAL ARRANGEMENT

OF EQUIPMENT ON DRAWINGS. ALL JUNCTION BOXES, AND

PULLBOXES SHOWN ARE MINIMUM REQUIREMENTS. PROVIDE

FITTINGS AND PULLBOXES OF ADEQUATE SIZE IN RACEWAY

SYSTEMS WHEREVER NECESSARY OR REQUIRED BY NATIONAL

ELECTRICAL CODE. PROVIDE EXPANSION JOINT FITTINGS FOR

RACEWAY PASSING THROUGH NEW OR EXISTING EXPANSION

JOINTS INSTALLED BETWEEN BUILDINGS. VERIFY EXACT

LOCATIONS AND DETAILS OF EXPANSION JOINTS PRIOR TO WORK.

COORDINATE ALL RACEWAY ROUTING, PULLBOXES, AND

EQUIPMENT LOCATIONS WITH OTHER TRADES TO AVOID

CONFLICTS OF EQUIPMENT INSTALLATIONS. ALL EMPTY

CONDUITS SHALL HAVE PULL WIRES.

19. CONDUIT OR OTHER ELECTRICAL COMPONENTS SHALL NOT BE

INSTALLED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY

INDICATED ON THE DRAWINGS OR APPROVED BY STRUCTURAL

ENGINEER.

20. PROVIDE ELECTRICAL CONNECTION FOR ALL FAN SPEED

SWITCHES. COORDINATE LOCATION OF CONNECTIONS WITH

MECHANICAL CONTRACTOR.

FEEDER SCHEDULE

1ɸ, 2W+G (3 WIRES TOTAL) 3ɸ, 4W+G (5 WIRES TOTAL)

CKT ID RACEWAY/WIRE CKT

AMPS CKT ID CONDUIT AND WIRE CKT

AMPS

[12-20] 3/4"C, 2#12, #12G 20 [34-20] 3/4"C, 4#12, #12G 20

[12-30] 3/4"C, 2#10, #10G 30 [34-30] 3/4"C, 4#10, #10G 30 [12-40] 3/4"C, 2#8, #10G 40 [34-40] 1"C, 4#8, #10G 40 [12-50] 3/4"C, 2#6, #10G 50 [34-50] 1"C, 4#6, #10G 50 [12-60] 1"C, 2#4, #10G 60 [34-60] 1-1/4"C, 4#4, #10G 60 [12-70] 1"C, 2#4, #8G 70 [34-70] 1-1/4"C, 4#4, #8G 70 [12-80] 1-1/4"C, 2#2, #8G 80 [34-80] 1-1/2"C, 4#2, #8G 80 [12-90] 1-1/4"C, 2#2, #8G 90 [34-90] 1-1/2"C, 4#2, #8G 90

[12-100] 1-1/4"C, 2#1, #8G 100 [34-100] 2"C, 4#1, #8G 100 [12-125] 1-1/4"C, 2#1, #6G 125 [34-125] 2"C, 4#1, #6G 125 [12-150] 1-1/4"C, 2#1/0, #6G 150 [34-150] 2"C, 4#1/0, #6G 150 [12-175] 1-1/2"C, 2#2/0, #6G 175 [34-175] 2"C, 4#2/0, #6G 175 [12-200] 1-1/2"C, 2#3/0, #6G 200 [34-200] 2"C, 4#3/0, #6G 200 [12-225] 2"C, 2#4/0, #4G 225 [34-225] 2-1/2"C, 4#4/0, #4G 225

[12-250] 2-1/2"C, 2-250KCM, #4G 250 [34-250] 3"C, 4-250KCM, #4G 250

[12-300] 2-1/2"C, 2-350KCM, #4G 300 [34-300] 3"C, 4-350KCM, #4G 300

[12-400] 2-SETS [2"C, 2#3/0, #3G] 400 [34-400] 2-SETS [2-1/2"C, 4#3/0, #3G] 400

3ɸ, 3W+G (4 WIRES TOTAL) [34-500] 2-SETS [3"C, 4-250KCM, #2G] 500

CKT ID CONDUIT AND WIRE CKT

AMPS

[34-600] 2-SETS [3"C, 4-350KCM, #1G] 600

[33-20] 3/4"C, 3#12, #12G 20 [34-700] 2-SETS [4"C, 4-500KCM, #1/0G] 700

[33-30] 3/4"C, 3#10, #10G 30 [34-800] 3-SETS [3"C, 4-300KCM, #1/0G] 800

[33-40] 3/4"C, 3#8, #10G 40 [34-1000] 3-SETS [4"C, 4-500KCM, #2/0G] 1000

[33-50] 1"C, 3#6, #10G 50 [34-1200] 4-SETS [3"C, 4-350KCM, #3/0G] 1200

[33-60] 1"C, 3#4, #10G 60 [34-1600] 4-SETS [4"C, 4-600KCM, #4/0G] 1600

[33-70] 1-1/4"C, 3#4, #8G 70 [34-2000] 5-SETS [4"C, 4-600KCM, 250KCM G] 2000

[33-80] 1-1/4"C, 3#2, #8G 80 480VΔ, 3ɸ, TRANSFORMER PRIMARY (3W+G)

[33-90] 1-1/4"C, 3#2, #8G 90 CKT ID CONDUIT AND WIRE CKT

AMPS

[33-100] 1-1/2"C, 3#1, #8G 100 [30H] 1"C, 3#4, #10G 60 [33-125] 1-1/2"C, 3#1, #6G 125 [45H] 1-1/2"C, 3#1, #8G 100 [33-150] 1-1/2"C, 3#1/0, #6G 150 [75H] 1-1/2"C, 3#1/0, #6G 150 [33-175] 2"C, 3#2/0, #6G 175 [112H] 2"C, 3#3/0, #6G 200

[33-200] 2"C, 3#3/0, #6G 200 [150H] 2-1/2"C, 3-250KCM, #4G 250

[33-225] 2"C, 3#4/0, #4G 225 [225H] 2-SETS [2"C, 3#3/0, #3G] 400

[33-250] 2-1/2"C, 3-250KCM, #4G 250 [300H] 2-SETS [3"C, 3-350KCM, #1G] 600

[33-300] 2-1/2"C, 3-350KCM, #4G 300 [500H] 3-SETS [3"C, 3-300KCM, #1/0G] 800

[33-400] 2-SETS [2"C, 3#3/0, #3G] 400 [15H] 3/4"C, 3#10, #10G 30

[33-500] 2-SETS [2-1/2"C, 3-250KCM, #2G] 500 208Y/120V, 3ɸ, TRANSFORMER SECONDARY (4W+G)

[33-600] 2-SETS [3"C, 3-350KCM, #1G] 600 CKT ID CONDUIT AND WIRE CKT

AMPS

[33-700] 2-SETS [3"C, 3-500KCM, #1/0G] 700 [30L] 2"C, 4#1, #6G 100

[33-800] 3-SETS [3"C, 3-300KCM, #1/0G] 800 [45L] 2"C, 4#1/0, #6G 150

[33-10000] 3-SETS [3"C, 3-500KCM, #2/0G] 1000 [75L] 2-1/2"C, 4#4/0, #2G 225

[33-1200] 4-SETS [3"C, 3-350KCM, #3/0G] 1200 [112L] 2-SETS [2-1/2"C, 4#3/0, #1/0G] 400

[33-1600] 4-SETS [4"C, 3-600KCM, #4/0G] 1600 [150L] 2-SETS [3"C, 4-350KCM, #2/0G] 600 [33-2000] 5-SETS [4"C, 3-600KCM, 250KCM G] 2000 [225L] 3-SETS [3"C, 4-300KCM, #2/0G] 800

[300L] 3-SETS [4"C, 4-500KCM, #3/0G] 1000

[500L] 4-SETS [4"C, 4-600KCM, #4/0G] 1600

[750L] 6-SETS [4"C, 4-600KCM, 250KCM G] 2500

[15L] 1-1/4"C, 4#4, #10G 60

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

SYMBOL LEGEND

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text S

AutoCAD SHX Text

REX

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

SYMBOL LEGEND

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

UP

DNDN

UP

DN

UPDNDNDN

UP

DN

UP

UP

DN

DN

UP

UP

UP

UP

DN DN

UP UP

TV

N

C L

CL

CL

UP

DN

UP

DN

UP

DN

DN

UP

CL

CL

CL

DN

UP

DN

DN

UPDN

UP

UP

UPDN

DN

DN

FD

FD

AP

DN

UP

CLCL

CL

UP

DN

DN

DN

UP

DN

UP

DNUP

FD FDFD FD

FD

FDFD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD FD FD FD FD FD FD

UP

FD

FD

FD

FD

FD

FD

FD

UP

FDFD

UP

UP

DN

DN

UP

DNUPUP

DN

DN

UPDNUP

UP

DNUPUP

DN

UP

DNDNDNDN

DN

DN

UP

DN

UP

FD

DN

UP

DN

UP

DN

UPUP

BLDG 10

AP

BLDG 1BLDG 9

BLDG 4 BLDG 3

BLDG 5

BLDG 6

BLDG 8

BLDG 7

BLDG 2

BLDG 11

Q D

E

F

G

B

P

K

M

N

J

H

L

C

(E)MH20

(E)EMH14

(E)MH21 (E)MH22

(E)MH25

(E)MH24

(E)MH23

(E)MH19

(E)EMH13(E)EMH12

(E)MH27

(E)EMH16

(E)MH26

(E)MH16

(E)MH17

(E)EMH11

(E)MH15

(E)EMH10

(E)EMH15

(E)EMH8

(E)MH14

(E)MH4

(E)EMH7

(E)MH13

(E)EMH9

(E)MH12

(E)EMH4

(E)EMH1

(E)EMH2

(E)MH5

(E)EMH6

(E)MH8

(E)MH9

(E)MH7

(E)EMH5

(E)UMH4

(E)UMH3

(E)UMH2

(E)UMH1

(E)MH2

(E)MH3

(E)MH6

(E)MH1

(E)UTILITY

SERVICE

ENTRANCE

(E)MH18

(E)UTILITY

SERVICE

ENTRANCE

(E)MH11

(E)MH10 (E)MH10

(E)EMH3

UP

DNDN

UP

DN

UPDNDNDN

UP

DN

UP

UP

DN

DN

UP

UP

UP

UP

DN DN

UP UP

TV

N

C L

CL

CL

UP

DN

UP

DN

UP

DN

DN

UP

CL

CL

CL

DN

UP

DN

DN

UPDN

UP

UP

UPDN

DN

DN

FD

FD

AP

DN

UP

CLCL

CL

UP

DN

DN

DN

UP

DN

UP

DNUP

FD FDFD FD

FD

FDFD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD FD FD FD FD FD FD

UP

FD

FD

FD

FD

FD

FD

FD

UP

FDFD

UP

UP

DN

DN

UP

DNUPUP

DN

DN

UPDNUP

UP

DNUPUP

DN

UP

DNDNDNDN

DN

DN

UP

DN

UP

FD

DN

UP

DN

UP

DN

UPUP

BLDG 10

AP

BLDG 1BLDG 9

BLDG 4 BLDG 3

BLDG 5

BLDG 6

BLDG 8

BLDG 7

BLDG 2

BLDG 11

Q D

E

F

G

B

P

K

M

N

J

H

L

C

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

STAMP

LOCATION

1/ 2'

3' 0'

1'

1/ 2' 0'

1' 4'

4' 8'

8' 8'

4' 2'

2'

1/ 8' 0'

1/ 0'

1/ 4' 0'

1' 2'

1' 1/ 2'

2'

1' 0'

3/ 8' 0'

1'

2' 4'

1/ 2' 0'

1/ 2'

1' 3'

6' 0'

1/ 4"

1/ 2"

3/ 0'

8'

4' 4'

Fi le

P at h

Revisions: Date:

10% BASIS OF DESIGN 07.08.2022 CONSULTANTS

TERPconsulting Fire + Life Safety 14241 E. 4th Avenue, Aurora CO, 80011 GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

04/25/2023

FULLY

SPRINKLEDSPRINKLED

PROGRAMMING

CONTRACTING

ACTIVITY

CENTAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

100% CONSTRUCTION

DOCUMENTS

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

629-22-700

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

FINAL BID DOCUMENTS 04.25.2023

NOT USED

1. FOR REFERENCE ONLY

D1

DEMOLITION PLAN NOTES

GENERAL NOTES

THIS DRAWING WAS PRODUCED FROM ORIGINAL

AS-BUILT DRAWINGS AND FIELD OBSERVATIONS, AND

MAY NOT REPRESENT AN ACCURATE AS-BUILT

CONDITION. DISCREPANCIES MAY BE ENCOUNTERED,

AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO

FIELD VERIFY ALL CONDITIONS.

SCALE: NTS

0 KEY PLAN

00-ES-000

OVERALL EXISTING ELECTRICAL SITE

PLAN

MER AJW

SCALE:

OVERALL EXISTING ELECTRICAL SITE PLAN

1/64"=1'-0"

30' 60'

THIS DRAWING WAS PRODUCED FROM ORIGINAL

AS-BUILT DRAWINGS AND FIELD OBSERVATIONS, AND

MAY NOT REPRESENT AN ACCURATE AS-BUILT

CONDITION. DISCREPANCIES MAY BE ENCOUNTERED,

AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO

FIELD VERIFY ALL CONDITIONS.

MONITOR

1C163

CHF (OC)

1C220

A CHF (OC)

1C222

SECY (OC)

1B208

ITAC (OC)

1B141

CS (OC)

1B139

OFF CHF (FS)

1B151

BA (OC)

1C224

ADM (OC)

1B140

MA ASST (OC)

1C226

CUB (FS)

1B175D

CUB (FS)

1B175C

CUB (FS)

1B192A

CUB (FS)

1B192B

MEDIA (FS)

1B154

OFF A CHF (FS)

1B152

CUB CST SRV (FS)

1B150

CUB (FS)

1B192C

SEC/WAIT (FS)

1B153

CUB (CD)

1B173C

CUB (CD)

1B171CCUB (CD)

1B173D

CHF (CD)

1B159

A CHF (CD)

1B158

LD CODE (CD)

1B162

LD CODE (CD)

1B161

CUB (CD)

1B172B

CUB (CD)

1B172F

CUB (CD)

1B170A

CUB (CD)

1B170C

CUB (CD)

1B173B

CUB (CD)

1B171D

CUB (CD)

1B173A

CUB (CD)

1B170D

CUB (CD)

1B170B

CUB (CD)

1B171A

CUB (CD)

1B172C

CUB (CD)

1B172D

CUB (CD)

1B172E

SECY (CD)

1B160

WORK (CD)

1B157

A CHF (HIM)

1B143

CHF (HIM)

1B144

SECY (HIM)

1B201

CUB (HIM)

1B193B

CUB (HIM)

1B195D

CUB (HIM)

1B192F

CUB (HIM)

1B192D

CUB (HIM)

1B192E

WAIT/ROI (HIM)

1B200

CHF (WA)

1B137

A CHF (WA)

1B138

SECY (WA)

1B134

OP CTR (WA)

1B130

OFF SPV (WA)

1B132

A CHF (HE)

1C135

CUB (MCCF)

1B174A

CUB (MCCF)

1B175A

CUB (MCCF)

1B174B

CUB (MCCF)

1B175E

CUB (MCCF)

1B175B

BUS CTR (HE)

1C125

CUB (MCCF)

1B174D

T

1B176

CHIEF

1C203

A CHF

1C201

TECH

1C196A

WORKROOM

1C205

CUB (MCCF)

1B174C

SUPV (MCCF)

1B155

IP SUP (HE)

1C134

IP CLRK (HE)

1C124

SECY (MCCF)

1C132B

CUB PSA (HE)

1C130B

CUB PSA (HE)

1C130A

CUB PSA (HE)

1C130C

ADMIS (HE)

1C122

CUB ELIG (HE)

1C131

CUB PSA (HE)

1C132D

A CHF

1C199

ACCNT CHF

1C214 ACCNT CHF

1C213

ACCNT CHF

1C212

ACCNT CHF

1C211

COMP AUDITOR

1C215

COMP OFFICER

1C216

BDGT

1C192E

BDGT

1C192B

BDGT

1C192A

BDGT

1C192F

BDGT

1C217A

TECH

1C192D

TECH

1C192C

TECH

1C196F

TECH

1C200A

SECRY

1C194B

TECH

1C194A TECH

1C196ETECH

1C194F

TECH

1C217B

TECH

1C194D

TECH

1C196C

TECH

1C196D

TECH

1C194E

AUDITOR

1C193

AUDITOR

1C197

AUDITOR

1C195

RECPT

1C190A

T

1C186

T

1C219

AUDITOR

1C191

BREAK

1C210

SERVICE BAY

1C114

EC

1C223

EC

1B180

SERVICE BAY

1B123

TR

1C114C

1A104B

NORM ELEC

1C114A

DETAILS (HE)

1C136

WAIT (OC)

1C227

CUB CS (HE)

1C132C

STOR (HE)

1C126

EMER ELEC

1C114B

TR

1B123D

1B114A

EMER ELEC

1B123A

NORM ELEC

1B123B

SEC/WAIT

1B106

CONF/CLASS (OC)

1B135

T

1B204

CUB (FS)

1B191A

CUB (CD)

1B171B

T

1B178

TR

1C228

WAIT

1C190

SERV ELEV LOBB

1B120

PUB ELEV LOBBY

1B100

WORKROOM (HIM)

1B194

CUB (CD)

1B173E

CLINICAL SUPER (NSA)

1B102

CLINICAL SUPER (NSA)

1B103

T

1C141

T

1C143

WC

1C144

LOUNGE

1C145

RECPT

1C137

PANTRY

1C146

CHAPLAIN

1B105

CHAPLAIN

1B107

CHAPLAIN

1B109

EUCHARIST

1B111

QUIET

1B116

T

1B108

T

1B110

STOR

1B112

HK

1B114

STOR/FILE (FS)

1B190

ISO (HIM)

1B203

PV (HIM)

1B142

STOR

1C196B

SLEEP

1C166

T/S

1C166A

ST

1C181

T/S

1C179A

T/S

1C174A

SLEEP

1C174

SLEEP

1C165

SLEEP

1C175

T/S

1C165A

T/S

1C164A

SLEEP

1C164

SLEEP

1C177

T/S

1C177A

T/S

1C175A

SLEEP

1C179

SLEEP

1C162

T/S

1C162A

WAIT

1C160

CC

1C178

CONF

1C185

RETAIL AREA

1C101

VESTIBULE

1C150

ADMIS (HE)

1C123

STOR

1C221

WAIT

1C132A

POLY

1C161

EQUIP

1C168 T

1C160A

BREAK

1C169

ELEV

BS-1

FUTURE ELEV

BS-2

ELEV

BS-4

ELEV

BS-3

STAIR

STB-1

CORR

1B-C01 CORR

1B-C02

CORR

1B-C03

AISLE

1B-C08

CORR

1B-C07

CORR

1B-C05

CORR

1B-C06

AISLE

1B-C09

AISLE

1B-C10

AISLE

1B-C11

AISLE

1B-C12

AISLE

1B-C13

AISLE

1B-C14

AISLE

1B-C15

AISLE

1B-C16

AISLE

1C-C01A

AISLE

1C-C01B

AISLE

1C-C01C

AISLE

1C-C01D

AISLE

1C-C03

AISLE

1C-C04

AISLE

1C-C04AAISLE

1C-C04B

AISLE

1C-C05

AISLE

1C-C06

AISLE

1C-C07

AISLE

1C-C12

AISLE

1C-C11

AISLE

1C-C09

AISLE

1C-C08

AISLE

1C-C08A

SECY (HE)

1B172A

STOR

1C133

1C100

HK

1C139

VESTIBULE

1B121

CORR

1C101-K

CORR

1B-C02A

HK

1B206

NOUR

1C180

AISLE

1C-C010

AISLE

1C-C07A

SECURITY

1C114D

1C104A

UNASSIGNED

1B174G

CUB (HIM)

1B192H

SECURITY

1B123C

CORR

1C-C02

SECY/WAIT (OC)

1C225

TECH

1C196G

RETAIL PREP

1C101A

CORR

1B-C04

AISLE

1B-C04A

AISLE

1C-C00

CORR

1C-C01

CLEAN

1C167

SOILED

1C176

ASR

1B113

CONNECTOR HALL

1B115A

TR

1B179

1B145

IT/LVSR

1C190B

1C150A

CHAPEL

1B115

CLOSET

1B115B

01-ED-011

01-ED-011

(E) PNL 'LC143'

(E) PNL 'P1411'

(E) PNL 'R12113B' (E) PNL 'R12113A'

(E) PNL 'MGAP'

PNL 'R12123B'(E) PNL 'R12123A'

01-ED-011

(E) PNL 'ECR1211'

(E) PNL 'LC1411'

(E) PNL 'L1411'

(E) PNL 'D1411'

(E) XFMR 'T6'

(E) PNL 'D1211'

(E) PNL 'R12112A'

(E) PNL 'R12112B'

(E) PNL 'R12111A'

(E) PNL 'R12111B'

(E) PNL 'ECR1212'

(E) PNL 'LC1412'

(E) PNL 'L1412'

(E) PNL 'D1412'

(E) XFMR 'T6'

(E) PNL 'D1212'

(E) PNL 'R12122B'

(E) PNL 'R12122A'

(E) PNL 'R12121B'

(E) PNL 'R12121A'

01-ED-011

(E) PNL 'P1412'

(E) PNL 'EIT1211'

(X)EIT1211-23

(X)EIT1211-21

(X)EIT1211-19

(X)EIT1211-17

(X)EIT1211-15

(X)EIT1211-13

(X)EIT1211-1

(X)EIT1211-35

(X)EIT1211-33

(X)EIT1211-31

(X)EIT1211-29

(X)EIT1211-27

(X)EIT1211-25

(E)UNLABELED

(E)UNLABELED

(E)UNLABELED

MOUNTED ON

CABLE TRAY

(TYP.)

(X)EIT1211-9,114

TR

1B123D

1B114A

(E) PNL 'EIT1212'

(X)EIT1212-29

(X)EIT1212-27

(X)EIT1212-25

(X)EIT1212-23

(X)EIT1212-21

(X)EIT1212-19

(X)EIT1212-17

(X)EIT1212-15

(X)EIT1212-13

(E)UNLABELED

(E)UNLABELED

(E)UNLABELED

(E)EIT1212-24

2 3

MOUNTED ON

CABLE TRAY

(TYP.)

(X)EIT1212-1,3

TR

1C114C

1A104B

(E) PNL 'EIT1214'

(X)EIT1214-6

(X)EIT1214-7

(X)EIT1214-8

(X)EIT1214-1

MOUNTED ON

CABLE TRAY

(TYP.)

(E)UNLABELED

(E)UNLABELED

IT/LVSR

1C190B

1C150A

(X)EIT1214-9,11

(X)UNLABELED

(X)UNLABELED

(X)UNLABELED

MOUNTED ON

CABLE TRAY

(TYP.)

(X)EIT1213-2,4 4

TR

1B179

1B145 (E) PNL 'EIT1213' 5

NORTH

KEY PLAN

KEY PLAN

Q B

C

D

E

F

G

J

H

K

L M

P

N

S H

O T

G U

N

F

IS

H E

R

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANTS

FOR OFFICIAL USE ONLY (FOUO)

04-25-2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

10% BASIS OF DESIGN 07.08.2022

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023 GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

TERP consulting Fire + Life Safety

14241 E. 4th Avenue, Suite 5-230 Aurora CO, 80011

FINAL BID DOCUMENTS 04.25.2023

A u to d e s k D o c s /2

-0

N e w O rl e a n s

E H

R M

/2 -0

N

O L

A E

H R

M

C O

N C

O U

R S

E

E le c I n t-

R

.r v t

01-ED-011

OVERALL FIRST FLOOR POWER

DEMOLITION PLAN - BLDG. 01

MER AJW

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

FINAL BID DOCUMENTS 629-22-700

3/32" = 1'-0"1

BLDG. 01 POWER OVERALL DEMOLITION PLAN - LEVEL 1

1/4" = 1'-0"4

ENLARGED POWER DEMO PLAN - TR 1B114A

1/4" = 1'-0"3

ENLARGED POWER DEMO PLAN - TR 1A104B

1/4" = 1'-0"2

ENLARGED POWER DEMO PLAN - LVSR 1C150A

PLAN NOTES

1 EXISTING ELECTRICAL RECEPTACLES TO BE REMOVED. CONTRACTOR TO REMOVE

EXISTING CONDUIT AND CONDUCTORS BACK TO SOURCE.

2 EXISTING ELECTRICAL RECEPTACLE TO REMAIN.

3 EXISTING ELECTRICAL PANEL TO REMAIN.

4 EXISTING UPS TO BE REMOVED. CONTRACTOR TO REMOVE EXISTING CONDUIT,

CONDUCTORS, AND JUNCTION BOXES BACK TO SOURCE.

5 EXISTING ELECTRICAL PANEL TO BE RELOCATED. REROUTE EXISTING CONDUIT AND

CONDUCTORS TO NEW LOCATION ON SHEET 01-EP-011

DEMOLITION GENERAL NOTES

1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO ASCERTAIN THE

CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES WITH THE COR PRIOR TO

INITIATION OF WORK. NO DEMOLITION SHALL OCCUR UNTIL AFTER THE NEW OR

REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR CUT OVER.

3. DISPOSE OF REMOVED EQUIPMENT UNLESS DIRECTED TO DO SO OTHERWISE BY OWNER.

4. COORDINATE EXTENT AND SCOPE OF DEMOLITION IN ALL SPACES WITH ARCHITECTURAL.

5. CONTRACTOR SHALL BE RESPONSIBLE TO TEMPORARILY MOVE AND RETURN FURNITURE,

FIXTURES, AND EQUIPMENT WITHIN SPACES AS REQUIRED TO COMPLETE EACH DAY'S

WORK. THE VA WILL REMOVE, OR SECURE, PHI, PPI, AND PERSONAL PROPERTY.

COORDINATE THIS WORK WITH THE COR.

6. PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF EXISTING STRUCTURE

AND FINISHES TO PREVENT ANY DAMAGE OF EXISTING FINISHES. ANY ACCIDENTAL DAMAGE

INCURRED TO EXISTING CONDITIONS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR

TO REPAIR OR CORRECT.

7. CONTRACTOR SHALL CONFIRM EXISTING CIRCUITING TO UPS EQUIPMENT AND RACK

MOUNTED RECEPTACLES IN EXISTING TELECOMMUNICATION ROOMS PRIOR TO

DEMOLITION. ANY EXISTING FEEDERS NOT SUPPLYING UPS EQUIPMENT OR RACK MOUNTED

RECEPTACLES TO REMAIN.

8. EXISTING RACK MOUNTED RECEPTACLES BEING UTILIZED TO REMAIN. CONTRACTOR TO

VERIFY RECEPTACLE UTLIZATION PRIOR TO DEMOLITION.

1/4" = 1'-0"5

ENLARGED POWER DEMO PLAN - LVSR 1B145

Revisions: Date:

MAY NOT REPRESENT AN ACCURATE AS-BUILT

CONDITION. DISCREPANCIES MAY BE ENCOUNTERED,

AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO

FIELD VERIFY ALL CONDITIONS.

NORTH

KEY PLAN

KEY PLAN

Q B

C

D

E

F

G

J

H

K

L M

P

N

S H

O T

G U

N

F

IS

H E

R

CLEAN

2B120

COMM CENTER

2B118

CONSULT

2C126

NOUR

2C108

TR

2C114C

2C114B

RETHERM

2B101

CONSULT

2C124

HK

2B112

TR

2B123D

2B110A

STOR/EQUIP

2B103

CLEAN

2B155D

2B159

CHUTE

2B105

COMM CENTER

2C104

MED ROOM

2B155B

SOILED

2B155E

2B161

SERVICE BAY

2B123

SERVICE BAY

2C114

OFF PHY/CON/NRS

2C120

HOUSE STAFF

2B104

PHARMACIST

2C118

ST

2C119

SOC WRK

2C121

HK

2C122

SOC WRK

2C123

PHY/CON/NRS

2C112

STAFF LOUNGE

2B102

STAFF LOCKER

2B126

DIET

2C116

NOUR

2B122

HEAD NURSE

2C113

CARE PROVIDER

2C111

STOR/EQUIP

2C103

HEAD NURSE

2B116

EC

2B153

NORM ELEC

2C114A

EMER ELEC

2C114B

NORM ELEC

2B123B

EMER ELEC

2B123A

SOILED

2C152B

2C152

CLEAN

2C106

EC

2C154

PATIENT

2B146

PATIENT NEG

2B143

PATIENT

2B145

PATIENT POS

2B165

PATIENT

2B151

PATIENT

2B152

PATIENT

2B157

PATIENT

2B159

PATIENT

2B161

PATIENT

2B163

PATIENT

2B164

PATIENT

2B144 PATIENT

2B148

PATIENT

2B150 PATIENT

2B154

PATIENT

2B156 PATIENT

2B158

PATIENT

2B160

PATIENT

2B162

PATIENT

2C145

PATIENT

2C151

PATIENT

2C147

PATIENT

2C157

PATIENT

2C159

PATIENT

2C161

PATIENT

2C163

PATIENT

2C155

PATIENT

2C149

PATIENT

2C160

PATIENT POS

2C165PATIENT

2C141

PATIENT

2C144

PATIENT

2C146 PATIENT

2C148

PATIENT

2C150

PATIENT

2C153

PATIENT

2C156

PATIENT

2C158

PATIENT

2C164

PATIENT NEG

2C140

CONF/ REPORT

2B106

SUB-STATION

2B132H

SUB-STATION

2B130A

SUB-STATION

2B130C

SUB-STATION

2B130E

SUB-STATION

2B132D SUB-STATION

2B132F

SUPPLY

2B130B

SUPPLY

2B132G

SUPPLY

2B132E

SUB-STATION

2C131GSUB-STATION

2C131C

SUB-STATION

2C131E

SUB-STATION

2C131A

SUB-STATION

2C133A

SUB-STATION

2C133C

RESPITE

2B166

T

2C145A

T

2C162A T

2C160A

T

2C151A

T

2C155A

T

2C157A

T

2C159A

T

2C161A

T

2C163A

T

2C164A

T

2C149A

T

2C158A

T

2C156A

T

2C153A

T

2C148A T

2C146A

T

2C144A

ISO T

2C142AISO T

2C140A

T

2C143A

T

2C147A

T

2B146A

T

2B140A T

2B142A

T

2B147A T

2B145A

T

2B149A

T

2B151A

T

2B152A

T

2B159A

T

2B161A

T

2B163A

ISO T

2B165A

ISO T

2B141A

T

2B164A

T

2B162A

T

2B160A

T

2B158A

T

2B156A T

2B154A

T

2B150A

T

2B148A

T

2B144A

ISO T

2B143A

MALE

2C101B

ANTE POS

2C165B

X-RAY

2C105

X-RAY ALC

2B115

HC ST

2B126A

TYP T

2B167

ANTE POS

2B165B

PATIENT NEG

2B141

PATIENT

2B142

PATIENT (BAR)

2B140

PATIENT

2B147

PATIENT

2B149

PATIENT NEG

2C142 PATIENT

2C162

ISO T

2C165A

PATIENT

2C143

T

2C141A

PUB ELEV LOBBY

2B100

SERV ELEV LOBBY

2B107

SUPPLY

2C131B

SUPPLY

2C131D

SUPPLY

2C131H

SUPPLY

2C133B

ST

2B125

T

2C167

FEMALE

2C101A

RESPITE

2C166

CARE PROVIDER

2B114

CORR

2B-C01A

CORR

2B-C01

CORR

2B-C04

CORR

2B-C02

CORR

2B-C03

AISLE

2B-C03A

AISLE

BP-8

CORR

2C-C03

CORR

2C-C04

CORR

2B-C01B

CORR

2B-C05

ELEV

BS-1

FUTURE ELEV

BS-2

ELEV

BS-4

ELEV

BS-3

STAIR

STB-1

SHAFT

SHB01

SHAFT

SHB03

SHAFT

SHC06

SHAFT

SHC05B

SHAFT

SHC05A

SUB-STATION

2C133E

SUPPLY

2C133D

SUPPLY

2B132C

SUPPLY

2C131F

CC

2B130F

CC

2C105A

CC

2C165C

CC

2B165C

ON CALL

2B129

ON CALL

2B131

PC1

2C115

CLEAN

2C152C

2C154

MED ROOM

2C152E

AISLE

BP-8

STAIR

STC-4

STAIR

STC-3

SECURITY

2C114D

SECURITY

2B123C

PC1

2C109

SUB-STATION

2B132B

CORR

2B-C04B

HC T/S

2B129A

CLST

2B129B

CLST

2B131A T/S

2B131B

ALCOVE

2C-C03B

ALCOVE

2B-C02A

T

2B157A

SUPPLY

2B130D

SUPPLY

2B132A

CORR

2C-C05

SHAFT

SHC05C

WAITING

2A100A

TR

2B155C

2B153

TR

2C152G

2C160

ELEV

BP-5

ELEV

BP-6

ELEV

BP-7

01-ED-021

01-ED-021

01-ED-021

01-ED-021

(E) PNL 'R12223B'

(E) PNL 'ECR12222'

(E) PNL 'R12223A'

(E) PNL 'R12213B'

(E) PNL 'R12213A'

(E) PNL 'ECR12212'

(E) PNL 'LC1421'

(E) PNL 'L1421'

(E) PNL 'D1421'

(E) XFMR 'T6'

(E) PNL 'D1221'

(E) PNL 'R12212B'

(E) PNL 'R12212A'

(E) PNL 'R12211B'

(E) PNL 'R12211A'

(E) PNL 'ECR12211B'

(E) PNL 'ECR12211A'

(E) PNL 'ECD1221'

(E) PNL 'ELSL1421'

(E) XFMR 'T2'

(E) XFMR 'T5'

(E) PNL 'ELSR1221'

(E) PNL 'EQR1221'

(E) XFMR 'T3-1'

(E) PNL 'ECL1421'

(E) PNL 'D1222'

(E) XFMR 'T6'

(E) PNL 'D1422'

(E) PNL 'L1422'

(E) PNL 'LC1422'

(E) PNL 'R12221A'

(E) PNL 'ECR12221B'

(E) PNL 'ECR12221A'

(E) PNL 'ELSL1422'

(E) XFMR 'T2'

(E) PNL 'ELSR1222'

(E) PNL 'EQR1222'

(E) XFMR 'T5'

(E) XFMR 'T3-1'

(E) PNL 'R12222B'

(E) PNL 'R12222A'

(E) PNL 'R12221B'

(E) PNL 'ECL1422'

(E) PNL 'EIT1221'

(X)EIT1221-25

(X)EIT1221-27

(X)EIT1221-29

(X)EIT1221-31

(X)EIT1221-1,3

(X)EIT1221-13

(X)EIT1221-15

(X)EIT1221-17

(X)UNLABELED MOUNTED ON

CABLE TRAY

MOUNTED ON

CABLE TRAY

(TYP.)

(E)EIT1221-24

(E)EIT1221-24

(E)EIT1221-24

(E)EIT1221-26

(X)EIT1221-9,11

TR

2B123D

2B110A

(E)EIT1221-26 2

(E) PNL 'EIT1222'

(X)EIT1222-29

(X)EIT1222-27

(X)EIT1222-25

(X)EIT1222-23

(X)EIT1222-21

(X)EIT1222-19

(X)EIT1222-17

(X)EIT1222-15

(X)EIT1222-13

MOUNTED ON

CABLE TRAY

(TYP.)

(E)EIT1222-26

(E)EIT1222-24

(E)EIT1222-24

(E)EIT1222-26

(E)EIT1222-24

(X)EIT1222-1,3

(X)EIT1222-5,7

TR

2C114C

2C114B

(X)EIT1224-1

(X)EIT1224-5

(X)EIT1224-7

(E)UNLABELED

(E) PNL 'EIT1224'

MOUNTED ON

CABLE TRAY

(TYP.)

TR

2C152G

2C160

(X)EIT1224-6,8

(X)EIT1224-7

(X)EIT1223-7

(X)EIT1223-9,11

(E)EIT1223-6

(E)EIT1223-8

MOUNTED ON

CABLE TRAY

(TYP.)

(E)EIT1223-10

(E) PNL 'EIT1223'

(X)EIT1223-1,34

TR

2B155C

2B153

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANTS

FOR OFFICIAL USE ONLY (FOUO)

04-25-2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

10% BASIS OF DESIGN 07.08.2022

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023 GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

TERP consulting Fire + Life Safety

14241 E. 4th Avenue, Suite 5-230 Aurora CO, 80011

FINAL BID DOCUMENTS 04.25.2023

A u to d e s k D o c s /2

-0

N e w O rl e a n s

E H

R M

/2 -0

N

O L

A E

H R

M

C O

N C

O U

R S

E

E le c I n t-

R

.r v t

01-ED-021

OVERALL SECOND FLOOR POWER

DEMOLITION PLAN - BLDG. 01

MER AJW

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

FINAL BID DOCUMENTS 629-22-700

3/32" = 1'-0"1

BLDG. 01 POWER OVERALL DEMOLITION PLAN - LEVEL 2

1/4" = 1'-0"4

ENLARGED POWER DEMO PLAN - TR 2B110A

1/4" = 1'-0"3

ENLARGED POWER DEMO PLAN - TR 2C114B

1/4" = 1'-0"2

ENLARGED POWER DEMO PLAN - TR 2C160

1/4" = 1'-0"5

ENLARGED POWER DEMO PLAN - TR 2B153

PLAN NOTES

1 EXISTING ELECTRICAL RECEPTACLES TO BE REMOVED. CONTRACTOR TO REMOVE

EXISTING CONDUIT AND CONDUCTORS BACK TO SOURCE.

2 EXISTING ELECTRICAL RECEPTACLE TO REMAIN.

3 EXISTING ELECTRICAL PANEL TO REMAIN.

4 EXISTING UPS TO BE REMOVED. CONTRACTOR TO REMOVE EXISTING CONDUIT,

CONDUCTORS, AND JUNCTION BOXES BACK TO SOURCE.

5 EXISTING ELECTRICAL RECEPTACLES FEEDING ICE MACHINE AND UNDERCOUNTER

REFRIGERATOR TO BE REMOVED. CONDUIT AND CONDUCTORS TO BE REROUTED TO NEW

LOCATION ON ASSOCIATED 'EP' SHEET. CONTRACTOR TO TRACE CIRCUIT PRIOR TO

DEMOLITION.

DEMOLITION GENERAL NOTES

1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO ASCERTAIN THE

CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES WITH THE COR PRIOR TO

INITIATION OF WORK. NO DEMOLITION SHALL OCCUR UNTIL AFTER THE NEW OR

REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR CUT OVER.

3. DISPOSE OF REMOVED EQUIPMENT UNLESS DIRECTED TO DO SO OTHERWISE BY OWNER.

4. COORDINATE EXTENT AND SCOPE OF DEMOLITION IN ALL SPACES WITH ARCHITECTURAL.

5. CONTRACTOR SHALL BE RESPONSIBLE TO TEMPORARILY MOVE AND RETURN FURNITURE,

FIXTURES, AND EQUIPMENT WITHIN SPACES AS REQUIRED TO COMPLETE EACH DAY'S

WORK. THE VA WILL REMOVE, OR SECURE, PHI, PPI, AND PERSONAL PROPERTY.

COORDINATE THIS WORK WITH THE COR.

6. PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF EXISTING STRUCTURE

AND FINISHES TO PREVENT ANY DAMAGE OF EXISTING FINISHES. ANY ACCIDENTAL DAMAGE

INCURRED TO EXISTING CONDITIONS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR

TO REPAIR OR CORRECT.

7. CONTRACTOR SHALL CONFIRM EXISTING CIRCUITING TO UPS EQUIPMENT AND RACK

MOUNTED RECEPTACLES IN EXISTING TELECOMMUNICATION ROOMS PRIOR TO

DEMOLITION. ANY EXISTING FEEDERS NOT SUPPLYING UPS EQUIPMENT OR RACK MOUNTED

RECEPTACLES TO REMAIN.

8. EXISTING RACK MOUNTED RECEPTACLES BEING UTILIZED TO REMAIN. CONTRACTOR TO

VERIFY RECEPTACLE UTLIZATION PRIOR TO DEMOLITION.

MAY NOT REPRESENT AN ACCURATE AS-BUILT

CONDITION. DISCREPANCIES MAY BE ENCOUNTERED,

AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO

FIELD VERIFY ALL CONDITIONS.

NORTH

KEY PLAN

KEY PLAN

Q B

C

D

E

F

G

J

H

K

L M

P

N

S H

O T

G U

N

F

IS

H E

R

EMER ELEC

3C114B

BLOOD GAS LAB

3C120

COMM CENTER

3C103

CONSULT

3C124

TR

3C114C

3C114B

CHUTE

3B105

COMM CENTER

3B118

HOUSE STAFF

3B104

HEAD NURSE

3C112

SOC WRK

3C121

SOC WRK

3C123

PHYS/CON/ NRS

3C110

STAFF LOCKER

3B126

DIET

3C116

CARE PROVIDER

3B114

HEAD NURSE

3B116

PHARMACIST

3C118

NOUR

3B122

TR

3B123D

3B110A

STOR/EQUIP

3B103

SERVICE BAY

3B123

SERVICE BAY

3C114

RETHERM

3B101

NORM ELEC

3B123B

EMER ELEC

3B123A

NORM ELEC

3C114A

SOILED

3C152B

3C152

CLEAN

3B120

FEMALE

3C101A

X-RAY ALC

3C104

PHYS/CON/ NRS

3C122

STOR/EQUIP

3C102

MALE

3C101B

X-RAY ALC

3B115

PATIENT NEG

3B141 PATIENT NEG

3B143

PATIENT

3B145

PATIENT

3B147

ISO T

3B165A

T

3B163A

T

3B161A

T

3B159A

PATIENT

3B149

T

3B157A

T

3B152A

PATIENT

3B151

PATIENT

3B140

PATIENT

3B142

PATIENT

3B144

PATIENT

3B146

PATIENT POS

3B165

T

3B164A T

3B160A

T

3B158A

T

3B156A T

3B162A

PATIENT

3B148

PATIENT

3B150

T

3B154A

T

3B151A

PATIENT

3B152

T

3B149A

T

3B147A T

3B145A

ISO T

3B141A

ISO T

3B143A

PATIENT

3B157

PATIENT

3B159

PATIENT

3B161

PATIENT

3B163

PATIENT

3B164

PATIENT

3B154

PATIENT

3B156

PATIENT

3B158

PATIENT

3B160

PATIENT

3B162

T

3B150A

T

3B148A T

3B146A

T

3B144A

T

3B142A

T

3B140A

EC

3C154

SUB-STATION

3B130A SUPPLY

3B130B

SUB-STATION

3B130C

SUPPLY

3B130D

SUB-STATION

3B130E

SUB-STATION

3B132DSUPPLY

3B132C

SUB-STATION

3B132HSUPPLY

3B132E

RESPITE

3B166

SUB-STATION

3B132F

SERV ELEV LOBBY

3B107

PUB ELEV LOBBY

3B100

HK

3B112

NOUR

3C108

CLEAN

3C106

SOILED

3B155E

3B161

EC

3B153

SUB-STATION

3C131A

SUB-STATION

3C131C

SUB-STATION

3C131E

SUB-STATION

3C133A

SUB-STATION

3C133C SUB-STATION

3C133E

T

3C163A

ISO T

3C140A

ISO T

3C142A

T

3C144A

T

3C146A

PATIENT

3C146

T

3C148A

PATIENT

3C148

PATIENT

3C150

T

3C150A

PATIENT

3C153

T

3C153A

T

3C156A

PATIENT

3C156

PATIENT

3C158

T

3C158A

T

3C162A

PATIENT

3C160

T

3C160A

T

3C141A

ISO T

3C165A

PATIENT

3C162

PATIENT

3C164

PATIENT

3C163

PATIENT

3C161PATIENT

3C159

PATIENT

3C157

SUPPLY

3C131B

SUPPLY

3C131D

SUPPLY

3C133B

RESPITE

3C166

T

3C164A

T

3C159A

T

3C161A T

3C157A

T

3C155A T

3C151A

T

3C149A

T

3C147A

T

3C145A T

3C143A

PATIENT NEG

3C140

PATIENT NEG

3C142

PATIENT

3C155

PATIENT

3C151

PATIENT

3C149

PATIENT

3C147

PATIENT

3C145

PATIENT

3C143

PATIENT

3C141

PATIENT POS

3C165

ANTE POS

3C165B

STAFF LOUNGE

3B102

ST

3B124

T

3B167

T

3C167

ANTE POS

3B165B

HC ST

3B126A

AISLE

3B-C01A

CORR

3B-C01

CORR

3B-C01B

CORR

3B-C02

CORR

3B-C05

CORR

3B-C03

CORR

3C-C03

CORR

3C-C04A

CORR

3C-C02

ELEV

BS-1

FUTURE ELEV

BS-2

ELEV

BS-4

ELEV

BS-3

STAIR

STB-1

SHAFT

SHB01

SHAFT

SHB03

SHAFT

SHC06

SHAFT

SHC05B

SHAFT

SHC05A

SUPPLY

3B132A

SUPPLY

3B132G

SUPPLY

3C133D

CC

3B130H

CC

3C109

HK

3C125

CC

3C165C

CC

3B165C

ST

3B227

CARE PROVIDER

3C230

CLEAN

3B155D

3B159

MED ROOM

3B155B AISLE

3B-C03A

CLEAN

3C152C

3C154

MED ROOM

3C152E

AISLE

3C-C02A

STAIR

STC-4

STAIR

STC-3

SECURITY

3C114D

SECURITY

3B123C

UNASSIGNED

3C117

PATIENT

3C144

CORR

3B-C04B

SUB-STATION

3B132B

SUPPLY

3C131F

SUB-STATION

3C131G

ALCOVE

3C-C03B

ALCOVE

3B-C02A

OFF PCI

3B131

HC ON CALL

3B129

HC T/S

3B129A

PHYS/CON/NRS

3B130

CLST

3B129B

CONSULT

3C126

SUPPLY

3C131H

SHAFT

SHC05C

CORR

3C-C06

WAITING

3A100A

TEL CLST

3B155C

3B153

TEL CLST

3C152D

3C160

CONF/ REPORT

1C190C

01-ED-031

01-ED-031

01-ED-031

01-ED-031

(E) PNL 'ECR12322'

(E) PNL 'R12323A'

(E) PNL 'R12323B'

(E) PNL 'ECR12312'

(E) PNL 'R12313B'

(E) PNL 'R12313A'

(E) PNL 'R12311A'

(E) PNL 'R12311B'

(E) PNL 'R12312A'

(E) PNL 'R12312B' (E) PNL 'L1431'

(E) PNL 'LC1431'

(E) PNL 'D1231'

(E) PNL 'ECD1231'

(E) PNL 'ECR12311B'

(E) PNL 'ECR12311A'

(E) XFMR 'T5'

(E) XFMR 'T3-1'

(E) PNL 'ECL1431'

(E) XFMR 'T6'

(E) XFMR 'T3-1'

(E) XFMR 'T5'

(E) PNL 'ECL1432'

(E) PNL 'ECD1232'(E) PNL 'ECR12321B'

(E) PNL 'ECR12321A'

(E) PNL 'R12322A'

(E) PNL 'R12322B'

(E) PNL 'LC1432'

(E) PNL 'L1432'

(E) PNL 'R12321B'

(E) PNL 'R12321A'

(E) XFMR 'T6'

(E) PNL 'D1232'

(E) PNL 'EIT1231B' (E) PNL 'EIT1231A'

(X)EIT1231A-27

(X)EIT1231A-29

(X)EIT1231A-31

(X)EIT1231A-1,3

(X)EIT1231A-13

(X)EIT1231A-15

(X)EIT1231A-17

(X)EIT1231A-19

(E)EIT1231A-26

(E)EIT1231A-24

(E)EIT1231A-24

(E)EIT1231A-26

(E)EIT1231A-24

MOUNTED ON

CABLE TRAY

(TYP.)

TR

3B123D

3B110A

(X)EIT1231B-1,3

(X)EIT1231A-21

(E) PNL 'EIT1232B'

(E) PNL 'EIT1232A'

(X)EIT1232A-27

(X)EIT1232A-25

(X)EIT1232A-23

(X)EIT1232A-21

(X)EIT1232A-19

(X)EIT1232A-17

(E)EIT1232A-24

(E)EIT1232A-24

(E)EIT1232A-26

(E)EIT1232A-24

MOUNTED ON

CABLE TRAY

(TYP.)

TR

3C114C

3C114B

(X)EIT1232A-1,3

(E)EIT1232A-262

(E)EIT1234-5

(E)EIT1234-6

(X)EIT1234-8

(X)EIT1234-1,3

MOUNTED ON

CABLE TRAY

(TYP.) (E) PNL 'EIT1234'

TEL CLST

3C152D

3C160

(X)EIT1234-9,114

(E)EIT1234-10 2

(X)EIT1233-6

(E)EIT1233-8

MOUNTED ON

CABLE TRAY

(TYP.)

(E) PNL 'EIT1233'

(X)EIT1233-5

TEL CLST

3B155C

3B153

(X)EIT1233-7,9

4 11

(E)EIT1233-102

(X)EIT1233-1,3

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANTS

FOR OFFICIAL USE ONLY (FOUO)

04-25-2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

10% BASIS OF DESIGN 07.08.2022

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023 GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

TERP consulting Fire + Life Safety

14241 E. 4th Avenue, Suite 5-230 Aurora CO, 80011

FINAL BID DOCUMENTS 04.25.2023

A u to d e s k D o c s /2

-0

N e w O rl e a n s

E H

R M

/2 -0

N

O L

A E

H R

M

C O

N C

O U

R S

E

E le c I n t-

R

.r v t

01-ED-031

OVERALL THIRD FLOOR POWER

DEMOLITION PLAN - BLDG. 01

MER AJW

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

FINAL BID DOCUMENTS 629-22-700

3/32" = 1'-0"1

BLDG. 01 POWER OVERALL DEMOLITION PLAN - LEVEL 3

1/4" = 1'-0"4

ENLARGED POWER DEMO PLAN - TR 3B110A

1/4" = 1'-0"3

ENLARGED POWER DEMO PLAN - TR 3C114B

1/4" = 1'-0"2

ENLARGED POWER DEMO PLAN - TR 3C160

1/4" = 1'-0"5

ENLARGED POWER DEMO PLAN - TR 3B153

DEMOLITION GENERAL NOTES

1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO ASCERTAIN THE

CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES WITH THE COR PRIOR TO

INITIATION OF WORK. NO DEMOLITION SHALL OCCUR UNTIL AFTER THE NEW OR

REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR CUT OVER.

3. DISPOSE OF REMOVED EQUIPMENT UNLESS DIRECTED TO DO SO OTHERWISE BY OWNER.

4. COORDINATE EXTENT AND SCOPE OF DEMOLITION IN ALL SPACES WITH ARCHITECTURAL.

5. CONTRACTOR SHALL BE RESPONSIBLE TO TEMPORARILY MOVE AND RETURN FURNITURE,

FIXTURES, AND EQUIPMENT WITHIN SPACES AS REQUIRED TO COMPLETE EACH DAY'S

WORK. THE VA WILL REMOVE, OR SECURE, PHI, PPI, AND PERSONAL PROPERTY.

COORDINATE THIS WORK WITH THE COR.

6. PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF EXISTING STRUCTURE

AND FINISHES TO PREVENT ANY DAMAGE OF EXISTING FINISHES. ANY ACCIDENTAL DAMAGE

INCURRED TO EXISTING CONDITIONS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR

TO REPAIR OR CORRECT.

7. CONTRACTOR SHALL CONFIRM EXISTING CIRCUITING TO UPS EQUIPMENT AND RACK

MOUNTED RECEPTACLES IN EXISTING TELECOMMUNICATION ROOMS PRIOR TO

DEMOLITION. ANY EXISTING FEEDERS NOT SUPPLYING UPS EQUIPMENT OR RACK MOUNTED

RECEPTACLES TO REMAIN.

8. EXISTING RACK MOUNTED RECEPTACLES BEING UTILIZED TO REMAIN. CONTRACTOR TO

VERIFY RECEPTACLE UTLIZATION PRIOR TO DEMOLITION.

PLAN NOTES

1 EXISTING ELECTRICAL RECEPTACLES TO BE REMOVED. CONTRACTOR TO REMOVE

EXISTING CONDUIT AND CONDUCTORS BACK TO SOURCE.

2 EXISTING ELECTRICAL RECEPTACLE TO REMAIN.

3 EXISTING ELECTRICAL PANEL TO REMAIN.

4 EXISTING UPS TO BE REMOVED. CONTRACTOR TO REMOVE EXISTING CONDUIT,

CONDUCTORS, AND JUNCTION BOXES BACK TO SOURCE.

5 EXISTING ELECTRICAL RECEPTACLES FEEDING ICE MACHINE AND UNDERCOUNTER

REFRIGERATOR TO BE REMOVED. CONDUIT AND CONDUCTORS TO BE REROUTED TO NEW

LOCATION ON ASSOCIATED 'EP' SHEET. CONTRACTOR TO TRACE CIRCUIT PRIOR TO

DEMOLITION.

MAY NOT REPRESENT AN ACCURATE AS-BUILT

CONDITION. DISCREPANCIES MAY BE ENCOUNTERED,

AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO

FIELD VERIFY ALL CONDITIONS.

NORTH

KEY PLAN

KEY PLAN

Q B

C

D

E

F

G

J

H

K

L M

P

N

S H

O T

G U

N

F

IS

H E

R

SERVICE BAY

4B123

SERVICE BAY

4C114

CONSULT

4B105

NOUR

4B122

TR

4B123D

4B114A

RETHERM

4B121

CHUTE

4B104

COMM CENTER

4B118

STAFF LOUNGE

4B109

CONF/ REPORT

4B106

HOUSE STAFF

4B107

RESIDENT CONF

4B108

PCI

4B102

SOC WRK

4B110

CLEAN

4B155D

4B159

DIET

4B125

HEAD NURSE

4B114

CARE PROVIDER

4B116

STOR/EQUIP

4B103

HC ST

4B126ASTAFF LOCKER

4B126

EC

4B153

TR

4C114C

4C132B

NORM ELEC

4B123B

EMER ELEC

4B123A

EMER ELEC

4C114B

NORM ELEC

4C114A

PATIENT NEG

4B143

MED ROOM

4B155B

SOILED

4B155E

4B161

CLEAN

4B120

ISO T

4B141A

ISO T

4B143A

PATIENT

4B163

T

4B145A

PATIENT

4B161

T

4B147A

PATIENT

4B159

T

4B149A

PATIENT

4B157

T

4B151A

PATIENT

4B152

T

4B140A

PATIENT

4B164

T

4B142A

PATIENT

4B162

T

4B144A

PATIENT

4B160

T

4B146A T

4B148A

PATIENT

4B158

T

4B150A

PATIENT

4B156

T

4B154A

PATIENT

4B154

T

4B156A

PATIENT

4B151

T

4B158A

PATIENT

4B149

T

4B160A

PATIENT

4B147

T

4B162A

PATIENT

4B145

T

4B164A

PATIENT

4B142

PATIENT

4B140

T

4B163A

PATIENT

4B150

T

4B161A

PATIENT

4B148

T

4B159A

PATIENT

4B146

T

4B157A

PATIENT

4B144

T

4B152A

SUB-STATION

4B130A

SUB-STATION

4B130C

SUB-STATION

4B130E

SUB-STATION

4B132H

SUB-STATION

4B132D

SUB-STATION

4B132F

RESPITE

4B166

ANTE POS

4B165B

PATIENT NEG

4B141

PATIENT POS

4B165

PUB ELEV LOBBY

4B100

SERV ELEV LOBBY

4B111

X-RAY ALC

4B115

SUPPLY

4B130D

SUPPLY

4B132C

SUPPLY

4B130B

SUPPLY

4B132E

ISO T

4C134A

BED STATION ISO

4C134

BED STATION

4C128

BED STATION

4C130

BED STATION

4C132

T

4C135

CLEAN

4C137

SOILED

4C141

EQ CLEAN STOR

4C136

MED

4C127

DIALYSATE STOR

4C120

CH NURSE

4C126

STOR STERILE

4C123

WATER TREAT

4C110

EQUIP SERVICE

4C111

WC

4C113

CUB

4C122B

CC

4C118

LOCKER

4C112

ST

4C121

T

4B167

T/S

4C106A

T/S

4C105A

T/S

4C104A

ON CALL

4C107ON CALL

4C103

ON CALL

4C106

ON CALL

4C105

ST

4B127A

ISO T

4B165A

NOUR

4C139

OFF PHYSICIAN

4C124

CUB

4C122A

T/S

4C107A

HC T/S

4C103A

T/S

4C102A

ON CALL

4C102

ON CALL

4C104

EQUIP SOIL/PREP

4C138

NURSE STA

4C125

AISLE

4B-C01A

CORR

4B-C01

CORR

4B-C02

CORR

4B-C03

CORR

4B-C04

CORR

4B-C04A

CORR

4C-C01

CORR

4C-C02

CORR

4C-C03

CORR

4C-C04

CORR

4C-C05

CORR

4C-C06

AISLE

4C-C06A

ELEV

BS-1

FUTURE ELEV

BS-2

ELEV

BS-4

ELEV

BS-3

STAIR

STB-1

SHAFT

SHB01

SHAFT

SHB03

SHAFT

SHC06

SHAFT

SHC05B

SHAFT

SHC05A

SUPPLY

4B132A

SUPPLY

4B132G

SCALE

4C119

HK

4B112

CC

4B165C

P/C/N OFFICE

4B113

AISLE

4B-C03A

STAIR

STC-4

SECURITY

4B123C

SECURITY

4C114D

SUB-STATION

4B132B

CORR

4B-C01B

CORR

4B-C04B

CLST

4C107B

CLST

4C105B

CLST

4C103B

CLST

4C102B

CLST

4C104B

CLST

4C106B

CORR

4B-C05

ALCOVE

4B-C02A

ALCOVE

4C136A

ALCOVE

4C128A

MALE

4C101B

FEMALE

4C101A

SHAFT

SHC05C

TR

4B155C

4B153

(E)ECR12412

(E)R12413B (E)R12413A

01-ED-041

01-ED-041

01-ED-041

(E) XFMR 'T3-1'

(E) PNL 'ECL1441'

(E) XFMR 'T5'

(E) PNL 'ECD1241'

(E) PNL 'EQR1241'

(E) PNL 'ELSL1441'

(E) PNL 'ECR12411B'

(E) PNL 'ECR12411A'

(E) PNL 'R12412B'(E) PNL 'R12412A'

(E) PNL 'L1441'

(E) PNL 'LC1441'

(E) PNL 'D1241'

(E) PNL 'R12411B'

(E) PNL 'R12411A'

(E) XFMR 'T6'

(E) XFMR 'T3-1'

(E) PNL 'ECL1442'

(E) XFMR 'T5'

(E) PNL 'ECR12421B'

(E) PNL 'ECR12421A'

(E) PNL 'ELSL1442'

(E) PNL 'EQR1242'

(E) PNL 'LC1442'

(E) PNL 'L1442'

(E) XFMR 'T5'

(E) PNL 'R12421B'

(E) PNL 'R12421A'

(E) PNL 'EIT1241'

(E)EIT1241-26

(E)EIT1241-24

(E)EIT1241-24

(E)EIT1241-26

(E)EIT1241-24

(X)EIT1241-19

(X)EIT1241-21

(X)EIT1241-17

(X)EIT1241-15

(X)EIT1241-13

(X)EIT1241-29

(X)EIT1241-27

(X)EIT1241-25

MOUNTED ON

CABLE TRAY

(TYP.)

TR

4B123D

4B114A1

4 (X)EIT1241-1,3

(E) PNL 'EIT1242'(E)EIT1242-24

(E)EIT1242-26

(E)EIT1242-24

(E)EIT1242-26

(X)EIT1242-13

(X)EIT1242-15

(X)EIT1242-25

(E)EIT1242-1,3

MOUNTED ON

CABLE TRAY

(TYP.)

(X)EIT1242-5,7

TR

4C114C

4C132B

(E)EIT1242-242

(X)EIT1243-1

(X)EIT1243-5

(E)EIT1243-8

(E)EIT1243-6

MOUNTED ON

CABLE TRAY

(TYP.)

(E) PNL 'EIT1243'

TR

4B155C

4B153

(X)EIT1243-9,11

(E)EIT1243-102

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANTS

FOR OFFICIAL USE ONLY (FOUO)

04-25-2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

10% BASIS OF DESIGN 07.08.2022

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023 GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

TERP consulting Fire + Life Safety

14241 E. 4th Avenue, Suite 5-230 Aurora CO, 80011

FINAL BID DOCUMENTS 04.25.2023

A u to d e s k D o c s /2

-0

N e w O rl e a n s

E H

R M

/2 -0

N

O L

A E

H R

M

C O

N C

O U

R S

E

E le c I n t-

R

.r v t

01-ED-041

OVERALL FOURTH FLOOR POWER

DEMOLITION PLAN - BLDG. 01

MER AJW

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

FINAL BID DOCUMENTS 629-22-700

3/32" = 1'-0"1

BLDG. 01 POWER OVERALL DEMOLITION PLAN - LEVEL 4

1/4" = 1'-0"3

ENLARGED POWER DEMO PLAN - TR 4B114A

1/4" = 1'-0"2

ENLARGED POWER DEMO PLAN - TR 4C132B

1/4" = 1'-0"4

ENLARGED POWER DEMO PLAN - TR 4B153

DEMOLITION GENERAL NOTES

1. VISIT AND EXAMINE THE SITE PRIOR TO INITIATION OF WORK TO ASCERTAIN THE

CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

2. CONTRACTOR SHALL COORDINATE ALL INTERRUPTIONS SERVICES WITH THE COR PRIOR TO

INITIATION OF WORK. NO DEMOLITION SHALL OCCUR UNTIL AFTER THE NEW OR

REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR CUT OVER.

3. DISPOSE OF REMOVED EQUIPMENT UNLESS DIRECTED TO DO SO OTHERWISE BY OWNER.

4. COORDINATE EXTENT AND SCOPE OF DEMOLITION IN ALL SPACES WITH ARCHITECTURAL.

5. CONTRACTOR SHALL BE RESPONSIBLE TO TEMPORARILY MOVE AND RETURN FURNITURE,

FIXTURES, AND EQUIPMENT WITHIN SPACES AS REQUIRED TO COMPLETE EACH DAY'S

WORK. THE VA WILL REMOVE, OR SECURE, PHI, PPI, AND PERSONAL PROPERTY.

COORDINATE THIS WORK WITH THE COR.

6. PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF EXISTING STRUCTURE

AND FINISHES TO PREVENT ANY DAMAGE OF EXISTING FINISHES. ANY ACCIDENTAL DAMAGE

INCURRED TO EXISTING CONDITIONS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR

TO REPAIR OR CORRECT.

7. CONTRACTOR SHALL CONFIRM EXISTING CIRCUITING TO UPS EQUIPMENT AND RACK

MOUNTED RECEPTACLES IN EXISTING TELECOMMUNICATION ROOMS PRIOR TO

DEMOLITION. ANY EXISTING FEEDERS NOT SUPPLYING UPS EQUIPMENT OR RACK MOUNTED

RECEPTACLES TO REMAIN.

8. EXISTING RACK MOUNTED RECEPTACLES BEING UTILIZED TO REMAIN. CONTRACTOR TO

VERIFY RECEPTACLE UTLIZATION PRIOR TO DEMOLITION.

PLAN NOTES

1 EXISTING ELECTRICAL RECEPTACLES TO BE REMOVED. CONTRACTOR TO REMOVE

EXISTING CONDUIT AND CONDUCTORS BACK TO SOURCE.

2 EXISTING ELECTRICAL RECEPTACLE TO REMAIN.

3 EXISTING ELECTRICAL PANEL TO REMAIN.

4 EXISTING UPS TO BE REMOVED. CONTRACTOR TO REMOVE EXISTING CONDUIT,

CONDUCTORS, AND JUNCTION BOXES BACK TO SOURCE.

5 EXISTING ELECTRICAL RECEPTACLES FEEDING ICE MACHINE AND UNDERCOUNTER

REFRIGERATOR TO BE REMOVED. CONDUIT AND CONDUCTORS TO BE REROUTED TO NEW

LOCATION ON ASSOCIATED 'EP' SHEET. CONTRACTOR TO TRACE CIRCUIT PRIOR TO

DEMOLITION.

UP

UP

F

F

F

O C

F

OC

MONITOR

1C163

CHF (OC)

1C220

A CHF (OC)

1C222

SECY (OC)

1B208

ITAC (OC)

1B141

CS (OC)

1B139

OFF CHF (FS)

1B151

BA (OC)

1C224

ADM (OC)

1B140

MA ASST (OC)

1C226

CUB (FS)

1B175D

CUB (FS)

1B175C

CUB (FS)

1B192A

CUB (FS)

1B192B

MEDIA (FS)

1B154

OFF A CHF (FS)

1B152

CUB CST SRV (FS)

1B150

CUB (FS)

1B192C

SEC/WAIT (FS)

1B153

CUB (CD)

1B173C

CUB (CD)

1B171CCUB (CD)

1B173D

CHF (CD)

1B159

A CHF (CD)

1B158

LD CODE (CD)

1B162

LD CODE (CD)

1B161

CUB (CD)

1B172B

CUB (CD)

1B172F

CUB (CD)

1B170A

CUB (CD)

1B170C

CUB (CD)

1B173B

CUB (CD)

1B171D

CUB (CD)

1B173A

CUB (CD)

1B170D

CUB (CD)

1B170B

CUB (CD)

1B171A

CUB (CD)

1B172C

CUB (CD)

1B172D

CUB (CD)

1B172E

SECY (CD)

1B160

WORK (CD)

1B157

A CHF (HIM)

1B143

CHF (HIM)

1B144

SECY (HIM)

1B201

CUB (HIM)

1B193B

CUB (HIM)

1B195D

CUB (HIM)

1B192F

CUB (HIM)

1B192D

CUB (HIM)

1B192E

WAIT/ROI (HIM)

1B200

CHF (WA)

1B137

A CHF (WA)

1B138

SECY (WA)

1B134

OP CTR (WA)

1B130

OFF SPV (WA)

1B132

A CHF (HE)

1C135

CUB (MCCF)

1B174A

CUB (MCCF)

1B175A

CUB (MCCF)

1B174B

CUB (MCCF)

1B175E

CUB (MCCF)

1B175B

BUS CTR (HE)

1C125

CUB (MCCF)

1B174D

T

1B176

CHIEF

1C203

A CHF

1C201

TECH

1C196A

WORKROOM

1C205

CUB (MCCF)

1B174C

SUPV (MCCF)

1B155

IP SUP (HE)

1C134

IP CLRK (HE)

1C124

SECY (MCCF)

1C132B

CUB PSA (HE)

1C130B

CUB PSA (HE)

1C130A

CUB PSA (HE)

1C130C

ADMIS (HE)

1C122

CUB ELIG (HE)

1C131

CUB PSA (HE)

1C132D

A CHF

1C199

ACCNT CHF

1C214 ACCNT CHF

1C213

ACCNT CHF

1C212

ACCNT CHF

1C211

COMP AUDITOR

1C215

COMP OFFICER

1C216

BDGT

1C192E

BDGT

1C192B

BDGT

1C192A

BDGT

1C192F

BDGT

1C217A

TECH

1C192D

TECH

1C192C

TECH

1C196F

TECH

1C200A

SECRY

1C194B

TECH

1C194A TECH

1C196ETECH

1C194F

TECH

1C217B

TECH

1C194D

TECH

1C196C

TECH

1C196D

TECH

1C194E

AUDITOR

1C193

AUDITOR

1C197

AUDITOR

1C195

RECPT

1C190A

T

1C186

T

1C219

AUDITOR

1C191

BREAK

1C210

SERVICE BAY

1C114

EC

1C223

EC

1B180

SERVICE BAY

1B123

TR

1C114C

1A104B

NORM ELEC

1C114A

DETAILS (HE)

1C136

WAIT (OC)

1C227

CUB CS (HE)

1C132C

STOR (HE)

1C126

EMER ELEC

1C114B

TR

1B123D

1B114A

EMER ELEC

1B123A

NORM ELEC

1B123B

SEC/WAIT

1B106

CONF/CLASS (OC)

1B135

T

1B204

CUB (FS)

1B191A

CUB (CD)

1B171B

T

1B178

TR

1C228

1C149

WAIT

1C190

SERV ELEV LOBB

1B120

PUB ELEV LOBBY

1B100

WORKROOM (HIM)

1B194

CUB (CD)

1B173E

CLINICAL SUPER (NSA)

1B102

CLINICAL SUPER (NSA)

1B103

T

1C141

T

1C143

WC

1C144

LOUNGE

1C145

RECPT

1C137

PANTRY

1C146

CHAPLAIN

1B105

CHAPLAIN

1B107

CHAPLAIN

1B109

EUCHARIST

1B111

QUIET

1B116

T

1B108

T

1B110

STOR

1B112

HK

1B114

STOR/FILE (FS)

1B190

ISO (HIM)

1B203

PV (HIM)

1B142

STOR

1C196B

SLEEP

1C166

T/S

1C166A

ST

1C181

T/S

1C179A

T/S

1C174A

SLEEP

1C174

SLEEP

1C165

SLEEP

1C175

T/S

1C165A

T/S

1C164A

SLEEP

1C164

SLEEP

1C177

T/S

1C177A

T/S

1C175A

SLEEP

1C179

SLEEP

1C162

T/S

1C162A

WAIT

1C160

CC

1C178

CONF

1C185

RETAIL AREA

1C101

VESTIBULE

1C150

ADMIS (HE)

1C123

STOR

1C221

WAIT

1C132A

POLY

1C161

EQUIP

1C168 T

1C160A

BREAK

1C169

ELEV

BS-1

FUTURE ELEV

BS-2

ELEV

BS-4

ELEV

BS-3

STAIR

STB-1

CORR

1B-C01 CORR

1B-C02

CORR

1B-C03

AISLE

1B-C08

CORR

1B-C07

CORR

1B-C05

CORR

1B-C06

AISLE

1B-C09

AISLE

1B-C10

AISLE

1B-C11

AISLE

1B-C12

AISLE

1B-C13

AISLE

1B-C14

AISLE

1B-C15

AISLE

1B-C16

AISLE

1C-C01A

AISLE

1C-C01B

AISLE

1C-C01C

AISLE

1C-C01D

AISLE

1C-C03

AISLE

1C-C04

AISLE

1C-C04AAISLE

1C-C04B

AISLE

1C-C05

AISLE

1C-C06

AISLE

1C-C07

AISLE

1C-C12

AISLE

1C-C11

AISLE

1C-C09

AISLE

1C-C08

AISLE

1C-C08A

SECY (HE)

1B172A

STOR

1C133

1C100

HK

1C139

VESTIBULE

1B121

CORR

1C101-K

CORR

1B-C02A

HK

1B206

NOUR

1C180

AISLE

1C-C010

AISLE

1C-C07A

SECURITY

1C114D

1C104A

UNASSIGNED

1B174G

CUB (HIM)

1B192H

SECURITY

1B123C

CORR

1C-C02

SECY/WAIT (OC)

1C225

TECH

1C196G

RETAIL PREP

1C101A

CORR

1B-C04

AISLE

1B-C04A

AISLE

1C-C00

CORR

1C-C01

CLEAN

1C167

SOILED

1C176

ASR

1B113

CONNECTOR HALL

1B115A

TR

1B179

1B145

IT/LVSR

1C190B

1C150A

CHAPEL

1B115

CLOSET

1B115B

01-EP-011

01-EP-011

(E) PNL 'LC1411'

(E) PNL 'L1411'

(E) PNL 'ECR1211'

(E) PNL 'D1411'

(E) PNL 'D1211'

(E) PNL 'R12112A'

(E) PNL 'R12112B'

(E) PNL 'P1411'

(E) PNL 'R12111A'

(E) PNL 'R12111B'

(E) XFMR 'T6'

(E) PNL 'LC143'

(E) PNL 'MGAP'

(E) PNL 'R12121B'

(E) PNL 'R12121A'

(E) PNL 'R12122A'

(E) PNL 'R12122B'

(E) PNL 'D1212'

(E) XFMR 'T6'

(E) PNL 'D1412'

(E) PNL 'LC1412'

(E) PNL 'L1412'

(E) PNL 'ECR1212'

(E) PNL 'R12123A'

(E) PNL 'R12123B'

(E) PNL 'R12113B'

(E) PNL 'R12113A'

01-EP-011

01-EP-011

(E) PNL 'P1412'

(E) PNL 'EIT1214'

60AS

60AF

ECR1212-37,39,41

ECR1212-33,35

(E)UNLABELED

(E)UNLABELED

(E)UNLABELED

(E) PNL 'EIT1211'

TR

1B123D

1B114A

EIT1211-1,3,5

EIT1211-7,9,11

R12112B-2,4,6

R12112B-8,10,12

60AS

60AF

(E)UNLABELED

(E)UNLABELED

(E)UNLABELED

(E)EIT1212-24

(E) PNL 'EIT1212'

TR

1C114C

1A104B

EIT1212-1,3,5

EIT1212-7,9,11

R12121B-38,40,42

R12121B-37,39,41

60AS

60AF

R12113B-37,39,41

TR

1B179

1B145

PNL 'EIT1213'

EIT1213-1,3,5

EIT1213-15

EIT1213-7,9,11

EIT1213-13

R12113B-35

S1 L1411-42 a

EIT1213-2

TR

1C228

1C149

EIT1214-19

EIT1214-21

EIT1214-7,9,11

R12123B-37,39,413

EIT1214-13,15,17 60AS

45AF

S1 L1412-42 a

EIT1214-6

LUMINAIRE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL # LAMP

TYPE

CRI DELIVERED

LUMENS

COLOR

TEMP

INPUT FINISH

WATTS

S1 STRIP LIGHT FIXTURE LITHONIA ZL1D SERIES LED 90 5337 3500 41

NOTES:

NORTH

KEY PLAN

KEY PLAN

Q B

C

D

E

F

G

J

H

K

L M

P

N

S H

O T

G U

N

F

IS

H E

R

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANTS

FOR OFFICIAL USE ONLY (FOUO)

04-25-2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

Kramer Gehlen & Associates Structural Engineers 400 Columbia St., Suite 240, Vancouver, WA 98660 Vancouver

10% BASIS OF DESIGN 07.08.2022

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023 GDM of…

This is the start of the file's text. The full file is on GovTribe.