2.1 - Drawings 01 of 17 - GI001 to GI003.pdf

PDF 11 MB Posted

Attached to
NOLA EHRM Infrastructure Upgrades Construction - New Orleans, LA 629-22-700
Solicitation number
36C77623B0038
Issued by

About this file

This document provides details on a federal contract opportunity for infrastructure upgrades at a Veterans Affairs facility in New Orleans, Louisiana. The solicitation number is 36C77623B0038 and seeks construction services for NOLA EHRM Infrastructure Upgrades at the New Orleans location. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The file attached is the first of seventeen drawings related to the project, covering items GI001 to GI003. Responses to the solicitation are due by the date listed on SAM.gov. Construction is expected to be completed within 24 months of award.

View the file

Other files

File Type Posted
36C77623B0038 0007.pdf PDF
Tech Questions Tracker - NOLA - 8-25-23.pdf PDF
Brand Name JA - NOLA EHRM.pdf PDF
Tech Questions Tracker - NOLA - 8-23-23.pdf PDF
36C77623B0038 0006.pdf PDF
36C77623B0038 0005.pdf PDF
Tech Questions Tracker - NOLA - 8-9-23.pdf PDF
36C77623B0038 0004.pdf PDF
Specs and Drawings - NOLA EHRM - Addendum No 2.pdf PDF
36C77623B0038 0003.pdf PDF
Specs and Drawings - NOLA EHRM - Addendum No 1.pdf PDF
36C77623B0038 0002.pdf PDF
NOLA EHRM Site Visit Sign-In Sheet 19 July 23.pdf PDF
36C77623B0038 0001.pdf PDF
Site Visit Instructions.pdf PDF
2.12 - Drawings 12 of 17 - 00-EG-001 to 02-ED-051.pdf PDF
2.2 - Drawings 02 of 17 - 000-AJ-601 to 000-AJ-606.pdf PDF
2.4 - Drawings 04 of 17 - 01-AE-011 to 02-AE-052.pdf PDF
2.17 - Drawings 17 of 17 - 04-FP-100 to 11-FP-110.pdf PDF
1 - Specifications.pdf PDF
2.10 - Drawings 10 of 17 - 04-TD-011 to 08-TD-051.pdf PDF
2.13 - Drawings 13 of 17 - 02-EP-011 to 03-EP-071.pdf PDF
2.5 - Drawings 05 of 17 - 02-AC-011 to 03-AE-071.pdf PDF
2.16 - Drawings 16 of 17 - 00-FP-000 to 03-FP-111.pdf PDF
2.11 - Drawings 11 of 17 - 08-TN-011 to 00-TJ-028.pdf PDF
2.9 - Drawings 09 of 17 - 02-TN-011 to 03-TN-071.pdf PDF
IFB 36C77623B0038 - 6-29-23.pdf PDF
6 - Contractor Safety and Environmental Record.docx DOCX document
4 - DBA Wage Rates - Orleans County - 06-16-23.pdf PDF
2.6 - Drawings 06 of 17 - 03-AC-011 to 11-AE-011.pdf PDF
2.8 - Drawings 08 of 17 - 00-TG-001 to 02-TD-052.pdf PDF
2.14 - Drawings 14 of 17 - 04-ED-011 to 10-EP-011.pdf PDF
2.15 - Drawings 15 of 17 - 01-EJ-001 to 00-EJ-026.pdf PDF
2.7 - Drawings 07 of 17 - 00-MK-001 to 10-MJ-011.pdf PDF
3 - HVAC Load Calculations.pdf PDF
5 - Limitations on Subcontracting - Construction.docx DOCX document
2.3 - Drawings 03 of 17 - 00-CG-001 to CJ-A102.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

10% BASIS OF DESIGN 07.08.2022 CONSULTANTS

APPLICABLE CODES, REGULATIONS,

VA DESIGN MANUALS

KEY PLANVICINITY MAP

GDM of Oregon

1000 W. STEUBEN ST. UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

GENERAL NOTES

NEW ORLEANS VA MEDICAL CENTER

ELECTRONIC HEALTH RECORD MODERNIZATION (EHRM)

INFRASTRUCTURE UPGRADES - NEW ORLEANS, LA

PROJECT NO. 629-22-700

CONTRACT NO. 36C77622C0049

100% FINAL BID DOCUMENTS

04-25-2023

FULLY

SPRINKLERED

35% SCHEMATIC DESIGN 11.10.2022

FOR OFFICIAL USE ONLY (FOUO)

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

A u to d e s k D o c s /2

-0

N e w

O rl e a n s

E H

R M

/2 -0

N

O L A

E H

R M

C o n c o u rs e

A rc h P ro d u c ti o n -R

.r v t

GI001

ES BS

COVER SHEET VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

100% FINAL BID

DOCUMENTS

629-22-700

APPLICABLE CODES, STANDARDS, VA DESIGN MANUALS AND DIRECTIVES

VA OFFICE OF ELECTRONIC HEALTH RECORD MODERNIZATION OEHRM SITE INFRASTRUCTURE AND ENDER USER DEVICE (EUD) REQUIREMENTS APRIL 15, 2021 (VERSION 2.0 CONCURRENCE) PARAGRAPH 2.9 PHYSICAL SECURITY DESIGN REQUIREMENTS STATES:

TELECOMMUNICATIONS ROOMS (TRS) AND DATA CENTERS SHALL COMPLY WITH THE FOLLOWING DESIGN MANUALS AND EHRM PROGRAM

REQUIREMENTS:

U.S. DEPARTMENT OF VETERANS AFFAIRS OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT TELECOMMUNICATIONS AND SPECIAL TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY

2016 (PG-18-12) HTTPS://WWW.CFM.VA.GOV/TIL/DGUIDE.ASAP

U.S. DEPARTMENT OF VETERANS AFFAIRS OFFICE OF INFORMATION & TECHNOLOGY (OIT) INFRA-

STRUCTURE STANDARDS FOR TELECOMMUNICATIONS SPACES VERSION 3.1 1 JULY 2021.

OIT DESIGN GUIDE TEMPLATES FOR CRITICAL INFRASTRUCTURE IN TELECOMMUNICATIONS

SPACES (CLINICAL AND NON-CLINICAL ENVIRONMENTS), APRIL 16, 2020

VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL, REV APRIL 1, 2021.

ANSI/TIA-942-B TELECOMMUNICATIONS INFRASTRUCTURE STANDARD FOR DATA CENTERS

VA HANDBOOK APPENDIX B 0730/4 PHYSICAL SECURITY REQUIREMENTS SECURITY AND LAW

ENFORCEMENT. APPENDIX B PHYSICAL SECURITY REQUIREMENTS FOR IT DATA CENTERS AND SEVER ROOMS, DECEMBER 12, 2012. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION, 1 JUNE 2021.

ACCESSIBILITY CODE

FEDERAL ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABASS), REV 2015

PG-18-13 VA FIRE BARRIER (A SUPPLEMENT TO FEDERAL BARRIERS ACT ACCESSIBILITY

STANDARDS) FIRE DESIGN GUIDE, DEC 2011

BUILDING CODES

INTERNATIONAL CODE COUNCIL (ICC)

IBC—INTERNATIONAL BUILDING CODE, 2021

IFC—INTERNATIONAL FIRE CODE, 2021

IFGC—INTERNATIONAL FUEL GAS CODE, 2021

IMC—INTERNATIONAL MECHANICAL CODE, 2021

IPC—INTERNATIONAL PLUMBING CODE, 2021

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA LIFE SAFETY CODE-101, 2021

NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHER, 2018 EDITION

NFPA 13 STANDARDS FOR INSTALLATION ON SPRINKLER SYSTEMS 2022

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2022

NFPA 70 NATIONAL ELECTRICAL CODE (NEC) ESSENTIALS 2020

NFPA 70E ELECTRICAL SAFETY IN THE WORKPLACE, 2021

NFPA 75 STANDARD FOR THE FIRE PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT, 2020.

NFPA 101 LIFE SAFETY CODE ESSENTIALS 2021

NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION ALTERATION AND DEMOLITION OPERATIONS, 2022

NFPA 2001 STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEMS, 2021

NFPA 855 STANDARD FOR THE INSTALLATION OF STATIONARY ENERGY STORAGE SYSTEMS, 2020

NFPA 99 HEALTHCARE FACILITIES CODE 2012

NFPA STANDARD FOR THE INSTALLATION OF LIGHTING PROTECTION 2020

NFPA 780 STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEMS

VA DESIGN MANUALS

VA OFFICE OF CONSTRUCTION AND FACILITY MANAGEMENT DESIGN MANUAL AUGUST 1, 2014

PG-18-1 MASTER CONSTRUCTION SPECIFICATIONS, HTTP://WWW.CFM.VA.GOV/TIL/SPEC.ASP2)

PG-18-3 DESIGN AND CONSTRUCTION PROCEDURES, APRIL 2019, HTTP://WWW.CFM.VA.GOV/TIL/CPRO.ASP

PG-18-14 ROOM FINISHES, DOOR AND HARDWARE SCHEDULE – DECEMBER 2018

PG-18-15 VOL C A/E SUBMISSIONS INSTRUCTION OF MINOR AND NRM CONSTRUCTION PROGRAM NOV 2008

PG-18-9 OIT SPACE PLANNING, CRITERIA, CH 232, OCT 2016

PG-18-12 OIT DESIGN GUIDE, FEB 2011

PG-18-5 EQUIPMENT GUIDE LIST, CH 232, OIT (AUG 2016)

PG 18-10 DESIGN MANUAL- TELECOMMUNICATIONS AND SPECIAL TELECOMMUNICATIONS SYSTEMS, FEB 2016

VA HVAC DESIGN MANUAL

HVAC DESIGN MANUAL—NOVEMBER 1, 2017, REV MAY 1, 2019, REV 3/1/2020 HTTP://WWW.CFM.VA.GOV/TIL/DMANUAL/DMLHVAC.PDF

PG-18-10 HVAC & ELECTRICAL DESIGN MANUALS

VA INTERIOR DESIGN

INTERIOR DESIGN MANUAL FOR NEW CONSTRUCTION AND RENOVATIONS OF HOSPITALS AND CLINICS — NOVEMBER 1, 2020

HTTP://WWW/CFM.VA.GOV/TIL/DMANUAL/DMLDHONH.PDF

VA ELECTRICAL DESIGN

VA ELECTRICAL DESIGN MANUAL – DECEMBER 1, 2019

VA LIGHTING DESIGN

LIGHTING DESIGN MANUAL — DECEMBER 2015 HTTP://WWW.CFM.VA.GOV/TIL/DMANUAL/DMLIGHTING.PDF

VA STRUCTURAL ENGINEERING

VA SEISMIC CODES AND STANDARDS, H-18-8 HTTP://WWW.CFM.VA.GOV/TIL/SEISMIC.ASP

VA SUSTAINABILITY

SUSTAINABLE DESIGN MANUAL MANUAL – REV 1 AUGUST 18, 2017, HTTPS://WWW.CFM.VA.GOV/TIL/SUSTAIN/DMSUSTAIN.PDF

VA ASBESTOS ABATEMENT

ASBESTOS ABATEMENT DESIGN MANUAL FOR NEW HOSPITALS, REPLACEMENT HOSPITALS, AMBULATORY CARE, CLINICAL ADDITIONS, ENERGY CENTERS, OUTPATIENT CLINICS, ANIMAL RESEARCH FACILITIES, LABORATORY BUILDINGS – JULY 2011

VA-JOINT COMMISSION CLARIFICATION DOCUMENTS

SUMMARY OF DISCUSSION ISSUES RELATED TO VHA IMPLEMENTATION OF THE JOINT COMMISSION ENVIRONMENT OF CARE (EC)

AND LIFE SAFETY (LS) STANDARDS, MAY 2021 REVISION. EFFECTIVE

DATE: MAY 1, 2021

VA STANDARD ALERTS

OFFICE OF INFORMATION AND TECHNOLOGY INFRASTRUCTURE STANDARD FOR TELECOMMUNICATION

SPACES, AUGUST 1, 2021. 003C2B-SA-017R01B

MECHANICAL

DESIGN STANDARDS

AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR-CONDITIONING ENGINEERS (ASHRAE)

STANDARD 62.1 – VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY, 2017

STANDARD 90.1 - ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS, 2013

STANDARD 170 - VENTILATION OF HEALTH CARE FACILITIES, 2021

SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION

HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE

HVAC SYSTEMS COMMISSIONING MANUAL, 2ND EDITION, 2013

SEISMIC RESTRAINT MANUAL GUIDELINES FOR MECHANICAL SYSTEMS, 3RD EDITION, 2008

US DEPARTMENT OF VETERAN’S AFFAIRS (VA)

HVAC DESIGN MANUAL (REVISION 1), PG18-10, 1 MAY 2021

SUSTAINABLE DESIGN MANUAL (REVISION 1), 18 AUGUST 2017

A. REQUIREMENTS FOR VA MINOR NEW CONSTRUCTION AND RENOVATION PROJECTS (I.E. UNDER

$20,000,000) WHOLE BUILDING COMMISSIONING MANUAL (REVISION 1), NOVEMBER 2013

ELECTRICAL DESIGN STANDARDS

UNDERWRITER’S LABORATORY, INC (UL) STANDARDS – 2019

ANSI/TIA-568-D SERIES, COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD, AND ITS PUBLISHED ADDENDA. -2017 ANSI/TIA 568.0-E, GENERIC TELECOMMUNICATIONS CABLING FOR CUSTOMER PREMISES, AND ITS PUBLISHED ADDENDA. – 2017 ANSI/TIA 568.1-E, COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD, AND ITS PUBLISHED ADDENDA. – 2017 ANSI/TIA 568.2-D, BALANCED TWISTED-PAIR TELECOMMUNICATIONS CABLING AND COMPONENTS. 2017

ANSI/TIA 568.3-D, OPTICAL FIBER CABLING COMPONENTS STANDARD, AND ITS PUBLISHED

ADDENDA. – 2017

ANSI/TIA 568.4-D BROADBAND COAXIAL CABLING AND COMPONENTS STANDARD

ANSI/TIA-569-C, COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS PATHWAYS AND SPACES, AND ITS PUBLISHED

ADDENDA. – 2017

ANSI/TIA-606-A, ADMINISTRATION STANDARD FOR THE TELECOMMUNICATIONS INFRASTRUCTURE OF COMMERCIAL BUILDINGS, AND

ITS PUBLISHED ADDENDA – 2017

ANSI/J-STD-607-A, COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS, AND

ITS PUBLISHED ADDENDA. – 2017

BUILDING INDUSTRIES CONSULTING SERVICES INTERNATIONAL (BICSI) – 2019

TELECOMMUNICATIONS DISTRIBUTION METHODS MANUAL (TDMM) -2020

NFPA 70E, 2021

CIVIL ENGINEERING DESIGN STANDARDS

VA SITE DEVELOPMENT DESIGN MANUAL — APRIL 1, 2021

INTERNATIONAL BUILDING CODE (IBC) — 2018

EHRM PROGRAM DESIGN ALERTS

00 VA OEHRM SITE INFRASTRUCTURE REQUIREMENTS V2.0

SOCAMES 6 DESIGN ALERT 1 - SOCAMES 6 DESIGN ALERT 2

SOCAMES 6 DESIGN ALERT 3 - SOCAMES 6 DESIGN ALERT 4 - SOCAMES 6 DESIGN ALERT 5

SOCAMES 6 DESIGN ALERT 6 - SOCAMES 6 DESIGN ALERT 7 - SOCAMES 6 DESIGN ALERT 8 - SOCAMES 6 DESIGN ALERT 9

1. CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH THE EXISTING SITE CONDITIONS, SECURITY PROVISIONS, LAYDOWN AREA AND OTHER SITE SPECIFIC GENERAL CONDITIONS WHICH MAY AFFECT THE BID VALUE FOR

THIS PROJECT.

2. THE DRAWINGS SHALL BE WORKED IN CONJUNCTION WITH THE TECHNICAL SPECIFICATIONS AND CONDITIONS OF THE PROJECT INCLUDED IN THE PROJECT MANUAL WHICH FORM A PART OF THE CONTRACT DOCUMENTS AND CONTAINS ADDITIONAL INFORMATION REQUIRED TO CONSTRUCT THE WORK OF THIS CONTRACT. IN THE EVENT OF A DISCREPANCY BETWEEN AND THE DRAWINGS THE

SPECIFICATIONS ALWAYS GOVERN.

3. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO THE START OF WORK. NOTIFY THE COR

OF ANY SIGNIFICANT CHANGES IN DIMENSIONS OR CONDITIONS.

4. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, TOOLS, EQUIPMENT AND NECESSARY FACILITIES, AND PERFORM ALL LABOR AND SERVICES OF EVERY DESCRIPTION AS MAY BE NECESSARY TO COMPLETE THE SCOPE OF WORK DEFINED ON THE DRAWINGS

AND SPECS.

5. THE CONTRACTOR SHALL ARRANGE FOR AND OBTAIN ALL VA ISSUED PERMITS (HOTWORK, ICRA, WEEKENDS, HOLIDAY'S, SHUTDOWN, ETC.), CERTIFICATES, INSPECTIONS, DEPARTMENT APPROVALS, ETC. FOR WORK PERFORMED UNDER THIS CONTRACT. PROVIDE COPIES OF ALL REQUIRED PERMITS, CERTIFICATES, INSPECTIONS AND AGENCY APPROVALS TO THE COR INCLUDING BUT NOT

LIMITED TO ICRA AND IFLS.

6. FABRICATE AND INSTALL ALL WORK IN STRICT ACCORDANCE WITH THE SPECIFICATIONS, ALL APPLICABLE STATE AND LOCAL CODES, AND THE GENERAL AND SUPPLEMENTARY CONDITIONS OF THE CONTRACT.

7. ALL CONTRACTORS AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR THE PROPER PERFORMANCE OF THEIR WORK, COORDINATING WITH OTHER TRADES, MEANS AND METHODS OF CONSTRUCTION, SAFETY AND SECURITY ON SITE.

8. CUTTING AND PATCHING SHALL BE PERFORMED BY EACH TRADE AS NECESSARY FOR THE PERFORMANCE AND INSTALLATION OF THE WORK. CUTTING AND PATCHING SHALL BE PERFORMED IN A WORKMANLIKE MANNER CONSISTENT WITH INDUSTRY STANDARDS FOR

FINISHES AND SUBSTRATES AFFECTED.

9. THE CONTRACTOR SHALL PROTECT THE FACILITY FROM WEATHER AND MAINTAIN SECURITY DURING ALL CONSTRUCTION WORK.

10. PROTECT EXISTING PROPERTY DURING CONSTRUCTION. REPAIR OR REPLACE, WITHOUT ADDITIONAL CHARGE TO THE OWNER, ANY

EXISTING WORK DAMAGED DURING THE COURSE OF CONSTRUCTION.

11. THE WORK SHALL BE COORDINATED IN GOOD FAITH WITH THE COR AND ALL GOVERNMENT EMPLOYEES 14 DAYS IN ADVANCE OF

BEGINNING EACH CONSTRUCTION ACTIVITY.

12. UNLESS ITEMS OF MATERIAL, EQUIPMENT OR WORK ARE SPECIFICALLY NOTED TO BE PROVIDED OR FURNISHED BY OTHERS, THEY

SHALL BE PROVIDED UNDER THIS CONTRACT.

13. ALL WORK SHALL BE PERFORMED BY SKILLED WORKERS IN A WORKMANLIKE AND PROFESSIONAL MANNER CONSISTENT WITH

INDUSTRY STANDARDS.

14. MATERIALS AND COMPONENTS AS SPECIFIED CONSTITUTE A STANDARD OF QUALITY, UNLESS OTHERWISE NOTED. EQUAL SUBSTITUTES WILL BE ACCEPTABLE ONLY WITH WRITTEN PRIOR APPROVAL BY THE CONTRACTING OFFICER SEVEN DAYS BEFORE BIDS ARE DUE. DO NOT ASSUME EQUALITY AND SUBMIT SHOP DRAWINGS FROM ALTERNATE VENDORS WHO HAVE NOT BEEN APPROVED IN WRITING BY THE ENGINEER. IN THE EVENT THIS HAPPENS, THE CONTRACTOR SHALL PROVIDE THE SYSTEM USED

IN THE BASIS OF DESIGN AT NO ADDITIONAL COST TO THE VA.

15. THE CONTRACTOR SHALL LEAVE THE SITE AND ALL BUILDINGS AND STRUCTURES IN PROPER WORKING ORDER AND SHALL, WITHOUT ADDITIONAL CHARGE, REPLACE ANY WORK, MATERIALS, OR EQUIPMENT FURNISHED AND INSTALLED UNDER THE CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FROM ORDINARY WEAR AND TEAR, WITHIN ONE (1) YEAR FROM THE DATE OF FINAL

ACCEPTANCE BY THE COR

16. CONTRACTOR SHALL SCHEDULE, COORDINATE, AND FACILITATE ALL POWER OUTAGES AND SHUTDOWNS. POWER OUTAGES AND

SHUTDOWNS MUST BE SCHEDULED WITH THE COR, 7 CALENDAR DAYS PRIOR TO OUTAGE.

17 FIELD VERIFY ALL EXISTING CONDITIONS INCLUDING BUT NOT LIMITED TO REGULATED MATERIALS ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, EQUIPMENT, AND ALL OTHER EXISTING SYSTEMS; MAKE NECESSARY PROVISIONS TO MAINTAIN THE INTEGRITY OF SAID SYSTEMS PRIOR TO THE COMMENCEMENT OF DEMOLITION, IF ANY, SEE MECHANICAL, ELECTRICAL, TELECOMMUNICATIONS & ARCHITECTURAL DRAWINGS FOR ANY SYSTEM OR PORTIONS THEREOF TO BE REMOVED, RELOCATED, REVISED OR ABANDONED.

18. ANY CONSTRUCTION INSTALLED IN CONFLICT WITH THE CONTRACT DOCUMENTS SHALL BE CORRECTED AT NO EXPENSE TO THE VA.

19. ALL REQUIRED EXITS FROM OCCUPIED PORTIONS OF THE BUILDING MUST BE MAINTAINED AT ALL TIMES. ESTABLISH PROCEDURES TO MINIMIZE CIRCULATION OF CONSTRUCTION PERSONNEL AND MATERIALS THROUGH OCCUPIED PORTIONS OF THE BUILDING.

KEEP ALL AREAS ADJACENT TO THE WORK AREA CLEAN.

20. PRIOR TO DELIVERY OF MATERIALS TO THE CONSTRUCTION ZONE AND REMOVAL OF WASTE FROM THE SITE, CHECK WITH THE COR FOR AN ACCEPTABLE ACCESS ROUTE AND TIME. UNDER NO CIRCUMSTANCES SHALL ANY AREA OUTSIDE THE CONSTRUCTION ZONE BE USED WITHOUT PRIOR APPROVAL FROM THE COR. ALL BUILDING INTERIOR STAGING AREAS SHALL BE PROTECTED WITH FIRE RESISTANT PLYWOOD ENCLOSURES. ALL TRASH SHALL BE REMOVED FROM THE BUILDING DAILY. CONSTRUCTION MATERIALS SHALL

NOT BE STORED IN CORRIDORS AT ANY TIME.

21. FIELD VERIFY ALL EXISTING DIMENSIONS, SERVICES, AND POINTS OF CONNECTION PRIOR TO START OF WORK.

22. THE DESIGN ADEQUACY, SAFETY, AND ERECTION OF BRACING, SHORING, SCAFFOLDING, AND TEMPORARY SUPPORTS AND

RESTRAINS IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

23. NOTIFY THE FACILITY OF TIMES WHEN THE CONSTRUCTION NOISE WILL BE EXCESSIVE. RESCHEDULE SUCH WORK IF SO REQUIRED BY

THE FACILITY.

24. NOTIFY THE COR OF ANY DISCREPANCIES DISCOVERED IN THE FIELD FOR CORRECTION ACTION.

25. FOR EXISTING FLOORS, CEILINGS, PARTITIONS, AND SERVICES TO REMAIN, PROTECT ALL FINISHES AND MATERIALS, AND REPAIR OR

REPLACE ALL ITEMS THAT ARE DAMAGED OR SOILED DURING THE COURSE OF CONSTRUCTION.

26. ALL ITEMS TO BE REMOVED AND REPLACED SHALL BE HANDLED WITH PROPER CARE AND STORED IN A SAFE PLACE TO PREVENT

DAMAGE; WHEN DAMAGED, REPLACED WITH NO EXPENSE TO THE VA.

27. ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED OR BRACED IN ACCORDANCE WITH PROVISIONS OF THE TECHNICAL

SPECIFICATIONS.

28. ALL DRAWINGS, THOUGH NOTED TO SCALE, ARE FOR ILLUSTRATION ONLY. DO NOT SCALE THE DRAWINGS. ITEMS WRONGLY LOCATED

BY DRAWING SCALING SHALL BE CORRECTED.

29. SIGNAGE CONSTRUCTION, FONT AND SIZE SHALL BE CONSISTENT WITH THE FACILITY'S EXISTING SIGNAGE SYSTEMS.

30. EXERCISE CARE DURING CONSTRUCTION TO MINIMIZE DISRUPTION OF THE MEDICAL CENTER ROUTINE, COORDINATE SEQUENCE OF WORK AND PHASING WITH THE COR TO MINIMIZE DISRUPTION OF THE MEDICAL CENTER. SOME OF THE WORK ITEMS REQUIRE THE WORK TO BE PERFORMED ONLY AT NIGHT, WEEKENDS, OR HOLIDAYS AT NO ADDITIONAL COST TO THE GOVERNMENT.

31. PRIOR TO DRILLING OR CORING EXISTING CONCRETE, CONTRACTOR SHALL LOCATE EXISTING REINFORCEMENT TO MAINTAIN ADEQUATE CLEARANCES FROM AND AVOID DAMAGE TO EXISTING REINFORCEMENT. CONTRACTOR SHALL USE NON-DESTRUCTIVE TESTING (NDT) TO LOCATE REINFORCEMENT. WHENEVER FEASIBLE, CONTRACTOR SHALL USE GROUND PENETRATING RADAR (GPR) OR MEANS OTHER THAN X-RAY. WHERE X-RAY IS REQUIRED, CONTRACTOR SHALL PROVIDE WRITTEN REQUEST A LEAST THREE(3) WEEKS PRIOR TO EVENT; WORK MAY BE REQUIRED TO BE PERFORMED OUTSIDE NORMAL WOK HOURS AND SHALL BE

DOCUMENTED ON THE THREE(3) WEEK LOOK AHEAD SCHEDULE.

32. PROTECT-IN-PLACE FIRE SUPPRESSION SYSTEMS DURING CONSTRUCTION.

33. IF SCOPE OF WORK RESULTS IN LONG-TERM CEILING REMOVAL, CONTRACTOR TO DISCUSS WITH COR WHETHER A RATED ENCLOSURE MUST BE CONSTRUCTED OR TEMPORARY UPRIGHT SPRINKLERS INSTALLED TO MEET NFPA REQUIREMENTS. REFER TO

NFPA 241 (2019), PARAGRAPH 8.6.2

34. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRE-STOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO

PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.

35. CONTRACTOR SHALL BE RESPONSIBLE TO TEMPORARILY MOVE AND RETURN FURNITURE, FIXTURES, AND EQUIPMENT WITHIN SPACES AS REQUIRED TO COMPLETE EACH DAY’S WORK. THE VA WILL REMOVE, OR SECURE, PHI, PPI, AND PERSONAL PROPERTY.

COORDINATE THIS WORK WITH THE COR.

36. PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF EXISTING STRUCTURE AND FINISHES TO PREVENT ANY DAMAGE OF EXISTING FINISHES. ANY ACCIDENTAL DAMAGE INCURRED TO EXISTING CONDITIONS WILL BE RESPONSIBILITY OF THE

CONTRACTOR TO REPAIR OR CORRECT.

37. THESE DRAWINGS WERE PRODUCED FROM ORIGINAL AS-BUILT DRAWINGS AND FIELD OBSERVATIONS AND MAY NOT REPRESENT AN ACCURATE AS-BUILT CONDITION. DISCREPANCIES MAY BE ENCOUNTERED AND IT

IS THE CONTRACTORS RESPONSIBILITY TO FIELD VERIFY ALL CONDITIONS.

KEY PLAN

Q B

C

D

E

F

G

J

H

K

L M

P

N

S H

O T

G U

N

F

IS

H E

R H

O U

S E

PROJECT TEAM

OWNER

SOUTHEAST LOUISIANA VETERANS

HEALTHCARE SYSTEM

(SLVHCS) NEW ORLEANS

ARCHITECT

GDM

2600 AMERICAN ROAD S.E. - SUITE 100

RIO RANCHO, NEW MEXICO 87124

575-300-1481

TELECOMMUNICATIONS

GDM

1584 McNEIL STREET - SUITE 200

DUPONT, WA 98237

360-915-5128

FIRE PROTECTION ENGINEER

TERP CONSULTING

14241 E. 4TH AVENUE - SUITE 5-230

AURORA, CO 80011

720-779-0797

MECHANICAL ENGINEER

GDM

1584 McNEIL STREET. - SUITE 200

DUPONT, WA 98237

360-539-1755

ELECTRICAL ENGINEER

GDM

1584 McNEIL STREET - SUITE 200

DUPONT, WA 98237

360-915-5128

INDUSTRIAL HYGIENE

GDM

23025 W. 15TH AVENUE - SUITE #2-105

PHOENIX, ARIZONA 85027

540-206-7416

CIVIL ENGINEER

GDM

500 ALA MOANA BLVD - SUITE 700

HONOLULU HAWAII 96843

808-551-5601

Revisions Date

1i

NORTH ARROW

STRUCTURAL GRIDLINE

BUILDING SECTION /

WALL SECTION

XX

XX-XXX

XX-XXX

XX

X

EXTERIOR ELEVATIONS

INTERIOR ELEVATIONS XX-XXX

X

XX

XX

XX-XXX

ENLARGED DETAIL DRAWING

ROOM NAME AND NUMBER

WINDOW TYPE

PARTITION ASSEMBLY

TYPE

ELEVATION MARK

DOOR NUMBER

X' - X"

X

GENERAL SYMBOLS LEGEND

NORTH

PROJECT NO.

BUILDING NO.

DRAWING NO.

PROJECT TITLE

FLS

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASEARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

STAMP

LOCATION

''1

CONSULTANTS

GDM of Oregon

1000 W. STEUBEN ST., UNIT 3

BINGEN, WA 98605

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

FOR OFFICIAL USE ONLY (FOUO)

04-25-2023

FULLY

SPRINKLED

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

10% BASIS OF DESIGN 07.08.2022

35% SCHEMATIC DESIGN 11.10.2022

65% DESIGN DEVELOPMENT 01.13.2023

95% CONSTRUCTION DOCUMENTS 03.17.2023

100% FINAL BID DOCUMENTS 04.25.2023

A u to d e s k D o c s

/2 -0

N e w O rl e a n s

E H

R M

/2 -0

N

O L A

E H

R M

C o n c o u rs e

A rc h

P ro d u c ti o n -R

.r v t

GI003

SYMBOLS, ABBREVIATIONS

ES BS

VA NEW ORLEANS (EHRM) ELECTRONIC

HEALTH RECORD MODERNIZATION

INFRASTRUCTURE UPGRADES

2400 CANAL STREET, NEW ORLEANS, LA 70119

100% FINAL BID

DOCUMENTS

629-22-700

J-BOX

HR HOUR

ELECTRICELEC

ETC

EXT

EXH

EW

EXP

EXIST

ENGR

EQUIP

ERD

EQ

ELEV

EMBED

EMER

AND SO FORTH OR ETCETERA

EACH WAY

EXPANSION OR EXPOSED

EXTERIOR, EXTERNAL, OR

EXHAUST

EXISTING

EQUIPMENT

EMBEDMENT

ELEVATION, OR ELEVATOR

EMERGENCY

ENGINEER

EQUAL

EXISTING ROOF DRAIN

INSUL

INT

INV

IN

ID

INC

IDS

HWC

HWR

HWS

HTG

HW

HS

INTRUSION DETECTION SYSTEM

INCORPORATED

IDENTIFICATION, INSIDE DIAMETER, OR

INTERIOR

INVERT

INCHES

HIGH STRENGTH OR

HOT WATER RETURN

HOT WATER SUPPLY

HOT WATER CIRCULATION

HEATING

HOT WATER

OUT

OPP

OH

OF/CI

OD

BLK

CJ

CFM

CI

CEM

CF

BW

CAB

CB

C

BTWN

BV

BTU

BN

BR

BS

BOT

BM

BLDG

BKG

BK

BITUM

BFF

BD

BC

AVE

CUBIC FEET PER MINUTE

BRITISH THERMAL UNIT

CASE IRON OR CENTER OF GRAVITY

CEMENT

CONSTRUCTION OR CONTROL JOINT

CONTRACTOR FURNISHED OR

BOTH WAYS

CABINET

CHANNEL CELSIUS

BALL VALVE

BETWEEN

CATCH BASIN OR CORNER BEAD

EIFS

EJ

EL

E

EF

EB

EA

DS

DTL

DWGTR

DO

DR

DN

DL

BELOW FINISHED FLOOR

BOTH SIDES

BUILDING

BEAM OR BENCH MARK

BEDROOM

BOUNDARY NAIL

BLOCK

BOTTOM

BITUMINOUS

BACKING

BOTTOM OF CURB

AVENUE

BACK

BOARD

DEMO

DIAG

DIM

DIP

DIA

DEPT

DF

DI

DET

DEFL

DBL

D

CUH

CSK

CU YD

CYL

ACST

APPROX

AHU

ASTM

AV

ARCH

ALT

ALUM

AIB

ADJ

AFF

ACT

ADD

AC

A/C

AB

AIR INFILTRATION BARRIER

ABOVE FINISHED FLOOR

ACOUSTICAL CEILING TILE

TESTING AND MATERIALS

AMERICAN SOCIETY FOR

AIR HANDLING UNIT

ALTERNATE

ALUMINUM

ARCHITECT

APPROXIMATE

AUDIO VISUAL

ADDENDUM

ACOUSTIC

ADJACENT, ADJOINING, OR

AIR CONDITIONING

ASBESTOS CEMENT OR

ANCHOR BOLT

CONC

CTB

CORR

CT

CPT

CONT

CONF

CONN

CONSTR

CMP

COL

CMU

CLO

CLR

CLG

CL

GPM

EXTERIOR INSULATION &

FINISH SYSTEM

EXPANSION JOINT

EXHAUST FAN

EXPANSION BOLT

ELEVATION

EAST

EACH

DOWNSPOUT

DEAD LOAD

DETAIL

DUMBWAITER

DITTO

DOOR, DRAIN, DRESSING ROOM

DOWN

HGT

HM

HORIZ

HP

HDPE

HDW

HDR

HD

HB

HC

H

GYP

GV

GYM

DEMOLITION

DIAGONAL DIAGRAM

DEPARTMENT

DRINKING FOUNTAIN

DUCTILE IRON PIPE

DIMENSION

DUCTILE IRON

DIAMETER

DETAIL

CABINET UNIT HEATER

COUNTERSUNK

DEFLECTION

CUBIC YARD

CYLINDER

DEPTH OR PENNY (NAIL)

DOUBLE

GALV

GLU LAM

GPH

GFI

GA

GAL

G

FRT

FURN

FTG

FT

FRP

FOM

FOS

FOF

MRG

GALLONS PER MINUTE

HIGH DENSITY POLYETHYLENE

HOLLOW METAL OR HECTOMETER

HORIZONTAL

HORSEPOWER OR

HEIGHT

HARDWARE

HEADER

HEAD

GATE VALVE

HOSE BIBB

HIGH

HOLLOW CORE

GYPSUM

GYMNASIUM

OC

OA

NUM

NTS

NOM

NIC

NO

MTL

N/A

NFS

N

MTD

MTG

MSL

FIRE RETARDENT TREATMENT

GROUND FAULT INTERRUPTER

FIBER REINFORCED POLYESTER OR

GAUGE OR GAGE OR

GALLONS PER HOUR

GLUE LAMINATED BEAM

GALVANIC OR GALVANIZED

GALLON

NATURAL GAS

FOOT OR FEET

FACE OF MASONRY

FACE OF STUD

FACE OF FINISH

FOOTING

FURNISH OR FURNITURE

MH

MISC

MO

MIN

MFR

MEZZ

MET

MEMB

MAX

MBH

MECH RM

MDO

MB

MACH

MATL

M

CORRUGATED METAL PIPE

CONCRETE MASONRY UNIT

CONCRETE

CORRIDOR

CERAMIC TILE

CONTINUOUS

CONFERENCE

CONNECT

CONSTRUCTION

CERAMIC TILE BASE

CARPET

OCCUPANCY, CLEANOUT, OR COMPANY

CENTERLINE

COLUMN

CLOSET

CEILING

CLEAR

FEC

FL

FLUOR

FN

FOC

FG

FF

FD

FDTN

FE

FDC

FB

FCO

FA

F

FIRE DEPARTMENT CONNECTION

FIRE EXTINGUISHER & CABINET

FACE OF CONCRETE OR

FLUORESCENT

FINISH NAIL

FINISH FACE

FINISH GRADE

FLOORLINE

FIRE BRICK

FIRE ALARM

FIRE EXTINGUISHER

FLOOR CLEANOUT

FOUNDATION

FLOOR DRAIN

FAHRENHEIT OR FEMALE

LF

LT

LT GA

LL

LAV

LBS

LAB

L

JT

KD

JB

JST

JAN

SIM SIMILAR

WD WOOD

OVERHANG

OPPOSITE

CONTRACTOR INSTALLED

OWNER FURNISHED/

OUTSIDE DIAMETER

OUTLET

STRUCTURAL INSULATED PANEL

SLAB-ON-GRADE

SPECIFICATION

SANITARY SEWER ORSS

SOG

SQ

SPEC

SMK

SIP

SL

SQUARE

SHEET METAL

SILL

WIDE FLANGE

WELDED WIRE FABRIC

WOOD FURRING STRIPS

WEIGHT

WOOD FRAME

WT

WWF

WFR

WF

MOISTURE RESISTANT GYP. BRD.

NON FROST SUSCEPTIBLE

NUMBER

NUMERAL

ON CENTER

OUTSIDE AIR OR OVERALL

NOMINAL

NOT IN CONTRACT

NOT TO SCALE

METAL

MOUNTED

NOT APPLICABLE

MEAN SEA LEVEL

NORTH

MOUNTING

THOUSANDS BTU PER HOUR

MEDIUM DENSITY OVERLAY

MANHOLE

MINIMUM MINUTE, MINUTE MINIMUM

MEZZANINE

MEMBRANE

MANUFACTURER

MASONRY OPENING OR

MISCELLANEOUS

METAL

MECHANICAL ROOM

MACHINE BOLT

MACHINE

MATERIAL

MAXIMUM

MALE

RESILIENTRESIL

RIGHT HAND

RIGHT HAND REVERSE

ROUND HEAD MACHINE SCREW

SHOP DRAWINGS, SMOKE DETECTOR OR

SQUARE FOOT (FEET)

SD

SEP

SHT

SF

SAN

SC

SA

S

SEPARATION

SHEET

SHADING COEFFICIENT OR SOLID CORE

SUPPLY AIR

SANITARY

SOUTH

RH

RHWS

RHMS

RHR

RFG

RFP

REV

ROUND HEAD WOOD SCREW

ROOFING

REVISION

REQUEST FOR PROPOSAL

POUNDS PER SQUARE FOOT

RUBBER BASE OR RESILIENT BASE

REFRACTORY REFRIGERATOR

REFLECTED CEILING PLAN

REINFORCE

RECESSED

REF

REQD

REINF

REFR

RD

REC

RB

RCP

REFERENCE

REQUIRED

ROAD OR ROOF DRAIN

RA

R

QA

PSF

PROP

PROJ

PREMLD

QUALITY ASSURANCE

RETURN AIR

RADIUS OR RISER

PROPERTY

PROJECT

PREMOLDED

LABORATORY

LAVATORY

LEAD LINED

LIGHT GAGE

LINEAL FEET

LIGHT

POUND

ANGLE

KILN DRIED OR KNOCKED DOWN

JUNCTION BOX

JANITOR

JOINT

JAMB

JOIST

PROFESSIONAL ENGINEER

POINT OF CONNECTION

PREFORMED JOINT FILLER

POST INDICATOR VALVE

PARALAM BEAM

PLASTIC LAMINATEPLAM

PMTL

PREFIN

PR

POC

PP

PLYWD

PLCS

PLB

PAINTED METAL

PREFINISH

POWER POLE

PAIR

PLACES

PLYWOOD

PH

PJF

PKG

PIV

P.E.

PEN

PC

PAVT

PHASE

PACKAGE

PAVEMENT

PENETRATION

PIECE, POLYCARBONATE OR

THK THICKNESS

UNITED STATES

UTILITY

VINYL COMPOSITION TILE

WATER CLOSET OR

VESTIBULE

VERTICAL

VENT THROUGH ROOF

VINYL WALL COVERING

VIDEO DISPLAY TERMINAL

VEST

W

WC

W/

VWC

VTR

WEST OR WIDE

WITH

VERT

VDT

VCT

V

UTIL

US

VOLT

TOP OF JOIST

TOP OF BEAM

TOP OF FOOTING

TOP OF CONCRETE

TYPICAL

TENSILE STRENGTH OR

TELEVISION

TOP OF STEEL

UNIT HEATER

HEAT TRANSFER COEFFICIENT

UNDERGROUND ELECTRICAL

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNDERGROUND TELEPHONE

TYP

UG/E

UG/T

UH

UL

UON

U

TOJ

TV

TS

TOS

TOC

TOF

TOB

STATION

STANDARD

STRUCTURAL

SHEET VINYL

SUSPENDED

STORAGE

STAIRS OR STREET

SYNTHETIC

TONGUE & GROOVE

TEMPERATURE OR TEMPORARY

TECHNICAL

TELEPHONE

TOP OF CURB

THROUGH BOLT OR TOWEL BAR

SV

T & G

TEMP

TEL

TECH

TC

TB

SYNTH

STRUCT

SUSP

STOR

STL JST

STD

STE

STA

ST

STEEL JOIST

SUITE

(E) EXISTING

(N) NEW

CF/CI CONTRACTOR FURINSHED/

GFGI GOV'T FURNISHED, GOV'T INSTALLED

FUT FUTURE

GYP BRD GYPSUM BOARD

PORTLAND CEMENT

OR DRIVE

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURINSHED/

OWNER INSTALLED

FACE OF CURB

OF/OI

OWNER INSTALLED

OWNER FURNISHED/

AAMA

ACT

AE

A/C

A LABEL

ACOUSTICAL CEILING TILE

AMERICAN ARCHITECTURAL

AIR CONDITIONING

ARCHITECT/ENGINEER

CLASS A DOOR

A/C UNIT AIR CONDITIONING UNIT

MANUFACTURERS ASSOCIATION

ABASS AGGREGATE BASE COURSE

ASPHALTIC CONCRETE

ACI AMERICAN CONCRETE INSTITUTE

ACS DR ACCESS DOOR

ACS FLR ACCESS FLOOR

ACS PNL ACESS PANEL

AD AREA DRAIN

ADC AUTOMATIC DOOR CLOSER

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJUSTABLE

ADMIN ADMINISTRATION

ADB AUTOMATIC DOOR BOTTOM

AFC ABOVE FINISHED COUNTER

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGA AMERICAN GAS ASSOCIATION

AGC ASSOCIATED GENERAL CONTRACTORS

AGGR AGGREGATE

AHJ AUTHORITY HAVING JURISDICTION

AHR ANCHOR

AIA AMERICAN INSTITUTE OF ARCHITECTS

AISC AMERICAN INSTITUTE OF STEEL

CONSTRUCTION

ALT NO ALTERNATE NUMBER

AMP AMPERE

AMT AMOUNT

ANOD ANODIZE

ANSI AMERICAN NATIONAL STANDARDS

INSTITUTE

ANT ANTENNA

APA AMERICAN PLYWOOD ASSOCIATION

APPD APPROVED

APT APARTMENT

AR AS REQUIRED

ASB ASBESTOS

ASI ARCHITECT'S SUPPLEMENTAL

INSTRUCTION

ASPH ASPHALT

ASKLR AUTOMATIC SPRINKLER

ASSN ASSOCIATION

ATCH ATTACHMENT

ATM AUTOMATIC TELLER MACHINE

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AVG AVERAGE

AW ACID WASTE

AWI ARCHITECTURAL WOODWORKING

INSTITUTE

AWPA AMERICAN WOOD PRESERVER'S

ASSOCIATION

AWS AMERICAN WELDING SOCIETY

AWT ACOUSTICAL WALL TREATMENT

B LABEL CLASS B DOOR

B PL BASE PLATE

BALC BALCONY

BAT BATTEN

BB BULLETIN BOARD

BD FT BOARD FEET (FOOT)

BEV BEVEL

BHMA BUILDER'S HARDWARE

MANUFACTURER'S ASSOCIATION

BI FLD DR BI-FOLDING DOORS

BLD BUILD

BL BUILDING LINE

BLKT BLANKET

BRCG BRACING

BRDG BRIDGING

BRDG JST BRIDGING JOIST

BRG BEARING

BRG PL BEARING PLATE

BRKT BRACKET

BRZ BRONZE

BSMT BASEMENT

BU BUSHEL

BUR BUILT-UP ROOFING

C CELSIUS CHANNEL

C CONC CASE CONCRETE

C LABEL CLASS C DOOR

C TO C CENTER TO CENTER

CAC CEILING ATTENUATION CLASS

CBB CEMENTITIOUS (BACKER) BOARD

CC CUBIC CENTIMETER

CCTV CLOSED CIRCUIT TELEVISION

CCW COUNTERCLOCKWISE

CD CONSTRUCTION DOCUMENTS OR

CONTRACT DOCUMENTS

CEM PLAS CEMENT PLASTER

CER CERAMIC

CEILING FAN

CFLG COUNTERFLASHING

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CAST IRON

OR CORNER GUARD

CGSFU CERAMIC GLASED STRUCTURAL

FACING UNITS

CH BD CHALKBOARD

CHEM CHEMICAL

CHFR CHAMFER

CHK CHECK

CIP CASE IN PLACE

CIR CIRCLE

CIRC CIRCULAR

CLDG CLADDING

CLG HT CEILING HEIGHT

cm SQUARE CENTIMETER cm CUBIC CENTIMETER

CM CONSTRUCTION MANAGEMENT

CNR CORNER

CNRT COUNTER

CO CARBON MONOXIDE, CERTIFICATE OF

CO 2 CARBON DIOXIDE

COM COMMON

COMB COMBINATION, COMBINED

COMM COMMUNICATION

COMP COMPONENT

CONC FLR CONCRETE FLOOR

COND CONDENSER OR CONDITION

CONTR CONTRACTOR

COORD COORDINATE

CPM CRITICAL PATH METHOD

CPRS COMPRESSIBLE

CRS COLD ROLLED STEEL

CRSI CONCRETE REINFORCING

STEEL INSTITUTE

CSB CONCRETE SPLASH BLOCK

CSG CASING

CSI CONSTRUCTION SPECIFICATIONS

INSTITUTE

CSMT CASEMENT

CSWK CASEWORK

CTF CERAMIC TILE FLOOR

CTG COATING

CTR CENTER CONTOUR

CTRL CONTROL

CTV CABEL TELEVISION

CU COPPER C

CU FT CUBIC FEET

CU IN CUBIC INCH

CURT CURTAIN

CYL L CYLIINDER LOCK

CW COLD WATER

D LABEL CLASS D DOOR

DAT DATUM

DB DECIBEL

DBL GLZ DOUBLE GLAZE

DC DIRECT CURRENT

DEG DEGREE

DEL DELETE

DIFF DIFFERENCE OR DIFFUSER

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE OR DIVISION

DOC DOCUMENT

DOUG FIR DOUGLAS FIR

DOZ DOZEN

DR CL DOOR CLOSER

DR FR DOOR FRAME

DR OPNG DOOR OPENING

DSGN DESIGN

DW DISHWASHER

DWG DRAWING

E LABEL CLASS E DOOR

EFF EFFICIENCY

EFS EXTERIOR FINISH SYSTEM

ELAST ELASTOMERIC

ELECTRIC DOOR OPENERELEC DR OP

EMER SHR EMERGENCY SHOWER

ENCL ENCLOSURE

ENVIR ENVIRONMENT

EPA ENVIRONMENTAL PROTECTION AGENCY

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EPO EMERGENCY POWER OFF

EPS EXPANDED POLYSTYRENE BOARD

(INSULATION)

EQL SP EQUALLY SPACED

EQUIV EQUIVALENT

ESC ESCAPE OR ESCUTCHEON

ESCAL ESCALATOR

ESMT EASEMENT

ESP ESPECIALLY

EST ESTIMATE

EWC ELECTRICAL WATER COOLER

EWS EYE WASH STATION

EXP BT EXPANSION BOLT

EXST GR EXISTING GRADE

EXTINGUISHER

EXT GR EXTERIOR GRADE

FAB FABRIC

FAC FACTOR

FACIL FACILITY

FAS FASCIA

FAS BD FASCIA BOARD

FCTY FACTORY

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND EQUIPMENT

FH FLAT HEAD OR FLAT HEAD SCREWS

FHC FIRE HOSE CABINET

FHMS FLAT HEAD MACHINE SCREW

FHP FULL HEIGHT PARTITION

FHWS FLAT HEAD WOOD SCREW

FIG FIGURE

FIL FILLET

FIN FINISH

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIN WD FINISH WOOD

FIXT FIXTURE

FLASH FLASHING

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLR FLOOR

FLR FIN FLOOR FINISH

FLR SK FLOOR SINK

FLUOR FIX FLUORESCENT FIXTURE

FM FACTORY MUTUAL

FM-G FACTORY MUTUAL-GLOBAL

FO FINISHED OPENING

FPM FEET PER MINUTE

FP FIRE PROTECTION OR FIREPROOF

FOW FACE OF WALL

FOUNT FOUNTAIN

FPS FEET PER SECOND

FR FIRE RATING, FIRE RESISTANT,

OR FRAME

FR SNK FLUSHING RIM SINK

FREQ FREQUENCY

FRMC FRAMING

FIBER REINFORCED PLASTIC

FRZ FREEZER

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FURG FURRING

FV FIELD VERIFY

FWC FABRIC WALLCOVERING

GYPSUM ASSOCIATON

GALV STL GALVANIZED STEEL

GB GRAB BAR

GC GENERAL CONTRACTOR

GD GUARD

GDR GUARD RAIL

GEN GENERAL OR GENERATOR

GFRC GLASS-FIBER-REINFORCED CONCRETE

GFRG GLASS-FIBER-REINFORCED GYPSUM

GFRP GLASS-FIBER-REINFORCED PLASTIC

GI GALVANIZED IRON

GL GLASS

GL BLK GLASS BLOCK

GR FLR GROUND FLOOR

GRAN GRANITE

GRTG GRATING

GSB GYPSUM SHEATHING BOARD

GSM GALVANIZED SHEET METAL

GSU GLAZED STRUCTURAL UNIT

GT GROUT

GUAR GUARANTEE

GUT GUTTER

GYP PLAS GYPSUM PLASTER

H PLAM HIGH PRESSURE

HAZ MAT HAZARDOUS MATERIALS

PLASTIC LAMINATE

HCWD HOLLOW CORE WOOD DOOR

HDBD HARDBOARD

HDNR HARDENER

HDO HIGH DENSITY OVERLAY

HDWD HARDWOOD

HEPA HIGH EFFICIENCY PARTICULATE

AIR (FILTER)

HEX HEXAGON

HF HIGH FREQUENCY

HGR HANGER

HMD HOLLOW METAL DOOR

HMDF HOLLOW METAL DOOR AND FRAME

HMF HOLLOW METAL FRAME

HNDRL HANDRAIL

HO HOLD OPEN

HOSP HOSPITAL

HIGH PRESSURE

HQ HEADQUARTERS

HEAT-STRENGTHENED (GLASS)

HSE HOUSE

HSKPG HOUSEKEEPING

HST HOIST

HT HEIGHT

HVAC HEATING, VENTILATION, AND

AIR CONDITIONING

HVY HEAVY

HYD HYDRANT

HYDR HYDRAULIC

I INTERSTATE (HIGHWAY) OR

MOMENT OF INERTIA

IAQ INDOOR AIR QUALITY

IBC INTERNATIONAL BUILDING CODE

INTERIOR DESIGN

ID NO IDENTIFICATION NUMBER

ILLUM ILLUMINATION

INCL INCLUDED

IND INDEPENDENT OR INDUSTRIAL

INFO INFORMATION

INSULATION

INTERCOM INTERCOMMUNICATION

INTL INTERNATIONAL

IRMA INVERTED ROOF MEMBRANE

ASSEMBLY

IWH INSTANTANEOUS WATER HEATER

KIT KITCHEN

KO KNOCKOUT

KPL KICKPLATE

LAD LADDER

LAM LAMINATE

LAM GL LAMINATED GLASS

LAU LAUNDRY

LBR LUMBER

LD BRG LOAD-BEARING

LDR LEADER

LED LIGHT EMITTING DIODE

LH LEFT HAND

LHR LEFT HAND REVERSE

LHR LEFT HAND REVERSE

LATENT HEAT RATIO

LIB LIBRARY

LIN LINEAR

LINO LINOLEUM

LIQ LIQUID

LKR LOCKER

LKR RM LOCKER ROOM

LKWASH LOCKWASHER

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMST LIMESTONE

LNDSCP LANDSCAPE

LR LIVING ROOM

LRG LARGE

LRV LOUVERED ROOF VENT

LS LUMP SUM

LT WT LIGHTWEIGHT

LTG LIGHTING

LTNG LIGHTNING

LVD LOUVERED

LVR LOUVER

LWC LIGHTWEIGHT CONCRETE

LWIC LIGHTWEIGHT INSULATING CONCRETE

LYR LAYER

MACH RM MACHINE ROOM

MAINT MAINTENANCE

MAN MANUAL

MATV MASTER ANTENNA

TELEVISION SYSTEM

MCB METAL CORNER BEAD

MD METAL DECK

ME MECHANICAL ENGINEER

MEAS MEASURE

MED MEDICAL MEDIUM, MEDIUM MEDICAL

MEK METHYL ETHYL KETONE

MEL MELAMINE

MEMO MEMORANDUM

MF MILL FINISH

MFD MANUFACTURED

MFG MANUFACTURING

MFR REC MANUFACTURER'S RECOMMENDATION

MGT MANAGEMENT

MIC MICROPHONE

MID MIDDLE

MIL STD MILITARY STANDARD

MIRR MIRROR

MIT MITER

MKR MARKER

ML METAL LATH

MLDG MOLDING (MOULDING)

MLWK MILLWORK

mm MILLIMETER

MOTOR OPERATED

MOD MODEL, MODIFY OR MODULE

MOD BIT MODIFIED BITUMEN

MON MONITOR

MOPR MOP RACK

MR MOISTURE RESISTANT

MS MACHINE SCREW OR MOP SINK

MULL MULLION

MW MICROWAVE

MWP MEMBRANE WATERPROOFING

NAAMM NATIONAL ASSOCIATION OF

ARCHITECTURAL METAL

MANUFACTURERS

NAT NATURAL

NATL NATIONAL

NC NOISE CRITERIA

NCOMBL NONCOMBUSTIBLE

NEC NATIONAL ELECTRICAL CODE

NEG NEGATIVE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT NEUTRAL

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NR NOISE REDUCTION

NRC NOISE REDUCTION COEFFICIENT

NRCA NATIONAL ROOFING CONTRACTORS

ASSOCIATION

NRP NONREMOVABLE

NS NARROW STILE

O/O OUT TO OUT

0 OXYGEN

OCC OCCUPY

OCT OCTAGON

OUTER DIMENSION

OFD OVERFLOW DRAIN

OFF OFFICE

OH DR OVERHEAD (COILING) DOOR

OPH OPPOSITE HAND

OPNG OPENING

OPR OPERABLE

OPT OPTIONAL

OR OPERATING ROOM OR

OUTSIDE RADIUS

ORD ORDNANCE OR OVERFLOW

ROOF DRAIN

ORG ORGANIC

ORIG ORIGINAL

ORN ORNAMENTAL

OSHA OCCUPATIONAL SAFETY AND

HEALTH ADMINISTRATION

OZ. OUNCE

PAR PARALLEL OR PARAPET

PARA PARAGRAPH

PART PARTIAL

PAT PATTERN

PB PUSHBUTTON

PBD PARTICLEBOARD

PCA PORTLAND CEMENT ASSOCIATION

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCD PAPER CUP DISPENSER

PCF POUNDS PER CUBIC FOOT

PCP PORTLAND CEMENT PLASTER

PEDESTALPED

PEND PENDANT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PGBD PEGBOARD

PHAR PHARMACY

PHOTO PHOTOGRAPH

PHS PHILLIPS HEAD SCREW

PL PROPERTY LINE

PL GL PLATE GLASS

PLASTER OR PLASTICPLAS

PLUMBINGPLBG

PNL PANEL

PNEU PNEUMATIC

POST OFFICEPO

PURCHASE ORDER

POLYETHYLENE (PLASTIC)POLY

PRCST PRECAST

PREFAB PREFABRICATE

PRELIM PRELIMINARY

PREP PREPARATION

PRESS PRESSURE

PREV PREVIOUS

PRKG PARKING

POLYVINYL CHLORIDE (PLASTIC)PVC

PTN

PTD

PT

PARTITION

PAPER TOWEL DISPENCER

PAINT, PNEUMATIC TUBE, OR

POUNDS PER SQUARE INCHPSI

PRESSURE TREATED

PAVINGPVG

POWERPWR

QC QUALITY CONTROL

QRY QUARRY

QT QUARRY TILE

QTB QUARRY TILE BASE

QTF QUARRY TILE FLOOR

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

RADIATORRAD

ROBE HOOKRB HK

REINFORCED BRICK MASONRYRBM

RUBBERRBR

RCVR RECEIVER

RECEIVEDRECD

RECEPTACLERECPT

RECTANGLERECT

REGISTERREG

REPAIRREP

REPLACEREPL

REQ REQUIRE

RETURNRET

REF RADIO FREQUENCY

RFI REQUEST FOR INFORMATION

RL ROOF LEADER

RLG RAILING

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RPM REVOLUTIONS PER MINUTE

RS ROUGH SAWN

RT RIGHT

RV ROOF VENT

RVS REVERSE

RWD REDWOOD

RWL RAIN WATER LEADER

SALV SALVAGE

SAMP SAMPLE

SAT SUSPENDED ACOUSTICAL TILE

SATC SUSPENDED ACOUSTICAL TILE CEILING

SB SPLASH BLOCK

SBS STYRENE BUTADIEN STYRENE

SBSTR SUBSTRATE

SCH SCHOOL

SCHED SCHEDULE

SCHEM SCHEMATIC

SCP SCUPPER

SCRN SCREEN

SCT STRUCTURAL CLAY TILE

SCWD SOLID CORE WOOD DOOR

OR SOAP DISPENSER

SIDINGSDG

SECTIONSECT

SEG SEGMENT

SEL SELECT

SOFTWOODSFTWD

SLIDING GLASS DOORSGD

SINGLESGL

SHR SHOWER

SHR HD SHOWER HEAD

SHRD SHOWER DRAIN

SHT MTL SHEET METAL

SHTHG SHEATHING

SHV SHELVING

SJ SCORED JOINT

SJI STEEL JOIST INSTITUTE

SK SKETCH

SKLT SKYLIGHT

SLD WDW HORIZONTAL SLIDING WINDOW

SLDG SLIDING

SLNT SEALANT

SM

SMOKE

SND SANITARY NAPKIN DISPENSER

SND INS SOUND INSULATION

SNDU SANITARY NAPKIN

DISPOSAL UNIT

SPRINKLERSPKLR

SPEAKERSPKR

SUPPLYSPLY

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SERVICE SINK

STAINLESS STEELSST

SOUND TRANSMISSION CLASSSTC

STL STEEL

STL LNTL STEEL LINTEL

STL PL STEEL PLATE

STL RF DK STEEL ROOK DECK

STL TB STEEL TUBING

STL TR STEEL TRUSS

STAINLESSSTNLS

STRINGERSSTR

STRUCTURAL STEELSTRUCT STL

SUBSTITUTESUB

SURFACESURF

SUSPENDED CEILIINGSUSP CLG

SWITCHSW

SWING DOORSWDR

SYMBOLSYM

SYSTEMSYS

TREADT

TIME AND MATERIALST & M

TILE COUNCIL OF AMERICATCA

TELEPHONE CONTROL PANELTCP

OR TRAFFIC CONTROL PLAN

TEMPERATURE

TOWEL DISPENSERTD

TERRAZZOTER

THERM THERMAL

THD THREAD

THRES THRESHOLD

THRU THROUGH

THRUOUT THROUGHOUT

TACKBOARDTK BD

TEMPEREDTMPD

TEMPERED GLASSTMPD BL

TRUE NORTHTN

TOP OF ___TO

TOP OF FOUNDATIONTO FDN

TOP OF MASONRYTOM

TOP OF PARAPETTOP

TOP OF WALLTOW

TOILET PAPER DISPENSERTPD

TOILET PAPER HOLDERTPH

TOWEL RACKTR

TRANSOMTRANS

TRANSPARENT WOOD FINISHTRANS WD FIN

TREATEDTRTD

TUBE STEEL

THERMOSTATTSTAT

UNDERCUTUC

UNDERCUT DOORUCD

UNDERGROUNDUGND

ULTIMATEULT

UNFINISHUNFIN

UNINTERRUPTIBLEUPS

POWER SUPPLY

URINALUR

ULTRAVIOLETUV

VACUUMVAC

VARIESVAR

OR VITRIFIED CLAY TILE

VEHICLEVEH

VENTILATIONVENT

VINYL FACED ACCOUSTICAL TILEVFAT

VICINITYVIC

VIDEOVID

VERIFY IN FIELDVIF

VENEERVNR

VOLATILE ORGANIC COMPOUNDVOC

VOLUMEVOL

VOLTAGEVOLT

VENEER PLASTERVP

VAPOR RETARDERVR

VINYL WALL FABRICVWF

W/O WITHOUT

WARR WARRANTY

WOOD BLOCKINGWBL

WALL COVERING

WATER CLOSET, WALL HUNGWC WL HNG

WATER CHILLERWCHR

WATER COOLER, WALL HUNGWCL WL MTD

WDW WINDOW

WALL FABRICWFAB

WFS

WATER HEATERWH

WAREHOUSEWHSE

WELDEDWLD

WIRE MESHWM

WATERPROOFINGWP

WATER PRESSURE DROPWPD

WATERPROOF MEMBRANEWPM

WEATHER RESISTANTWR

WEATHERSTRIPWS

WAINSCOTWSCT

CROSS BRACEX BRACE

EXTRUDED POLYSTYRENEXPS

YARDYD

YEARYR

BOARD (INSULATION)

TYPICAL ABBREVIATIONS

Revisions: Date:

File details come from the government source that posted it. Updated .