This solicitation is for an Indefinite-Delivery, Indefinite-Quantity, Multiple Award Construction Contract to provide large general construction projects primarily in the Hampton Roads Area of Responsibility in Virginia. The solicitation is seeking proposals for design-build and design-bid-build construction services for facilities within the scope of the Naval Facilities Engineering Command. Projects may include new construction, renovation, and repair work. The multiple award contracts have no defined limits and will have ordering periods extending up to 60 months after award. The Department of the Navy is the issuing agency.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTIONSYMBOL
PROVIDE TELEPHONE AND DATA SYSTEMS
TELEPHONE TERMINAL BACKBOARD - SIZE AS INDICATED.
WIRE, CONDUIT AND RACEWAY
CABLE TRAY, SIZE AND TYPE AS INDICATED.
NOTE REFERENCE - TYPICALLY LOCATED ON SAME SHEET
WHERE SYMBOL IS USED.
COMBINATION OUTLET BOX WITH MODULAR JACKS. PROVIDE
WITH (4) CAT6 CONNECTORS AND (4) CAT6 UTP CABLES IN 1"
CONDUIT TO UNCLASSIFIED TELECOM RACK OR ENCLOSURE
AND TERMINATE ON PATCH PANEL. MOUNT +18" AFF, UON.
POINT OF CONNECTION NEW-TO-EXISTING (SEE LEGEND NOTE
1 THIS SHEET)
POINT OF DEMOLITION
ROOM NUMBER.
GENERAL
EQUIPMENT CONNECTIONS
JUNCTION BOX AS INDICATED.J
GROUNDING BUS BAR. TYPE AS INDICATED.
OUTLET FOR LOCAL CABLE SERVICE PROVIDER. PROVIDE
OUTLET WITH (1) F-TYPE FEMALE CONNECTOR WITH RG6
COAXIAL CABLE IN 3/4" CONDUIT RUN BACK TO SERVICE
PROVIDERS HEAD END EQUIPMENT LOCATED IN COMM ROOM
140. RUN CONDUITS ABOVE FINISHED CEILING SPACE. MOUNT +
60" AFF, UON.
PROTECTED ENTRANCE TERMINAL.P.E.T.
VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
TE
LE
C O
M M
U N
IC
A
TI
O
N S
L E
G E
N D
A N
D N
O
TE
S
RC
12822793
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
T-001
TELECOMMUNICATIONS LEGEND
GENERAL NOTES
1. OPENING CREATED IN A FIRE OR SMOKE RATED WALL OR FLOOR BY
PROVISION OF ANY ELECTRICAL DEVICE OR CONDUIT, SHALL BE SEALED
AFTER THE WORK IS COMPLETED WITH A UL APPROVED FIRE/SMOKE
SEALANT APPROPRIATE TO RE-ESTABLISH THE PREVIOUS RATING OF
THE WALL OR FLOOR. SEE ARCHITECTURAL PLANS FOR FIRE RATED
WALLS/FLOORS AND THEIR RATING.
2. WHERE CABLE TRAY IS NOT USED, INDIVIDUAL CONDUIT WITH BUSHINGS
SHALL BE INSTALLED FROM THE TELECOMMUNICATIONS ROOM TO EACH
OUTLET, UNLESS OTHERWISE NOTED. CONDUIT LENGTHS ARE NOT TO
EXCEED 100' BETWEEN PULL POINTS AND NO MORE THAN 180 DEGREES
OF BEND BETWEEN PULL POINTS.
3. SEE "ES" AND "ESD" SERIES SHEETS FOR EXTERIOR
TELECOMMUNICATIONS WORK.
4. PROVIDE NYLON PULLSTRING IN EMPTY CONDUIT.
5. PROVIDE "SPARE" DUCTS AND CONDUITS WITH NYLON PULLSTRING AND
END CAPS.
6. SEE SHEET "E-001" FOR ADDITIONAL ABBREVIATIONS.
LEGEND NOTES
1. WHERE A NEW-TO-EXISTING CONNECTION IS INDICATED, PROVIDE
MATERIAL AND LABOR REQUIRED TO MAKE THE CONNECTION.
GENERAL COMMUNICATIONS
DEMOLITION NOTES
1. WHERE DEMOLITION WORK FOR BUILDING SERVICES(S) IS SHOWN, ALL
WORK RELATED TO SERVICE INTERRUPTIONS/OUTAGES SHALL BE
COORDINATED IN ADVANCE WITH EACH OF THE BASE FACILITIES
RESPECTIVE SERVICE(S). PROVIDE IN ADVANCE, DETAILED AND
SCHEDULED TIME FRAME OF WORK FOR SERVICE INTERCEPTION(S)
FROM START TO COMPLETION OF THE WORK INTENDED AND MUST BE
SUBMITTED IN WRITING A MINIMUM OF 6 WEEKS IN ADVANCE. APPROVAL
FROM BASE FACILITIES NAVAL COMPUTER AND TELECOMMUNICATIONS
AREA MASTER STATION (NCTAMS) MUST BE OBTAINED PRIOR TO START
OF DEMOLITION WORK.
2. THE FOLLOWING WORK SHALL BE DONE PRIOR TO START OF
DEMOLITION WORK.
A. CONTRACTOR TO INSTALL 4" CONDUIT AND 100 PAIR COPPER
CABLE FROM MANHOLE V33 TO MANHOLE V51A TO FEED EXISTING
BUILDING V64.
B. NCTAMS WILL SEVER CURRENT 100 PAIR COPPER CABLE AT
MANHOLE U14 THAT FEEDS TO MANHOLE V52.
C. NCTAMS WILL SPLICE NEW CABLE IN MANHOLE V33, MANHOLE
V51A, MANHOLE U14 AND MANHOLE 9.
D. NCTAMS WILL SEVER CURRENT 100 PAIR COPPER CABLE AT
MANHOLE V51A THAT FEEDS TO MANHOLE V52.
E. COPPER CABLE BETWEEN MANHOLE U14 AND MANHOLE V52 AND
MANHOLE V51A WILL BE REMOVED BY CONTRACTOR.
F. MANHOLE V52 WILL BE REMOVED BY CONTRACTOR.
TELECOM ABBREVIATIONS
AFF
AFG
BG
BLDG
DWG
LAN
NCTAMS
TEL
TG
TMGB
UTP
OSP
IDC
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BELOW GRADE
BUILDING
DRAWING
LOCAL AREA NETWORK
NAVAL COMPUTER AND TELECOMMUNICATIONS
AREA MASTER STATION
TELEPHONE
TELECOMMUNICATIONS GROUND BUS
TELECOMMUNICATIONS MAIN GROUND BUS
UNSHIELDED TWISTED PAIR
OUTSIDE PLANT
INSULATION DISPLACEMENT CONTACT
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
ELEC.
FILTER
STORAGE
CORR.
BLAST
MEDIA
STORAGE
BLAST
MEDIA
RECOVERY
COMPRESSOR
ROOM
PMB BAY
TT401
C1
+48"
WOMEN'S
LOCKER
ROOM
(CLEAN)
CORR.
AIR DRY
MATCHLINE
TT102
PMB
STORAGE
LOCKER
ROOM
(DIRTY)
MEN'S
LOCKER
ROOM
(CLEAN)
CORR.
+48"
+48"
JAN.
HAZARDOUS LOCATION
LISTED AREA
HAZARDOUS LOCATION
LISTED AREA
COMM.
109 VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
TE
LE
C O
M M
U N
IC
A
TI
O
N S
P
LA
N
A R
E A
A
RC
12822794
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
TT101
1/8" = 1' - 0"
0 5' 10' 15' 30'
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
AREA
A
AREA
B
AREA
D
AREA C
V-147
SCALE: 1/8" = 1'-0"
TELECOMMUNICATIONS PLAN - AREA A
1 AREA ELECTRICALLY CLASSIFIED AS HAZARDOUS CLASS II, DIVISION 1,
PER NEC ARTICLE 500.5 AND GROUP G PER NEC ARTICLE 500.6. PROVIDE
APPROPRIATE LISTED ELECTRICAL DEVICES WITHIN THIS AREA.
2 AREA ELECTRICALLY CLASSIFIED AS HAZARDOUS CLASS I, DIVISION 1
PER NEC ARTICLE 500.5 AND GROUP C PER NEC ARTICLE 500.6. PROVIDE
APPROPRIATE LISTED ELECTRICAL DEVICES WITHIN THIS AREA.
3 (2) 4" CONDUITS WITH BUSHINGS RUN ABOVE FINISHED CEILING SPACE.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
MEN'S
LOCKER
ROOM
(CLEAN)
CORR.
PAINT BAY
EXHAUST
AIR
PLENUM
PAINT BAY
BREAK
+48"
MECH
104A
+48" 3
MATCHLINE
TT101
MATCHLINE
TT103
+48"
HAZARDOUS LOCATION
LISTED AREA
ISSUE
120E
AIR LOCK
AIR LOCK
120C
PAINT BAY
STORAGE
VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
TE
LE
C O
M M
U N
IC
A
TI
O
N S
P
LA
N
A R
E A
B
RC
12822795
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
TT102
1/8" = 1' - 0"
0 5' 10' 15' 30'
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
AREA
A
AREA
B
AREA
D
AREA C
V-147
SCALE: 1/8" = 1'-0"
TELECOMMUNICATIONS PLAN - AREA B
1 (2) 4" CONDUITS WITH BUSHINGS RUN ABOVE FINISHED CEILING SPACE.
2 AREA ELECTRICALLY CLASSIFIED AS HAZARDOUS CLASS I, DIVISION 1,
PER NEC ARTICLE 500.5 AND GROUP C PER NEC ARTICLE 500.6. PROVIDE
APPROPRIATE LISTED ELECTRICAL DEVICES WITHIN THIS AREA.
3 DATA OUTLET FOR DDC CONTROLS. MOUNT ADJACENT TO EQUIPMENT
BEING SERVED.
4 18" SQUARE X18" DEEP WITH REMOVABLE COVER ABOVE FINISHED
CEILING SPACE.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
ADMIN
TOOL CRIB
MATERIAL
STORAGE
PAINT
STORAGE
MECHANICAL
ROOM
EQUIPMENT
CLEANING
STENCIL
ROOM
CORR.
PAINT
MIXING
ADMIN
CLOSET
101A
MOTHER'S
ROOM
2 1
MATCHLINE
TT102
MATCHLINE
TT104
HAZARDOUS LOCATION
LISTED AREA 3
VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
TE
LE
C O
M M
U N
IC
A
TI
O
N S
P
LA
N
A R
E A
C
RC
12822796
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
TT103
1/8" = 1' - 0"
0 5' 10' 15' 30'
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
AREA
A
AREA
B
AREA
D
AREA C
V-147
SCALE: 1/8" = 1'-0"
TELECOMMUNICATIONS PLAN - AREA C
1 (2) 4" CONDUITS RUN WITH BUSHINGS ABOVE FINISHED CEILING SPACE.
2 18" SQUARE X18" DEEP WITH REMOVABLE COVER ABOVE FINISHED CEILING
SPACE.
3 AREA ELECTRICALLY CLASSIFIED AS CLASS I, DIVISION 1 PER NEC ARTICLE
500.5 AND GROUP C. PER NEC ARTICLE 500.6 PROVIDE APPROPRIATE LISTED
ELECTRICAL DEVICES WITHIN THIS AREA.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
TOILET
WASH
RACK
STORAGE
WATER
TREATMENT
SYSTEM
WASH
RACK BAY
TT401
C3
DECONTAMINATION
CENTRAL
CHEMICAL
STORAGE
SOLVENT
STORAGE
FIRE
PROTECTION
ELEC.
+48"
MATCHLINE
TT103
+48"
HAZARDOUS LOCATION
LISTED AREA
TOILET
LOCKER
ROOM
(DIRTY)
JAN.
CORR.
WASH
RACK
(PROCESS)
WASH
RACK
EQUIPMENT
COMM.
VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
TE
LE
C O
M M
U N
IC
A
TI
O
N S
P
LA
N
A R
E A
D
RC
12822797
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
TT104
1/8" = 1' - 0"
0 5' 10' 15' 30'
GRAPHIC SCALE(S)
KEY PLAN
# KEY NOTES
AREA
A
AREA
B
AREA
D
AREA C
V-147
SCALE: 1/8" = 1'-0"
TELECOMMUNICATIONS PLAN - AREA D
1 AREA ELECTRICALLY CLASSIFIED AS HARZARDOUS CLASS II, DIVISION 1
PER NEC ARTICLE 500.5 AND GROUP G PER NEC ARTICLE 500.6. PROVIDE
APPROPRIATE LISTED ELECTRICAL DEVICES WITHIN THIS AREA. PROVIDE
CONDUIT APPROVED FOR WET LOCATION APPLICATION WITHIN THIS
AREA.
2 (2) 4" CONDUITS RUN ABOVE FINISHED CEILING SPACE.
3 18" SQUARE X18" DEEP WITH REMOVABLE COVER ABOVE FINISHED
CEILING SPACE.
4 DATA OUTLET FOR FIRE ALARM ANNUNCIATOR PANEL. MOUNT ADJACENT
TO EQUIPMENT BEING SERVED.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
COMM.
+48"
T2
TT401
P .E
.T
TT401
13 7
T1
TT401
TT401
FIRST FLOOR
0' - 0"
ADMIN ROOF
14' - 0"
TT401
(2) 4" CONDUITS
STUBBED THROUGH
WALL.
VERTICAL RUN
OF CABLE TRAY
LIGHT FIXTURE,
TYPICAL
FIRST FLOOR
0' - 0"
ADMIN ROOF
14' - 0"
TT401
4" CONDUIT STUBBED
THROUGH WALL.
VERITICAL RUN OF CABLE TRAY
LIGHT FIXTURE,
TYPICAL
FIRST FLOOR
0' - 0"
ADMIN ROOF
14' - 0"
T2
4" CONDUIT
VERTICAL RUN OF CABLE TRAY
LIGHT FIXTURE,
TYPICAL
FIRST FLOOR
0' - 0"
ADMIN ROOF
14' - 0"
VERTICAL RUN OF CABLE TRAY
LIGHT FIXTURE,
TYPICAL
VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
E N
LA
R
G E
D T
E
LE
C O
M M
U N
IC
A
T
IO
N S
RC
12822798
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
TT401
NOT TO SCALE (TT104)C3
ENLARGED COMMUNICATION ROOM 140
NOT TO SCALE (TT101)C1
ENLARGED COMMUNICATION ROOM 109
1/4" = 1' - 0" 0 5' 10' 15'1'
GRAPHIC SCALE(S)
# KEY NOTES
1 (2) 4" CONDUITS. STUB CONDUITS DOWN TO CABLE TRAY.
2 3/4" THICK FIRE RATED PLYWOOD BACKBOARD. MOUNT +18" AFF UP TO 9'-6"
AFF.
3 UNCLASSIFIED FLOOR MOUNTED TELECOM/DATA RACK.
4 12" WIDE X 4" DEEP LADDER TYPE UNCLASSIFIED CABLE TRAY.
5 GROUND BAR "TGB"
6 4" CONDUIT FOR TELECOM ENTRY TO BUILDING. STUB-UP 18" AFF. SEE
SHEET ES101 FOR CONTINUATION.
7 GROUND BAR "TGB", MOUNT +24" AFF.
8 SPACE ALLOTTED FOR LOCAL COMMERCIAL CABLE SERVICE PROVIDERS
EQUIPMENT. STUB DOWN CONDUITS FROM OUTLETS DOWN TO 7'-6" AFF.
9 PROVIDE THRU-WALL PENETRATION FOR CONDUITS.
10 MOUNT BOTTOM OF CABLE TRAY TO TOP OF FLOOR MOUNTED
TELECOM/DATA RACK.
11 TELECOM/DATA RACK VERTICAL CABLE MANAGEMENT.
12 FRONT OF TELECOM/DATA RACK.
13 PROTECTED ENTRANCE TERMINATION ENCLOSURE.
14 2" CONDUIT STUBBED UP 4" AFF FOR LOCAL CABLE PROVIDERS CABLING.
15 2" CONDUIT BELOW FLOOR SLAB TO EXTERIOR HANDHOLE. SEE SHEET
ES101.
NOT TO SCALE (TT401)1
Section 1
NOT TO SCALE (TT401)2
Section 2
NOT TO SCALE (TT401)3
Section 3
NOT TO SCALE (TT401)4
Section 4
4" CONDUIT
PANEL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
(P.E.T)
SURGE
PROTECTION
WITH 710
INPUT AND
66 OUTPUT
12 PORT FIBER
ENCLOSURE
CROSS CONNECT IDC
FOR TELEPHONE OSP
48 PORT CAT6
TIA/EIA 568A
COMMUNICATION SERVICE
ENTRANCE FROM HANDHOLE ON SITE
SEE SHEET ES101
(1) 12 STRAND SINGLE
MODE, OSP FIBER OPTIC
CABLE IN INNERDUCT
(1) 25 PAIR, OSP COPPER
TELEPHONE CABLE
4" CONDUIT STUB-UP,
3'-6" AFF.
30' FIBER OPTIC CABLE LOOP
TELECOMMUNICATIONS
PLYWOOD BACKBOARD
FLOOR MOUNTED
EQUIPMENT RACK WITH (2)
VERTICAL POWER STRIPS.
TYPICAL DATA/VOICE
OUTLET SHOWN ON
PLANS
CAT6 CABLES IN CONDUIT BACK
TO CABINET EQUIPMENT RACK.
FIBER DISTRIBUTION / TERMINATION
WITH TYPE LC CONNECTION.
48 PORT PATCH PANEL WITH
110 TYPE TERMINATION.
#6 AWG TELECOM
BONDING, TYP, UON.
TMGB - PER TIA 607-C
#3/0 AWG TO BUILDING MAIN
ELECTRICAL GROUND BAR "MDGB".
FINISHED FLOOR
WALL MOUNTED CABLE MANAGEMENT
RING, TYPICAL.
(2) VERTICAL RACK MOUNTED CABLE
MANAGEMENT ONE ON EACH SIDE.
UNCLASSIFIED RACK
SEE SPECIFICATION SECTION 27 10 00
FOR RACK EQUIPMENT CONFIGURATION
AND REQUIREMENTS.
GENERAL NOTES:
PROVIDE HORIZONTAL CABLE MANAGEMENT (2U) BETWEEN
EACH PATCH PANEL, CROSS CONNECT, AND FIBER
ENCLOSURE.
12 PORT FIBER
ENCLOSURE
CROSS CONNECT IDC
FOR TELEPHONE OSP
48 PORT CAT6
TIA/EIA 568A
FLOOR MOUNTED
EQUIPMENT RACK WITH (2)
VERTICAL POWER STRIPS.
TYPICAL DATA/VOICE
OUTLET SHOWN ON
PLANS
CAT6 CABLES IN CONDUIT BACK
TO CABINET EQUIPMENT RACK.
FIBER DISTRIBUTION / TERMINATION
WITH TYPE LC CONNECTION.
24 PORT PATCH PANEL WITH
110 TYPE TERMINATION.
#6 AWG TELECOM
BONDING, TYP, UON.
TGB - PER TIA 607-C
#3/0 AWG TO BUILDING MAIN
ELECTRICAL GROUND BAR "MDGB".
(2) VERTICAL RACK MOUNTED CABLE
MANAGEMENT ONE ON EACH SIDE.
UNCLASSFIED RACK
SEE SPECIFICATION SECTION 27 10 00
FOR RACK EQUIPMENT CONFIGURATION
AND REQUIREMENTS.
#3/0 AWG
PLYWOOD BACKBOARD
COMM
ROOM 140
COMM
ROOM 109
(1) 12 STRAND, 8/125 UM, OS1
SINGLE MODE FIBER AND 25 PAIR
UTP COPPER. SEE GENERAL
NOTES THIS SECTION.
25 PAIR COPPER BACKBONE
VOICE DATA
DATA DATA
SPARE
RJ-45 8-PIN MODULAR JACK CAT 6
FOR VOICE AND BLUE FOR DATA
HIGH IMPACT COVER PLATE
TERMINATE AND LABEL PORTS
AS INDICATED
BLANK EXPANSION PORT
SPARE PORT
21 3 4 5 6 7 8
PAIR 2
PAIR 1PAIR 3 PAIR 4
BR
W-BR
W-BL
W-G
G
W-0
BL
RJ-45 JACK POSITIONS
TERMINATED TIA/EIA T568A
VIRGINIA BEACH, VA 23462
SUITE 1400
757·455·5800 FAX 757·455·5638
WWW.CLARKNEXSEN.COM
4525 MAIN STREET
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 7 FEBRUARY 2019
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
N40085-19-D-9041
1614720
1 2 3 4 5
Approved by Brett D. Ingle, Captain, USN, Commander, with Fleet Readiness Center
Mid-Atlantic, via Email.
14 Sept 2020
P -1
C
O R
R O
S
IO
N C
O N
T R
O L
P A
IN
T
F A
C
IL
IT
Y
TE
LE
C O
M M
U N
IC
A
TI
O
N S
R
IS
E R
RC
12822799
RTK MSW
SDS/RSF
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
EJA
NBJ
DSN
TT701
SCALE: 12" = 1'-0"C1
TELECOMMUNICATIONS RISER DIAGRAM
SCALE: 12" = 1'-0"A1
TYPICAL COMBINATION VOICE/DATA OUTLET
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
| T-001 - TELECOMMUNICATIONS LEGEND AND NOTES |
| TT101 - TELECOMMUNICATIONS PLAN -AREA A |
| TT102 - TELECOMMUNICATIONS PLAN -AREA B |
| TT103 - TELECOMMUNICATIONS PLAN -AREA C |
| TT104 - TELECOMMUNICATIONS PLAN -AREA D |
| TT401 - ENLARGED TELECOMMUNICATIONS |
| TT701 - TELECOMMUNICATIONS RISER |
| 2020-09-14T10:43:24-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:43:40-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:43:40-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:43:40-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:43:41-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:43:41-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:43:41-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:44:17-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:45:03-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:45:04-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:45:04-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:45:05-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:45:05-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-14T10:45:05-0400 | |
| Virginia Beach | |
| Reynaldo Cabreros | |
| I, Reynaldo Cabreros, am signing to approve this document. |
| 2020-09-25T08:54:42-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:55:46-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:55:48-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:55:49-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:55:50-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:55:52-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:55:53-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:07-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:24-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:26-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:27-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:29-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:30-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2020-09-25T08:56:31-0400 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
File details come from the government source that posted it. Updated .