CP Relocation 260553 Identification for Electrical Systems

View the file

Other files for this federal contract opportunity

Other files attached to Illinois National Guard Multiple Award Task Order Contract, newest first.
File Type Posted
260548.pdf PDF
079200.pdf PDF
220700.pdf PDF
014213.pdf PDF
092900.pdf PDF
260533.pdf PDF
260536.pdf PDF
233300.pdf PDF
013113.pdf PDF
012300.pdf PDF
220529.pdf PDF
014000.pdf PDF
013300.pdf PDF
101400.pdf PDF
081416.pdf PDF
081113.pdf PDF
014333.pdf PDF
222316.pdf PDF
055000.pdf PDF
Table of Contents.pdf PDF
221119.pdf PDF
230700.pdf PDF
260526.pdf PDF
017700.pdf PDF
220553.pdf PDF
012900.pdf PDF
061000.pdf PDF
263213.pdf PDF
260529.pdf PDF
000115.pdf PDF
096513.pdf PDF
015000.pdf PDF
233113.pdf PDF
013200.pdf PDF
260500.pdf PDF
017329.pdf PDF
220500.pdf PDF
230500.pdf PDF
001000.pdf PDF
016000.pdf PDF
262416.pdf PDF
095113.pdf PDF
013300-PFOIL Form 341.pdf PDF
E-202-Work.pdf PDF
G01-G0.1.pdf PDF
H101-A101.pdf PDF
P101-A101.pdf PDF
H102-A101.pdf PDF
A701-A701.pdf PDF
E-001-Work.pdf PDF
Show all 50

Illinois National Guard Multiple Award Task Order Contract has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DCFT #082207

Hanson #03S1408GGB

260553-1 260553

IDENTIFICATION FOR

ELECTRICAL SYSTEMS

DIVISION 26- ELECTRICAL

SECTION 260553 – IDENTIFICATION FOR

ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Identification for raceway and metal-clad cable.

2. Identification for conductors and communication and control cable.

3. Underground-line warning tape.

4. Warning labels and signs.

5. Instruction signs.

6. Equipment identification nameplates.

7. Miscellaneous identification products.

1.3 SUBMITTALS

A. Product Data: For each electrical identification product indicated.

B. Identification Schedule: An index of nomenclature of electrical equipment and system components used in identification signs and labels.

C. Samples: For each type of label and sign to illustrate size, colors, lettering style, mounting provisions, and graphic features of identification products.

1.4 QUALITY ASSURANCE

A. Comply with ANSI A13.1 and ANSI C2.

B. Comply with NFPA 70.

C. Comply with 29 CFR 1910.145.

260553-2 260553

1.5 COORDINATION

A. Coordinate identification names, abbreviations, colors, and other features with requirements in the Contract Documents, Shop Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual, and with those required by codes, standards, and 29 CFR 1910.145.

Use consistent designations throughout Project.

B. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied.

C. Coordinate installation of identifying devices with location of access panels and doors.

D. Install identifying devices before installing acoustical ceilings and similar concealment.

PART 2 - PRODUCTS

2.1 RACEWAY AND METAL-CLAD CABLE IDENTIFICATION MATERIALS

A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway and cable size.

B. Color for Printed Legend:

1. Power Circuits: Black letters on an orange field.

C. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

2.2 CONDUCTOR AND COMMUNICATION- AND CONTROL-CABLE IDENTIFICATION

MATERIALS

A. Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils thick by 1 to 2 in. (25 mm to 50 mm) wide.

B. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.

2.3 UNDERGROUND-LINE WARNING TAPE

A. Description: Permanent, bright-colored, continuous-printed, polyethylene tape:

1. Not less than 3 in. (75 mm) wide by 5 mils thick.

2. Compounded for permanent direct-burial service.

260553-3 260553

3. Embedded continuous metallic strip or core.

4. Printed legend shall indicate type of underground line.

2.4 WARNING LABELS AND SIGNS

A. Comply with NFPA 70 and 29 CFR 1910.145.

B. Self-Adhesive Warning Labels: Factory printed, multicolor, pressure-sensitive adhesive labels, configured for display on front cover, door, or other access to equipment, unless otherwise indicated.

C. Metal-Backed, Butyrate Warning Signs: Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs with 0.0396 in. (1.005 mm) galvanized-steel backing; and with colors, legend, and size required for application. 1/4 in. (6.4 mm) grommets in corners for mounting.

Nominal size, 10 by 14 in. (254 mm by 355.6 mm).

D. Warning label and sign shall include, but are not limited to, the following legends:

1. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN

FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36 IN. (900

MM)."

2.5 EQUIPMENT IDENTIFICATION NAMEPLATES

A. Engraved, Laminated Acrylic or Melamine Label: Punched or drilled for screw mounting.

Black letters on a white background.

B. Lettering: Approximately 1/2 in. (13 mm) high for floor mounted equipment and 3/16 in. (4.76

mm) high for wall mounted equipment. Wording shall identify function of device to which nameplates is attached or identify equipment served by device.

2.6 MISCELLANEOUS IDENTIFICATION PRODUCTS

A. Cable Ties: Fungus-inert, self-extinguishing, 1-piece, self-locking, Type 6/6 nylon cable ties:

1. Minimum Width: 3/16 in. (4.76 mm).

2. Tensile Strength: 50 lb (22.67 kg), minimum .

3. Temperature Range: Minus 40 to plus 185°F (4°C to 85°C).

4. Color: Black, except where used for color-coding.

B. Paint: Paint materials and application requirements are specified in Division 09 painting Sections.

C. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.

260553-4 260553

PART 3 - EXECUTION

3.1 APPLICATION

A. Accessible Raceways and Metal-Clad Cables, 600-Volt or Less, for Service, Feeder, and Branch Circuits More Than 50 A: Identify with orange self-adhesive vinyl label.

B. Accessible Raceways and Cables of Auxiliary Systems: Identify the following systems with color-coded, snap-around, color-coding bands:

1. Fire Alarm System: Red.

2. Fire-Suppression Supervisory and Control System: Red and yellow.

3. Security System: Blue and yellow.

4. Telecommunication System: Green and yellow.

5. Control Wiring: Green and red.

C. Branch-Circuit Conductor Identification: Where there are conductors for more than three branch circuits in same junction or pull box, use color-coding conductor tape. Identify each ungrounded conductor according to source and circuit number.

D. Conductors to Be Extended in the Future: Attach write-on tags to conductors and list source and circuit number.

E. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, signal, sound, intercommunications, voice, and data connections:

1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points. Identify by system and circuit designation.

2. Use system of marker tape designations that is uniform and consistent with system used by manufacturer for factory-installed connections.

3. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and Operation and Maintenance Manual.

F. Locations of Underground Lines: Identify with underground-line warning tape for power, lighting, communication, and control wiring and optical fiber cable. Install underground-line warning tape for both direct-buried cables and cables in raceway.

G. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Comply with 29 CFR 1910.145 and apply self-adhesive warning labels. Identify system voltage with black letters on an orange background. Apply to exterior of door, cover, or other access:

1. Equipment with Multiple Power or Control Sources: Apply to door or cover of equipment including, but not limited to, the following:

a. Power transfer switches.

b. Controls with external control power connections.

260553-5 260553

2. Equipment Requiring Workspace Clearance According to NFPA 70: Unless otherwise indicated, apply to door or cover of equipment but not on flush panelboards and similar equipment in finished spaces.

H. Instruction Signs:

1. Operating Instructions: Install instruction signs to facilitate proper operation and maintenance of electrical systems and items to which they connect. Install instruction signs with approved legend where instructions are needed for system or equipment operation.

2. Emergency Operating Instructions: Install instruction signs with white legend on a red background with minimum 3/8 in. (9.52 mm) high letters for emergency instructions at equipment used for power transfer.

I. Equipment Identification Nameplates: On each unit of equipment, install unique designation nameplate that is consistent with wiring diagrams, schedules, and Operation and Maintenance Manual. Apply nameplates to disconnect switches and protection equipment, central or master units, control panels, control stations, terminal cabinets, and racks of each system. Systems include power, lighting, control, communication, signal, monitoring, and alarm systems unless equipment is provided with its own identification:

1. Labeling Instructions:

a. Indoor Equipment: Engraved, laminated acrylic or melamine nameplate. Unless otherwise indicated, provide a single line of text with 1/2 in. (13 mm) high letters on 1-1/2 in. (37 mm) high nameplate; where two (2) lines of text are required, use nameplates 2 in. (50 mm) high.

b. Outdoor Equipment: Engraved, laminated acrylic or melamine nameplate.

c. Elevated Components: Increase sizes of nameplates and letters to those appropriate for viewing from the floor.

2. Equipment to Be Labeled:

a. Panelboards, electrical cabinets, and enclosures.

b. Access doors and panels for concealed electrical items.

c. Electrical switchgear and switchboards.

d. Transformers.

e. Emergency system boxes and enclosures.

f. Disconnect switches.

g. Enclosed circuit breakers.

h. Motor starters.

i. Push-button stations.

j. Power transfer equipment.

k. Contactors.

l. Remote-controlled switches, dimmer modules, and control devices.

m. Power-generating units.

n. Voice and data cable terminal equipment.

o. Television/audio components, racks, and controls.

p. Fire-alarm control panel and annunciators.

260553-6 260553

q. Security and intrusion-detection control stations, control panels, terminal cabinets, and racks.

r. Monitoring and control equipment.

s. Uninterruptible power supply equipment.

t. Terminals, racks, and patch panels for voice and data communication and for signal and control functions.

J. Arch Flash and Shock Hazard Analysis:

1. The Contractor shall provide Arch Flash and Shock Hazard Warning Signage on all electrical distribution and control equipment in accordance with 2005 NEC Section 110.16, which requires that panel-boards, enclosed circuit breakers, disconnect switches, control panels, motor controls, etc. that are likely to require examination, adjustment, servicing or maintenance while energized, shall be field marked to warn qualified persons of potential arc flash hazards. The markings shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.

2. This requirement is intended to help reduce the occurrence of serious injury or death due to arcing faults to those working on or near energized electrical equipment. The warning labels are to indicate to a qualified worker who intends to open the equipment for analysis of work that a serious hazard exists and that the worker should follow appropriate work practices and wear appropriate personal protective equipment for the specific hazard.

3. The labels shall include at least the following information: (1) flash hazard boundary; (2) cal/cm2 flash hazard at 18 in. (457.2 mm); (3) PPE Level and PPE required to work on the equipment; (4) shock hazard involved; (5) limited approach boundary; (6) restricted approach boundary; and prohibited approach boundary.

3.2 INSTALLATION

A. Verify identity of each item before installing identification products.

B. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment.

C. Apply identification devices to surfaces that require finish after completing finish work.

D. Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.

E. Attach non-adhesive signs and plastic labels with screws and auxiliary hardware appropriate to the location and substrate.

F. System Identification Color Banding for Raceways and Cables: Each color band shall completely encircle cable or conduit. Place adjacent bands of two-color markings in contact, side by side. Locate bands at changes in direction, at penetrations of walls and floors, at 50 ft (15 m) maximum intervals in straight runs, and at 25 ft (7.6 m) maximum intervals in congested areas.

260553-7 260553

G. Color-Coding for Phase Identification, 600-Volt and Less: Use the colors listed below for ungrounded service, feeder, and branch-circuit conductors:

1. Color shall be factory applied or, for sizes larger than No. 10 AWG if authorities having jurisdiction permit, field applied.

2. Colors for 240/120-Volt Circuits:

a. Phase A: Black.

b. Phase B: Red.

c. Phase C: Blue.

3. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6 in. (150 mm) from terminal points and in boxes where splices or taps are made. Apply last two (2) turns of tape with no tension to prevent possible unwinding.

Locate bands to avoid obscuring factory cable markings.

H. Underground-Line Warning Tape: During backfilling of trenches install continuous underground-line warning tape directly above line at 12 in. (300 mm) below finished grade.

END OF SECTION 260553