095113.pdf

PDF 23 KB Posted

Attached to
Illinois National Guard Multiple Award Task Order Contract Federal contract opportunity
Solicitation number
W91SMC-09-R-0017
Issued by
Department of the Army Illinois Army National Guard

About this file

CP Relocation 095113 Acoustical Panel Ceilings

View the file

Other files for this federal contract opportunity

Other files attached to Illinois National Guard Multiple Award Task Order Contract, newest first.
File Type Posted
260548.pdf PDF
079200.pdf PDF
220700.pdf PDF
014213.pdf PDF
092900.pdf PDF
260533.pdf PDF
260536.pdf PDF
233300.pdf PDF
013113.pdf PDF
012300.pdf PDF
220529.pdf PDF
014000.pdf PDF
013300.pdf PDF
101400.pdf PDF
081416.pdf PDF
081113.pdf PDF
014333.pdf PDF
222316.pdf PDF
055000.pdf PDF
Table of Contents.pdf PDF
221119.pdf PDF
230700.pdf PDF
260526.pdf PDF
017700.pdf PDF
220553.pdf PDF
012900.pdf PDF
061000.pdf PDF
263213.pdf PDF
260529.pdf PDF
000115.pdf PDF
096513.pdf PDF
015000.pdf PDF
233113.pdf PDF
013200.pdf PDF
260500.pdf PDF
017329.pdf PDF
220500.pdf PDF
230500.pdf PDF
001000.pdf PDF
016000.pdf PDF
262416.pdf PDF
017823.pdf PDF
E-202-Work.pdf PDF
G01-G0.1.pdf PDF
H101-A101.pdf PDF
P101-A101.pdf PDF
H102-A101.pdf PDF
A701-A701.pdf PDF
E-001-Work.pdf PDF
E-301-Work.pdf PDF
Show all 50

Illinois National Guard Multiple Award Task Order Contract has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DCFT #082207

Hanson #03S1408GGB

095113-1 095113

ACOUSTICAL PANEL

CEILINGS

DIVISION 09 - FINISHES

SECTION 095113 - ACOUSTICAL PANEL

CEILINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes acoustical panels and exposed suspension systems for ceilings. The intent of this section is for the Contractor to furnish and install acoustical panel ceiling materials and components as required to accommodate new and modified construction and to match the components of the existing acoustical panel ceiling system in type, appearance and performance characteristics. The components covered under this Section include ceiling panels (tiles), grid, suspension system components, hangers, clips, fasteners, attachments and other appurtenances required to result in a complete and finished ceiling installation.

1.3 QUALITY ASSURANCE

A. Acoustical Testing Agency Qualifications: An independent testing laboratory, or an NVLAP-accredited laboratory, with the experience and capability to conduct the testing indicated.

NVLAP-accredited laboratories must document accreditation, based on a "Certificate of Accreditation" and a "Scope of Accreditation" listing the test methods specified.

B. Source Limitations:

1. Acoustical Ceiling Panel: Obtain each type through one (1) source from a single manufacturer TO MATCH EXISTING CEILINGS.

2. Suspension System: Obtain each type through one (1) source from a single manufacturer

TO MATCH EXISTING CEILINGS.

C. Source Limitations: Obtain each type of acoustical ceiling panel and supporting suspension system through one (1) source from a single manufacturer TO MATCH EXISTING CEILINGS.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Deliver acoustical panels, suspension system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.

095113-2 095113

B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.

C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.

1.5 PROJECT CONDITIONS

A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use:

1. Pressurized Plenums: Operate ventilation system for not less than forty-eight (48) hours before beginning acoustical panel ceiling installation.

1.6 COORDINATION

A. Coordinate layout and installation of acoustical panels and suspension system with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, fire-suppression system, and partition assemblies.

PART 2 - PRODUCTS

2.1 ACOUSTICAL PANELS, GENERAL

A. Acoustical Panel Colors and Patterns: Match appearance characteristics of the existing acoustical panel ceilings in the work areas included under this contract.

2.2 ACOUSTICAL PANELS FOR ACOUSTICAL PANEL CEILING

A. Products: Subject to compliance with requirements, furnish and install acoustical panel ceiling materials and components as required to accommodate new and modified construction and to match the components of the existing acoustical panel ceiling system in type, appearance and performance characteristics. The components covered under this Section include ceiling panels (tiles), grid, suspension system components, hangers, clips, fasteners, attachments and other appurtenances required to result in a complete and finished ceiling installation.

2.3 METAL SUSPENSION SYSTEMS, GENERAL

A. Finishes and Colors, General: Match appearance characteristics of the existing acoustical panel ceilings in the work areas included under this contract.

B. Attachment Devices: Size for five (5) times the design load indicated in ASTM C 635, Table 1, "Direct Hung," unless otherwise indicated.

095113-3 095113

2.4 METAL SUSPENSION SYSTEM FOR ACOUSTICAL PANEL CEILING

A. Products: Subject to compliance with requirements, furnish and install acoustical panel ceiling materials and components as required to accommodate new and modified construction and to match the components of the existing acoustical panel ceiling system in type, appearance and performance characteristics. The components covered under this Section include ceiling panels (tiles), grid, suspension system components, hangers, clips, fasteners, attachments and other appurtenances required to result in a complete and finished ceiling installation.

2.5 METAL EDGE MOLDINGS AND TRIM

A. Products: Subject to compliance with requirements, furnish and install acoustical panel ceiling materials and components as required to accommodate new and modified construction and to match the components of the existing acoustical panel ceiling system in type, appearance and performance characteristics. The components covered under this Section include ceiling panels (tiles), grid, suspension system components, hangers, clips, fasteners, attachments and other appurtenances required to result in a complete and finished ceiling installation.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings:

1. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.

3.3 INSTALLATION

A. General: Install acoustical panel ceilings to comply with ASTM C 636 and seismic design requirements indicated, per manufacturer's written instructions and CISCA's "Ceiling Systems Handbook:"

1. Fire-Rated Assembly: Install fire-rated ceiling systems according to tested fire-rated design.

095113-4 095113

B. Suspend ceiling hangers from building's structural members and as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

3. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

4. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.

5. Secure wire hangers to ceiling suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

6. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both structure to which hangers are attached and type of hanger involved.

Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.

7. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.

8. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.

9. Do not attach hangers to steel deck tabs.

10. Do not attach hangers to steel roof deck. Attach hangers to structural members.

11. Space hangers not more than 48 in. (1,200 mm) o.c. along each member supported directly from hangers, unless otherwise indicated; provide hangers not more than 8 in.

(200 mm) from ends of each member.

12. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or postinstalled anchors.

D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels:

1. Apply acoustical sealant in a continuous ribbon concealed on back of vertical legs of moldings before they are installed.

2. Screw attach moldings to substrate at intervals not more than 16 in. (400 mm) o.c. and not more than 3 in. (75 mm) from ends, leveling with ceiling suspension system to a tolerance of 1/8 in. in 12 ft (3.2 mm in 3.6 m). Miter corners accurately and connect securely.

3. Do not use exposed fasteners, including pop rivets, on moldings and trim.

095113-5 095113

E. Install suspension system runners so they are square and securely interlocked with one another.

Remove and replace dented, bent, or kinked members.

F. Install acoustical panels with undamaged edges and fit accurately into suspension system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit:

1. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension system runners and moldings.

2. For reveal-edged panels on suspension system runners, install panels with bottom of reveal in firm contact with top surface of runner flanges.

3. For reveal-edged panels on suspension system members with box-shaped flanges, install panels with reveal surfaces in firm contact with suspension system surfaces and panel faces flush with bottom face of runners.

4. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.

5. Install hold-down clips in areas indicated, in areas required by authorities having jurisdiction, and for fire-resistance ratings; space as recommended by panel manufacturer's written instructions, unless otherwise indicated.

6. Install clean-room gasket system in areas indicated, sealing each panel and fixture as recommended by panel manufacturer's written instructions.

7. Protect lighting fixtures and air ducts to comply with requirements indicated for fire-resistance-rated assembly.

3.4 CLEANING

A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

END OF SECTION 095113