This request for information and federal contract opportunity notice concerns repairs and renovations to Building 102 at Mansfield Air National Guard Base in Ohio. The project includes fire protection, mechanical, plumbing and electrical systems work along with exterior brick, siding and window replacements. The construction duration is 577 days with award determined by lowest price from responsible small businesses. The pre-bid conference is July 30th and bids are due August 23rd. The NAICS code is 236220 with $36.5 million size standard. The project value is estimated between $10-25 million. The solicitation is available on FedBizOpps and questions should be directed to the email provided.
RFI 29 and response
View the file
Other files for this federal contract opportunity
Show all 50
Repair Maintenance Hangar, B102 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
R E
Q U
E S
T O
R S
E C
T
IO
N
From: Date:
To:
1. Solicitation Number:
W91364-19-B-7001
2. Location of Project:
Mansfield Ohio ANG
3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)
Attachments: Date Response Required:
By: Title:
Requestor's FAX Number: Requestor's Telephone Number:
Bill Typewritten Text Per P-402 drawing 3" SS line from EDF-1 connects to the existing 4" SS,but on CU-103 the 3" SS connects to an TY fitting coming off an new 4" SS extending from existing 4"SS north to last TY connecting the new sanitary lines from the Work Shops. Which Is Correct?
R E
S P
O N
S E
To: Date:
Response:
This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.
This information is a proposed change to the solicitation/contract. An amendment will be issued.
Contracting Officer:
X athomp14 Text Box Response: CU-103 is correct. The new 4" SS parallel to the building is intended to collect flows from EDF-1, FD-1 and FCO-1.
File details come from the government source that posted it. Updated .