RFI_19.pdf

PDF 2 MB Posted

Attached to
Repair Maintenance Hangar, B102 Federal contract opportunity
Solicitation number
W9136419B7001
Issued by
Department of the Army Ohio Army National Guard

About this file

This document contains a request for information and federal contract opportunity notice for repair and renovation work at an Air National Guard base in Mansfield, Ohio. The solicitation seeks bids for demolition, fire protection, mechanical, plumbing and electrical systems work, along with exterior brick, siding and window replacements. The construction period is 577 calendar days with no optional items. Bids will be evaluated without discussion and awarded to the responsible bidder. The small business set-aside has a NAICS code of 236220 and $36.5 million size standard. A pre-bid conference is scheduled for July 30th and bids are due August 23rd. Interested contractors must register in the System for Award Management and view solicitation documents through the Federal Business Opportunities website. The official plans and specifications are only located on the government website.

RFI 19 and response

View the file

Other files for this federal contract opportunity

Other files attached to Repair Maintenance Hangar, B102, newest first.
File Type Posted
W91364-19-B-7001_0003.pdf PDF
RFI_27a.pdf PDF
RFI_27a_attach1.pdf PDF
RFI_15.pdf PDF
RFI_24_attach2.pdf PDF
RFI_34.pdf PDF
RFI_21.pdf PDF
RFI_17.pdf PDF
RFI_31.pdf PDF
RFI_26.pdf PDF
RFI_25.pdf PDF
RFI_20.pdf PDF
RFI_18.pdf PDF
RFI_13.pdf PDF
RFI_16.pdf PDF
RFI_04.pdf PDF
B102,_site_visit_2.0.pdf PDF
RFI_09.pdf PDF
RFI_09_attachment.pptx PPTX presentation
RFI_07.pdf PDF
W91364-19-B-7001_0001.pdf PDF
RFI_05.pdf PDF
RFI_06.pdf PDF
RFI_03.pdf PDF
Full_size_drawings_10.pdf PDF
Full_size_drawings_12.pdf PDF
Full_size_drawings_8.pdf PDF
Full_size_drawings_11.pdf PDF
Full_size_drawings_2a.pdf PDF
Full_size_drawings_4b.pdf PDF
Full_size_drawings_6a.pdf PDF
Full_size_drawings_7a.pdf PDF
Full_size_drawings_15.pdf PDF
Full_size_drawings_13.pdf PDF
Full_size_drawings_6b.pdf PDF
Full_size_drawings_17.pdf PDF
Full_size_drawings_4a.pdf PDF
Full_size_drawings_14.pdf PDF
Pre-Bid_Conference_slides_B102.pptx PPTX presentation
Attach7_Vol_6_Drawings_11.pdf PDF
Attach7_Vol_6_Drawings_2.pdf PDF
Attach9-RFI_template.doc DOC document
Attach1-Scope_of_Work-B102.pdf PDF
EXHIBIT_A-CLIN_Pricing_Summary.xlsx XLSX spreadsheet
Attach7_Vol_6_Drawings_3.pdf PDF
Attach7_Vol_6_Drawings_7.pdf PDF
Attach7_Vol_6_Drawings_8.pdf PDF
Attach8-Temp_Restrooms.pdf PDF
Attach7_Vol_6_Drawings_6.pdf PDF
Attach7_Vol_6_Drawings_13.pdf PDF
Show all 50

Repair Maintenance Hangar, B102 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION

R E

Q U

E S

T O

R S

E C

T

IO

N

From: Date:

To: Contracting Officer

1. Solicitation Number:

W91364-19-B-7001

2. Location of Project:

Mansfield Ohio ANG

3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)

Attachments: Date Response Required:

By: Title:

Requestor's FAX Number: Requestor's Telephone Number:

kfortney Typewritten Text

1. Are all circuit breakers being primary injection tested including small panel breakers or is there a cut point as far as amperage? 100 amps and above?

2. Is the testing only on new electrical equipment and not on existing equipment?

3. I see there is a lightning protection spec but I cannot find anything referenced in the drawings. Please clarify.

R E

S P

O N

S E

To: Date:

Response:

This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.

This information is a proposed change to the solicitation/contract. An amendment will be issued.

Contracting Officer:

X lcopping Text Box

1. Are all circuit breakers being primary injection tested including small panel breakers or is there a cut point as far as amperage? 100 amps and above?

Per spec 26 24 13 Perform primary current injection tests on the entire current circuit in each section of assembly in the switchboard only.

2. Is the testing only on new electrical equipment and not on existing equipment?

Testing is for new electrical equipment.

3. I see there is a lightning protection spec but I cannot find anything referenced in the drawings. Please clarify.

As per spec 26 41 00, the existing LPS and grounding systems are to be inspected and document deficiencies. Refer to this spec for details of the inspection and documentation requirements.