This document includes a Request for Information and federal contract opportunity notice regarding repair and renovation work at Mansfield Air National Guard Base in Ohio. The solicitation seeks bids for a construction project with a duration of 577 calendar days. Work includes demolition, fire protection and suppression systems, mechanical, plumbing and electrical upgrades, and exterior repairs. The procurement is set aside for small businesses with a NAICS code of 236220 and size standard of $36.5 million in average annual revenue. The pre-bid conference is scheduled for July 30th and bids are due on August 23rd. The solicitation and plans are available through the Federal Business Opportunities website.
RFI 28 and response
View the file
Other files for this federal contract opportunity
Show all 50
Repair Maintenance Hangar, B102 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
R E
Q U
E S
T O
R S
E C
T
IO
N
From:
Date:
To: Contracting Officer
1. Solicitation Number:
W91364-19-B-7001
2. Location of Project:
Mansfield Ohio ANG
3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)
1. found something in the Spec that says the company has to be licensed in Ohio, but what about each technician? Do they need to be licensed as well?
2. If I understand correctly the hydrants will be supplied by the existing underground water supply. With that being said is the Hose Stream Allowance being added to the Ground Storage Tank size?
3. For Hydraulic Calculation purposes we would not need to include the 500 gpm hose stream. Correct?
4. Spec Section 21 13 13.00.10 Paragraph 1.4.1 Fire Protection Specialists need to be onsite during the installation of the Fire System.
Would this apply to Fire Alarm?
Attachments:
Date Response Required:
By:
Title:
Requestor's FAX Number:
Requestor's Telephone Number:
R E
S P
O N
S E
To: Date:
Response:
1. found something in the Spec that says the company has to be licensed in Ohio, but what about each technician? Do they need to be licensed as well?
No spec section is referenced. The company and the registered Professional Engineer shall be licensed in the state of Ohio. NICET is a national certification.
2. If I understand correctly the hydrants will be supplied by the existing underground water supply. With that being said is the Hose Stream Allowance being added to the Ground Storage Tank size?
Usable gallons for storage tanks is 55,936 gallons in the design narrative.
3. For Hydraulic Calculation purposes we would not need to include the 500 gpm hose stream. Correct?
If there are no hydrants off of the supply and no interior hose stations, the calculations will not be required to include the hose flows.
4. Spec Section 21 13 13.00.10 Paragraph 1.4.1 Fire Protection Specialists need to be onsite during the installation of the Fire System. Would this apply to Fire Alarm?
Section 28 31 76 requires the services and review of a qualified engineer for design services. The Supervisor is required to be a NICET IV Fire Alarm Technician and shall supervise the installation of the system. Technician shall have a minimum of 4 years of experience and be factory trained. Testing is required to be performed by a factory trained NICET IV technician. For full requirements of the fire alarm qualifications, see spec section 28 31 76 section 1.7.1
This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.
This information is a proposed change to the solicitation/contract. An amendment will be issued.