RFI_28.pdf

PDF 186 KB Posted

Attached to
Repair Maintenance Hangar, B102 Federal contract opportunity
Solicitation number
W9136419B7001
Issued by
Department of the Army Ohio Army National Guard

About this file

This document includes a Request for Information and federal contract opportunity notice regarding repair and renovation work at Mansfield Air National Guard Base in Ohio. The solicitation seeks bids for a construction project with a duration of 577 calendar days. Work includes demolition, fire protection and suppression systems, mechanical, plumbing and electrical upgrades, and exterior repairs. The procurement is set aside for small businesses with a NAICS code of 236220 and size standard of $36.5 million in average annual revenue. The pre-bid conference is scheduled for July 30th and bids are due on August 23rd. The solicitation and plans are available through the Federal Business Opportunities website.

RFI 28 and response

View the file

Other files for this federal contract opportunity

Other files attached to Repair Maintenance Hangar, B102, newest first.
File Type Posted
Bid_opening_attendance.pdf PDF
Abstract_B102_signed.pdf PDF
W91364-19-B-7001_0003.pdf PDF
RFI_36.pdf PDF
RFI_23.pdf PDF
RFI_24_attach2.pdf PDF
RFI_34.pdf PDF
RFI_24_attach1.pdf PDF
RFI_27.pdf PDF
RFI_10.pdf PDF
RFI_14.pdf PDF
RFI_17.pdf PDF
RFI_31.pdf PDF
RFI_26.pdf PDF
RFI_25.pdf PDF
RFI_18.pdf PDF
RFI_13.pdf PDF
RFI_16.pdf PDF
RFI_04.pdf PDF
RFI_07.pdf PDF
RFI_06.pdf PDF
RFI_02.pdf PDF
RFI_01.pdf PDF
Full_size_drawings_7b.pdf PDF
Full_size_drawings_13.pdf PDF
Full_size_drawings_6b.pdf PDF
Full_size_drawings_17.pdf PDF
Full_size_drawings_4a.pdf PDF
Full_size_drawings_14.pdf PDF
Full_size_drawings_10.pdf PDF
Full_size_drawings_12.pdf PDF
Pre-Bid_sign_in_sheet.pdf PDF
Pre-Bid_Conference_slides_B102.pptx PPTX presentation
Attach4-Vol_3_Specs.pdf PDF
Attach7_Vol_6_Drawings_4.pdf PDF
Attach2-Vol_1_BOD_1a.pdf PDF
Attach7_Vol_6_Drawings_10.pdf PDF
Attach7_Vol_6_Drawings_1a.pdf PDF
Attach5-Vol_4_Specs.pdf PDF
Attach7_Vol_6_Drawings_7.pdf PDF
Attach7_Vol_6_Drawings_8.pdf PDF
Attach8-Temp_Restrooms.pdf PDF
Attach7_Vol_6_Drawings_6.pdf PDF
Attach7_Vol_6_Drawings_13.pdf PDF
Attach7_Vol_6_Drawings_11.pdf PDF
Attach7_Vol_6_Drawings_2.pdf PDF
Attach9-RFI_template.doc DOC document
Attach1-Scope_of_Work-B102.pdf PDF
EXHIBIT_A-CLIN_Pricing_Summary.xlsx XLSX spreadsheet
Attach7_Vol_6_Drawings_3.pdf PDF
Show all 50

Repair Maintenance Hangar, B102 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION

R E

Q U

E S

T O

R S

E C

T

IO

N

From:

Date:

To: Contracting Officer

1. Solicitation Number:

W91364-19-B-7001

2. Location of Project:

Mansfield Ohio ANG

3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)

1. found something in the Spec that says the company has to be licensed in Ohio, but what about each technician? Do they need to be licensed as well?

2. If I understand correctly the hydrants will be supplied by the existing underground water supply. With that being said is the Hose Stream Allowance being added to the Ground Storage Tank size?

3. For Hydraulic Calculation purposes we would not need to include the 500 gpm hose stream. Correct?

4. Spec Section 21 13 13.00.10 Paragraph 1.4.1 Fire Protection Specialists need to be onsite during the installation of the Fire System.

Would this apply to Fire Alarm?

Attachments:

Date Response Required:

By:

Title:

Requestor's FAX Number:

Requestor's Telephone Number:

R E

S P

O N

S E

To: Date:

Response:

1. found something in the Spec that says the company has to be licensed in Ohio, but what about each technician? Do they need to be licensed as well?

No spec section is referenced. The company and the registered Professional Engineer shall be licensed in the state of Ohio. NICET is a national certification.

2. If I understand correctly the hydrants will be supplied by the existing underground water supply. With that being said is the Hose Stream Allowance being added to the Ground Storage Tank size?

Usable gallons for storage tanks is 55,936 gallons in the design narrative.

3. For Hydraulic Calculation purposes we would not need to include the 500 gpm hose stream. Correct?

If there are no hydrants off of the supply and no interior hose stations, the calculations will not be required to include the hose flows.

4. Spec Section 21 13 13.00.10 Paragraph 1.4.1 Fire Protection Specialists need to be onsite during the installation of the Fire System. Would this apply to Fire Alarm?

Section 28 31 76 requires the services and review of a qualified engineer for design services. The Supervisor is required to be a NICET IV Fire Alarm Technician and shall supervise the installation of the system. Technician shall have a minimum of 4 years of experience and be factory trained. Testing is required to be performed by a factory trained NICET IV technician. For full requirements of the fire alarm qualifications, see spec section 28 31 76 section 1.7.1

This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.

This information is a proposed change to the solicitation/contract. An amendment will be issued.

Contracting Officer:

X