This document contains a Request for Information and response regarding a solicitation notice for repair and renovation work at an Air National Guard facility in Mansfield, Ohio. The solicitation seeks bids for Project No. PBXP 132166 to repair and renovate fire protection, mechanical, plumbing, electrical, and telecommunications systems at Building 102. Exterior brick and metal siding also require renovation along with window and door replacements. The construction duration is 577 calendar days with no additive bid items or options. Bids will be evaluated without discussions and awarded in accordance with FAR procedures to the responsible bidder. The small business set-aside has a NAICS code of 236220 with a $36.5 million average annual revenue size standard. The estimated value is between $10-25 million. The pre-bid conference is July 30 and bids are due August 23. Interested contractors must register in SAM and check the FedBizOpps website periodically for amendments.
RFI 25 and response
View the file
Other files for this federal contract opportunity
Show all 50
Repair Maintenance Hangar, B102 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
R E
Q U
E S
T O
R S
E C
T
IO
N
From: Date:
To: Contracting Officer
1. Solicitation Number:
W91364-19-B-7001
2. Location of Project:
Mansfield Ohio ANG
3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)
Attachments: Date Response Required:
By: Title:
Requestor's FAX Number: Requestor's Telephone Number:
kfortney Typewritten Text
1. Per note 28 on drawing ED110, and note D1 on drawing AD110, there is an existing overhead electrical line to an adjacent building called out to be removed and re-routed underground. There is no further information that we could find on the electrical drawings as to the size of this existing wire, how far the wire has to travel, to what building the wire goes to, what panel this wire is fed from and to, and if the new wire is to be direct buried or in a duct bank? Could you please clarify this scope of work.
R E
S P
O N
S E
To: Date:
Response:
This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.
This information is a proposed change to the solicitation/contract. An amendment will be issued.
Contracting Officer:
X
DA055439
Image
DA055439
Text Box
2. The cable in overhead conduit is shown in the screen shot below, drawing TD110. Coax cable to central fire station. This falls under the Telecom scope.
DA055439
Text Box
1. The overhead electrical cable shown on AD110 Detail 2E was not verified at the site visit and did not appear on the utilities drawings. The cable did not appear to be in service as no breakers in the electrical room are assigned to a circuit that could be identified as leaving the Hanger building. We could not determine if the cable was at one time feeding an exterior load or building. Therefore, we request the contractor to verify and determine the electrical cable purpose. It was assumed the cable would be demo'd and removed.