RFI_26.pdf

PDF 132 KB Posted

Attached to
Repair Maintenance Hangar, B102 Federal contract opportunity
Solicitation number
W9136419B7001
Issued by
Department of the Army Ohio Army National Guard

About this file

This document includes a request for information and a related federal contract solicitation notice. The request for information seeks clarification on containment trenches and compressed air regulators specified for a project located at the Mansfield Air National Guard Base in Mansfield, Ohio. The solicitation notice is for project number PBXP 132166 to repair and renovate a maintenance hangar at the Mansfield Air National Guard Base, including fire protection, mechanical, plumbing and electrical systems work, as well as exterior renovations. The contract duration is 577 calendar days with no additive bid items or options. The solicitation is set aside for small businesses with a revenue size standard of $36.5 million. The pre-bid conference is July 30, 2019 and bids are due August 23, 2019. The solicitation and plans are available on FedBizOpps and questions should be directed to the listed contracting officer.

RFI 26 and response

View the file

Other files for this federal contract opportunity

Other files attached to Repair Maintenance Hangar, B102, newest first.
File Type Posted
RFI_32.pdf PDF
RFI_35.pdf PDF
RFI_27a_attach2.pdf PDF
RFI_27a.pdf PDF
W91364-19-B-7001_0002.pdf PDF
RFI_29.pdf PDF
RFI_24.pdf PDF
RFI_30.pdf PDF
RFI_15.pdf PDF
RFI_33.pdf PDF
RFI_19.pdf PDF
RFI_21.pdf PDF
RFI_22.pdf PDF
RFI_20.pdf PDF
RFI_08.pdf PDF
RFI_12.pdf PDF
B102,_site_visit_2.0.pdf PDF
RFI_09.pdf PDF
W91364-19-B-7001_0001.pdf PDF
RFI_05.pdf PDF
RFI_03.pdf PDF
Full_size_drawings_16.pdf PDF
Full_size_drawings_9.pdf PDF
Full_size_drawings_3.pdf PDF
Full_size_drawings_5.pdf PDF
Full_size_drawings_2b.pdf PDF
Full_size_drawings_1.pdf PDF
Full_size_drawings_10.pdf PDF
Full_size_drawings_12.pdf PDF
Full_size_drawings_8.pdf PDF
Full_size_drawings_11.pdf PDF
Full_size_drawings_2a.pdf PDF
Full_size_drawings_4b.pdf PDF
Full_size_drawings_6a.pdf PDF
Full_size_drawings_7a.pdf PDF
Pre-Bid_Conference_minutes_B102.pdf PDF
Attach6-Vol_5_Specs.pdf PDF
Attach7_Vol_6_Drawings_12.pdf PDF
W91364-19-B-7001.pdf PDF
Attach7_Vol_6_Drawings_1b.pdf PDF
Attach7_Vol_6_Drawings_9.pdf PDF
EXHIBIT_B-Sealed_Bid_Checklist,_Reminders.pdf PDF
Attach7_Vol_6_Drawings_5.pdf PDF
Attach3-Vol_2_Specs.pdf PDF
Attach7_Vol_6_Drawings_11.pdf PDF
Attach7_Vol_6_Drawings_2.pdf PDF
Attach9-RFI_template.doc DOC document
Attach1-Scope_of_Work-B102.pdf PDF
EXHIBIT_A-CLIN_Pricing_Summary.xlsx XLSX spreadsheet
Attach7_Vol_6_Drawings_3.pdf PDF
Show all 50

Repair Maintenance Hangar, B102 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION

R E

Q U

E S

T O

R S

E C

T

IO

N

From: Date:

To: Contracting Officer

1. Solicitation Number:

W91364-19-B-7001

2. Location of Project:

Mansfield Ohio ANG

1. 3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy) 19-0016-003

1. Is there a speck make/model # for the containment trenches out in the hanger area?

Shown on drawing S‐101‐103 Note #8. Detail on S‐501 Detail #10 doesn’t mention either.

Is there a basis of design?

2. Per spec 22.13.1 Compressed air regulator requires a brass body unit. Is there a basis of design manufacturer/model #.

Attachments: Date Response Required:

By: Title:

Requestor's FAX Number: Requestor's Telephone Number:

R E

S P

O N

S E

To: Date:

Response:

1. Is there a speck make/model # for the containment trenches out in the hanger area?

Shown on drawing S‐101‐103 Note #8. Detail on S‐501 Detail #10 doesn’t mention either.

Is there a basis of design?

There is no specific basis of design identified. A traffic rated FRP trench drain unit that’s intended to be cast into fresh concrete is acceptable. The drain should be 6”‐8” wide.

2. Per spec 22.13.1 Compressed air regulator requires a brass body unit. Is there a basis of design manufacturer/model #.

There is no basis of design identified. Part 2.13.1 of 22 00 00 states brass body or equal. A pressure regulator body constructed of zinc or aluminum die castings that is rated for the service is acceptable.

This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.

This information is a proposed change to the solicitation/contract. An amendment will be issued.

Contracting Officer:

X

File details come from the government source that posted it. Updated .