This document provides details for a federal contract solicitation to repair and renovate a maintenance hangar at Mansfield Air National Guard Base in Ohio. The solicitation is for project number PBXP 132166 and includes repair and renovation of fire protection and suppression systems, mechanical, plumbing, and electrical work. Exterior brick veneer and metal siding also require renovation along with replacement of windows and doors to meet energy efficiency and security goals. The construction period is 577 calendar days from notice to proceed. The solicitation is set aside 100% for small businesses with a North American Industry Classification code of 236220 and $36.5 million average annual revenue size standard. The pre-bid conference is July 30, 2019 and bids are due August 23, 2019. The solicitation and plans are available on the Federal Business Opportunities website. The facility is located at the 179th Airlift Wing, Ohio Air National Guard in Mansfield, Ohio.
RFI 24 and response (attachments included and also follow)
View the file
Other files for this federal contract opportunity
Show all 50
Repair Maintenance Hangar, B102 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION
R E
Q U
E S
T O
R S
E C
T
IO
N
From: Date:
To: Contracting Officer
1. Solicitation Number:
W91364-19-B-7001
2. Location of Project:
Mansfield Ohio ANG
1. M‐401, note 7; Is the Government provided Chilled Water System equipment (relocated from another building on base) relocated to the Mechanical room by the Government or by the Mech contractor?
2. Are detailed shop drawings available for our use to bid the installation of this equipment?
3. Can a site visit be scheduled for the Mech contractor to review this equipment and mechanical room?
4. In specification section 086045/2.5.2/c: Grid Size is listed as 12” x 24”. However, drawing A‐201 and A‐602 show a nominal grid of 24”x 12”. Which grid is to be used?
5. On drawing A‐602, the W5 panel is called out as 14’‐4” long. The center section is drawn differently from the ends. What is this center section and how long is it?
6. In specification section 086045 it calls for U‐factor of 0.14 and Solar heat gain coefficient of 0.16 (2.5.3) with light transmission of 9% (2.5.2/a) with condensation index rating of 80 (2.5.4). All of this is achievable with a thermally‐broken grid core. However, in 2.3.2 it calls for a Non combustible grid core, which would require an aluminum grid core. If thermally‐broken, all above are accurate. If aluminum grid core is required solar heat gain number, U‐factor and condensation factors are affected. Should the panels have a thermally‐ broken or aluminum grid core?
7. In specification section 086045/1.6 is calls out for the warranty to include a manufacturer’s warranty for installation. As manufacturer is a material supplier workmanship and installation would not be covered in the ten year warranty covering items 1.6/a.b.c. and d. Is this acceptable?
8. In specification section 086045/2.6/j it calls out for exposed aluminum to be from manufacturer’s standard range, which would involve a selection from 13 standard colors with a finish per AAMA 2604. Is this acceptable?
9. In specification section 086045/l – Design Criteria it discusses Blast Loads. As drawing S‐001 calls out for the building to be a low occupancy building, would the panels not be exempt from UFC4‐010‐01 min. standards? If not exempt, please provide charge weight and stand‐off distance.
10. Will the existing AFFF Foam currently stored in the Hangar Bladder Tank be disposed of off‐site, or will the Base like to keep the AFFF Foam? If the Base would like to keep will they be providing the storage containers?
Attachments: Date Response Required:
By: Title:
Requestor's FAX Number: Requestor's Telephone Number:
R E
S P
O N
S E
To: Date:
Response:
See Responses Below
This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.
This information is a proposed change to the solicitation/contract. An amendment will be issued.
Contracting Officer:
X
1. M‐401, note 7; Is the Government provided Chilled Water System equipment (relocated from another building on base) relocated to the Mechanical room by the Government or by the Mech contractor?
Govt will deliver to the building, Contractor will move into the mech room and install.
2. Are detailed shop drawings available for our use to bid the installation of this equipment?
This equipment is part of a separate project to support the Hydraulic Test Stand in its current location in an adjacent building. Contact Contracting Officer for shop/installation drawings for this equipment.
3. Can a site visit be scheduled for the Mech contractor to review this equipment and mechanical room?
Detailed drawings and O&M manual are attached. Project is for the relocation and install of equipment as GFCI. The
Government does not intend to extend bid period or provide additional site visits until after contract award. Two separate opportunities for site visits were provide previously.
4. In specification section 086045/2.5.2/c: Grid Size is listed as 12” x 24”. However, drawing A‐201 and A‐602 show a nominal grid of 24”x 12”. Which grid is to be used?
The grid size on the drawings shows and calls out the same dimensions as the grid size indicated in the specifications.
The drawings are clear as to the orientation of the panels.
5. On drawing A‐602, the W5 panel is called out as 14’‐4” long. The center section is drawn differently from the ends.
What is this center section and how long is it?
The width of the center section is allowed to vary depending on widths manufacturer’s proprietary standard components – overall width is 14’‐4”, subtraction of (4) NOM. frame widths, less (8) NOM. 12” wide panels results in the center section width.
6. In specification section 086045 it calls for U‐factor of 0.14 and Solar heat gain coefficient of 0.16 (2.5.3) with light transmission of 9% (2.5.2/a) with condensation index rating of 80 (2.5.4). All of this is achievable with a thermally‐ broken grid core. However, in 2.3.2 it calls for a Non combustible grid core, which would require an aluminum grid core. If thermally‐broken, all above are accurate. If aluminum grid core is required solar heat gain number, U‐factor and condensation factors are affected. Should the panels have a thermally‐ broken or aluminum grid core?
The panels should have a thermally broken grid core.
7. In specification section 086045/1.6 is calls out for the warranty to include a manufacturer’s warranty for installation.
As manufacturer is a material supplier workmanship and installation would not be covered in the ten year warranty covering items 1.6/a.b.c. and d. Is this acceptable?
Specification submittal section requires the submittal of the warranty, so acceptance of final terms will be by submittal reviewer; however, the intent is to warranty the completed installation. The manufacturer is required to warranty the product, installer warranty the installation.
8. In specification section 086045/2.6/j it calls out for exposed aluminum to be from manufacturer’s standard range, which would involve a selection from 13 standard colors with a finish per AAMA 2604. Is this acceptable?
If the selected manufacturer provides the product in only 13 standard colors, a final selection will be made from one of those colors.
9. In specification section 086045/l – Design Criteria it discusses Blast Loads. As drawing S‐001 calls out for the building to be a low occupancy building, would the panels not be exempt from UFC4‐010‐01 min. standards? If not exempt, please provide charge weight and stand‐off distance.
The translucent panels are not required to be designed for blast resistance.
10. Will the existing AFFF Foam currently stored in the Hangar Bladder Tank be disposed of off‐site, or will the Base like to keep the AFFF Foam? If the Base would like to keep will they be providing the storage containers?
AFFF has been removed from the system and the suppression system for the hangar bay has been disabled/ inoperable in anticipation of this project..
Design Conditions Datasheet
MLP Effective Date:10/1/2018 Mansfield ANG
Generated on 2018-10-17 E.2.0.12053.0-D.66.0040(REV. v8_09.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW18.05 Page_1_of_2
Unit Tag Qty Model No Net Cooling
Capacity (ton.R) Nominal Voltage Refrigerant Type
CH-1 1 QTC3060THE46XFBSDTX 61.41 460-3-60.0 R410A
PIN:
QTC3060THE 46XFBSDTXA XXBLXCXX44 XE1XXXHXXX XAXGXXXXXX AXXXBXXXT5
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90
Evaporator Data Evaporator Data (Cont.) Performance Data EWT (°F) 54.00 Fluid Volume (USGAL) 5.389 EER (Btu/W ∙h) 10.28
LWT (°F) 44.00 Min. Flow Rate (USGPM) 60.23 NPLV.IP (Btu/W ∙h) 15.56
Design Flow Rate (USGPM) 151.0 Max. Flow Rate (USGPM) 324.9
Evap. Press. Drop (ft H2O) 11.0
Fluid Propylene
Glycol (%) 25 Condenser Data Physical Data
Strainer Press. Drop (ft H2O) 2.25 Ambient Temp. Design (°F) 95.0 Rigging Wt. (lb) 4645
Ext. Kit Press. Drop (ft H2O) 0.000 Altitude (ft) 0.000 Operating Wt. (lb) 4689
Total Press. Drop (ft H2O) 13.2 Compressor Type Scroll - Hermetic Refrigerant Charge (lb) 86
Fouling Factor (h.ft².F/Btu) 0.000100
Electrical Data Circuit 1 2 3 4
Compressor RLA 24 / 24 / 24 27 / 27
Fan QTY/FLA (each) 2 / 4 2 / 4
High LRA Current 145 / 145 / 145 180 / 180
Single Point Min. Circuit Ampacity 161
Recommended Fuse/CB Rating 175
Max. Inverse Time CB Rating 175
Max. Dual Element Fuse Size (A) 175 Operating Condition Electrical Data Unit Short Circuit Withstand (STD) 5 [kA] Compressor kW 64.97
Wires Per Phase 1 Total Fan kW 6.720
Wire Range (Lug Size) #6 AWG - 350 kcmil Total kW 71.69
Starter Type Across The Line Total kW with Hydrokit
Power 75.42
Notes:
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Unit contains freeze protection fluids in the evaporator with a leaving chilled fluid temperature above 32 DEG F [0 DEG C] and is certified when rated per the Standard with water. Auxiliary components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included in the compressor and fan power
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit (EAc4).
Design Conditions Datasheet
MLP Effective Date:10/1/2018 Mansfield ANG
Generated on 2018-10-17 E.2.0.12053.0-D.66.0040(REV. v8_09.idd) Datasheet Spec
Unit Folder: CH-1 Software Version: YW18.05 Page_2_of_2
Part Load Rating Data
Stage Ambient (°F) Capacity (ton.R) Total kW Unit Efficiency 1 95.0 61.41 71.69 10.28
2 87.4 53.64 53.42 12.05
3 76.2 42.16 35.61 14.21
4 64.3 29.98 21.12 17.03
5 55.0 13.86 8.985 18.52
Sound Power Levels (In Accordance with AHRI 370)
Stage Ambient
(°F)
63 Hz
(dB)
125 Hz
(dB)
250 Hz
(dB)
500 Hz
(dB)
1 kHz
(dB)
2 kHz
(dB)
4 kHz
(dB)
8 kHz
(dB)
LWA
1 95.0 96 95 91 91 88 86 81 77 93
2 87.4 96 95 91 91 88 85 81 77 93
3 76.2 96 95 91 91 87 85 81 77 93
4 64.3 93 92 88 88 85 82 78 74 90
5 55.0 90 89 85 85 82 79 75 71 87
Note: Unit is equipped with Low Sound Fans.
Performance at AHRI Conditions
Evaporator Data Condenser Data Performance Data EWT (°F) 54.00 Ambient Temp. (°F) 95.0 EER (Btu/W ∙h) 10.38
LWT (°F) 44.00 Altitude (ft) 0.000 IPLV.IP (Btu/W ∙h) 15.60
Flow Rate (USGPM) 148.5 Net Cooling Capacity
(ton.R) 62.20
Pressure Drop (ft H2O) 8.63
Fluid Water
Fouling Factor (h.ft².F/Btu) 0.000100
Fluid Volume (USGAL) 1.424
Note: Unit rated at design condition capacity.
Pump Curve
Report
Project Name Unit Tag Date Chiller Type Mansfield ANG CH-1 2018-10-17 Air Cooled Scroll Chillers
PIN Version QTC3060THE46XFBSDTXAXXBLXCXX44XE1XXXHXXXXAXGXXXXXXAXXXBXXXT5 E.2.0.12053.0-D.66.0040
MLP Effective Date:10/1/2018 Mansfield ANG
Generated on 2018-10-17 E.2.0.12053.0-D.66.0040(REV. v8_09.idd) Pump Curve Specification
Unit Folder: CH-1 Software Version: YW18.05 Page_1_of_1
QTC3060THE Hydro Kit Data Flow 151.0 USGPM Impeller Diameter 5.4 in Efficiency 74 %
Head 19.7 ft H2O NPSHR 4.95 ft H2O Pump QTY 1
Hydrokit Hydrokit T
Hydrokit Performance Data PUMP Motor Size/Speed 2950 RPM Chiller Internal PD 19.7 ft H2O Head Safety Factor -0.0489 ft H2O
Pump Motor HP 5 hp Total Head Required 19.7 ft H2O Pump Type VSD Single Pump
(Full Feat) revans@northrich.com Rectangle revans@northrich.com Rectangle
Submittal Ref. #: 697911.1 rev1
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 1506-005.0
Project name: Mansfield Air Nat Guard
Location: Manfield OH Representative: Northrich Company
Date submitted: 10/18/2018 4:19:50 PM Phone number: (216) 581-4750
Engineer: e-mail: revans@northrich.com
Contractor: Submitted by: Robert Evans
Application design data
Tag number: PP-1 Pipe orientation: Single
Suction pressure: 0 ftService: Process Pump
Location: Fluid: Water:
Quantity: 1 Operating temperature: 60 F
Viscosity: 31 SSUDuty flow per pump: 60 USgpm
Specific gravity: 1.0000Duty head: 55 psig
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (BS1400 Grade LG1)
Rating: ANSI-125 Shaft sleeve: 316 SS
Connections: Inlet: 1.5 in, Outlet: 1.5 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (BS1452 GR220) Flush line: Braided Stainless Steel
Stub Shaft: Stainless Steel
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 5 hp Inverter motor type: Inverter Duty
Frame number: 184JM Efficiency: NEMA Prem (12.12)
Enclosure: TEFC Operating speed @ 100% flow: 3399 rpm Motor Electrics: 460/3/60 Operating speed @ 50% flow: 2411 rpm
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12
Digital inputs:
Analog outputs: 1 (current)
Fused disconnect switch: None 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
BHP at 50% load/flow and 55% of design head:
0.93 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)
Meets ASHRAE 90.1: No EMI/RFI control: Integrated filter to meet EN61800-3 Min. maintained sys. pressure: 22 psig Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.
** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 10/22/2018, Ref. # 697911.1 rev1 Page 1 of 4
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: PP-1 Service: Process Pump Location:
--- Motor Data --- Motor Size: 5 hp
--- Design Duty Point --- Flow: 60 usgpm Head: 55 psi Impeller: 6.19 in
--- Performance Data ---
• NPSHR: 2.8934 psi
• Eff. @ Design: 51.84 %
• BHP @ Design: 3.71 hp
• Mtr Capability @ Rated Spd: 4.75 hp
• %Mtr Safety: 27.99%
• BEP @ Design Imp.:
53.19 % @ 75.5 usgpm
• %max imp. range: 100.00 %
• Outlet Velocity: 9.46 ft/s
• VFD Op.Speed: 3399 rpm
• VFD Setting: 57.8 Hz
Series 4380 Design Envelope: 1506-005.0 @ 57.8 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 20 40 60 80 100 120 140 160
Flow (usgpm)
Head
(psi)
6.19 in
4.50 in
System
6.19 in
5 hp
49%
46%
Water:, spgr= 1.0000
PT13-3-0 (3.30.1.14)
ANSI/HI 14.6.3.4.1
--- Admin Data --- Tag Num: PP-1 Service: Process Pump Location:
--- Motor Data --- Motor Size: 5 hp
--- Design Duty Point --- Flow: 60 usgpm Head: 55 psi Impeller: 6.19 in
--- Control Data ---
1. Hmax @ 57.8 Hz:
• 60 @ 55, 3.71 hp
2. Control (QPC) @ 53.4 Hz:
• 52.9 @ 47.7, 2.87 hp
3. Control (QPC) @ 49.0 Hz:
• 45.5 @ 40.9, 2.15 hp
4. Control (QPC) @ 44.4 Hz:
• 37 @ 34.6, 1.53 hp
5. Control (QPC) @ 39.9 Hz:
• 27.7 @ 29, 1.03 hp
6. Index @ 35.5 Hz:
• 15 @ 24.1, 0.61 hp
7. Hmin: 22 psi 33.5 Hz:
• Setting= 40.00% Hmax
Series 4380 Design Envelope: 1506-005.0
Integrated Intelligent Variable Speed with Sensorless Control
0 20 40 60 80 100 120 140 160
Flow (usgpm)
Head
(psi)
63.0 Hz
35.5 Hz
33.5 Hz
18.0 Hz
System
Avg.Load (QPC)
57.8 Hz
5 hp
Index Flow (25.0% Duty Flow)
Water:, spgr= 1.0000
PT13-3-0 (3.30.1.14)
ANSI/HI 14.6.3.4.1
www.armstrongfluidtechnology.com 10/22/2018, Ref. # 697911.1 rev1 Page 2 of 4
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 60 USgpm 67.3 psi 50.80 %
Design point 60 USgpm 55 psig 51.84 %
50% average flow (with default load profile) 30 usgpm 30.3 psi 46.46 %
Dimensional data (not for construction)
Top viewSide view
Weight: 267 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.5 5ANSI-125 4 0.53.88
Outlet 1.5 5ANSI-125 4 0.53.88
*Equally spaced straddling centreline
Special instructions
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10 UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors www.armstrongfluidtechnology.com 10/22/2018, Ref. # 697911.1 rev1 Page 3 of 4
Project # : 697911.1 rev1 Submittal
Product: Expansion
Model: Expansion Equipment
Project Number: 697911.1.1 Representative: Northrich Company
9545 Midwest Ave, St A Cleveland, Ohio 44125
Name: Mansfield Air Nat Guard Reference: 697911.1.1
Phone: (216) 581-4750, Fax: (216) 581-4701
Date:
Location: Manfield OH
Order No: 10/18/2018 Engineer:
Submitted by: Robert Evans Date: 10/22/2018 Contractor:
Approved by: Date:
SYSTEM DATA
Tag Num : Service :
Location : Qty : 1 Selection Method : Manual
Application: Heating
This has been a Manual Selection, so no data is available.
Expansion Tank Tank Model :35-L : 1Tank Qty
:10.0 us galTank Volume Max. Working Pres. : 125 psi
• Not for Domestic Potable Water Systems.Charge Pressure: 26.8 ft
• Designed and constructed per ASME, Section VIII, Division 1.
Standard factory charge is 12 psi (83 kPa) unless otherwise specified. • California Code Sight-glass available upon request.
• Allow a minimum of 18" (457 mm) clearance for system piping.
Shell : Carbon Steel WORKING TEMPERATURE : 240°F (115°C)
Bladder : Heavy Duty Butyl WORKING PRESSURE :125 psi (862 kPa) www.armstrongfluidtechnology.com 10/22/2018, Ref. # 697911.1 rev1 Page 4 of 4
S. A. Armstrong Limited 23 Bertrand Avenue Toronto, Ontario Canada, M1L 2P3 T: (416) 755-2291 F (Main): (416) 759-9101
Armstrong Pumps Inc.
93 East Avenue North Tonawanda, New York U.S.A. 14120-6594 T: (716) 693-8813 F: (716) 693-8970
Armstrong Holden Brooke Pullen Wenlock Way Manchester United Kingdom, M12 5JL T: +44 (0) 161 223 2223 F: +44 (0) 161 220 9660 © S.A. Armstrong Limited 2010
For Armstrong locations worldwide, please visit www.armstrongintegrated.com
SUBMITTAL
JOB:
ENGINEER:
CONTRACTOR:
REPRESENTATIVE:
ORDER NO:
SUBMITTED BY:
APPROVED BY:
DATE:
DATE:
DATE:
MAXIMUM OPERATING CONDITIONS
Working Temperature 240°F (115°C) Working Pressure 125 psi (862 kPa)
FILE NO: 37.521
DATE: Feb. 18, 2010
SUPERSEDES: 37.521
DATE: Feb. 04, 2009
L Series - Pre-Charged (ASME) Expansion Tank
MODEL NO. ORDERED: _____________ QTY.: ________
TAG NO.: _______________
CHARGE PRESSURE: ______________ psi/kPa
Standard factory charge is 12 psi (83 kPa) unless otherwise specified.
MATERIALS OF CONSTRUCTION
Shell Carbon Steel Bladder Heavy Duty Butyl
Not for Domestic Potable Water Systems.
Designed and constructed per ASME, Section VIII, Division 1.
California Code Sight-glass available upon request.
Allow a minimum of 18” (457 mm) clearance for system
Model Tank
Volume
Maximum Acceptance
Volume A B
System Connection
NPT
Shipping Weight gal. in. (mm) in. (mm) in. (mm) lbs. (kg)
35-L 10 (38) 10 (38) 12 (305) 25 (635) 0.75 (19) 40 (18) 50-L 13 (49) 13 (49) 14 (356) 25 (635) 0.75 (19) 50 (23) 85-L 23 (87) 23 (87) 16 (406) 37 (940) 1.00 (19) 90 (41) 130-L 35 (132) 35 (132) 20 (508) 37 (940) 1.00 (19) 125 (57) gal. (L) (L)
TYPICAL SPECIFICATION
Furnish and install, as shown on the plans, Armstrong Model ______-L ASME pre-charged Bladder Expansion Tank, stamped 125 psi (862 kPa) working pressure.
Each tank will be supplied with a heavy duty butyl replaceable bladder. Tank shall be supplied with a ring base, lifting rings, and NPT system connection. An air charging valve connection (standard tire valve) shall be provided to facilitate adjusting pre-charge pressure to meet actual system conditions.