RFI_08.pdf

PDF 147 KB Posted

Attached to
Repair Maintenance Hangar, B102
Solicitation number
W9136419B7001
Issued by

About this file

This document includes a Request for Information and response regarding a federal contract solicitation for repair and renovation work at Mansfield Air National Guard Base in Ohio. The solicitation requires repair and upgrades to fire protection, mechanical, plumbing and electrical systems as well as exterior brick, siding, windows and doors. The work must meet energy efficiency and security standards and is set aside for small businesses with a revenue size standard of $36.5 million. The pre-bid conference is July 30th and bids are due August 23rd. Interested parties must register in SAM and view documents on FedBizOpps as amendments will only be posted there. The response provides specifications for aluminum sunshades to be installed at window locations as shown on floor plans and elevations.

RFI 08 and responses

View the file

Other files

File Type Posted
Bid_opening_attendance.pdf PDF
Abstract_B102_signed.pdf PDF
W91364-19-B-7001_0003.pdf PDF
RFI_27a_attach2.pdf PDF
RFI_35.pdf PDF
RFI_27a.pdf PDF
RFI_27a_attach1.pdf PDF
RFI_32.pdf PDF
W91364-19-B-7001_0002.pdf PDF
RFI_34.pdf PDF
RFI_24_attach1.pdf PDF
RFI_29.pdf PDF
RFI_24_attach2.pdf PDF
RFI_24.pdf PDF
RFI_15.pdf PDF
RFI_30.pdf PDF
RFI_36.pdf PDF
RFI_28.pdf PDF
RFI_23.pdf PDF
RFI_25.pdf PDF
RFI_26.pdf PDF
RFI_21.pdf PDF
RFI_19.pdf PDF
RFI_33.pdf PDF
RFI_31.pdf PDF
RFI_17.pdf PDF
RFI_14.pdf PDF
RFI_27.pdf PDF
RFI_10.pdf PDF
RFI_22.pdf PDF
RFI_18.pdf PDF
RFI_13.pdf PDF
RFI_20.pdf PDF
RFI_04.pdf PDF
RFI_16.pdf PDF
RFI_09_attachment.pptx PPTX presentation
RFI_07.pdf PDF
B102,_site_visit_2.0.pdf PDF
RFI_09.pdf PDF
RFI_12.pdf PDF
W91364-19-B-7001_0001.pdf PDF
RFI_05.pdf PDF
RFI_06.pdf PDF
RFI_03.pdf PDF
RFI_02.pdf PDF
Full_size_drawings_15.pdf PDF
Full_size_drawings_7b.pdf PDF
Full_size_drawings_10.pdf PDF
Full_size_drawings_3.pdf PDF
Full_size_drawings_2b.pdf PDF
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION

R E

Q U

E S

T O

R S

E C

T

IO

N

From: Date:

To: Contracting Officer

1. Solicitation Number:

W91364-19-B-7001

2. Location of Project:

Mansfield Ohio ANG

3. Information Requested: (Include Specification Section and/or Drawing Number and Page if inquiring about a discrepancy)

Regarding the sunshades:

1. There is no specification. Please provide one.

2. There are no dimensions for the sunshades shown on the drawings. Should we scale the drawings to get the size?

3. The sunshades are shown graphically on the floor plans and reflected ceiling plans but not noted. They are not shown at all on the elevation drawings.

Attachments: Date Response Required:

By: Title:

Requestor's FAX Number: Requestor's Telephone Number:

R E

S P

O N

S E

To: Date:

Response:

1. There is no specification. Please provide one.

See attached page for specification.

2. There are no dimensions for the sunshades shown on the drawings. Should we scale the drawings to get the size?

The sunshades shall extend 2 inches beyond each side of the window frame. Width shall be 3’- 0” measured from exterior face of wall. Depth shall be 8 inches.

3. The sunshades are shown graphically on the floor plans and reflected ceiling plans but not noted. They are not shown at all on the elevation drawings.

The sunshades are shown on the elevations but not keynoted. They are required at all locations shown on the floor plans and reflected ceiling plans.

This information is a clarification of the solicitation/contract and does not change the contract terms or conditions.

This information is a proposed change to the solicitation/contract. An amendment will be issued.

Contracting Officer:

X

SECTION 10 71 10

SUNSHADES

1. General

a. Sunshades shall be provided and installed by the contractor, and shall be a complete ready to install system including fascia channels, tensioning rods, and attachment hardware.

b. Sunshades shall be rated by engineering analysis or testing for 120 MPH wind speeds in accordance with ASCE 7. Provide analysis or testing documentation sealed by a professional engineer.

c. Submit the following

i. Manufacturer’s data sheet including preparation instructions, storage and handling requirements recommendations and installation method.

ii. Shop drawings including system components, dimensions, attachments, and accessories.

iii. Sustainability documentation including percentages by weight of post-consumer and pre-consumer recycled content, location and distance from project of material manufacturer and material point of origin, and a statement indicating cost for each regional material and the fraction by weight that is considered regional.

iv. Two complete sets of color chips representing full range of available colors.

Color shall be selected by the COR.

v. Manufacturer's warranty and certificate certifying products meet or exceed specified requirements.

vi. Manufacturer's maintenance instructions

d. Manufacturer’s and installers shall each have 5 years minimum experience manufacturing and installing similar sun screen systems.

e. All welders shall be AWS certified.

2. Products

a. Frames and blades: Extruded aluminum alloy

b. Metal Components: Aluminum Alloy

c. Frames: 1/8” minimum thickness.

d. Hardware, Anchors, and Fasteners: Stainless steel or hot dip galvanized for corrosion resistance. Provide measures to protect against corrosion of dissimilar metals.

e. Finishes: Two coat minimum fluoropolymer; 70 percent PVDF resin by weight complying with AAMA 2605, 1.2 mils dry film thickness. 20 year coating warranty against peeling, blistering, chips, cracks, or checks.

3. Execution

a. Do not begin installation until substrates have been properly prepared.

b. Prepare surfaces and install sunshades in accordance with manufacturer's instructions and in proper relationship with adjacent construction.

c. Protect installed products until completion of project. Touch-up, repair, or replace damaged products, repairs shall be approved by the COR.

File details come from the government source that posted it. Updated .