This document contains a solicitation for the construction of a Low Observable Component Repair Facility to support F-22 aircraft at Langley Air Force Base in Virginia. The project includes construction of a 6,735 square meter facility with four high bays - three for low observable critical repair work and one wash rack. The facility will provide spaces for corrosion control hangars, shops, administration, and building systems support. Site utilities must provide power and communications to support F-22 maintenance equipment. Construction is expected to last 730 calendar days. The solicitation was issued by the Department of the Army Corps of Engineers Norfolk District for the construction of the repair facility in accordance with Defense Department facilities standards and sustainable building practices.
View the file
Other files for this federal contract opportunity
Show all 50
F-22 Low Observable Component Repair Facility (LOCRF) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WATER METER SCHEDULE
TAG LOCATION SERVES EQUIPMENT NAME NOTES
WM-1 MECHANICAL ROOM DOMESTIC WATER SUPPLY DOMESTIC WATER METER 1
NOTES:
1. THREE-INCH SIZE, WITH PULSING OUTPUT SUITABLE FOR DDC SYSTEM AND DATA LOGGING. RATED LEAD
FREE AND NSF 61. PROVIDE WITH OPTIONAL STRAINER.
WATER HEATER SCHEDULE
TAG APPLICATION EWT
(F)
LWT
(F)
CAPACITY
(GAL)
FIRST HOUR
CAPACITY (GPH)
TYPE
ELECTRICAL
SHIP WT
(LBS)
UNIT
DIMENSIONS
(H" x DIA.")
REMARKS
VOLTAGE PHASE AMPS
WH-1 DOMESTIC HW 40 160 120 552 GAS 120 V 1 <10A 875 75-1/2 x 34 1, 2
WH-2 WASHRACK HWC 40 160 40 50 ELECTRIC 277 V 1 10.8 108 46-1/4 X 22-1/4 3
NOTES:
1. HIGH EFFICIENCY MODULATING BURNER, VERTICAL ALIGNMENT, 150 PSIG DESIGN PRESSURE, PLUG AND CORD CONNECTION.
2. 500,000 BTU/HR INPUT, 1" GAS CONNECTION, 4" AIR INLET AND 4" VENT.
3. 3,000 WATT INPUT, ENAMEL LINED TANK WITH MAGNESIUM ANODE AND 2-1/2" RIGID POLYURETHANE INSULATION, UL LISTED, EQUIPPED WITH ASME TEMPERATURE AND PRESSURE RELIEF VALVE, SURFACE MOUNTED THERMOSTAT WITH INTEGRAL, MANUAL RESET, HIGH LIMIT CONTROL.
TRAP PRIMER SCHEDULE
TAG TYPE POWER LOCATION
OPERATING RANGE
NOTES
TEMPERATURE PRESSURE
ETP-1 ELECTRIONIC 115V / 1PH / 6.3 WATT SEE NOTE 2 32F - 125F 20 - 150 PSI 1,2
NOTES:
1. ELECTRONIC TRAP PRIMER WITH SOLENOID VALVE AND 1" AIR GAP AND BUILT-IN TIMER. PROVIDE 16GA RECESSED ENCLOSURE WITH STAINLESS STEEL ACCESS DOOR. MOUNT MINIMUM 18 INCHES ABOVE FINISHED FLOOR. PROVIDE DISTRIBUTION UNIT FOR
MULTIPLE PRIMER LINES WHERE REQUIRED.
2. FIELD LOCATE AT EACH FLOOR DRAIN AND FLOOR SINK. CONCEAL IN WALL OR ABOVE CEILING IN ACCESSIBLE LOCATION.
PLUMBING FIXTURES SCHEDULE
TAG ITEM
CONNECTIONS
REMARKS
WASTE VENT C.W. H.W.
FIXTURES
BFP-1 BACKFLOW PREVENTER - - 6" - RATED FOR DOMESTIC WATER, SCHEDULE 40 STAINLESS STEEL HOUSING. DOUBLE CHECK VALVE TYPE.
BFP-2 BACKFLOW PREVENTER - - 1" - RATED FOR DOMESTIC WATER SYSTEM, BRONZE HOUSING, FNPT ENDS, QUARTER-TURN BALL VALVES
BFP-3 BACKFLOW PREVENTER - - - 1" RATED FOR DOMESTIC WATER SYSTEM, BRONZE HOUSING, FNPT ENDS, QUARTER-TURN BALL VALVES, -HW SUFFIX FOR HOT WATER CONDITION.
BFP-4 BACKFLOW PREVENTER - - 2" - RATED FOR DOMESTIC WATER SYSTEM, BRONZE HOUSING, FNPT ENDS, QUARTER-TURN BALL VALVES
ESS-1 EMERGENCY SAFETY STATION - - 1" 1"
EMERGENCY SAFETY SHOWER AND EYEWASH COMBINATION UNIT. TYPE 304 STAINLESS STEEL CONSTRUCTION. INSTALLED WITH A TV-2 VALVE. MEETS ANSI Z358.1-2009 REQUIREMENTS. 2" TW CONNECTION. PROVIDE WITH ELECTRIC FLASHING LIGHT AND ALARM HORN UNIT. FLOW SWITCH WITH LIGHT/HORN. CLASS 1 / DIV 1 LISTED.
EWC-1 ELECTRIC WATER COOLER 1-1/2" 2" 1/2" - TWO LEVEL ADA VANDAL PROOF DRINKING FOUNTAIN WITH CHILLER. AUTOMATIC BOTTLE FILLER. CHILLER WITH RECOVERY RATE OF 8GPH. ALL FIXTURES STAINLESS STEEL.
HB-1 HOSE BIBB - EXTERIOR - - 3/4" -
AUTOMATIC DRAINING, FREEZELESS WALL HYDRANT WITH HOSE CONNECTION ANTI-SIPHON VACUUM BREAKERS. EXTERIOR IS CHROME FINISH WITH ONE PIECE VALVE PLUNGER. PROVIDE WITH 1/4 TURN BALL VALVE FOR
ISOLATION.
HB-2 HOSE BIBB - INTERIOR - - 3/4" 3/4"
AUTOMATIC DRAINING, MILD CLIMATE HOT AND COLD WATER WALL HYDRANT WITH HOSE CONNECTION ANTI-SIPHON VACUUM BREAKERS. EXTERIOR IS BRASS FINISH WITH TWO HANDLE OPERATION. PROVIDE WITH 1/4 TURN
BALL VALVE FOR ISOLATION.
HR-1 HOSE REEL - AIR (TOOL) - - - - SPRING REWIND HOSE REEL, 50' LENGTH, 1/2" NPT. SIZE AND VALVING PER DETAILS.
HR-2 HOSE REEL - AIR (PAINT) - - - - SPRING REWIND HOSE REEL, 25' LENGTH, 1/2" NPT. SIZE AND VALVING PER DETAILS.
HR-3 HOSE REEL - AIR (PAINT) - - - - SPRING REWIND HOSE REEL, 50' LENGTH, 1/2" NPT. SIZE AND VALVING PER DETAILS.
LAV-1 LAVATORY 1-1/2" 2" 1/2" 1/2" WALL MOUNT LAVATORY, 30" LENGTH, ONE FAUCET, 0.5 GPM AERATOR AUTOMATIC FAUCETS. PROVIDE 120V, 15A GFCI OUTLET.
LAV-2 LAVATORY 1-1/2" 2" 1/2" 1/2" WALL MOUNT LAVATORY, 60" LENGTH, TWO FAUCET, 0.5 GPM AERATOR AUTOMATIC FAUCETS, 120V/20 AMP CIRCUIT.
LAV-3 LAVATORY 1-1/2" 2" 1/2" 1/2" WALL MOUNT LAVATORY, 90" LENGTH, THREE FAUCET, 0.5 GPM AERATOR AUTOMATIC FAUCETS. PROVIDE 120V, 15A GFCI OUTLET.
RPBP-1 REDUCED PRESSURE BACKFLOW PREVENTER - - - - 1 INCH CONNECTION. ASSE 1013 REDUCED PRESSURE PRINCIPLE BLACKFLOW PREVENTER. BRONZE BODY CONSTRUCTION. WITH STRAINER. REPLACEABLE SEATS. RATED AT 10 GPM AT 12 PSI PRESSURE DROP.
RW-1 RESPIRATOR WASHER - - - 3/4" HOSE DRAIN TO FLOOR SINK. WITH POWER CORD, 120V / 15 AMP, 1 PHASE, 20A BREAKER REQUIRED. PROVIDE RECUCED PRESSURE/DOUBLE CHECK VALVE TYPE BACKFLOW-PREVENTION DEVICE.
SH-1 SHOWER 2" 2" 1/2" 1/2" SINGLE PIVOT ACTION HANDLE, SHOWER TRIM KIT, LIMITED TO 1.3 GPM. ADJUSTABLE TEMPERATURE LIMIT STOP. PROVIDE SHOWER HEAD ARM AND FLANGE.
SHP-1 SHOWER 2" 2" 1/2" 1/2" GELCOAT POLYESTER CONSTRUCTION. WHEELCHAIR ACCESSIBLE. PROVIDE WITH FD-1 FOR DRAINAGE. WITH TILE FLANGE. FULLY GROUT BASE.
SK-1 KITCHEN SINK 2" 1-1/2" 1/2" 1/2" DOUBLE BASIN STAINLESS STEEL ELKAY LK6000 MANUAL DECK MOUNTED FAUCET CHROME PLATED SOLID BRASS BODY WITH 1.5 GPM FLOW CONTROL.
TV-1 TEMPERING VALVE - - 2" 2" THERMOSTATIC MIXING VALVE, RATED FOR DOMESTIC WATER, 2" SUPPLY OUTLET, 120 DEG F, ADJUSTABLE. LEAD-FREE.
TV-2 TEMPERING VALVE - - 1" 1" THERMOSTATIC MIXING VALVE, RATED FOR DOMESTIC WATER, SUPPLY OUTLET 85 DEG F, ADJUSTABLE. STAINLESS STEEL SURFACE MOUNT ENCLOSURE. FOR MOUNTING ADJACENT TO ESS-1.
UR-1 URINAL 2" 2" 3/4" - VITREOUS CHINA WALL HUNG TOP SPUD URINAL. 3/4" IPS EXPOSED 1 GPF MANUAL FLUSHOMETER VALVE.
UR-2 URINAL - ADA 2" 2" 3/4" - SAME AS UR-1, MOUNTED AT ADA HEIGHT.
WC-1 WATER CLOSET 4" 2" 1" - FLOOR MOUNT VITREOUS CHINA WATER CLOSET, 1.28GPF, TOP SPUD AND FLUSHOMETER VALVE. PROVIDE WITH WHITE, OPEN FRONT SEAT WITH LID.
WC-2 WATER CLOSET - ADA 4" 2" 1" - SAME AS WC-1, MOUNTED AT ADA HEIGHT.
PS-1 WASHRACK PUMP STATION - - 3/4" 3/4" CONTRACTOR FURNISHED, CONTRACTOR INSTALLED EQUIPMENT. INCLUDES HOSE REEL.
F-1 WASHRACK FOAMER - - - -
CONTRACTOR FURNISHED, CONTRACTOR INSTALLED EQUIPMENT. HIGH VOLUME FOAM APPLICATOR, STD. WATER PRESSURE 35-125 PSI INLET, 1/2" WATER CONNECTION FROM PS-1. PROVIDE 5 CFM COMPRESSED AIR WITH 1/4" CONNECTION. PROVIDE LOCAL BACKFLOW PREVENTION PER MANUFACTURER'S INSTRUCTIONS.
DRAINAGE
CB-1 CATCH BASIN 16" - - - 26-1/4" WIDE X 40" LONG, 34-3/4" DEEP. HDPE INLINE CATCH BASIN W/ GRATE. DUCTILE IRON SLOTTED GRATE. CUSTOM 18" OUTLET ADAPTER, FIELD TRANSITION TO 16" PIPE. SAME LOAD RATING AS TD-1.
FCO-1 FLOOR CLEANOUT - - - - FINISHED FLOOR. CAST IRON BODY. SIZED TO MATCH PIPE SIZE.
FCO-2 FLOOR CLEANOUT 8" - - - CAST IRON BODY, STAINLESS STEEL TOP, INSIDE CAULK OUTLET. ADJUSTABLE TYPE, EXTRA HEAVY-DUTY CLEANOUT FOR 16" BAY & WASHRACK DRAINAGE SYSTEM.
FD-1 FLOOR DRAIN 2" 2" - - ROUND TOP W/ TRAP PRIMER. ROUGH FINISH IN UNOCCUPIED AREAS, NICKEL FINISH IN OCCUPIED AREAS.
FD-2 FLOOR DRAIN 4" 2" - - ROUND TOP W/ TRAP PRIMER. ROUGH FINISH IN UNOCCUPIED AREAS, NICKEL FINISH IN OCCUPIED AREAS.
FS-1 FLOOR SINK 4" 2" - - 12" SQUARE 8" DEEP ACID RESISTANT EANAMELED CAST IRON, PROVIDE WITH GRATE, TRAP PRIMER, AND SEDIMENT BUCKET.
TD-1 TRENCH DRAIN - - - -
MODULAR PRESLOPED HDPE TRENCH DRAIN SYSTEM APPROXIMATELY 21" WIDE. GRATE SHALL MEET REQUIREMENTS FOR 100,000 LB SINGLE WHEEL LOAD WITH 250 PSI TIRE PRESSURE. PROVIDE ADEQUATE SEGMENTS FOR
LENGTH SHOWN.
TD-2 TRENCH DRAIN - - - -
DECORATIVE DUCTILE IRON GRATE FOR FOOT TRAFFIC RATED TO 2500 LB PER SQUARE FOOT OR GREATER, SEE STRUCTURAL FOR ADDITIONAL REQUIREMENTS. FOR CONTAINMENT ONLY; NO OUTLET. CLOSED END CAP.
PROVIDE ADEQUATE SEGMENTS FOR LENGTH SHOWN.
YCO-1 YARD CLEANOUT - - - - PROVIDE CAST IRON BODY WATER TIGHT ABS COUNTERSUNK PLUG.
EXPANSION TANK SCHEDULE (PLUMBING)
TAG SYSTEM TYPE TANK VOLUME
(GAL)
ACCEPT. VOLUME
(GAL)
MIN. FILL
TEMP (F)
OPERATING
TEMP (F)
MAX. SYS
TEMP (F)
CHARGE
PSIG
RELIEF
PSIG
NOTES
ET-3 DOMESTIC HOT WATER DIAPHRAGM 15 10 40 140 160 60 125 1
ET-4 HOT WATER (WASHRACK) DIAPHRAGM 5 3.3 40 140 160 60 125 1
NOTES:
1. EXPANSION TANK SUITABLE FOR POTABLE WATER, NSF-61 LISTED.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
R H
A M
M E
T T
N A
O F
IL
E
N O
A
W -2
-R
-2
BIM 360://3012011031_F22 LOW OBSERVABLE FACILITY LOCRF/3012011031_LOCRF_P_R19.rvt
1/20/2022 3:08:35 PM
P-601
P L
U M
B
IN
G S
C H
E D
U L
E S
F Y
F
-2 F
O R
M A
L T
R A
IN
IN
G U
N
IT
F
T U
M
M
IL
L E
R
S W
IL
S
O N
B L
IT
T L E
-2
-2
L O
W O
B S
E R
V A
B L
E C
O M
P O
S
IT
E R
E P
A
IR
F A
C
IL
IT
Y
L
O C
R F
A
M E
N D
M E
N T
-2
-2
-2
-2
GENERAL NOTES:
1. ALL POWERED PLUMBING EQUIPMENT TO HAVE MINIMUM 10KA SHORT
CIRCUIT CURRENT RATING.
2. PLUMBING EQUIPMENT ANCHORAGE AND AT/FP BRACING ARE TO BE
DETAILED IN A DEFERRED SUBMITTAL PROVIDED BY THE CONTRACTOR,
SEE S-001.