Attch 10- LOCRF 20Oct21 Blended Drawings Part 1 of 3.pdf

PDF 46 MB Posted

Attached to
F-22 Low Observable Component Repair Facility (LOCRF)
Solicitation number
W9123621R2023
Issued by

About this file

This solicitation is for the construction of a Low Observable Component Repair Facility to support additional F-22A aircraft relocated to Langley Air Force Base in Virginia. The project includes construction of a 6,735 square meter facility with three corrosion control hangar bays, one wash rack bay, shops, administration spaces, restrooms, and building systems support. Each hangar bay will be equipped with appropriate air filtration systems. The facility must be able to withstand seismic and wind loads according to applicable codes and designs. Sustainable design principles will be incorporated. The facility will provide maintenance spaces, fire protection, utilities, and security for specialized F-22A stealth technology repairs. The construction contract duration is estimated at 730 calendar days. The solicitation was issued by the Department of the Army Corps of Engineers Norfolk District.

View the file

Other files

File Type Posted
Attachment 7- Revised Small Business Participation Plan.pdf PDF
W9123621R2023 Amendment 14.pdf PDF
Attachment 8 - Revised Bid Schedule.pdf PDF
W9123621R2023 Amendment 13.pdf PDF
Attch 39 08 33 23 AMENDMENT 09 FEB 22.pdf PDF
Attch 40 06 61 16 AMENDMENT 09 FEB 22.pdf PDF
W9123621R2023 Amendment 12.pdf PDF
Attch 41 Copy of GFE Equipment List_mjm edits 2020.09.24.xlsx XLSX spreadsheet
Attch 38 LOCRF DRAWINGS AMENDMENT 09FEB2022.pdf PDF
Attch 38 08 81 00 Glazing.pdf PDF
Attch 34 13 34 19 METAL BUILDING SYSTEMS.pdf PDF
Attch 37 33 32 16 PACKAGED UTILITY WASTEWATER PUMPING STATION.pdf PDF
W9123621R2023 LOCRF Amendment 11.pdf PDF
Attch 21 01FEB2022 AMENDMENT_DRAWINGS.pdf PDF
Attch 28 03 45 00 PRECAST ARCHITECTURAL CONCRETE.pdf PDF
Attch 22 A 011 EQUIPMENT SCHEDULE METALS TECH and SHOPS.pdf PDF
Attch 29 06 61 16 SOLID SURFACE FABRICATIONS.pdf PDF
Attch 24 P 601 PLUMBING SCHEDULES.pdf PDF
Attch 23 A 533 ROOF DETAILS.pdf PDF
Attachment 8 - Revised CLIN Schedule.pdf PDF
Attch 35 32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENT.pdf PDF
Attch 25 01 11 00 Appendix to 01 11 00 Government Furnished Equipment.pdf PDF
Attch 30 08 34 16 CORROSION CONTROL HANGAR DOORS.pdf PDF
Attch 36 32 13 14.13 CONCRETE PAVING FOR AIRFIELDS AND OTHER HEAVY DUTY PAVEMENTS.pdf PDF
Attch 32 09 97 13.27 HIGH PERFORMANCE COATING FOR STEEL STRUCTURES.pdf PDF
Attch 31 09 90 00 PAINTS AND COATINGS.pdf PDF
Attch 27 01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS.pdf PDF
Attch 26 01 14 00 WORK RESTRICTIONS.pdf PDF
Attch 33 10 56 26.13 MOBILE STORAGE SHELVING UNITS (MECHANICALLY-ASSISTED).pdf PDF
W9123621R2023 Amendment 10.pdf PDF
Site Visit 10 January.pdf PDF
Attachment 20 LOCRF RTA Specifications.pdf PDF
Attachment 16 LOCRF RTA DWGS PART 2 OF 3.pdf PDF
W9123621R2023 Amendment 9.pdf PDF
Attachment 15 LOCRF RTA DWGS PART 1 OF 3.pdf PDF
Attachment 17 LOCRF RTA DWGS PART 3 OF 3.pdf PDF
Attachment 14 LOCRF RTA AF Sust Scoresheet GP vFeb2017.xlsx XLSX spreadsheet
Attachment 19 LOCRF RTA SID PACKAGE.pdf PDF
Attachment 18 LOCRF RTA FF and E PACKAGE.pdf PDF
W9123621R2023 Amendment 8.pdf PDF
Attch 13- LOCRF 20Oct21 Blended Drawings Part 3 of 3.pdf PDF
Attch 11- LOCRF 20Oct21 Blended Drawings Part 2 of 3.pdf PDF
Attch 12- LOCRF 20Oct21 Blended Specifications.pdf PDF
W9123621R2023 Amendment 7.pdf PDF
W9123621R2023 Amendment 6.pdf PDF
W9123621R2023 LOCRF Amend 5.pdf PDF
W9123621R2023 Amendment 4.pdf PDF
A.07.24 - Amendment 3.pdf PDF
A.07.24 - Amendment 2.pdf PDF
A.07.24 - Amendment 1.pdf PDF
Show 40 more

Latest 50 of 63 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

US Army Corps of Engineers ®

SOLICITATION NO.:

CONTRACT NO.:

ISSUE DATE:

VOLUME:

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

R H

A M

M E

T T

N A

O F

IL

E

N O

A

W -2

-R

-2

BIM 360://3012011031_F22 LOW OBSERVABLE FACILITY LOCRF/3012011031_LOCRF_G_R19.rvt

9/13/2021 1:49:57 PM

G-001

C O

V E

R S

H E

E T

F Y

F

-2 F

O R

M A

L T

R A

IN

IN

G U

N

IT

F

T U

D

S

T A

P L E

S

D S

T A

P L E

S

N G

IG

A

N T

E

-1

-2

READY TO ADVERTISE

L O

W O

B S

E R

V A

B L

E C

O M

P O

S

IT

E R

E P

A

IR

F A

C

IL

IT

Y

L

O C

R F

09-14-2021

FY19 F-22 FORMAL TRAINING UNIT (FTU)

LOW OBSERVABLE COMPOSITE REPAIR FACILITY (LOCRF)

PROJECT LOCATION

N

PROJECT LOCATION MAP

PROJECT VICINITY MAP

HAMPTON

NEWPORT NEWS

JOINT BASE, LANGLEY - EUSTIS (JBLE)

READY TO ADVERTISE

OPEN COMPETITION OF PRODUCTS

DURING DESIGN PRODUCTS ARE IDENTIFIED AND VALIDATED TO MEET THE NECESSARY

TECHNICAL REQUIREMENTS OF THE PROJECT, AND ARE INDICATED AS "BASIS OF DESIGN"

WITHIN THE DESIGN DOCUMENTS. THIS DOES NOT LIMIT THE PROVISION OF THE PRODUCTS

AS OTHER PRODUCTS THAT MEET THE STATED TECHNICAL REQUIREMENTS ARE ALSO

ACCEPTABLE. PRODUCTS LISTED HEREIN ARE NOT INTENDED TO BE PROPRIETARY UNLESS

SPECIFICALLY INDICATED. ALTERNATE PRODUCTS WILL BE EVALUATED AND MAY BE ACCEPTED

ON THE BASIS OF COMPLIANCE WITH THE SALIENT AND PERFORMANCE CHARACTERISTICS

OF THE SPECIFICATIONS.

W91236-21-R-2023

NOTE TO READERS

Redesign AE Modification P00002 (Aug 2021): The project is experiencing minor redesign to incorporate some customer requested changes including the addition of a dedicated chiller in the administrative spaces, relocation and resizing of the High Expansion Foam (HEF) tank and incorporation of a contractor provided small-part paint booth in Room 141. Due to this limited scope change, this 100% PreFinal submittal includes only those drawings and specifications that were changed from the previous RTA set (Jan 2021). Subsequent design submittals are scheduled to include all documents.

“Blended Set, 21Oct21.

Includes documents changed in Fall 2021 blended with any unchanged Mar2021 RTA documents. Not for Construction.”

BLENDED 21OCT21

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

R H

A M

M E

T T

N A

O F

IL

E

N O

A

W -2

-R

-2

BIM 360://3012011031_F22 LOW OBSERVABLE FACILITY LOCRF/3012011031_LOCRF_G_R19.rvt

9/13/2021 1:49:57 PM

G-002

S H

E E

T I

N D

E X

F Y

F

-2 F

O R

M A

L T

R A

IN

IN

G U

N

IT

F

T U

D

S

T A

P L E

S

D S

T A

P L E

S

N G

IG

A

N T

E

-1

-2

READY TO ADVERTISE

L O

W O

B S

E R

V A

B L

E C

O M

P O

S

IT

E R

E P

A

IR

F A

C

IL

IT

Y

L

O C

R F

SHEET INDEX

SHEET NUMBER SHEET NAME

EP101D POWER PLAN - AREA D

EP101E POWER PLAN - AREA E

EP102 POWER PLAN - ROOF

EP103 BLDG 330 - LIGHTING AND POWER PLAN

EP401 ENLARGED POWER PLAN - ELECTRICAL ROOMS

EP402 ENLARGED POWER PLAN - MECHANICAL ROOM

EP501 POWER DETAILS

EP502 POWER DETAILS

EP503 POWER DETAILS

EP601 POWER RISER DIAGRAM

EP701 PANELBOARD SCHEDULES

EP702 PANELBOARD SCHEDULES

EP703 PANELBOARD SCHEDULES

EP704 PANELBOARD SCHEDULES

EP705 PANELBOARD SCHEDULES

EP706 PANELBOARD SCHEDULES

EP707 PANELBOARD SCHEDULES

EP708 PANELBOARD SCHEDULES

EP709 MECHANICAL EQUIPMENT SCHEDULE

EP710 EQUIPMENT SCHEDULE

EG101 GROUNDING PLAN

EG102 LIGHTNING PROTECTION PLAN

EG103 CATHODIC PROTECTION PLAN

EG104 CATHODIC PROTECTION PLAN

EG501 LIGHTNING PROTECTION DETAILS

EG502 LIGHTNING PROTECTION DETAILS

EG601 GROUNDING RISER DIAGRAM

16. TELECOMMUNICATIONS

T-001 TELECOMMUNICATIONS GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

T-002 TELECOMMUNICATIONS DIAMOND PLAN

TS100 TELECOMMUNICATIONS SITE PLAN - OVERALL

TD101 TELECOMMUNICATIONS DEMOLITIONS SITE PLAN - PARTIAL

TD102 TELECOMMUNICATIONS DEMOLITIONS SITE PLAN - PARTIAL

TS101 TELECOMMUNICATIONS DEMOLITION SITE PLAN - PARTIAL

TS102 TELECOMMUNICATIONS DEMOLITION SITE PLAN - PARTIAL

TS103 TELECOMMUNICATIONS DEMOLITION SITE PLAN - PARTIAL

TS104 TELECOMMUNICATIONS DEMOLITION SITE PLAN - PARTIAL

TS105 TELECOMMUNICATIONS DEMOLITION SITE PLAN - PARTIAL

TS501 TELECOMMUNICATIONS SITE DETAILS

T-100 OVERALL TELECOMMUNICATIONS PLAN

T101A TELECOMMUNICATIONS PLAN - AREA A

T101B TELECOMMUNICATIONS PLAN - AREA B

T101C TELECOMMUNICATIONS PLAN - AREA C

T101D TELECOMMUNICATIONS PLAN - AREA D

T101E TELECOMMUNICATIONS PLAN - AREA E

T-102 BLDG 330 - TELECOMMUNICATIONS PLAN

T-401 ENLARGED TELECOMMUNICATIONS PLANS

T-501 TELECOMMUNICATION DETAILS

T-502 TELECOMMUNICATION DETAILS

T-503 TELECOMMUNICATION DETAILS

T-601 TELECOMMUNICATIONS RISER DIAGRAMS

T-602 TELECOMMUNICATION DETAIL

X-001 SECURITY LEGEND AND ABBREVIATIONS

X-100 OVERALL SECURITY SYSTEMS PLAN

X101A SECURITY SYSTEMS PLAN - AREA A

X101B SECURITY SYSTEMS PLAN - AREA B

X101C SECURITY SYSTEMS PLAN - AREA C

X101D SECURITY SYSTEMS PLAN - AREA D

X101E SECURITY SYSTEMS PLAN - AREA E

X-501 SECURITY SYSTEMS DETAILS

X-601 SECURITY SYSTEMS RISER DIAGRAM

17. AUDIO VISUAL

TA001 AUDIO VISUAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

TA100 OVERALL AUDIO VISUAL PLAN

TA101A AUDIO VISUAL PLAN - AREA A

TA501 AUDIO VISUAL DETAILS

TA601 AUDIO VISUAL SIGNAL FLOWS

SHEET INDEX

SHEET NUMBER SHEET NAME

11. PLUMBING

P-001 PLUMBING GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

P-101 UNDERFLOOR PLUMBING PLAN - OVERALL

P101A UNDERFLOOR PLUMBING PLAN - AREA A

P101B UNDERFLOOR PLUMBING PLAN - AREA B

P101C UNDERFLOOR PLUMBING PLAN - AREA C

P101D UNDERFLOOR PLUMBING PLAN - AREA D

P101E UNDERFLOOR PLUMBING PLAN - AREA E

P-110 FIRST FLOOR PLUMBING PLAN - OVERALL

P110A FIRST FLOOR PLUMBING PLAN - AREA A

P110B FIRST FLOOR PLUMBING PLAN - AREA B

P110C FIRST FLOOR PLUMBING PLAN - AREA C

P110D FIRST FLOOR PLUMBING PLAN - AREA D

P110E FIRST FLOOR PLUMBING PLAN - AREA E

P-401 ENLARGED PLANS - PLUMBING

P-402 ENLARGED PLANS - PLUMBING

P-501 PLUMBING DETAILS

P-502 PLUMBING DETAILS

P-601 PLUMBING SCHEDULES

P-602 PLUMBING SCHEDULES

P-701 HIGH EXPANSION FOAM CONTAINMENT DIAGRAMS

P-702 WASTE AND VENT RISER DIAGRAM

P-703 DOMESTIC WATER RISER DIAGRAM

13. MECHANICAL

M-001 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

MP101 FIRST FLOOR PIPING PLAN - OVERALL

MP101A FIRST FLOOR PIPING PLAN - AREA A

MP101B FIRST FLOOR PIPING PLAN - AREA B

MP101C FIRST FLOOR PIPING PLAN - AREA C

MP101D FIRST FLOOR PIPING PLAN - AREA D

MP101E FIRST FLOOR PIPING PLAN - AREA E

MH101 FIRST FLOOR VENTILATION PLAN - OVERALL

MH101A FIRST FLOOR VENTILATION PLAN - AREA A

MH101B FIRST FLOOR VENTILATION PLAN - AREA B

MH101C FIRST FLOOR VENTILATION PLAN - AREA C

MH101D FIRST FLOOR VENTILATION PLAN - AREA D

MH101E FIRST FLOOR VENTILATION PLAN - AREA E

MH103 BUILDING 330 VENTILATION PLANS

M-140 MECHANICAL ROOF PLAN

M-301 LO BAY SECTION N-S

M-302 LO BAY SECTION E-W

M-303 SECTIONS - AIR HANDLING EQUIPMENT

M-304 SECTIONS

M-305 MECHANICAL ROOM SECTIONS

M-306 SECTION - AHU-2 & AHU-3

M-307 SECTION - LO HALLWAY

M-308 SECTION-WASHRACK

M-401 ENLARGED PLAN - MECHANICAL ROOM EQUIPMENT LAYOUT

M-402 ENLARGED PLAN - MECHANICAL ROOM PIPING

M-403 ENLARGED PLAN - MECHANICAL ROOM VENTILATION

M-501 DETAILS - HEATING

M-502 DETAILS - VENTILATION

M-503 DETAILS - HEATING

M-601 SCHEDULES - HEATING/COOLING

M-602 SCHEDULES - HEATING/COOLING

M-603 SCHEDULES - VENTILATION

M-604 SCHEDULES - VENTILATION

M-701 DIAGRAMS - HEATING/COOLING

M-702 DIAGRAMS - WATER-COOLED CHILLER PIPING

M-703 DIAGRAM - LO BAY AND PAINT BOOTH AIRFLOW

M-704 DIAGRAMS - AIR-COOLED CHILLER PIPING

M-801 CONTROL SEQUENCES

M-802 CONTROL SEQUENCES

M-803 CONTROL SEQUENCES

M-804 CONTROL SEQUENCES

M-805 CONTROL SEQUENCES

M-806 CONTROL SEQUENCES

M-807 CONTROL SEQUENCES

M-808 CONTROL SEQUENCES

M-809 CONTROL SEQUENCES

M-810 CONTROL SEQUENCES

M-811 CONTROL SEQUENCES

M-812 CONTROL SEQUENCES

M-813 CONTROL SEQUENCES

M-814 CONTROL SEQUENCES

M-815 CONTROL SEQUENCES

14. ELECTRICAL

E-001 ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

E-002 HAZARDOUS CLASSIFICATION PLAN

ES100 ELECTRICAL SITE PLAN - OVERALL

ED101 ELECTRICAL DEMOLITION SITE PLAN - PARTIAL

ED102 ELECTRICAL DEMOLITION SITE PLAN - PARTIAL

ES101 ELECTRICAL SITE PLAN - PARTIAL

ES102 ELECTRICAL SITE PLAN - PARTIAL

ES501 ELECTRICAL SITE DETAILS

ES502 ELECTRICAL SITE DETAILS

ES601 ELECTRICAL SITE ONE-LINE DIAGRAM

EL100 OVERALL LIGHTING PLAN

EL101A LIGHTING PLAN - AREA A

EL101B LIGHTING PLAN - AREA B

EL101C LIGHTING PLAN - AREA C

EL101D LIGHTING PLAN - AREA D

EL101E LIGHTING PLAN - AREA E

EL102 LIGHTING PLAN - ROOF

EL501 LIGHTING CONTROL DETAILS

EL502 LIGHTING CONTROLS DETAILS

EL601 LUMINAIRE SCHEDULE

EL602 LUMINAIRE DETAILS

EL603 LUMINAIRE DETAILS

EP100 OVERALL POWER PLAN

EP101A POWER PLAN - AREA A

EP101B POWER PLAN - AREA B

EP101C POWER PLAN - AREA C

SHEET INDEX

SHEET NUMBER SHEET NAME

A-201 BUILDING ELEVATIONS

A-202 BUILDING ELEVATIONS

A-203 PARTIAL BUILDING ELEVATIONS

A-204 PARTIAL BUILDING ELEVATIONS

A-205 PARTIAL BUILDING ELEVATIONS

A-206 PARTIAL BUILDING ELEVATIONS

A-207 PARTIAL BUILDING ELEVATIONS

A-301 BUILDING SECTION

A-302 BUILDING SECTION

A-303 BUILDING SECTION

A-304 BUILDING SECTION

A-305 BUILDING SECTIONS

A-311 EXTERIOR WALL SECTIONS

A-312 EXTERIOR WALL SECTIONS

A-313 EXTERIOR WALL SECTIONS

A-314 EXTERIOR WALL SECTIONS

A-401 ENLARGED PLANS

A-402 ENLARGED PLANS & CASEWORK ELEVATIONS & SECTIONS

A-403 ENLARGED PLANS - AIR SHOWERS

A-404 RESTROOM ELEVATIONS

A-405 LOCKERS/SHOWERS ELEVATIONS

A-406 TOWER - ENLARGED PLANS

A-501 PLAN DETAILS

A-511 CEILING & EXPANSION JOINT DETAILS

A-521 SECTION DETAILS - CTK ENCLOSURE

A-522 SECTION DETAILS

A-531 ROOF DETAILS

A-532 ROOF DETAILS

A-533 ROOF DETAILS

A-534 ROOF DETAILS

A-541 BUILDING ELEVATION DETAILS

A-542 BUILDING ELEVATION DETAILS

A-551 EXTERIOR DOOR DETAILS

A-552 INTERIOR DOOR DETAILS

A-553 SPECIALTY DOOR DETAILS

A-554 OVERHEAD DOOR DETAILS

A-561 WINDOW & FRAME TYPES

A-562 WINDOW DETAILS

A-563 WINDOW DETAILS

A-564 LOUVER DETAILS

A-601 DOOR FRAMES & TYPES

A-602 DOOR SCHEDULE

A-701 LO BAY BOOTH FITOUT

A-702 SMALL PARTS PAINT BOOTH FITOUT

A-801 EXTERIOR SIGNAGE

A-802 STRIPING PLAN - OVERALL

08. INTERIOR DESIGN

I-101 FIRST FLOOR INTERIOR FINISH PLAN - OVERALL

I101A FIRST FLOOR INTERIOR FINISH PLAN - AREA A

I101B FIRST FLOOR INTERIOR FINISH PLAN - AREA B

I101C FIRST FLOOR INTERIOR FINISH PLAN - AREA C

I101D FIRST FLOOR INTERIOR FINISH PLAN - AREA D

I101E FIRST FLOOR INTERIOR FINISH PLAN - AREA E

I-601 ROOM FINISH SCHEDULE, LEGEND AND NOTES

I-611 SIGNAGE SCHEDULE, ELEVATIONS AND NOTES

I831A PARTIAL FIRST FLOOR INTERIOR SIGNAGE PLAN - AREA A

I831B PARTIAL FIRST FLOOR INTERIOR SIGNAGE PLAN - AREA B

I831C PARTIAL FIRST FLOOR INTERIOR SIGNAGE PLAN - AREA C

I831D PARTIAL FIRST FLOOR INTERIOR SIGNAGE PLAN - AREA D

I831E PARTIAL FIRST FLOOR INTERIOR SIGNAGE PLAN - AREA E

08. INTERIORS

IF101 FIRST FLOOR INTERIOR FURNITURE PLAN - OVERALL

IF101A FIRST FLOOR INTERIOR FURNITURE PLAN - AREA A

IF101B FIRST FLOOR INTERIOR FURNITURE PLAN - AREA B

IF101C FIRST FLOOR INTERIOR FURNITURE PLAN - AREA C

IF101D FIRST FLOOR INTERIOR FURNITURE PLAN - AREA D

IF101E FIRST FLOOR INTERIOR FURNITURE PLAN - AREA E

10. FIRE ALARM

FA001 FIRE ALARM GENERAL NOTES, SYMBOLS & ABBREVIATIONS

FA101 FIRST FLOOR FIRE ALARM REFLECTED CEILING PLAN - OVERALL

FA101A FIRST FLOOR FIRE ALARM REFLECTED CEILING PLAN - AREA A

FA101B FIRST FLOOR FIRE ALARM REFLECTED CEILING PLAN - AREA B

FA101C FIRST FLOOR FIRE ALARM REFLECTED CEILING PLAN - AREA C

FA101D FIRST FLOOR FIRE ALARM REFLECTED CEILING PLAN - AREA D

FA101E FIRST FLOOR FIRE ALARM REFLECTED CEILING PLAN - AREA E

FA501 FIRE ALARM DETAILS

FA502 FIRE ALARM DETAILS

FA601 FIRE ALARM SEQUENCE OF OPERATIONS

FA701 FIRE ALARM RISER DIAGRAMS

10. FIRE PROTECTION

FX001 FIRE PROTECTION GENERAL NOTES, SYMBOLS & ABBREVIATIONS

FX101 FIRST FLOOR FIRE SUPPRESSION PLAN - OVERALL

FX101A FIRST FLOOR FIRE SUPPRESSION PLAN - AREA A

FX101B FIRST FLOOR FIRE SUPPRESSION PLAN - AREA B

FX101C FIRST FLOOR FIRE SUPPRESSION PLAN - AREA C

FX101D FIRST FLOOR FIRE SUPPRESSION PLAN - AREA D

FX101E FIRST FLOOR FIRE SUPPRESSION PLAN - AREA E

FX401 FIRE PROTECTION ENLARGED PLANS

FX402 FIRE PROTECTION SECTIONS

FX501 FIRE PROTECTION DETAILS

FX901 FIRE PROTECTION ISOMETRICS

SHEET INDEX

SHEET NUMBER SHEET NAME

CP100 AIRFIELD PHASING PLAN

CP101 APRON AND TOWWAY GEOMETRY PLAN

CP201 APRON AND TOWWAY JOINT LAYOUT PLAN

CP301 APRON AND TOWWAY SPOT ELEVATION PLAN

CP401 APRON AND TOWWAY TYPICAL SECTIONS

CP501 APRON AND TOWWAY JOINT DETAILS

CP502 APRON AND TOWWAY JOINT DETAILS

CP503 APRON AND TOWWAY JOINT DETAILS

CM101 APRON AND TOWWAY MARKING PLAN

CM501 APRON AND TOWWAY MARKING DETAILS

5.0 LANDSCAPE

L-101 LANDSCAPE PLAN

L-102 LANDSCAPE PLAN

L-103 LANDSCAPE PLAN

L-104 LANDSCAPE PLAN

L-105 LANDSCAPE PLAN

L-501 LANDSCAPE DETAILS

06. STRUCTURAL

S-001 GENERAL STRUCTURAL NOTES

S-002 GENERAL STRUCTURAL NOTES

S-003 WIND PRESSURE CHARTS & DIAGRAMS

S-101 FOUNDATION PLAN - OVERALL

S101A FOUNDATION PLAN - AREA A

S101B FOUNDATION PLAN - AREA B

S101C FOUNDATION PLAN - AREA C

S101D FOUNDATION PLAN - AREA D

S101E FOUNDATION PLAN - AREA E

S-102 SLAB PLAN - OVERALL

S102A SLAB PLAN - AREA A

S102B SLAB PLAN - AREA B

S102C SLAB PLAN - AREA C

S102D SLAB PLAN - AREA D

S102E SLAB PLAN - AREA E

S-103 ROOF FRAMING PLAN - OVERALL

S103A ROOF FRAMING PLAN - AREA A

S103B ROOF FRAMING PLAN - AREA B

S103C ROOF FRAMING PLAN - AREA C

S103D ROOF FRAMING PLAN - AREA D

S103E ROOF FRAMING PLAN - AREA E

S-104 LINTEL PLAN

S-201 ENTRY TOWER FRAMING ELEVATIONS

S-202 DUCT TOWER FRAMING ELEVATIONS

S-301 FOUNDATION SECTIONS - I

S-302 FOUNDATION SECTIONS - II

S-303 PEMB FOUNDATION SECTIONS & DETAILS

S-311 HANGAR SECTION - LO BAY

S-312 HANGAR SECTION - WASH RACK

S-321 ROOF FRAMING SECTIONS - I

S-322 ROOF FRAMING SECTIONS - II

S-323 ROOF FRAMING SECTIONS - III

S-324 ENTRY TOWER SECTIONS & DETAILS

S-325 MISC. SECTIONS & DETAILS

S-326 CHILLER ENCLOSURE FRAMING DETAILS

S-331 SITE SECTIONS & DETAILS - I

S-332 SITE SECTIONS & DETAILS - II

S-401 ENLARGED PLANS - I

S-402 ENLARGED PLANS - II

S-501 CONCRETE DETAILS - I

S-502 CONCRETE DETAILS - II

S-503 CONCRETE DETAILS - III

S-504 CONCRETE DETAILS - IV

S-511 ROOF FRAMING DETAILS - I

S-512 ROOF FRAMING DETAILS - II

S-513 ROOF FRAMING DETAILS - III

S-514 MASONRY DETAILS - I

S-515 MASONRY DETAILS - II

S-516 MASONRY DETAILS - III

S-601 SCHEDULES - GENERAL

S-700 H.E.F. DISCHARGE TANK PLAN

S-701 STORAGE TANK DETAILS

S-702 STORAGE TANK STRUCTURAL DETAILS

S-901 3D PERSPECTIVE VIEWS

07. ARCHITECTURAL

A-001 GENERAL NOTES, ABBREVIATIONS AND SYMBOLS

A-002 ABA ACCESSIBILITY GUIDELINES

A-003 ABA PLAN

A-004 SECURE AREAS PARTIAL PLANS

A-005 AIRCRAFT CLEARANCE REQUIREMENT PLAN & SECTIONS

A-006 PARTITION TYPES

A-007 PARTITION TYPES

A-008 PARTITION HEAD CONDITIONS

A-009 PENETRATION DETAILS

A-010 PENETRATION DETAILS

A-011 EQUIPMENT SCHEDULE - METALS TECH & SHOPS

A-020 BLDG 330 COMM ROOM - DEMO & NEW

AS101 ARCHITECTURAL SITE PLAN

AS501 ARCHITECTURAL SITE PLAN DETAILS - CHILLER

AS502 ARCHITECTURAL SITE PLAN DETAILS - DUMPSTER ENCLOSURE

A-101 FIRST FLOOR PLAN - OVERALL

A101A FIRST FLOOR PLAN - AREA A

A101B FIRST FLOOR PLAN - AREA B

A101C FIRST FLOOR PLAN - AREA C

A101D FIRST FLOOR PLAN - AREA D

A101E FIRST FLOOR PLAN - AREA E

A-102 ROOF PLAN - OVERALL

A102A ROOF PLAN - AREA A

A102B ROOF PLAN - AREA B

A102C ROOF PLAN - AREA C

A102D ROOF PLAN - AREA D

A102E ROOF PLAN - AREA E

A-111 FIRST FLOOR REFLECTED CEILING PLAN - OVERALL

A111A FIRST FLOOR REFLECTED CEILING PLAN - AREA A

A111B FIRST FLOOR REFLECTED CEILING PLAN - AREA B

A111C FIRST FLOOR REFLECTED CEILING PLAN - AREA C

A111D FIRST FLOOR REFLECTED CEILING PLAN - AREA D

A111E FIRST FLOOR REFLECTED CEILING PLAN - AREA E

A-141 AIR BARRIER PLAN & SECTIONS

SHEET INDEX

SHEET NUMBER SHEET NAME

00. GENERAL

G-001 COVER SHEET

G-002 SHEET INDEX

G-003 CODE COMPLIANCE SUMMARY

G-004 CODE COMPLIANCE SUMMARY

G-005 CODE COMPLIANCE SITE PLAN

G-006 FIRST FLOOR LIFE SAFETY PLAN - OVERALL

PH101 PHASE 1 SITE DIAGRAM

PH102 PHASE 2 SITE DIAGRAM

PH103 PHASE 3 SITE DIAGRAM

02. SURVEY / MAPPING

VF001 LEGENDS AND NOTES

VF100 EXISTING CONDITIONS PLAN

VF101 EXISTING CONDITIONS PLAN

VF102 EXISTING CONDITIONS PLAN

VF103 EXISTING CONDITIONS PLAN

VF104 EXISTING CONDITIONS PLAN

VF105 EXISTING CONDITIONS PLAN

VF106 EXISTING CONDITIONS PLAN

VF107 EXISTING CONDITIONS PLAN

04.CIVIL

C-001 LEGEND AND GENERAL NOTES

C-002 CONSTRUCTION ACCESS PLAN

C-003 EROSION AND SEDIMENT CONTROL - PHASE 1 PLAN INITIAL

C-004 EROSION AND SEDIMENT CONTROL - PHASE 1 PLAN FINAL

C-005 EROSION AND SEDIMENT CONTROL - PHASE 2 PLAN INITIAL

C-006 EROSION AND SEDIMENT CONTROL - PHASE 2 PLAN FINAL

C-007 EROSION AND SEDIMENT CONTROL - PHASE 2A PLAN INITIAL

C-008 EROSION AND SEDIMENT CONTROL - PHASE 2A PLAN FINAL

C-009 EROSION AND SEDIMENT CONTROL - PHASE 3 PLAN INITIAL

C-010 EROSION AND SEDIMENT CONTROL - PHASE 3 PLAN FINAL

CD001 DEMOLITION LEGEND & NOTES

CD100 EXISTING CONDITIONS - OVERALL

CD101 DEMOLITION PLAN

CD102 DEMOLITION PLAN

CD103 DEMOLITION PLAN

CD104 DEMOLITION PLAN

CD105 DEMOLITION PLAN

CD106 DEMOLITION PLAN

CD107 DEMOLITION PLAN

CS001 SITE LAYOUT LEGEND & CONTROL POINTS

CS101 SITE LAYOUT PLAN

CS102 SITE LAYOUT PLAN

CS103 SITE LAYOUT PLAN

CS104 SITE LAYOUT PLAN

CS105 SITE LAYOUT PLAN

CS106 SITE LAYOUT PLAN

CS107 SITE LAYOUT PLAN

CG001 GRADING LEGEND & NOTES

CG002 STORM SCHEDULES & NOTES

CG101 GRADING & DRAINAGE PLAN

CG102 GRADING & DRAINAGE PLAN

CG103 GRADING & DRAINAGE PLAN

CG104 GRADING & DRAINAGE PLAN

CG105 GRADING & DRAINAGE PLAN

CG106 GRADING & DRAINAGE PLAN

CG107 GRADING & DRAINAGE PLAN

CG201 STORM SEWER PROFILES

CG202 STORM SEWER PROFILES

CG203 STORM SEWER PROFILES

CG204 STORM SEWER PROFILES

CG205 STORM SEWER PROFILES

CG206 STORM SEWER PROFILES

CG700 POST DEVELOPMENT DRAINAGE AREAS

CG701 STORMWATER MANAGEMENT CALCULATIONS

CG702 STORMWATER MANAGEMENT CALCULATIONS

CG703 STORMWATER MANAGEMENT CALCULATIONS

CU001 UTILITY LEGEND, CONTROL POINTS & SCHEDULES

CU101 UTILITY PLAN

CU102 UTILITY PLAN

CU103 UTILITY PLAN

CU104 UTILITY PLAN

CU105 UTILITY PLAN

CU106 UTILITY PLAN

CU107 UTILITY PLAN

CU201 SANITARY FORCE MAIN PROFILE

CU202 SANITARY FORCE MAIN PROFILE

CU203 SANITARY FORCE MAIN PROFILE

CU204 SANITARY FORCE MAIN PROFILE

CU205 SANITARY FORCE MAIN PROFILE

CU206 SANITARY SEWER PROFILE

CU207 8" DOMESTIC WATER PROFILE

CU208 8" DOMESTIC WATER PROFILE

CU209 8" DOMESTIC WATER PROFILE

CU210 12" FIRE WATER PROFILE

CU211 HEF MAIN PROFILE

C-501 EROSION AND SEDIMENT CONTROL DETAILS AND NOTES

C-502 EROSION AND SEDIMENT CONTROL DETAILS AND NOTES

C-503 EROSION AND SEDIMENT CONTROL DETAILS AND NOTES

C-504 EROSION AND SEDIMENT CONTROL DETAILS AND NOTES

C-505 EROSION AND SEDIMENT CONTROL DETAILS

C-506 DETAILS

C-507 DETAILS

C-508 DETAILS

C-509 DETAILS

C-510 DETAILS

C-511 DETAILS

C-512 DETAILS

C-513 DETAILS

C-514 DETAILS

C-515 DETAILS

C-516 DETAILS

C-517 DETAILS

FIRE PROTECTION / LIFE SAFETY / ACCESSIBILITY CODE REVIEW

LOW OBSERVABLE COMPONENT REPAIR FACILITY (LOCRF), JBLE, HAMPTON, VA

PROJECT'S APPLIED CODES & STANDARDS

UFC 1-200-01: DOD BUILDING CODE, 8 OCTOBER 2019

UFC 3-600-01: DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES, WITH CHANGE 4, 7 FEBRUARY 2020

UFC 4-021-01: DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, WITH CHANGE 1, JANUARY 2010

UFC 4-211-01: AIRCRAFT MAINTENANCE HANGARS, WITH CHANGE 2, MAY 18, 2020

IBC 2018: INTERNATIONAL BUILDING CODE, FOR FIRE RESISTANCE REQUIREMENTS, ALLOWABLE FLOOR AREA, BUILDING HEIGHT

LIMITS, AND BUILDING SEPARATION DISTANCE, EXCEPT AS MODIFIED BY UFC 3-600-01

NFPA 1, 2018: FIRE CODE, FOR DETERMINING VEHICLE ACCESS REQUIREMENTS

NFPA 101, 2018: LIFE SAFETY CODE, FOR BUILDING EGRESS AND LIFE SAFETY EXCEPT AS MODIFIED IN UFC 3-600-01

NFPA 10, 2018: STANDARD FOR PORTABLE FIRE EXTINGUISHERS

NFPA 13, 2019: STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS, MINIMUM REQUIREMENTS FOR DESIGN AND

INSTALLATION OF AUTOMATIC FIRE SPRINKLER SYSTEMS AND EXPOSURE PROTECTION

NFPA 20, 2019: STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION, FOR CONSTRUCTION &

INSTALLATION RQMTS FOR FIRE PUMPS

NFPA 30, 2018: FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, FOR CONSTRUCTION REQUIREMENTS AND FIRE RESISTANCE

RATINGS FOR LIQUID STORAGE AREAS

NFPA 70, 2020: NATIONAL ELECTRICAL CODE (NEC)

NFPA 80, 2019: STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES

NFPA 72, 2019: NATIONAL FIRE ALARM AND SIGNALING CODE

NFPA 90A, 2018: STANDARD INSTALLATION OF AIR CONDITIONING & VENTILATION SYSTEMS, FOR PROTECTION OF OPENINGS, SHAFTS, FIRE DAMPERS, SMOKE DAMPERS, PENETRATIONS AND FAN CONTROL

NFPA 291, 2019: RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS

ABA (ARCHITECTURAL BARRIERS ACT) ACCESSIBILITY STANDARDS FOR DOD FACILITIES, CHAPTERS 1-10, ADOPTED BY DOD BY

MEMORANDUM DATED OCTOBER 2015

1. BUILDING CODE REQUIREMENTS:

A. OCCUPANCY CLASSIFICATION:

B OFFICES, CIRCULATION, SIMULATOR ROOMS, CLASSROOMS, AND CONFERENCE

ROOMS < 50 OCCUPANTS

IBC CHAPTER 3

F-1 WORKSHOP, INDUSTRIAL/SPRAYING NOT CONSIDERED HIGH HAZARD

H-3 HAZARDOUS STORAGE/USE EXCEED MAQS.

B. CONSTRUCTION TYPE: TYPE IIB CONSTRUCTION

IBC CHAPTER 6

C. MIXED USE & OCCUPANCY SEPARATIONS UNLIMITED AREA BUILDING IN ACCORDANCE WITH IBC SECTION 507.4 AND 507.8. EACH

OCCUPANCY IS UNLIMITED IN ACCORDANCE WITH THE UNLIMITED AREA BUILDING.

GROUP H-3 OCCUPANCIES ARE REQUIRED TO BE SEPARATED WITH 1-HOUR

CONSTRUCTION IN ACCORDANCE WITH TABLE 508.4 PER IBC 507.8.3.

B, F-1 AND S-1 OCCUPANCIES DO NOT REQUIRE FIRE RESISTANCE RATED SEPARATIONS

IN ACCORDANCE WITH IBC SECTION 508.3.

IBC SECTION 508

D. AREA LIMITATIONS / MODIFICATIONS: UNLIMITED AREA BUILDING IN ACCORDANCE WITH IBC SECTION 507.4 AND 507.8. EACH

OCCUPANCY, EXCEPT AS NOTED, IS UNLIMITED IN ACCORDANCE WITH THE UNLIMITED

AREA BUILDING. THE AGGREGATE AREA OF GROUP H OCCUPANCIES IS LIMITED TO 10%

OF THE AREA OF THE BUILDING OR THE AREA LIMITATION FOR GROUP H OCCUPANCIES

SPECIFIED IN IBC SECTION 506. IBC SECTION 507.8.2 REQUIRES NOT LESS THAN 25

PERCENT OF THE H-3 PERIMETER TO BE AN EXTERIOR WALL.

ALLOWABLE H-3 AREA IS 7,200 SF BASED ON 10% OF THE 72,000 SF BUILDING. 14,000 SF

ALLOWABLE BY TABLE 506.2. 1,029 SF DESIGNATED AS H-3.

MINIMUM PERIMETER OF H-3 AREA TO BE 41'-1" BASED ON 30% OF PERIMETER (INTERIOR

AND EXTERIOR) OF 137'-0". 41'-10" PROVIDED.

IBC SECTION 503, 506, 507

E. HEIGHT LIMITATIONS: ALLOWABLE BUILDING HEIGHT IS UNLIMITED WHEN THE BUILDING IS CONSTRUCTED

IN ACCORDANCE WITH UFC 4-211-01. THE NUMBER OF STORIES IS BASED ON IBC AND

IS PERMITTED 2 STORIES ABOVE GRADE. THE BUILDING IS 1 STORY AND COMPLIES

WITH BUILDING HEIGHT LIMITATIONS.

UFC 4-211-01 SECTION 3-3.1.7

F. VERTICAL ENCLOSURES, CONTINUITY &

PROTECTION:

THE BUILDING IS 1 STORY AND DOES NOT HAVE STAIRS OR SHAFTS REQUIRING A FIRE

RESISTANCE RATING.

IBC: SECTION 708, NFPA 101: 7.2.2, 8.6

G. OPENING PROTECTIVES & THRU-

PENETRATIONS

1-HOUR FIRE BARRIER: 1-HOUR THRU-PENETRATIONS, 45-MINUTE OPENING PROTECTIVES.

NFPA 101: 8.3 THRU 8.6, NFPA 80 AND 90A

SMOKE PARTITION: SEALED THRU-PENETRATIONS, SELF-CLOSING/SELF-LATCHING

OPENING PROTECTIVES.

H. HORIZONTAL ASSEMBLIES: THE BUILDING IS 1 STORY AND DOES NOT HAVE FIRE RESISTANCE RATED HORIZONTAL

ASSEMBLIES. THE PAINT BAY CEILING IS REQUIRED TO HAVE A 1-HOUR FIRE

RESISTANCE RATING.

IBC: SECTION 712, UFC 4-211-02: 3-2.2.4

I. FIRE RESISTIVE REQUIREMENTS: TYPE IIB IN ACCORDANCE WITH IBC CHAPTER 6.

IBC: TABLE 601 AND SECTION 602 PRIMARY STRUCTURAL FRAME - 0 HOUR RATING

EXTERIOR BEARING WALLS - 0 HOUR RATING

INTERIOR BEARING WALLS - 0 HOUR RATING

EXTERIOR NONBEARING PARTITIONS - 0 HOUR RATING

INTERIOR NONBEARING PARTITIONS - 0 HOUR RATING

FLOOR CONSTRUCTION & SECONDARY MEMBERS - 0 HOUR RATING

ROOF CONSTRUCTION & SECONDARY MEMBERS - 0 HOUR RATING

J. ENCLOSURE PROTECTION: HAZMAT STORAGE ROOM (GROUP H-3) - 1-HOUR FIRE BARRIER WITH 45-MINUTE

PROTECTIVE. B (IBC TABLE 508.4)

NFPA 101: SPECIFIC OCCUPANCY CHAPTERS SPRAY BOOTH - 1-HOUR FIRE BARRIER WITH 45-MINUTE PROTECTIVE OR 3 FT.

SEPARATION DISTANCE FROM OTHER OPERATIONS. A,B (NFPA 33 SECTION 5.5)

ASME A17.1

CONTROL AREA - 1-HOUR FIRE BARRIER WITH 45-MINUTE PROTECTIVE. B (NFPA 400 TABLE

5.2.2.1)UFC 4-211-01

FIRE PUMP ROOM - 1-HOUR FIRE BARRIER WITH 45-MINUTE PROTECTIVE. B (UFC

4-211-01 SECTION 3-6.7)

UFC 4-211-02

HANGAR BAY SEPARATION - 1-HOUR FIRE BARRIER WITH 45-MINUTE PROTECTIVE. B

(UFC 4-211-01 SECTION 3-3.1.3)

HIGHER HAZARD ROOMS - SEPARATION WITH SMOKE PARTITION. (NFPA 101 SECTION 8.7.1)

K. FIRE PROTECTION SYSTEM: WET-PIPE SPRINKLER SYSTEMS WILL BE PROVIDED THROUGHOUT THE BUILDING.

HANGAR BAYS WILL BE PROVIDED WITH HIGH EXPANSION (HI-EX) FOAM SYSTEMS. THE

BUILDING WILL BE PROVIDED WITH A FIRE PUMP TO SUPPLEMENT THE PRESSURE

PROVIDED BY THE FIRE PUMPS IN B348.

UFC 3-600-01: CHAPTER 9

UFC 4-211-01: CHAPTER 3

UFC 3-600-01: CHAPTER 9 LIGHT HAZARD: 0.1 GPM/SF OVER 1,500 SF. OFFICES, CORRIDORS, BATHROOMS, LOCKER ROOMS, CONFERENCE ROOMS.

UFC 3-600-01: APPENDIX B

ORDINARY HAZARD: 0.2 GPM/SF OVER 2,500 SF. MEP SPACES, STORAGE, INDUSTRIAL

AREAS, WELD SHOPS, LO CORRIDOR.

EXTRA HAZARD: 0.3 GPM/SF OVER 2,500 SF. HAZARDOUS MATERIALS STORAGE ROOM.

HANGAR HAZARD: 0.2 GPM/SF OVER 5,000 SF. HANGAR BAYS.

UFC 3-600-01: CHAPTER 9-7 COVERAGE PER SPRINKLER MUST BE IN ACCORDANCE WITH NFPA 13.

NFPA 13 LIGHT HAZARD: 225 SF

ORDINARY HAZARD: 130 SF

EXTRA HAZARD: 100 SF

UFC 4-211-01: CHAPTER 3 HI-EX GENERATORS TO BE WITHIN CLOSE PROXIMITY BUT NOT OVER THE AIRCRAFT.

HI-EX SYSTEM TO COVER 90% OF THE SILHOUETTE WITHIN 1 MINUTE AND PROVIDE A

DEPTH OF 3.2 FEET WITHIN 4 MINUTES. HYDRAULIC CALCULATIONS PERFORMED WITH

FOAM SYSTEM AND CEILING-LEVEL SPRINKLER SYSTEM FLOWING.

L. AVAILABLE WATER SUPPLY TESTING HYDRANT FLOW TESTS WERE PERFORMED ON JUNE 19, 2020 AND WITNESSED BY THE

DESIGN TEAM.

FLOW HYDRANT: SOUTH OF B361

PRESSURE HYDRANT: NORTH OF B361 ADJACENT TO B379.

STATIC: 58 PSI

RESIDUAL: 40 PSI

FLOW: 1,000 GPM.

TESTED LOOP TO PROVIDE SUPPLY TO NEW FIRE HYDRANTS AND PROVIDE ADEQUATE

FIRE FLOW.

FIRE PROTECTION SYSTEMS WILL BE SERVED FROM BUILDING 348 FIRE PUMP HOUSE.

BUILDING 348 HAS FOUR 2,000 GPM PUMPS AT 100 PSI ARRANGED IN PARALLEL.

UFC 3-600-01: 9-6.4

NFPA 291

M. WATER STORAGE TANK REQUIREMENTS EXISTING 1,000,000 GALLON TANK (NOMINAL) PROVIDED TO SUPPLY BUILDING 348. NO

NEW STORAGE PROVIDED.

UFC 3-600-01: CHAPTER 9-4

N. BACKFLOW PREVENTER & TESTING NO BACKFLOW PREVENTION ASSEMBLIES WILL BE PROVIDED OUTSIDE OF OR IN THE

BUILDING AS THE BUILDING IS SERVED FROM A DEDICATED FIRE WATER STORAGE

TANK AND PUMP HOUSE IN B348.NFPA 13: 8.16.4.6.1

UFC 3-600-01; 9-6.6.1

O. FIRE PUMP(S) FIRE PROTECTION SYSTEMS WILL BE SUPPLIED FROM BUILDING 348. BUILDING 348 HAS

4, 100 PSI 2000 GPM FIRE PUMPS INSTALLED IN PARALLEL. THE LOCRF BUILDING WILL BE

PROVIDED A 100 PSI 500 GPM FIRE PUMP WHICH SERVES THE BUILDING ONLY. THE

PUMP WILL BE ARRANGED TO PROVIDE PRESSURE TO THE FOAM SYSTEMS ONLY.

SPRINKLER SYSTEMS WILL BE SUPPLIED SOLELY FROM BUILDING 348.

UFC 3-600-01: 9-5

NFPA 20

2. LIFE SAFETY REQUIREMENTS:

A. CLASSIFICATION OF OCCUPANCY: BUSINESS, INDUSTRIAL - GENERAL, INDUSTRIAL - HIGH HAZARD AND STORAGE.

THE BUILDING IS A MIXED OCCUPANCY BUILDING AND IS REQUIRED TO MEET NFPA 101

SECTION 6.1.14.3 WHERE THE BUILDING MUST COMPLY WITH THE MOST RESTRICTIVE

REQUIREMENTS OF THE OCCUPANCIES INVOLVED.

NFPA 101: CH 6

B. OCCUPANT LOAD:

NFPA 101: 7.3.1.2 & CHAPTERS 12-42

C. CAPACITY OF MEANS OF EGRESS:

NFPA 101: 7.3.3 & CHAPTERS 12-42

D. NUMBER OF EXITS: TWO EXITS REQUIRED FROM ANY STORY AND SECTION OF THE STORY. 21 EXITS FROM

THE FIRST FLOOR ARE PROVIDED, INCLUDING EXITS FROM DEDICATED BUILDING

SERVICE/MEP SPACES. HIGH HAZARD SPACES ARE REQUIRED TO HAVE 2 MEANS OF

EGRESS FROM THE SPACE SIZED AT 0.4 IN./PERSON.

NFPA 101: 7.4 & CHAPTERS 12-42

E. ARRANGEMENT OF MEANS OF EGRESS EXITS ARE REQUIRED TO BE SEPARATED BY NOT LESS THAN ONE-THIRD THE OVERALL

DIMENSION IN A SPRINKLERED BUILDING. EXITS ARE ADEQUATELY SEPARATED AROUND

THE PERIMETER OF THE BUILDING.NFPA 101: 7.5 & CHAPTERS 12-42

F. TRAVEL DISTANCE TO EXITS:

BUSINESS: 100 FEET 50 FEET 300 FEETNFPA 101: 7.6 & CHAPTERS 12-42

INDUSTRIAL: 100 FEET 50 FEET 250 FEET

UNLIMITED

HIGH HAZARD:

G. ILLUMINATION OF MEANS OF EGRESS: ILLUMINATION OF STAIRS SHALL BE 10 FT-CANDLE AND 1 FT-CANDLE FOR WALKING

SURFACES DURING OCCUPANCY. ILLUMINATION WILL BE PROVIDED BY LIGHTING

FIXTURES. REFER TO ELECTRICAL DRAWINGS.NFPA 101: 7.8 & CHAPTERS 12-42

H. EMERGENCY LIGHTING: ILLUMINATION SHALL BE FOR 90 MINUTES AND PROVIDE NOT LESS THAN AN AVERAGE 1

FT-CANDLE. LIGHTING FIXTURES WITH INTEGRAL BATTERY PACKS WITH 90 MINUTES OF

BATTERY POWER WILL BE PROVIDED. REFER TO ELECTRICAL DRAWINGS.NFPA 101: 7.9 & CHAPTERS 12-42

I. MARKING OF MEANS OF EGRESS: ACCESS TO EXITS SHALL BE MARKED WHERE THE EXIT OR WAY TO REACH THE EXIT IS

NOT READILY APPARENT. EXIT SIGNS WILL BE INSTALLED WHERE THE DIRECTION TO

THE EXIT IS NOT READILY APPARENT. REFER TO ELECTRICAL DRAWINGS.NFPA 101: 7.10 & CHAPTERS 12-42

J. INTERIOR FINISH CLASSIFICATION LIMITS:

BUSINESS (NEW): WALL A, B OR C A, B OR C A, B OR C

FLOOR I, II OR NO REQ.1

NFPA 101: TABLE A.10.2.2

INDUSTRIAL: WALL A, B OR C A, B OR C A, B OR C

FLOOR I, II OR NO REQ.1 I, II OR NO REQ.1

K. DETECTION, ALARM & COMMUNICATIONS: A FIRE ALARM SYSTEM IS REQUIRED SINCE OCCUPANCY IS GREATER THAN 100 TOTAL

OCCUPANTS (40.3.4.1). THE SYSTEM WILL BE ACTIVATED BY MANUAL MEANS, FIRE

DETECTION AND SPRINKLER SYSTEM ACTIVATION AND PROVIDE OCCUPANT

NOTIFICATION. IN ADDITION, FLAME DETECTION, FOAM START/STOP STATION AND A

RELEASING SERVICE FIRE ALARM CONTROL UNIT SHALL BE PROVIDED. THE FIRE ALARM

SYSTEM MUST BE COMBINED WITH THE FACILITY MASS NOTIFICATION SYSTEM UTILIZING

A FIRE ALARM CONTROL UNIT AND MASS NOTIFICATION AUTONOMOUS CONTROL UNIT

(FMCP). THE HIGH EXPANSION FOAM RELEASING SYSTEM WILL BE DEDICATED VIA A

RELEASING SERVICE FIRE ALARM CONTROL UNIT (RSFACU).

CO DETECTION IS REQUIRED IN FACILITIES WITH COMBUSTIBLE FUEL BURNING

EQUIPMENT BUT OMITTED IN OPEN SPACES WITH CEILING HEIGHTS GREATER THAN 12

FEET PER UFC 3-600-01 SECTION 9-19.2.3.

UFC 3-600-01, 9-18 AND 9-19

NFPA 101: 9.6 & CHAPTERS 12-42

OCCUPANCY COMMON PATH DEAD-END TRAVEL DISTANCE

25 FEET 150 FEET

DOORS SPACED 150 FEET

ALONG PERIMETER

HANGAR:

OTHER SPACES

O. SMOKE DAMPERS: SMOKE DAMPERS ARE NOT REQUIRED BECAUSE THE AIR INLETS AND OUTLETS ARE

LIMITED TO A SINGLE SMOKE COMPARTMENT AND AIR-HANDLING UNITS ARE

LOCATED ON THE FLOOR THEY SERVE OR ON THE ROOF ABOVE.IBC: SECTION 716

NFPA 90A: 4.3.10.2, 5.3.5.1

P. DUCT SMOKE DETECTORS DUCT SMOKE DETECTORS INSTALLED DOWNSTREAM OF THE AIR FILTERS AND AHEAD

OF ANY BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A CAPACITY GREATER

THAN 2,000 CFM.NFPA 90A: 6.4.2.1

Q. ELEVATORS NO ELEVATORS ARE LOCATED IN THE BUILDING. THE BUILDING IS A SINGLE STORY.

UFC 3-600-01: 4-12

IBC CHAPTER 30

R. ROOF ACCESS: A STAIR TO THE ROOF IS NOT REQUIRED. ACCESS TO THE ROOF REQUIRED TO BE BY

AN ALTERNATING TREAD DEVICE, SHIP'S LADDER OR PERMANENT LADDER. A LADDER

TO THE ROOF HAS BEEN PROVIDED.UFC 3-600-01: 2-9

IBC Chapter 1009.13

S. HAZARDOUS LOCATIONS ALL SPACES WITHIN 5 FEET HORIZONTALLY AND 5 FEET VERTICALLY FROM THE

AIRCRAFT SHALL BE A MINIMUM CLASS I DIVISION 2. SPACES ADJACENT TO THE HANGAR

BAYS ARE NOT REQUIRED TO BE CONSIDERED HAZARDOUS AS THE DOOR HAS SEALED

OPENINGS EXCEPT WITHIN 3 FEET RADIUS OF ALL DOORS SHALL BE CLASS I DIVISION 2.

THE SPRAY ROOMS IN THE LO BAYS SHALL BE CLASS I DIVISION 1 THROUGHOUT.

HANGAR BAYS AND THE HAZARDOUS MATERIALS STORAGE ROOM WILL BE CLASSIFIED

IN ACCORDANCE WITH NFPA 70.

NFPA 70:

UFC 4-211-01: 3-7.1

UFC 4-211-02: 3-7.2

T. FIRE DEPT VEHICLE ACCESS ONE MEANS OF ALL-WEATHER GROUND ACCESS TO ALLOW EMERGENCY VEHICLES

UNIMPEDED ACCESS TO THE FACILITY. ALL-WEATHER GROUND ACCESS MUST BE PAVED,

START FROM THE ROAD, AND TERMINATE NO FARTHER THAN 33 FEET FROM AN

EXTERIOR DOOR ACCESSIBLE FOR FIRE DEPARTMENT INGRESS. THE ROUTE BETWEEN

THE ACCESS SURFACE AND EXTERIOR DOOR MUST BE ABLE TO BE TRAVERSED WITHOUT

THE USE OF A LADDER. ADDITIONALLY, PROVIDE SUITABLE EXTERIOR FIRE APPARATUS

ACCESS ON AT LEAST TWO COMPLETE SIDES OF THE BUILDING INCLUDING APRONS,

AUTOMOTIVE PARKING AREAS, FIRE APPARATUS ACCESS ROADS AND STABILIZED

LANDSCAPED AREAS.

ACCESS IS PROVIDED TO THE APRON-SIDE DOORS FOR FIRE DEPARTMENT INGRESS TO

THE FACILITY.

UFC 3-600-01: 2-10

NFPA 1: 3.5

U. FIRE HYDRANT INSTALLATION HYDRANTS REQUIRED AT NOT MORE THAN 300 FOOT SPACING AROUND THE BUILDING.

UFC 3-600-01: 3-7.3 ALL PARTS OF THE FACILITY EXTERIOR MUST BE WITHIN 350 FEET OF A HYDRANT.

HYDRANTS WILL NOT BE INSTALLED IN FRONT OF HANGAR BAY DOORS.

ONE HYDRANT WILL BE PROVIDED WITHIN 100 FEET OF EACH CORNER OF THE BUILDING.

WHERE THE APRON ABUTS THE BUILDING, HYDRANTS WILL BE LOCATED WITHIN 10

FEET OF THE BUILDING.

HYDRANTS ADJACENT TO AIRFIELD PAVEMENT WILL NOT HAVE THEIR TOPS MORE THAN

2.5 FEET ABOVE THE LEVEL OF ADJACENT AIRFIELD PAVEMENT.

V. KITCHEN COOKING EXHAUST EQUIPMENT THERE IS NO KITCHEN IN THE FACILITY.

NFPA 101: 9.2.3, CHAPTERS 12-42

NFPA 96

3. MASS NOTIFICATION:

UFC 4-021-01 A COMBINED FIRE ALARM AND MASS NOTIFICATION SYSTEM WILL BE INSTALLED UTILIZING

A FIRE ALARM CONTROL UNIT AND MASS NOTIFICATION AUTONOMOUS CONTROL UNIT

(FMCP). ALL NOTIFICATION APPLIANCES WILL UTILIZE CLEAR STROBES AND BE MARKED

"ALERT." AMBER LENSES AND APPLIANCES MARKED "FIRE" WILL NOT BE USED. TEXT

SIGNS WILL BE SCROLLING TYPE, PROGRAMMABLE AND DISPLAY THE SAME CONTENT OF

THE VOICE MESSAGE BEING PLAYED. TEXT SIGNS TO BE INSTALLED OVER SUBSTANTIAL

MEANS OF EGRESS. EXTERIOR DOORS FROM A SINGLE ROOM DO NOT REQUIRE A TEXT

SIGN.

ENGINEERING AND CONSTRUCTION

BULLETIN 2018-17

4. ACCESSIBILITY REQUIREMENTS:

ABA CHAPTERS 1-10 THE FACILITY SHALL BE COMPLETELY ACCESSIBLE IN ACCORDANCE WITH ABA.

NFPA 33, 2018: STANDARD FOR SPRAY APPLICATION USING FLAMMABLE OR COMBUSTIBLE MATERIALS

NFPA 11, 2016: STANDARD FOR LOW-, MEDIUM-, AND HIGH-EXPANSION FOAM

NFPA 24, 2019, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES

NFPA 400, 2019: HAZARDOUS MATERIALS CODE

A - THE LO BAY SPRAY BOOTHS ARE SEPARATED FROM OTHER OPERATIONS BY MORE

THAN 3 FT. AND, THEREFORE, DO NOT REQUIRE FIRE-RESISTANCE RATED

CONSTRUCTION. THE SPRAY BOOTH IN THE PANEL SPRAY ROOM WILL BE PROVIDED

WITH ADMINISTRATIVE CONTROLS AND FLOOR MARKINGS SUCH THAT THE REQUIRED 3

FT. SEPARATION FROM OTHER OPERATIONS IS PROVIDED. THEREFORE, THE BOOTH WILL

NOT HAVE A FIRE RESISTANCE RATING.

B - A FIRE DAMPER IS NOT REQUIRED FOR DUCTED PENETRATIONS THROUGH 1-HOUR

FIRE-RESISTANCE RATED PARTITIONS (NFPA 90A SECTION 5.3.1). A 90-MINUTE RATED

FIRE DAMPER IS REQUIRED IN ALL AIR-TRANSFER OPENINGS IN 1-HOUR FIRE-

RESISTANCE RATED PARTITIONS (NFPA 90A SECTION 5.3.1).

REFER TO OCCUPANT LOAD TABLE ON SHEET G004.

REFER TO EXIT CAPACITY TABLE ON SHEET G004.

NFPA 409, 2016: STANDARD ON AIRCRAFT HANGARS (ONLY APPLICABLE WHERE REFERENCED SPECIFICALLY BY THE UFC)

UFC 4-211-01: 3-3.1.2

UFC 4-211-01: 3-3.1.11

L. PORTABLE FIRE EXTINGUISHERS: FIRE EXTINGUISHERS ARE REQUIRED IN THE BUILDING PER NFPA 101. FIRE

EXTINGUISHERS WILL BE PROVIDED IN ACCORDANCE WITH NFPA 10.

NFPA 101: 9.7.4

M. CORRIDORS: CORRIDORS ARE NOT REQUIRED TO BE RATED SINCE THE BUILDING IS PROTECTED

THROUGHOUT BY A SUPERVISED AUTOMATIC SPRINKLER SYSTEM. A MINIMUM

CORRIDOR WIDTH OF 44 INCHES MUST BE MAINTAINED FOR ANY CORRIDOR

SERVING AN OCCUPANT LOAD OF 50 OCCUPANTS OR MORE AND 36 INCHES

SERVING LESS THAN 50 OCCUPANTS (NFPA 101 SECTION 7.3.4).

NFPA 101: CHAPTERS 12-42

N. FIRE DAMPERS: NO FIRE DAMPERS ARE REQUIRED AS ALL PENETRATIONS THROUGH 1-HOUR FIRE

RESISTANCE-RATED PARTITIONS ARE DUCTED. NO 2-HOUR CONSTRUCTION IS

PROVIDED.NFPA 90A: 5.3.1, 5.4.1 & 5.4.2

NFPA 33: 5.5

NFPA 400: TABLE 5.2.2.1

UFC 4-211-01

UFC 4-211-02: AIRCRAFT CORROSION CONTROL AND PAINT FACILITIES, 1 DECEMBER 2012

UFC 4-010-01: DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 12 DECEMBER 2018

UFC 4-211-01

N/A

N/A

STORAGE: WALL A, B OR C A, B OR C A, B OR C

FLOOR I, II OR NO REQ.1

S-1 LO BAYS, STORAGE ROOMS, ELECTRICAL ROOMS AND MECHANICAL ROOMS

EXITS EXIT ACCESS CORRIDORS

1 MINIMUM RADIANT FLUX OF 0.1 W/CM2 REQUIRED

A.

B.

D.

E.

G.

H.

T.

I.

K.

L.

N.

P.

R.

Q.

S.

U.

X.

O.

J.

M.

V.

W.

F.

C.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

R H

A M

M E

T T

N A

O F

IL

E

N O

A

W -2

-R

-2

BIM 360://3012011031_F22 LOW OBSERVABLE FACILITY LOCRF/3012011031_LOCRF_FP_R19.rvt

9/10/2021 10:53:38 AM

G-003

C O

D E

C O

M P

L

IA

N C

E S

U M

M A

R Y

F Y

F

-2 F

O R

M A

L T

R A

IN

IN

G U

N

IT

F

T U

C

B

U T

T E

R W

O R

T H

L

IV

E R

S O

N

J A

N D

E R

S O

N

-1

-2

READY TO ADVERTISE

L O

W O

B S

E R

V A

B L

E C

O M

P O

S

IT

E R

E P

A

IR

F A

C

IL

IT

Y

L

O C

R F

SHEET NOTES:

1. THE OCCUPANCY CLASSIFICATION SHOWN ON THE OCCUPANT LOAD

CALCULATIONS TABLE IS FOR REFERENCE ONLY. THE OCCUPANT LOAD IS

CALCULATED PER ROOM USING SQUARE FOOTAGE AND OCCUPANT LOAD

FACTOR/USE DEFINED IN NFPA 101 AND UFC 3-600-01.

TOTAL 3

HALLWAY 153 - EXTERIOR 36 33 0.2 165 7

STORAGE 155 - EXTERIOR 36 33 0.2 165 1

TOTAL 496

EXIT DISCHARGE DOOR NOMINAL WIDTH CLEAR WIDTH FACTOR EGRESS CAPACITY ACTUAL USE

VESTIBULE 100 - EXTERIOR 72 66 0.2 330 120

ADMIN HALLWAY 101 ADJACENT TO 107 - EXTERIOR 36 33 0.2 165 63

LO BAY 1 - SW EXTERIOR 36 33 0.2 165 6

EXIT ACCESS DOOR NOMINAL WIDTH CLEAR WIDTH FACTOR EGRESS CAPACITY ACTUAL USE

HAZMAT STORAGE - SOUTH DOOR 76 70 0.4 175 2

HAZMAT STORAGE - EAST DOOR 76 70 0.4 175 1

LO BAY 1 - NE EXTERIOR 36 33 0.2 165 6

OPEN STORAGE - EXTERIOR 36 33 0.2 165 4

LO BAY 2 - NE EXTERIOR 36 33 0.2 165 6

LO HALLWAY ADJACENT TO HAZMAT - EXTERIOR 36 33 0.2 165 53

LO HALLWAY ADJACENT TO MECHANICAL - EXTERIOR 36 33 0.2 165 61

MECHANICAL 133 - EXTERIOR 36 33 0.2 165 8

FIRE 135 - EXTERIOR 72 66 0.2 330 2

ELECTRIC 134 - EXTERIOR 72 66 0.2 330 1

LO BAY 3 - NW EXTERIOR 36 33 0.2 165 6

LO BAY 3 - NE EXTERIOR 36 33 0.2 165 6

METALS TECH WELDING - NORTH EXTERIOR 36 33 0.2 165 21

METALS TECH MACHINE - EAST EXTERIOR 36 33 0.2 165 60

HALLWAY 144 - EXTERIOR 36 33 0.2 165 52

WASH RACK - NW EXTERIOR 36 33 0.2 165 6

WASH RACK - NE EXTERIOR 36 33 0.2 165 6

MECHANICAL 151 - EXTERIOR 72 66 0.2 330 1

154 COMM 80 GROUP S-1 STORAGE IT 300 1

155 RR 65 GROUP B BUSINESS BUSINESS 150 1

156 OFFICE 222 GROUP F-1 GENERAL INDUSTRIAL BUSINESS 150 2

157 STORAGE 246 GROUP S-1 STORAGE STORAGE 500 1

158 WASHRACK 5983 GROUP S-1 STORAGE STORAGE 500 12

TOTAL 496

107 CONFERENCE ROOM 429 GROUP B BUSINESS UNCONCENTRATED ASSEMBLY 15 29

108 AIR SHOWER 67 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 1

109 STORAGE 46 GROUP S-1 STORAGE STORAGE 500 1

110 COMM 114 GROUP S-1 STORAGE IT 300 1

111 ELEC 99 GROUP S-1 STORAGE MEP 500 1

112 JAN 53 GROUP S-1 STORAGE STORAGE 500 1

113 WOMEN RR 251 GROUP B BUSINESS BUSINESS 150 2

114 MEN RR 305 GROUP B BUSINESS BUSINESS 150 3

115 BREAK ROOM 599 GROUP B BUSINESS UNCONCENTRATED ASSEMBLY 15 40

116 AIR SHOWER 47 GROUP B BUSINESS BUSINESS 150 1

117 LAUNDRY / RESPIRATOR ROOM 342 GROUP B BUSINESS INDUSTRIAL 100 4

118 WOMEN'S DIRTY LOCKER ROOM 269 GROUP B BUSINESS LOCKER 50 6

119 WOMEN'S SHWR 164 GROUP B BUSINESS LOCKER 50 4

120 WOMEN'S CLEAN LOCKER ROOM 231 GROUP B BUSINESS LOCKER 50 5

121 MEN DIRTY LOCKER ROOM 531 GROUP B BUSINESS LOCKER 50 11

122 MEN SHWR 376 GROUP B BUSINESS LOCKER 50 8

123 MEN CLEAN LOCKER ROOM 472 GROUP B BUSINESS LOCKER 50 10

124A LO HALLWAY 2198 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 22

124B LO HALLWAY 1556 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 16

124C LO HALLWAY 1955 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 20

124D LO HALLWAY 431 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 5

125 FILTER ROOM 652 GROUP S-1 STORAGE STORAGE 500 2

126 LO BAY 1 5636 GROUP S-1 GENERAL INDUSTRIAL STORAGE 500 12

127 OPEN STORAGE 1844 GROUP S-1 STORAGE STORAGE 500 4

128 LO BAY 2 5658 GROUP S-1 GENERAL INDUSTRIAL STORAGE 500 12

129 FILTER ROOM 652 GROUP S-1 STORAGE STORAGE 500 2

130 HAZMAT STG/DISPENSARY 1029 GROUP H-3 HIGH-HAZARD STORAGE STORAGE 500 3

131 LO BAY 3 5635 GROUP S-1 GENERAL INDUSTRIAL STORAGE 500 12

132 FILTER ROOM 652 GROUP S-1 STORAGE STORAGE 500 2

133 MECHANICAL 3306 GROUP S-1 STORAGE MEP 500 7

134 ELECTRIC 690 GROUP S-1 STORAGE MEP 500 2

135 FIRE 697 GROUP S-1 STORAGE MEP 500 2

136 LO UNISEX RR 61 GROUP B BUSINESS BUSINESS 150 1

137 JAN 29 GROUP S-1 STORAGE STORAGE 500 1

138 LO UNISEX RR 62 GROUP B BUSINESS BUSINESS 150 1

139 LO COMM 113 GROUP S-1 STORAGE IT 300 1

140 HOPPER 265 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 3

141 PANEL SPRAY ROOM 1955 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 20

142 BONDING/LAYUP AREA 1956 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 20

143 DAMAGE REMOVAL/PREPARATION AREA 1938 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 20

144 HALLWAY 165 GROUP B BUSINESS BUSINESS 150 2

145 UNISEX RR 56 GROUP B BUSINESS BUSINESS 150 1

146 UNISEX RR 56 GROUP B BUSINESS BUSINESS 150 1

147 JAN. 29 GROUP S-1 STORAGE BUSINESS 150 1

148 METALS TECH STAFF 808 GROUP B BUSINESS # OF SEATS # OF SEATS 20

149A METALS TECH SHOP - MACHINE 5209 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 53

149B METALS TECH SHOP - WELD 4154 GROUP F-1 GENERAL INDUSTRIAL INDUSTRIAL 100 42

149C CTK 541 GROUP F-1 GENERAL INDUSTRIAL STORAGE 500 2

150 HALLWAY 156 GROUP B BUSINESS BUSINESS 150 2

150A MEN SHOWER/ LOCKER 249 GROUP B BUSINESS LOCKER 50 5

150B WOMEN SHOWER/ LOCKER 187 GROUP B BUSINESS LOCKER 50 4

151 MECH ROOM 263 GROUP B BUSINESS MEP 500 1

152 HALLWAY 151 GROUP B BUSINESS BUSINESS 150 2

153 ELECTRIC 81 GROUP S-1 STORAGE MEP 500 1

ROOM # NAME SF

OCCUPANCY CLASSIFICATION

USE

OCCUPANT LOAD

FACTOR

OCCUPANTS

IBC LSC

100 VEST 113 GROUP B BUSINESS BUSINESS 150 1

101 ADMIN HALLWAY 1032 GROUP B BUSINESS BUSINESS 150 7

102 COMPUTER ROOM 768 GROUP B BUSINESS BUSINESS 150 6

103 LO/CRF STAFF 348 GROUP B BUSINESS BUSINESS 150 3

104 TELEPHONE 43 GROUP B BUSINESS COLLABORATION 30 2

105 TELEPHONE 43 GROUP B BUSINESS COLLABORATION 30 2

106 FABRICATIONS FLIGHT 348 GROUP B BUSINESS BUSINESS 150 3

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

R H

A M

M E

T T

N A

O F

IL

E

N O

A

W -2

-R

-2

BIM 360://3012011031_F22 LOW OBSERVABLE FACILITY LOCRF/3012011031_LOCRF_FP_R19.rvt

3/12/2021 12:53:29 PM

G-004

C O

D E

C O

M P

L

IA

N C

E S

U M

M A

R Y

F Y

F

-2 F

O R

M A

L T

R A

IN

IN

G U

N

IT

F

T U

C

B

U T

T E

R W

O R

T H

L

IV

E R

S O

N

J A

N D

E R

S O

N

-1

-2

READY TO ADVERTISE

L O

W O

B S

E R

V A

B L

E C

O M

P O

S

IT

E R

E P

A

IR

F A

C

IL

IT

Y

L

O C

R F

SCALE: N.T.S.

B6

EXIT CAPACITY TABLE

SCALE: N.T.S.

B1

OCCUPANT LOAD TABLE

0W 1 0W

8W

W

W

0W

W

W

W

6W

W

W

0 W

8W

W

W

W

8W

W

W

8W

W

2W

2W

W

W

W

2W

W

8W

W

6W

W

W

0W

W

W

0W

6W

W

W

W

W

2W

W

W

8W

W

6W

W

W

8W

W

W

W

6W

W

W

W

6W

8W

W

8W

6W

W

8W

6W

W

W

W

W

8W

0W

0W

W

6W

0W

W

W

W

W

W

0W

W

8W

6W

8W

6W

6W

0W

W

W

W

6W

8W

0W

0W

W

8W

W

6W

6W

W

8W

6W

6W

W

6W

W

2W

0W

W

W

0W

W

W

6W

W

W

W

W

4W

W

8W

W

6W

W

W

0W

W

W

0W

6W

W

W

W

W

0W

6W

W

W

W

6W

W

0W

2W

6 W

W

W

W

W

W

6W

W

W

0W

W

W

W

8W

6W

W

0W

2W

8W

0W

W

0W

W

W

W

W

W

0W

W

W

W

W

W

W

6W

0W

1W

W

6W

W

3W

2W

4W

2W

2W

2W

1W

4W

W

388376

H E F

12" HEF

" F

6" W.

8" W.

W

SEPARATION DISTANCES

UFC 4-211-01 SECTION 3-3.1.8 REQUIRES COMPLIANCE WITH IBC AND NFPA

409. NFPA 409 REQUIRES 50 FEET OF SEPARATION.

A SEPARATION OF 60 FEET IS REQUIRED BY IBC SECTION 507.4. 60 FEET TO

BUILDING 794. ALL OTHER BUILDINGS GREATER THAN 60 FEET.

BUILDING PERIMETER USED FOR FRONTAGE

NO FRONTAGE INCREASES REQUIRED AS THE BUILDING WILL BE

CONSTRUCTED AS AN UNLIMITED AREA AIRCRAFT PAINT HANGAR IN

ACCORDANCE WITH IBC SECTION 507.4 AND 507.8. BUILDING TO BE PROVIDED

SEPARATION OF 60 FEET.

FIRE DEPARTMENT ACCESS

EXISTING FIRE DEPARTMENT ACCESS TO THE AIRFIELD IS THROUGH THE

PROJECT SITE. THE PROJECT WILL INCLUDE THE ADDITION OF TWO FIRE

DEPARTMENT ACCESSES TO THE APRON OF THE BUILDING AND NEW

CONNECTION TO THE AIRFIELD.

THE APRON PROVIDES FIRE DEPARTMENT ACCESS WITHIN 33 FEET OF AN

EXTERIOR DOOR FOR FIRE DEPARTMENT INGRESS.

FIRE LANE WIDTH, MARKING, APPROACH ROADS AND TURN RADIUS

ALL ACCESSES TO BE 20 FEET WIDE OR GREATER AND HAVE AN

UNOBSTRUCTED CLEARANCE OF 13 FEET 6 INCHES. ALL FIRE DEPARTMENT

ACCESS ROADS WILL BE PAVED AND BE CAPABLE OF SUPPORTING A FIRE

SERVICE APPARATUS. NO TURNING RADIUS OR DEAD ENDS ARE EXPECTED

SINCE TWO NEW ACCESS TO THE APRON IS AVAILABLE.

TYPE AND QUANTITY OF ANTITERRORISM SECURE ACCESS

THE BUILDING IS LOCATED WITHIN THE BASE SECURE BOUNDARY. 33 FOOT

UNOBSTRUCTED SPACE PROVIDED.

INTENDED MAIN ENTRANCE TO THE FACILITY

THE MAIN ENTRANCE TO THE FACILITY IS THE VESTIBULE TO THE

ADMINISTRATIVE AREA OF THE LO BAYS.

LOCATION OF FIRE DEPARTMENT CONNECTIONS

FIRE DEPARTMENT CONNECTION IS LOCATED ON THE NORTH EXTERIOR

WALL OF METALS TECH SHOP 149A.

FIRE HYDRANTS, POST INDICATOR VALVES AND CONNECTED DISTRIBUTION

FIRE HYDRANTS ARE SERVED FROM THE DOMESTIC/WATER LOOP ON BASE

AND ARE NOT SERVED FROM THE PRESSURIZED FIRE LOOP. THE SERVICE

MAIN SERVING HYDRANTS FOR BUILDING 361 WILL BE EXTENDED TO PROVIDE

HYDRANTS AROUND THE BUILDING.

HYDRANTS ARE REQUIRED AT 300 FOOT INTERVALS ALONG FIRE

DEPARTMENT ACCESS ROADS. ALL PARTS OF THE FACILITY EXTERIOR MUST

BE WITHIN 350 FEET OF A HYDRANT. HYDRANTS WILL NOT BE INSTALLED IN

FRONT OF HANGAR BAY DOORS. ONE HYDRANT WILL BE PROVIDED WITHIN

100 FEET OF EACH CORNER OF THE BUILDING. WHERE THE APRON ABUTS

THE BUILDING, HYDRANTS WILL BE LOCATED WITHIN 10 FEET OF THE

BUILDING. HYDRANTS ADJACENT TO AIRFIELD PAVEMENT WILL NOT HAVE

THEIR TOPS MORE THAN 2.5 FEET ABOVE THE LEVEL OF ADJACENT AIRFIELD

PAVEMENT. HYDRANTS WILL BE PROVIDED, AS REQUIRED.

SECTIONAL VALVES ARE REQUIRED TO BE PROVIDED SUCH THAT A

COMBINED 5 HYDRANTS OR THREE BUILDING FEEDS ARE NOT OUT OF

SERVICE WITH A SINGLE BREAK OF A PIPE. SECTIONAL VALVES WILL BE

PROVIDED, AS REQUIRED. A POST INDICATOR VALVE IS REQUIRED ON THE

INCOMING FIRE SERVICE AND IS REQUIRED TO BE LOCATED AT LEAST 40

FEET FROM THE BUILDING. POST INDICATOR VALVES WILL BE LOCKED IN THE

NORMAL POSITION. A POST INDICATOR VALVES WILL BE PROVIDED, AS

REQUIRED.

FIRE PUMP ROOM

THE BASE HAS PRESSURIZED UNDERGROUND SERVICE MAINS AND SERVICE

LATERALS FROM THE FIRE PUMPS LOCATED IN BUILDING 348.

BUILDING 348 HOUSES FOUR (4) FIRE PUMPS EACH RATED AT 100 PSI 2000

GPM. ALL FOUR (4) PUMPS ARE ARRANGED IN PARALLEL SUCH THAT THE

FLOW RATINGS ARE ADDITIVE.

THE DESIGN INCLUDES A NEW FIRE PUMP IN THE FIRE PUMP/FIRE FOAM

ROOM WHICH WILL SERVE THE FOAM SYSTEMS ONLY. SPRINKLER SYSTEMS

WILL BE SEPARATED PRIOR TO THE PUMP AND RELY ON PRESSURE

PROVIDED BY BUILDING 348. THE BUILDING PUMP WILL BE RATED AT 100 PSI

500 GPM.

WATER STORAGE TANKS

THE EXISTING WATER STORAGE TANK SERVING BUILDING 348 WILL CONTINUE

TO SERVE BUILDING 348.

HAZARDOUS MATERIAL SPILL CONTAINMENT TANKS

ONE 5,200 GALLON FUEL CAPTURE TANK (OWT-1) WILL BE PROVIDED IN

MECHANICAL ROOM 151.

ONE 38,000 GALLON FOAM/WATER CAPTURE TANK (HCT-1) FOR

CONTAINMENT OF THE DISCHARGE OF THE HIGH EXPANSION FOAM SYSTEM

WILL BE PROVIDED. TANK SIZING BASED ON CRITERIA PROVIDED BY OWNER.

CODE COMPLIANCE SITE PLAN

60' - 0"

BUILDING 348 - EXISTING FIRE PUMP HOUSE - FOUR (4)

100 PSI 2000 GPM FIRE PUMPS ARRANGED IN PARALLEL

EXISTING WATER STORAGE TANK

- 1,000,000 GALLONS

33' - 0

33' - 0"

33' - 0

NEW FIRE HYDRANT

WITH ISOLATION VALVE

MAIN ENTRANCE

FIRE PUMP/FOAM TEST HEADER

NEW FIRE HYDRANT WITH ISOLATION VALVE

NEW FIRE HYDRANT WITH ISOLATION VALVE

NEW 12-INCH EXTENSION OF

FIRE SERVICE FROM B348

NEW 8-INCH EXTENSION OF WATER MAIN

SERVING HYDRANTS

NEW 8-INCH EXTENSION OF WATER

MAIN SERVING HYDRANTS

FIRE/FOAM ROOM

NEW FIRE DEPARTMENT

ACCESS TO AIRFIELD

NEW FIRE DEPARTMENT

ACCESS TO AIRFIELD

ATFP SETBACK

LOCRF

BUILDING

20' - 0"

HIGH EXPANSION FOAM

CONTAINMENT TANK (HCT-1)

SECTIONAL VALVE

SECTIONAL VALVE

SECTIONAL VALVE

SECTIONAL VALVE

NEW FIRE HYDRANT WITH ISOLATION VALVE

NEW PIV ON INCOMING FIRE SERVICE

AT LEAST 40'-0" FROM THE BUILDING

22' - 0

NEW FUEL CAPTURE TANK (OWT-1)

FIRE DEPARTMENT CONNECTION

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

R H

A M

M E

T T

N A

O F

IL

E

N O

A

W -2

-R

-2

BIM 360://3012011031_F22 LOW OBSERVABLE FACILITY LOCRF/3012011031_LOCRF_FP_R19.rvt

9/10/2021 10:53:39 AM

G-005

C O

D E

C O

M P

L

IA

N C

E S

IT

E

P L

A N

F Y

F

-2 F

O R

M A

L T

R A

IN

IN

G U

N

IT

F

T U

C

B

U T

T E

R W

O R

T H

L

IV

E R

S O

N

J A

N D

E R

S O

N

-1

-2

READY TO ADVERTISE

L O

W O

B S

E R

V A

B L

E C

O M

P O

S

IT

E R

E P

A

IR

F A

C

IL

IT

Y

L

O C

R F

SCALE: 1" = 100'-0"

A1

CODE COMPLIANCE SITE PLAN

N

SCALE: = 100'-0"

0 100 200100

1"

C A

A A

A

A

C

C

A

C

A

A

A

A

A

A

A

A

A

A

C

C

C

B

C

D

A

AA

AA

A

A

A

S S

S S

S S

S S

S S

S S

S

S

S

S

S S

S

S S

S

S S

S S

S

S

S SS S S S S S S S S S

SS SS

S

S

S

S SS

1 5 8

B

F

L

E

4'

6"

66' - 6" 66' - 6"

66' - 6"

66' - 6"

70' - 6"

TD - 202 FT, 250 FT ALLOWED

CPT - 77 FT, 100 FT ALLOWED

TD - 104 FT, 250 FT ALLOWED

CPT - 27 FT, 100 FT ALLOWED

TD - 138 FT, 250 FT ALLOWED

CPT - 38 FT, 100 FT ALLOWED

2 4 763

H

J

D

3.7 9 11 12 17 191410 15 1813 16

N

K.5

J.5

H.5

G.5

"6'

6"

7'

6"

7'

6"

66' - 6"

66' - 6"17

RR

LO BAY 1

FILTER ROOM

OPEN STORAGE

LO BAY 2

FILTER ROOM

LO HALLWAY

124B

HAZMAT

STG/DISPENSARY

LO HALLWAY

124C

FILTER ROOM

LO BAY 3

WASHRACK

MECH ROOM

OFFICE

STORAGE

CTK

149C

METALS TECH SHOP -

MACHINE

149A

METALS TECH STAFF

JAN.

UNISEX RR

MEN SHOWER/ LOCKER

150A

WOMEN SHOWER/

LOCKER

150B

LO HALLWAY

124A

ELECTRIC

MECHANICAL

LO UNISEX RR

LO UNISEX RR

HOPPER

PANEL SPRAY ROOM

BONDING/LAYUP AREA

DAMAGE

REMOVAL/PREPARATION

AREA

AIR SHOWER

LAUNDRY /

RESPIRATOR ROOM

WOMEN DIRTY LOCKER

ROOM

WOMEN CLEAN LOCKER

ROOM

WOMEN SHWR

MEN DIRTY LOCKER

ROOM

MEN SHWR

WOMEN RR

MEN RR

MEN CLEAN LOCKER

ROOM

BREAK ROOM

TELEPHONE

COMPUTER ROOM

LO/CRF STAFF

CONFERENCE ROOM

FABRICATIONS FLIGHT

TELEPHONE

ADMIN HALLWAY

HALLWAY

HALLWAY

LO COMM

FIRE

VEST

JAN

COMM

ELEC

JAN

METALS TECH SHOP -

WELD

149B

AIR SHOWER

STORAGE

UNISEX RR

HALLWAY

LO HALLWAY

124D

COMM

ELECTRIC

38' - 6"32' - 6"

K.2

K

G.8

G

C

A.5

A

B.2

KEYED NOTES:

DEAD-END CORRIDOR OF 34 FEET. 50 FEET ALLOWED.1

DEAD-END CORRIDOR OF 15 FEET. 50 FEET ALLOWED.2

TRAVEL DISTANCE OF 156 FEET. 250 FEET ALLOWED. COMMON PATH OF

TRAVEL OF 0 FEET, 100 FEET ALLOWED.

TRAVEL DISTANCE OF 172 FT. 250 FEET ALLOWED. COMMON PATH OF

TRAVEL OF 0 FEET, 100 FEET ALLOWED.

TRAVEL DISTANCE OF 73 FEET. 250 FEET ALLOWED. COMMON PATH OF

TRAVEL OF 40 FEET, 100 FEET ALLOWED.

SMALL PARTS SPRAY BOOTH TO BE INSTALLED AND SEPARATED FROM

OTHER OPERATIONS BY AT LEAST 3 FEET. NO FIRE RESISTANCE RATING IS

REQUIRED PER NFPA 33 SECTION 5.5. ADMINISTRATIVE CONTROLS AND

FLOOR MARKINGS TO BE PROVIDED TO PROHIBIT STORAGE AND

OPERATIONS WITHIN 3 FEET OF THE SPRAY BOOTH. ALL ELECTRICAL

EQUIPMENT WITHIN THE SPRAY BOOTH SHALL BE CLASS I DIVISION 1. ALL

AREAS WITHIN 3 FEET (VERTICALLY AND HORIZONTALLY) OF ANY SPRAY

BOOTH OPENING SHALL BE CLASS I DIVISION 2. SPRAY BOOTH TO BE

PROVIDED WITH ALL REQUIRED INTERLOCKS TO COMPLY WITH NFPA 33 FOR

SPRAY BOOTHS USED FOR DRYING AT ELEVATED TEMPERATURES.

SPRAY OPERATIONS NOT PERFORMED OUTSIDE OF SPRAY BOOTH. AREAS

OUTSIDE OF SPRAY BOOTH SHALL COMPLY WITH NFPA 30, SECTION 18.5

INCIDENTAL OPERATIONS.

SHEET NOTES:

1. HAZARDOUS MATERIALS CONTROL AREAS TO BE PROVIDED WITH A

MINIMUM 1-HOUR FIRE BARRIER SEPARATION. FOUR CONTROL AREAS ARE

PERMITTED AND ARE CONFIGURED AS FOLLOWS:

- LO BAY 1 - 225 GALLONS COMBINED CLASS IA/IB/IC MAXIMUM EXPECTED.

- LO BAY 2 - 225 GALLONS COMBINED CLASS IA/IB/IC MAXIMUM EXPECTED.

- LO BAY 3 - 225 GALLONS COMBINED CLASS IA/IB/IC MAXIMUM EXPECTED.

- REMAINDER OF BUILDING (EXCLUDING THE HAZMAT STORAGE ROOM,

WHICH IS GROUP H-3)

2. HAZMAT STORAGE ROOM CLASSIFIED AS H-3 (IBC) AND LEVEL 3

PROTECTION, HIGH-HAZARD INDUSTRIAL (LSC AND NFPA 30). SEPARATION

OF 1-HOUR FIRE BARRIERS TO BE PROVIDED IN ACCORDANCE WITH IBC

TABLE 508.4 FOR SEPARATION OF H-3 AND B, F-1 AND S-1. AREA NOT

CONSIDERED PART OF CONTROL AREA(S) REFERENCED ABOVE.

3. WASHRACK TO BE SEPARATED FROM OTHER AREAS WITH 1-HOUR FIRE

BAR…