UFGS_08_91_00_Metal_Wall_Louvers_-_UFGS_08_91_00.pdf
PDF 47 KB Posted
- Attached to
- Fort Benning MATOC
- Solicitation number
- W911SF-18-R-0022
About this file
This document provides specifications for metal wall louvers to be installed as part of a federal construction project. The specifications cover materials, finishes, fasteners and accessories for formed metal louvers constructed of galvanized or stainless steel sheet no thinner than 16 U.S. gage. Louvers must bear the AMCA certified ratings program seal for air performance and resist a wind load of 30 pounds per square foot with a water penetration of no more than 0.20 ounces per square foot at 800 feet per minute. Screens and frames must be the same material and finish as the louvers. Installation requirements are also provided.
This federal contract opportunity notice is for an Indefinite Delivery/Indefinite Quantity (IDIQ) contract to provide construction and repair services at U.S. Army Garrison Fort Benning, Georgia. The minimum guarantee is $5,000 for the five-year ordering period with a minimum order of $2,000 and maximum task order of $5 million. The NAICS code is 236220 and size standard is $36.5 million. The solicitation number is W911SF-18-R-0022 and will be available on January 28, 2019 with proposals due February 28, 2019. The contract is set aside 100% for small business. The scope of work includes construction, repair, site work, reporting and record keeping. The point of contact is provided.
View the file
Other files
Show 40 more
Latest 50 of 138 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 08 91 00 Page 1
SECTION 08 91 00
METAL WALL LOUVERS
05/ 11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced . The publications are referred to within the text by the basic designation only.
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL (AMCA)
AMCA 500-D (2012) Laboratory Methods of Testing
Dampers for Rating
AMCA 511 (2010) Certified Ratings Program for Air Control Devices
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AAMA
AMERICAN ARCHITECTURAL
MANUFACTURERS ASSOCIATION (AAMA)
(2015) Voluntary Specification, Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604 (2013) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605 (2013) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic
Coatings on Aluminum Extrusions and Panels
AAMA 611 (2014) Voluntary Specification for Anodized Architectural Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM Al008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High- Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardened
ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated
SECTION 08 91 00 Page 2
(Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B209 (2014) Standard Specification for
Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B209M (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)
ASTM B221 (2014) Standard Specification for
Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B221M (2013) Standard Specification for
Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G " designation identifies the office that will review the submittal for the Government . Submit the following in accordance with Section 01 33 00 SUBM ITTAL PROCEDURES:
SD-02 Shop Drawings
Wall louvers
SD-03 Product Data
Metal Wall Louvers
SD-04 Samples
Wall louvers; G
1.3 DELIVERY, STORAGE, AND PROTECTION
Deliver materials to the site in an undamaged condition. Carefully store materials off the ground to provide proper ventilation, drainage, and protection against dampness. Louvers shall be free from nicks, scratches, and blemishes. Replace defective or damaged materials with new.
1.4 DETAIL DRAWINGS
Show all information necessary for fabrication and installation of wall louvers. Indicate materials, sizes, thicknesses, fastenings, and profiles.
1.5 COLOR SAMPLES
Colors of finishes for wall louvers and door louvers shall closely match the colors of the walls installed in.
SECTION 08 91 00 Page 10
PART 2 PRODUCTS
2 .1 MATERIALS
2 .1.1 Galvanized Steel Sheet
ASTM A653/A653M , coating designation Z275 G90.
2 .1.2 Aluminum Sheet
ASTM B209M ASTM B209, alloy 3003 or 5005 with temper as required for forming.
2 .1.3 Omitted
2. 1.4 Stainless Steel
Type 302 or 304, with 2B finish.
2. 1.5 Cold Rolled Steel Sheet
ASTM A1008/A1008M, Class 1, with matte finish. Use for interior louvers only.
2 .2 METAL WALL LOUVERS
Weather resistant type, with bird screens and made to withstand a wind load of not less than 30 pounds per square foot. Wall louvers shall bear the AMCA certified ratings program seal for air performance and water penetration in accordance with AMCA 500-D and AMCA 511. The rating shall show a water penetration of 0.06 kilograms or less per square meter 0.20 or less ounce per square foot of free area at a free velocity of 244 meters 800 feet per minute.
2 .2.1 Omitted
2 .2.2 Formed Metal Louvers
Formed of zinc-coated cold rolled or stainless steel sheet not thinner than 16 U .S. gage.
2 .2.3 Mullions and Mullion Covers
Same material and finish as louvers. Provide mullions for all louvers more than 1500 mm 5 feet in width at not more than 1500 mm 5 feet on centers. Provide mullions covers on both faces of joints between louvers.
2 .2.4 Screens and Frames
For steel louvers, provide 1/2 inch square mesh, 2.5 or 1.5 mm 12 or 16 gage zinc-coated steel; 12.5 mm 1/2 inch square mesh, 1.5 mm 16 gage copper; or 6 mm 1/4 inch square mesh, 1.5 mm thick 16 gage zinc-coated steel or copper bird screening. Mount screens in removable, re-wirable frames of same material and finish as the louvers.
SECTION 08 91 00 Page 11
2 .3 OMITTED
2 .4 FASTENERS AND ACCESSORIES
Provide stainless steel screws and fasteners for zinc-coated or stainless steel screws and fasteners for steel louvers.
Provide other accessories as required for complete and proper installation.
2 .5 FINISHES
2 .5.1 Omitted
2 .5.2 Steel
Provide factory-applied coating. Clean and phosphate treat exposed surfaces and apply rust-inhibitive primer and baked enamel finish coat,
0.025 mm one mil minimum total dry film thickness, color to match wall colors.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.l Wall Louvers
Install using stops or moldings, flanges, strap anchors, or jamb fasteners as appropriate for the wall construction and in accordance with manufacturer's recommendations.
3 .l. 2 Omitted
3 .l. 3 Screens and Frames
Attach frames to louvers with screws or bolts.
3.2 PROTECTION FROM CONTACT OF DISSIM ILAR MATERIALS
3.2.l Copper or Copper-Bearing Alloys
Paint copper or copper-bearing alloys in contact with dissimilar metal with heavy-bodied bituminous paint or separate with inert membrane.
3.2.2 Omitted
3.2.3 Metal
Paint metal in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.