SYRING SE-T101-ARCH C.pdf

PDF 220 KB Posted

Attached to
2025 E-Rate Network Cabling Additions
Solicitation number
RFP-SCC-250000001194-3
Issued by
Genesee County, Michigan

About this file

This is a structured cabling design document for Syring Elementary School in the Swartz Creek Community Schools system, created by Convergent Technology Partners. The floor plan and technical specifications detail the installation requirements for Category 6A UTP cabling throughout the school building, including wall and ceiling mounting locations. The design was completed in January 2025, with initial design work done in December 2024.

The technical specifications require all UTP cable to be ANSI/TIA Category 6A, installed in surface-mounted single-gang back boxes with white two-port faceplates. Wall locations must be centered below whiteboards at standard height, and all cabling below the ceiling must be concealed in contractor-provided raceway. The plan includes requirements for service loops, white 8P/8C (RJ45) jack terminations, and cabinet grounding. The floor plan shows the layout of telecom cabinets, bus-bars, and UTP locations throughout the school building, with specific mounting and installation requirements detailed in the general notes section.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TGB

SYMBOL LEGEND

UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION, QTY

AS NOTED

TELECOM CABINET

TELECOM BUS-BAR

LOW VOLTAGE SLEEVE

REPLACE CABINETR

R

1 1

1 1

1 11 1

1 11 1

1 11 1

1 11 1

1 11 11 1

1 11 11 11 1

1 1

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA

CATEGORY 6A. PLACE WALL

LOCATIONS IN A SURFACE MOUNTED

SINGLE-GANG BACK BOX WITH A

WHITE TWO PORT FACEPLATE.

2. THE UNUSED TOP PORT OF THE

FACEPLATE IS TO BE FILLED WITH A

BLANK KEYSTONE JACK INSERT.

3. PLACE WALL LOCATIONS CENTERED

BELOW WHITEBOARD AT STANDARD

HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS,

CENTER THE INSTALLATION ON THE

WALL AT STANDARD HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED

BY CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH

SERVICE LOOP LONG ENOUGH TO

REACH THE FARTHEST LOCATION IN

THE ASSOCIATED ROOM. SECURELY

FASTEN SERVICE LOOP TO

STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES

ON WHITE 8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE

ESTIMATED, USE BEST PRACTICES

FOR INSTALLATION LOCATION.

9. FOR ESTIMATES ASSUME ALL

CABINETS NEED GROUNDING.

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/27/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

SYRING ELEMENTARY

SCHOOL

T101

NTS

SYRING FLOOR PLAN

SE-T101

Sheets and Views
ARCH C