MIDDLE SCHOOL MS-T101-MS-T101E.pdf

PDF 841 KB Posted

Attached to
2025 E-Rate Network Cabling Additions
Solicitation number
RFP-SCC-250000001194-3
Issued by
Genesee County, Michigan

About this file

This is a structured cabling technical drawing/specification document for Swartz Creek Community Schools' Swartz Creek Middle School, designed by Convergent Technology Partners. The drawing details specifications for Category 6A UTP cable installation throughout Unit E of the middle school, including wall and ceiling mounting locations, telecom cabinets, and bus-bar placements. The design was completed in two phases, with initial design by EGH on 12/17/2024 and subsequent design by DLF on 1/27/2025.

The technical specifications require all UTP cable to be ANSI/TIA Category 6A standard, with wall locations using surface-mounted single-gang back boxes with white two-port faceplates. Installation requirements include specific placement guidelines for wall locations (centered below whiteboards at standard height), cable concealment in contractor-provided raceways, and service loop requirements for ceiling locations. All Category 6A cables must terminate on white 8P/8C (RJ45) jacks, and all cabinets require grounding. The drawing includes a floor plan of Unit E showing the placement of various network infrastructure components and a detailed symbol legend for wall UTP locations, ceiling UTP locations, telecom cabinets, telecom bus-bars, and replace cabinets.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 1

TGB

SYMBOL LEGEND

WALL UTP LOCATION, QTY AS

NOTED

CEILING UTP LOCATION, QTY AS

NOTED

TELECOM CABINET

TELECOM BUS-BAR

REPLACE CABINETR

B

A

C D

E

FF

GENERAL NOTES

1. ALL UTP CABLE SHALL BE ANSI/TIA

CATEGORY 6A. PLACE WALL LOCATIONS IN

A SURFACE MOUNTED SINGLE-GANG BACK

BOX WITH A WHITE TWO PORT FACEPLATE.

2. THE UNUSED TOP PORT OF THE

FACEPLATE IS TO BE FILLED WITH A BLANK

KEYSTONE JACK INSERT.

3. PLACE WALL LOCATIONS CENTERED

BELOW WHITEBOARD AT STANDARD

HEIGHT.

4. LOCATIONS WITHOUT WHITEBOARDS,

CENTER THE INSTALLATION ON THE WALL

AT STANDARD HEIGHT.

5. ALL CABLE BELOW CEILING SHALL BE

CONCEALED IN RACEWAY PROVIDED BY

CONTRACTOR.

6. PROVIDE CEILING LOCATION WITH SERVICE

LOOP LONG ENOUGH TO REACH THE

FARTHEST LOCATION IN THE ASSOCIATED

ROOM. SECURELY FASTEN SERVICE LOOP

TO STRUCTURE.

7. TERMINATE ALL CATEGORY 6A CABLES ON

WHITE 8P/8C (RJ45) JACKS.

8. LOCATION OF BUS BLOCKS ARE

ESTIMATED, USE BEST PRACTICES FOR

INSTALLATION LOCATION.

9. FOR ESTIMATES ASSUME ALL CABINETS

NEED GROUNDING.

C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473

Phone: 810.720.3820 www.ctpartners.net

T E C H N O L O G Y P A R T N E R S

TECHNOLOGY DESIGN I CONSULTING I PLANNING

1/27/2025 DESIGN DLF

12/17/2024 DESIGN EGH

DATE ISSUE AUTHOR

SWARTZ CREEK

COMMUNITY SCHOOLS

STRUCTURED CABLING

SWARTZ CREEK

MIDDLE SCHOOL

MS-T101E

KEYMAP

101E

NTS

M.S. UNIT E

Sheets and Views
MS-T101E

File details come from the government source that posted it. Updated .