This is a technical specification drawing for structured cabling at Swartz Creek Middle School's natatorium, prepared by Convergent Technology Partners. The drawing details the requirements for Category 6A UTP cable installation throughout the natatorium facility, including both the upper and first floor areas. The design was completed in December 2024 and January 2025, with specific requirements for wall and ceiling cable locations, faceplate installations, and telecommunications cabinet placement.
The technical specifications require all UTP cable to be ANSI/TIA Category 6A compliant, with specific installation requirements including surface-mounted single-gang back boxes with white two-port faceplates, blank keystone jack inserts for unused ports, and concealed raceway cabling below the ceiling. The drawing includes detailed general notes for installation standards, such as placement requirements relative to whiteboards, service loop specifications for ceiling locations, and grounding requirements for all cabinets. The floor plans show the layout of various rooms including storage areas, offices, locker rooms, and laundry facilities, with telecommunications infrastructure placement clearly marked using the provided symbol legend.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U N
IT
A
U N
IT
F
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
TGB
SYMBOL LEGEND
WALL UTP LOCATION, QTY AS
NOTED
CEILING UTP LOCATION, QTY AS
NOTED
TELECOM CABINET
TELECOM BUS-BAR
REPLACE CABINETR
B
A
C D
E
FF
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
UNIT F
GENERAL NOTES
1. ALL UTP CABLE SHALL BE ANSI/TIA
CATEGORY 6A. PLACE WALL LOCATIONS IN
A SURFACE MOUNTED SINGLE-GANG BACK
BOX WITH A WHITE TWO PORT FACEPLATE.
2. THE UNUSED TOP PORT OF THE
FACEPLATE IS TO BE FILLED WITH A BLANK
KEYSTONE JACK INSERT.
3. PLACE WALL LOCATIONS CENTERED
BELOW WHITEBOARD AT STANDARD
HEIGHT.
4. LOCATIONS WITHOUT WHITEBOARDS,
CENTER THE INSTALLATION ON THE WALL
AT STANDARD HEIGHT.
5. ALL CABLE BELOW CEILING SHALL BE
CONCEALED IN RACEWAY PROVIDED BY
CONTRACTOR.
6. PROVIDE CEILING LOCATION WITH SERVICE
LOOP LONG ENOUGH TO REACH THE
FARTHEST LOCATION IN THE ASSOCIATED
ROOM. SECURELY FASTEN SERVICE LOOP
TO STRUCTURE.
7. TERMINATE ALL CATEGORY 6A CABLES ON
WHITE 8P/8C (RJ45) JACKS.
8. LOCATION OF BUS BLOCKS ARE
ESTIMATED, USE BEST PRACTICES FOR
INSTALLATION LOCATION.
9. FOR ESTIMATES ASSUME ALL CABINETS
NEED GROUNDING.
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
1/27/2025 DESIGN DLF
12/17/2024 DESIGN EGH
DATE ISSUE AUTHOR
SWARTZ CREEK
COMMUNITY SCHOOLS
STRUCTURED CABLING
SWARTZ CREEK
MIDDLE SCHOOL
MS-T101F
KEYMAP
T101F
NTS
UPPER NATATORIUM
T101F
NTS
1ST FLOOR NATATORIUM